⚫ Clock synchronization using IRIG-B, SNTP Simple Network Time Protocol, PPS Pulse-Per- Second and PPM Pulse-Per-Minute, IEEE1588 ⚫ Auxiliary functions for simple tests and commissioning
Trang 3Copyright © 2019 NR All rights reserved
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may
be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights
The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice
To the extent required the products described herein meet applicable IEC and IEEE standards, but
no such assurance is given with respect to local codes and ordinances because they vary greatly Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us
Trang 5Preface
About This Document
This manual describes the configuration scheme in multiple application scenarios for PCS-9705S Bay Control Unit, including how to connect the device to a computer and to configure functions, such as control, protection, measurement and supervision in using of configuration tool
To start using this manual for application configuration, user should know the basic operations of the configuration tool PCS-Studio
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment (module or device) However, it comprises important information that must be followed for personal safety, as well as to avoid material damage Information is highlighted and illustrated as follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will result
in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage
Indicates that property damage can result if the measures specified are
not taken
Important information about the product, please pay attention to avoid undesired result
Instructions and Warnings
The following hazard statements apply to this device
Disconnect or de-energize all external connections BEFORE opening this
device Contact with hazardous voltages and currents inside this device can cause electrical shock resulting in injury or death
Trang 6Contact with instrument terminals can cause electrical shock that can result
in injury or death
Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment
Have ONLY qualified personnel service this equipment If you are not
qualified to service this equipment, you can injure yourself or others, or cause equipment damage
This device is shipped with default passwords Default passwords should
be changed to private passwords at installation Failure to change each default password to a private password may allow unauthorized access NR shall not be responsible for any damage resulting from unauthorized access
DO NOT look into the fibre (laser) ports/connectors
DO NOT look into the end of an optical cable connected to an optical output
DO NOT perform any procedures or adjustments that this instruction
manual does not describe
During installation, maintenance, or testing of the optical ports, ONLY use the test equipment qualified for Class 1 laser products!
Incorporated components, such as LEDs, transceivers, and laser emitters,
are NOT user serviceable Return units to NR for repair or replacement
Trang 7Equipment components are SENSITIVE to electrostatic discharge (ESD)
Undetectable permanent damage can result if you do not use proper ESD procedures Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment If your facility is not
equipped to work with these components, contact NR about returning this device and related NR equipment for service
Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables Please use the wiring method recommended in the manual for communication terminals
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power Equipment damage can result otherwise
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure
The firmware may be upgraded to add new features or enhance/modify
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand
Trang 8For example: the access path of protection settings is: Main Menu→Settings→Protection
Settings
⚫ Settings not in the table should be placed in brackets
For example: the system setting [Opt_SysFreq]
⚫ Cross-references are presented in italics
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
⚫ Binary input signals, binary output signals, analogues, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold
For example: press the button "ENT"
Trang 11Three-phase Corresponding Relationship
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Warranty
This product is covered by the standard NR 10-year warranty For warranty details, please
consult the manufacturer or agent for warranty information
Document Structure
