Preface About This Manual The manual describes the protection, control, measurement and supervision functions with the information of relevant hardware for PCS-978S Transformer Relay..
Trang 3Copyright © 2020 NR All rights reserved
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may
be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know -how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights
The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice
To the extent required the products described herein meet applicable IEC and IEEE standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly
Although every reasonable effort is made to present current and accurate inform ation, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us
Trang 5Preface
About This Manual
The manual describes the protection, control, measurement and supervision functions with the information of relevant hardware for PCS-978S Transformer Relay
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment (module or device) However, it comprises important information that must be followed for personal safety, as well as to avoid material damage Information is highlighted and illustrated
as follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage
Indicates that property damage can result if the measures specified are
not taken
Important information about the device, product handling or a certain section of the documentation which must be given particular attention
Instructions and Warnings
The following hazard statements apply to this device
Disconnect or de-energize all external connections BEFORE opening this
device Contact with hazardous voltages and currents inside this device can cause electrical shock resulting in injury or death
Trang 6Contact with instrument terminals can cause electrical shock that can result in injury or death
Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment
Have only qualified personnel service this equipment If you are not qualified to service this equipment, you can injure yourself or others, or cause equipment damage
This device is shipped with default passwords Default passwords should
be changed to private passwords at installation Failure to change each default password to a private password may allow unauthorized access
NR shall not be responsible for any damage resulting from unauthorized access
DO NOT look into the fiber (laser) ports/connectors
DO NOT look into the end of an optical cable connected to an optical
output
DO NOT perform any procedures or adjustments that this instruction
manual does not describe
During installation, maintenance, or testing of the optical ports, ONLY use the test equipment qualified for Class 1 laser products!
Incorporated components, such as LEDs, transceivers, and laser emitters,
Trang 7are NOT user serviceable Return units to NR for repair or replacement
Equipment components are SENSITIVE to electrostatic discharge (ESD)
Undetectable permanent damage can result if you do not use proper ESD procedures Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment If your facility is not
equipped to work with these components, contact NR about returning this device and related NR equipment for service
Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables Please use the wiring method recommended in the manual for communication terminals
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power Equipment damage can result otherwise
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure
The firmware may be upgraded to add new features or enhance/modify
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand
Document Conventions
The abbreviations and acronyms in this manual are explained in “Appendix A Glossary” The
Trang 8Glossary also contains definitions of important terms
Menu path is connected with the arrow "→" and bold
For example: the access path of protection settings is: MainMenu→Settings→Protection Settings
Settings not in the table should be placed in brackets
For example: the system setting [Opt_SysFreq]
Cross-references are presented in italics
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold
For example: press the button "ENT"
Trang 11on the target sections of this manual as your job needs and responsibilities dictate An overview of each manual section and section topics follows
Trang 127 System Functions
Describes how to perform fundamental operations such as clock synchronization, communicating with the device, switching active setting group, checking relay status, reading event reports and SER (Sequential Events Recorder) records
Describes the abbreviations adopted in this manual
Document Revision History
PN: ZL_PCS-978S_X_Technical Manual_EN_Overseas General_X
Trang 13R1.10 R1.20 2019-12-09
Modification of voltage selection diagram
Update of switchgear control function
Update of VT circuit supervision
Update of technical data
Add switchgear position verification
Add the description about digital substation application
Add the description about digital interface
Add technical data of GOOSE and SV
Add certifications of IEC 61850, DNP, PRP, HSR, IEEE
1588
Add alarm signals of GOOSE and SV
Add NET-DSP plug-in module (NR6112B)
Add SV communication settings
Add GOOSE send links and receiving links
Add SV links
Add reactor protection application scenario
Update of technical data
Add reactor current differential protection function 87R and inter-turn fault protection function 21IT
Add binary input and binary output module NR6661
Add mechanical relay input and output module NR6662