This manual is a comprehensive work covering all aspects of device application and configuration Read the sections that pertain to your application to gain valuable information about configuring the device To concentrate on the target sections of this manual as your job needs and responsibilities dictate An overview of each manual section and section topics follows
1 Functions and Applications
Introduction of device functions and typical application scenarios
Trang 12Basic functions configuration methods, including functions selection through MOT, diagram drawing
of LCD display, communication protocol selection and setting, user authority management, configuration of binary inputs and outputs, programmable logic, etc
Appendix A Glossary
List of abbreviations adopted in this manual
Document Revision History
P/N: ZL_PCS-9705S_X_Application Manual_EN_Overseas General_X
Trang 131.2 Typical Application Scenarios 1-5
1.2.1 Single Circuit Breaker (with Single Busbar, App1) 1-5
1.2.2 Single Circuit Breaker (with Double Busbars, App1) 1-7
1.2.3 Double Circuit Breakers (App2) 1-8
1.2.4 Multiple Busbars (App3) 1-9
1.2.5 Bus Coupler (App3) 1-10
1.2.6 Transformer Sides (App4) 1-11
1.2.7 Multiple Bays of One Busbar (App5) 1-12
1.2.8 I/O Box (App7) 1-13
Trang 141
Trang 151
1.1 Functions
1.1.1 Basic Functions
⚫ Multiple setting groups
⚫ Flexibly configurable binary inputs (max 361)
⚫ Flexibly configurable binary outputs (max 107)
⚫ Configuration of max.40 users and allow each user to own different password and access
authority
⚫ Function shortcuts key, which can be configured by software tool to execute express
operations
⚫ Clock synchronization using IRIG-B, SNTP (Simple Network Time Protocol), PPS (Pulse-Per-
Second) and PPM (Pulse-Per-Minute), IEEE1588
⚫ Auxiliary functions for simple tests and commissioning
1.1.2 Control Functions
⚫ Switchgear control
⚫ Double point status synthesis
⚫ Remote/Local control mode switch
⚫ Interlocking logic for control
⚫ Direct control
⚫ Closing synchronism check with voltage selection
⚫ Switchgear tripping counter
⚫ Tap position indication and control
1.1.3 Protection Functions
⚫ Breaker failure protection
➢ Phase-segregated re-trip and three-phase re-trip
➢ Optional current criterion (phase overcurrent element, zero-sequence overcurrent
element, negative-sequence overcurrent element)
➢ Optional circuit breaker position check logic
➢ Two time delay settings
Trang 161 ⚫ Transfer trip protection
➢ Three-phase or phase-segregated
⚫ Automatic reclosing
➢ One shot or multi-shot reclosing
➢ 1-pole AR, 3-pole AR or 1/3-pole AR
➢ Optional trigger mode, by protection operating and external binary input
➢ Support of synchronism check logic and voltage check logic
1.1.4 Measurement and Metering
⚫ U, I, P, Q, Cos
⚫ Positive, negative and zero sequences
⚫ Max.15th harmonics
⚫ Energy metering (active and reactive energies for import and export)
⚫ Power Quality Supervision (PQS) with Total Harmonic Distortion (THD), deviation and unbalance
⚫ DC analogue inputs (0~±20mA or 0~±10V)
⚫ DC analogue outputs (4~20mA, 0~10V, 0~5V or 0~20mA)
1.1.5 Synchrophasor Measurement
⚫ The integrated phasor Measurement Unit (PMU) function of synchrophasor measurement is compatible with IEEE C37.118-2005, IEEE C37.118.1-2011, IEEE C37.118.2-2011 and IEEE C37.118.1a-2014
⚫ Supporting time synchronization by IRIG-B signal
⚫ Supporting P Class or M Class measurement (user selectable)
⚫ Measurement of three-phase and single-phase voltage and current
⚫ Measurement of positive/negative/zero-sequence voltage and current
⚫ Calculation of active power, reactive power, system frequency, and rate-of-change of frequency (ROCOF)
⚫ Measurement of up to 32 binary status (user configurable)
⚫ Output of synchrophasor with timestamp, support of multiple protocols (TCP, TCP-UDP, UDP) and multiple data rates (2f0, f0, f0/2) for maximum 4 clients (PDC)
Trang 171
1.1.6 Monitoring
⚫ CT circuit failure Supervision (CTS)
⚫ VT circuit failure Supervision (VTS)
⚫ Self-diagnostic
⚫ Powerful faults recording (max buffer for 10,000 sampled points at 4.8 or 9.6 kHz)
⚫ Event recorder including 1024 change-of-state events, 1024 supervision events, 256 control
logs and 1024 device logs
⚫ Disturbance recorder including 32 disturbance records with waveforms (format compatible with
➢ IEC 61850 Ed1 & Ed2
➢ IEC 62439 Parallel Redundancy Protocol (PRP)
➢ IEC 62439 High-availability Seamless Ring (HSR) Redundancy Protocol
➢ IEEE 802.1w Rapid Spanning Tree Protocol (RSTP)
⚫ Support for digital substation
➢ Extendable quantity of communication interfaces
➢ Support of IEC 61850 MMS Server
➢ Support of IEC 61850-8-1 GOOSE
➢ Support of IEC 61850-9-2LE SMV
⚫ Up to four 10Base-T/100Base-TX copper Ethernet ports
⚫ Up to four 100Base-FX optical Ethernet ports
⚫ Two RS-485 serial ports for communication or printer
⚫ One RS-485/TTL serial port for clock synchronization
⚫ RJ45 debugging ports for both front and rear sides
Trang 18⚫ 4 Programmable operator pushbuttons with user-configurable labels
⚫ Up to 15/18 programmable target LEDs with user-configurable labels
⚫ 1 RS-485 rear ports for printer
⚫ Language switchover: English+ selected language
⚫ Configuration tool: PCS-Studio
1.1.9 Additional functions
⚫ User programmable logic
⚫ System phase sequences rotation function (ABC or ACB)
⚫ Clock synchronization
➢ IRIG-B: IRIG-B via RS-485 differential level or TTL level
➢ PPS: Pulse per second (PPS) via RS-485 differential level or binary input
➢ PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
➢ IEEE1588: Clock message based on IEEE1588 via optical fibre interface
➢ SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
➢ SNTP (BC): Broadcast SNTP mode via Ethernet network
➢ Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol, Modbus protocol and DNP3.0 protocol
Trang 19App4 Transformer sides App5 Bays
App7 I/O box
1.2.1 Single Circuit Breaker (with Single Busbar, App1)
In this scenario, the PCS-9705S is applied to a single circuit breaker with a single busbar The
three-phase CT and VT are adopted for measurement and protection of the line CB The
single-phase VT is connected to the busbar for synchronism check An optional single-single-phase CT may be
adopted for the residual current of line CB
The circuit breaker and the relevant disconnector switches and earthing switches in this bay could
be controlled by the device Breaker failure protection and auto-reclosing function are optional to
be adopted as the backup of line protection Meanwhile, supervision functions of analog input
channels, binary input channels, CT secondary circuits, VT secondary circuits, switchgear tripping
counter, etc are equipped for the operating reliability and safety of the device Moreover, phasor
measurement unit (PMU) function for synchrophasor measurement may be integrated
Trang 20FR CTS
VTS 25
CILO XSWI
79
Trang 211
1.2.2 Single Circuit Breaker (with Double Busbars, App1)
In this scenario, the PCS-9705S is applied to a single circuit breaker with double busbars The
three-phase CT and VT are adopted for measurement and protection of the line CB Two
single-phase VTs are connected to the two busbars respectively for synchronism check An optional
single-phase CT may be adopted for the residual current of line CB
The circuit breaker and the relevant disconnector switches and earthing switches in this bay could
be controlled by the device Breaker failure protection and auto-reclosing function are optional to
be adopted as the backup of line protection Meanwhile, supervision functions of analog input
channels, binary input channels, CT secondary circuits, VT secondary circuits, switchgear tripping
counter, etc are equipped for the operating reliability and safety of the device Moreover, phasor
measurement unit (PMU) function for synchrophasor measurement may be integrated
VTS 25
CILO XSWI
79
Trang 221 1.2.3 Double Circuit Breakers (App2)
In this scenario, the PCS-9705S is applied to the tie CB and one bus CB in 3/2 CB arrangement Two three-phase CTs are adopted for measurement of the tie CB and one bus CB A three-phase
VT is adopted between the tie CB and one bus CB for measurement of the outgoing line Three single-phase VTs are connected to the two busbars and the other outgoing line respectively for synchronism check
The three circuit breakers and the relevant disconnector switches and earthing switches in this arrangement could be controlled by the device Meanwhile, supervision functions of analog input channels, binary input channels, CT secondary circuits, VT secondary circuits, switchgear tripping counter, etc are equipped for the operating reliability and safety of the device
CSWI
FR
Busbar1
1VT 3CTs
CTS VTS 25
CILO
*
XSWI XCBR
52
84 PQS
52 3VTs
Bus1 CB
Bus2 CB
Trang 231
1.2.4 Multiple Busbars (App3)
In this scenario, the PCS-9705S is applied to up to 4 busbars A three-phase VT is adopted for
measurement of each busbar
The relevant disconnector switches and earthing switches of busbars and outgoing lines could be
controlled by the device Meanwhile, supervision functions of analog input channels, binary input
channels, VT secondary circuits, switchgear tripping counter, etc are equipped for the operating
reliability and safety of the device
Trang 241 1.2.5 Bus Coupler (App3)
In this scenario, the PCS-9705S is applied to a bus coupler between two busbars The three-phase
CT is adopted for measurement of the bus coupler Two three-phase VTs are adopted for measurement of the two busbars respectively
The bus coupler and the relevant bus disconnector switches and earthing switches in this bay could
be controlled by the device Meanwhile, supervision functions of analog input channels, binary input channels, CT secondary circuits, VT secondary circuits, switchgear tripping counter, etc are equipped for the operating reliability and safety of the device
FR VTS
Trang 251
1.2.6 Transformer Sides (App4)
In this scenario, the PCS-9705S is applied to up to 4 sides of a transformer A three phase CT is
adopted for measurement between the busbar and the transformer of each side A three-phase VT
is adopted for measurement of each side
The circuit breakers and relevant disconnector switches and earthing switches could be controlled
by the device Meanwhile, supervision functions of analog input channels, binary input channels,
CT secondary circuits, VT secondary circuits, switchgear tripping counter, etc are equipped for the
operating reliability and safety of the device
CSWI
FR
3VTs 3CTs
Trang 261 1.2.7 Multiple Bays of One Busbar (App5)
In this scenario, the PCS-9705S is applied to up to 6 bays with one busbar A three-phase CT and
a single-phase VT are adopted for measurement of each bay A three-phase VT is connected to the busbar An optional single-phase CT may be adopted for the residual current of each bay The circuit breaker and the relevant disconnector switches and earthing switches in each bay could
be controlled by the device Meanwhile, supervision functions of analog input channels, binary input channels, CT secondary circuits, VT secondary circuits, switchgear tripping counter, etc are equipped for the operating reliability and safety of the device
CSWI
FR CTS
VTS 25
CILO XSWI
1VTs
1CT 3CTs *
* 52
.
Trang 271
1.2.8 I/O Box (App7)
In this scenario, the PCS-9705S is applied for binary or DC analogue input and output signals
There is no adoption of instrument transformer for any AC analogue sampling input Besides the
CPU and PWR modules, all the slots could be equipped with I/O modules for binary input, binary
output, DC analogue input and DC analogue output signals
For the maximum capacity, this device supports 361 binary inputs, 107 binary outputs, 72 DC
analogue inputs or 48 DC analogue outputs at a time
Trang 281
Trang 292
2 Configuration Tool
Table of Contents
2.1 Brief Introduction of PCS-Studio 2-1
2.2 Connection to Debugging Computer 2-1
2.2.1 Via Front RJ45 Port 2-1
2.2.2 Via Ethernet Interface on CPU Module 2-2
2.3 Validation of Configuration 2-2
Trang 302
Trang 312
2.1 Brief Introduction of PCS-Studio
The PCS-Studio is the configuration and debugging software of PCS S series devices It provides
the following configuration functions:
⚫ Device information configuration
Viewing and editing project name, user configuration file version, file modification time, etc
⚫ Global function configuration
MOT selection, system configuration, function object activation/deactivation, etc
⚫ Human-machine interface configuration
Single Line Diagram (SLD) drawing for LCD display, definition of LED indicators, shortcut keys,
user-level waveform recording, etc
⚫ Communication configuration
Support of multiple communication protocols, including IEC 61850 (Edition 1 & Edition 2), IEC
60870-5-103, DNP3.0, Modbus, etc
⚫ IO signal configuration
Binary inputs, binary outputs, AC and DC analogue inputs, etc
⚫ User-defined logic programming
Complete and rich symbol library for user-defined logic programming
⚫ Parameter setting
Setting, import and export of device parameters
⚫ Online debugging
Debugging through visual pages and virtual LCD screen
2.2 Connection to Debugging Computer
On the front panel of the device, there is a multiplex RJ45 port which is the debugging port for
connection to a portable computer Meanwhile, the CPU plug-in module is equipped with several
Ethernet interfaces which may also be used to communicate with debugging computer
2.2.1 Via Front RJ45 Port
By default, the IP address of front debugging port is “100.100.100.100” with the subnet mask
“255.255.255.000” If this address conflicts with any other Ethernet port on CPU module Through
the device front human-machine interface, please call up the modification menu by pressing the
key combination "◄ + ◄ - ENT" under the default LCD display screen and change the default
Trang 322
address
2.2.2 Via Ethernet Interface on CPU Module
Firstly, a connection between the device and the computer must be established by setting the IP address and subnet mask of the corresponding interfaces Configure the IP address and the subnet
mask of corresponding Ethernet interface through MainMenu → Settings → Global Settings →
Comm Settings → General Comm Settings
The IP addresses and the subnet masks of device PC should be in the same network segment Take the second Ethernet interface (LAN2) on CPU module as an example:
Device Debugging PC
IP address [IP_LAN2] = 198.87.96.XXX 198.87.96.102
Subnet mask [Mask_LAN2] = 255.255.255.0 255.255.255.0
LAN enabling setting [En_LAN2] = Enabled
“XXX” can be any value from 0 to 255 except 102
2.3 Validation of Configuration
To take effect of all kinds of offline configuration work through PCS-Studio, it is necessary to regenerate the device configuration file (*.devs) and download it to the device A reboot of device
is obligatory after the download for the validation of any modification
All function configuration described in the following chapters are offline tasks, which requires the “file generation, file downloading and device reboot” process for validation
Trang 333.3 Breaker Failure Protection (50BF) 3-2
3.3.1 Selection and Enabling 3-2
3.3.2 Input and Output Signals 3-2
3.3.3 Breaker Failure Initiation 3-3
3.4 Transfer Trip (TT) 3-4
3.4.1 Selection and Enabling 3-4
3.4.2 Input and Output Signals 3-4
3.4.3 Receiving of Transfer Trip Command 3-5
3.5 Trip Logic (TRP) 3-6
3.5.1 Selection and Enabling 3-6
3.5.2 Input and Output Signals 3-6
3.5.3 Output of Protective Operation 3-6
3.5.4 Enforcing of Three-phase Tripping 3-7
3.6 Automatic Reclosing (79) 3-7
3.6.1 Selection and Enabling 3-7
3.6.2 Input and Output Signals 3-7
3.6.3 Synchronism Check 3-10
3.6.4 Reclosing Mode 3-10
3.6.5 Initiation 3-11
3.6.6 Blocking 3-11
3.6.7 Power Line Communication Lost 3-12
3.6.8 Cooperation with Another AR 3-12
3.6.9 Circuit Breaker Energy 3-13
3.6.10 Pause of AR Procedure 3-14
Trang 343
Trang 353
3.1 Selection of Protective Function
In the PCS-9705S Bay Control Unit, certain protective functions are available in two application
scenarios: Single Circuit Breaker (App1) and Double Circuit Breakers (App2) For such scenarios,
the integrated protective functions serve as backup protection to complete the protection scheme
of the protected object with other protective device If a protective function has not been selected,
its related settings, signals and menu are hidden from both the LCD screen of device and the menu
and libraries of configuration tool
To select a protective function:
⚫ Firstly, make sure that the option "Single circuit breaker" or "Double circuit breakers" has
been selected through the path: Project Node → IED Node → Device Setup → Global
Config → MOT → U1 Application in the PCS-Studio configuration tool
⚫ Select the option "Basic + Backup protection" in the "S1 Software" field
⚫ Locate the protective function through the path: Project Node → IED Node → Device Setup
→ Global Config → Function Group and double click the "Option" column to select the
option "ON" or "OFF"
3.2 Enabling/Blocking of Function
If a function is selected or activated manually or by factory predefinition, it is enabled by default
Every function provides an input terminal of enabling and another input terminal of blocking Locate
these two terminals "XXXX.Enable" and "XXXX.Block" through the path: Variable DB →
Destination → Function_Logic → Page: Function Name → Component: XXXX in the
PCS-Studio configuration tool To establish the function enabling/blocking logic, user may connect these
two terminals to binary signal(s), such as binary input from contact (refer to the Section Binary
Inputs), result of logic calculation (refer to the Section User-programmable Logic) or function link
for local/remote control (refer to the Section Function Links)
Trang 363
3.3 Breaker Failure Protection (50BF)
3.3.1 Selection and Enabling
If this function is selected (refer to the Section Selection of Protective Function) and enabled (refer
to the Section Enabling/Blocking of Function), the related settings, signals and menu should be
displayed in the PCS-Studio configuration tool
3.3.2 Input and Output Signals
Breaker failure protection adopts phase current, zero sequence current and negative sequence current in operating criteria Therefore, the three-phase current analog input must be configured
correctly (refer to the Section AC Analog Inputs)
The available input and output terminals in PCS-Studio configuration tool are listed below:
Input terminals: Variable DB → Destination → Function_Logic → Page: BF_Protection →
Component: CB*.50BF
CB*.50BF.Enable Input signal of enabling breaker failure protection
CB*.50BF.Block Input signal of blocking breaker failure protection
CB*.50BF.ExtTrpA Input signal of initiating breaker failure protection (phase-A)
CB*.50BF.ExtTrpB Input signal of initiating breaker failure protection (phase-B)
CB*.50BF.ExtTrpC Input signal of initiating breaker failure protection (phase-C)
CB*.50BF.ExtTrp3P Input signal of initiating breaker failure protection (three-phase)
CB*.50BF.ExtTrp_WOI Input signal of initiating breaker failure protection with the position check of the circuit breaker CB*.50BF.52b Input signal of three-phase open position of three circuit breaker
Output terminals: Variable DB → Source → Function_Logic → Page: BF_Protection →
Component: CB*.50BF.
CB*.50BF.Op_ReTrpA Breaker failure protection operates to re-trip phase-A circuit breaker
CB*.50BF.Op_ReTrpB Breaker failure protection operates to re-trip phase-B circuit breaker
CB*.50BF.Op_ReTrpC Breaker failure protection operates to re-trip phase-C circuit breaker
CB*.50BF.Op_ReTrp3P Breaker failure protection operates to re-trip three-phase circuit breaker
CB*.50BF.Op_t1 Breaker failure protection operates with the time delay [50BF.t1_Op]
CB*.50BF.Op_t2 Breaker failure protection operates with the time delay [50BF.t2_Op]
Trang 373
CB*.50BF.On Breaker failure protection is enabled
CB*.50BF.Blocked Breaker failure protection is blocked
CB*.50BF.Valid Breaker failure protection is valid
CB*.50BF.StA Breaker failure protection starts (phase-A)
CB*.50BF.StB Breaker failure protection starts (phase-B)
CB*.50BF.StC Breaker failure protection starts (phase-C)
CB*.50BF.St Breaker failure protection starts (three-phase)
CB*.50BF.Alm_Init The initiating signal of breaker failure protection is abnormal
3.3.3 Breaker Failure Initiation
Normally, the configuration of Breaker Failure Initiation (BFI) logic via internal protection logic has
been pre-defined as the factory default configuration If BFI by external tripping signal is required,
the corresponding configuration should be made
⚫ Open or create a configuration page under the path: Project Node → IED Node → Program →
Function_Logic → in the PCS-Studio configuration tool
⚫ Locate the input terminal(s) of such function in: Variable DB → Destination →
Function_Logic → Page: BF_Protection → Component: CB*.50BF
➢ "CB*.50BF.ExTrpA", "CB*.50BF.ExTrpB" and "CB*.50BF.ExTrpC" for phase-segregated
BFI
Connect the terminals to phase-segregated tripping outputs from another protective
device (e.g line protection) in the configuration page;
➢ "CB*.50BF.ExTrp3P" for three-phase BFI
Connect the terminal to three-phase tripping output from another protective device (e.g
busbar protection);
➢ "CB*.50BF.ExTrp_WOI" for single-phase BFI
Connect the terminal to the corresponding phase tripping output from another protective
device in the configuration page
Trang 383
For the operation of certain protection function, such as overvoltage protection, the fault current maybe too small to initiate breaker failure protection To make sure that breaker failure protection can reliably operate, the
"CB*.50BF.ExTrp_WOI" terminal, which stands for "without current" criteria is
equipped for BFI Once this input terminal is energized, the status of normally closed auxiliary contact of circuit breaker is selected in addition in current check
to initiate breaker failure timer
⚫ Locate the output terminal(s) of protection in: Variable DB → Source → Function_Logic →
Page: BF_Protection → Component: CB*.50BF Connect the terminal(s) to the input(s) of
another function if necessary
3.4 Transfer Trip (TT)
3.4.1 Selection and Enabling
If this function is selected (refer to the Section Selection of Protective Function) and enabled (refer
to the Section Enabling/Blocking of Function), the related settings, signals and menu should be
displayed in the PCS-Studio configuration tool
3.4.2 Input and Output Signals
The available input and output terminals in PCS-Studio configuration tool are listed below:
Input terminals: Variable DB → Destination → Function_Logic → Page: DTT_Protection →
Component: TT
TT.Enable Input signal of enabling transfer trip
TT.Block Input signal of blocking transfer trip
TT.Init_3P Input signal of initiating transfer trip (Three phase)
TT.Init_A Input signal of initiating transfer trip (Phase A)
TT.Init_B Input signal of initiating transfer trip (Phase B)
TT.Init_C Input signal of initiating transfer trip (Phase C)
Output terminals: Variable DB → Source → Function_Logic → Page: DTT_Protection →
Component: TT.
Trang 393
TT.On Transfer trip is enabled
TT.Blocked Transfer trip is blocked
TT.Valid Transfer trip is valid
TT.Op_3P Transfer trip operates (Three phase)
TT.Op_A Transfer trip operates (Phase A)
TT.Op_B Transfer trip operates (Phase B)
TT.Op_C Transfer trip operates (Phase C)
TT.Alm The initiating signal of transfer trip is abnormal
3.4.3 Receiving of Transfer Trip Command
The device can trip circuit breaker by receiving the transfer trip signal via contact of binary input or
GOOSE communication protocol from another device The configuration method is:
⚫ Make sure that the corresponding binary signals have been correctly configured as binary
inputs (refer to the Section Binary Inputs) or GOOSE receiving signals (refer to the Section
GOOSE Communication)
⚫ Open or create a configuration page under the path: Project Node → IED Node → Program →
Function_Logic → in the PCS-Studio configuration tool
⚫ Locate the input terminal(s) of such function in: Variable DB → Destination →
Function_Logic → Page: DTT_Protection → Component: TT
➢ "TT.Init_A", " TT.Init_B" and " TT.Init_C" for phase-segregated tripping
In the configuration page, connect the terminals to the corresponding binary input signals,
which locate in the path: Variable DB → Source → Function_Logic → BI or Page:
UserPage_GOOSE → …;
➢ "TT.Init_3P" for three-phase tripping
In the configuration page, connect the terminal to the corresponding binary input signal,
which locates in the path: Variable DB → Source → Function_Logic → BI or Page:
UserPage_GOOSE → …;
Trang 403
3.5 Trip Logic (TRP)
3.5.1 Selection and Enabling
If this function is enabled (refer to the Section Enabling/Blocking of Function), the related settings,
signals and menu should be displayed in the PCS-Studio configuration tool
3.5.2 Input and Output Signals
The available input and output terminals in PCS-Studio configuration tool are listed below:
Input terminals: Variable DB → Destination → Function_Logic → Page: CB_TripOut →
Component: CB*.
CB*.Enable Input signal of enabling trip logic of circuit breaker
CB*.Block Input signal of blocking trip logic of circuit breaker
CB*.PrepTrp3P Input signal of three-phase tripping permission
Output terminals: Variable DB → Source → Function_Logic → Page: CB_TripOut →
Component: CB*.
CB*.TRP.On Tripping logic of circuit breaker is enabled
CB*.TrpA Tripping phase A of circuit breaker
CB*.TrpB Tripping phase B of circuit breaker
CB*.TrpC Tripping phase C of circuit breaker
CB*.Trp Tripping any phase of circuit breaker
CB*.Trp3P Tripping three phases of circuit breaker
CB*.BFI_A Protection tripping signal of phase A configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off
CB*.BFI_B Protection tripping signal of phase B configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off
CB*.BFI_ C Protection tripping signal of phase C configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off
CB*.BFI Protection tripping signal configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off
3.5.3 Output of Protective Operation
This function may block/unblock the circuit breaker tripping output which is issued by protective functions