Replace the NET-DSP module NR6112B with NR6113
Deletion of the DC analogue input module NR6631B
Trang 15Figure 1.1-1 Two-winding transformer 1-1
Figure 1.1-2 Three-winding transformer 1-1
Figure 1.1-3 Auto-transformer with two sides 1-2
Figure 1.1-4 Auto-transformer with three sides 1-2
Figure 1.1-5 Typical application of an auto-transformer 1-3
Figure 1.1-6 Typical application of a shunt reactor 1-3
Trang 161
Trang 171
1.1 Application
PCS-978S transformer relay provides fast and selective protection, control and monitoring for
two-winding transformers, three-winding transformers, auto-transformers, as well as shunt
reactors The full transformer protections are configurable by user Ancillary functions of fault
diagnostic, disturbance records, event records and communication function are integrated in the
Trang 18Figure 1.1-4 Auto-transformer with three sides
The function diagrams for protecting an auto-transformer and a reactor are respectively shown below
Trang 1951P Alm 87W 87T
Figure 1.1-5 Typical application of an auto-transformer
52 52
Figure 1.1-6 Typical application of a shunt reactor
Trang 201
The PCS-978S is applicable not only to conventional substations, but also to digital substations It supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network interfaces with high real-time performance The process level network supports peer-to-peer (P2P) mode and networking mode, including single network mode and dual network mode The station level network could also receive and send MMS messages (such as interlocking signals) or process level GOOSE messages (such as trip signals)
1.2 Protection Functions
ANSI Protection Functions Remark
87T Transformer differential protection
Biased differential protection with three slopes
Biased DPFC differential protection
Unrestrained instantaneous differential protection
Optional inrush current distinguished principles: harmonic criterion or waveform distortion
Optional harmonic blocking modes: self-adaptive 1Pblk1P mode, 2PBlk3P mode, 1Pblk3P mode
Overexcitation detection: fifth harmonic or third harmonic criterion
Optional transfer methods: △→Y or Y→△
Independent CT saturation criterion
Differential CT circuit failure supervision
64REF Restricted earth-fault protection
Optional direction element
CT transient characteristic difference detection
CT saturation detection based on 2nd and 3rd harmonics
87W Winding differential protection
CT transient characteristic difference detection
CT saturation detection based on 2nd and 3rd harmonics
87R Reactor differential protection
Biased DPFC differential protection
Biased current differential protection
Independent CT saturation criterion
Harmonic blocking criterion
Differential CT circuit failure supervision
21IT Inter-turn fault protection
Zero-sequence power directional element and zero-sequence impedance element
CT and VT circuit failure blocking
24 Overexcitation protection
Two stages definite-time overexcitation protection
Stage 1 of definite-time overexcitation protection for trip purpose
Stage 2 of definite-time overexcitation protection for alarm purpose
One stage inverse-time overexcitation protection for both alarm purpose and trip purpose
Trang 211
ANSI Protection Functions Remark
67P
50/51P Phase overcurrent protection
6 stages with independent logic by default
Voltage control element for each stage
Optional direction element for each stage
Optional definite-time characteristic and inverse-time characteristic for each stage
Trip purpose or alarm purpose for each stage
Harmonic control element for each stage
67G
50/51G Earth fault protection
4 stages with independent logic by default
Optional direction element for each stage
Optional measured zero-sequence current or calculated zero-sequence current
Optional definite-time characteristic and inverse-time characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
Harmonic control element for each stage
67Q
50/51Q
Negative-sequence overcurrent
protection
Up to 2 stages with independent logic
Optional direction element for each stage
Optional definite-time characteristic and inverse-time characteristic for each stage
49 Thermal overload protection
Two stages thermal overload protection, and one stage for alarm purpose and the other stage for trip purpose
50BF Breaker failure protection
Up to 6 circuit breakers are supported
Phase-segregated re-trip and three-phases re-trip
Optional current criterion (phase overcurrent element, zero-sequence overcurrent element, negative-sequence overcurrent element)
Optional circuit breaker position check
Two time delays
59P Overvoltage protection
Up to 2 stages with independent logic
Optional definite-time characteristic and inverse-time characteristic for each stage
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Selectable trip purpose or alarm purpose for each stage
Trang 221
ANSI Protection Functions Remark
27P Undervoltage protection
Up to 2 stages with independent logic
Optional definite-time characteristic and inverse-time characteristic for each stage
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Blocked by instantaneous VT circuit failure
Selectable trip purpose or alarm purpose for each stage
59G Residual overvoltage protection
Up to 2 stages with independent logic
Optional measured zero-sequence voltage or calculated zero-sequence voltage
Optional definite-time characteristic and inverse-time characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
81O Overfrequency protection Up to 2 stages with independent logic
Voltage control element 81U Underfrequency protection Up to 4 stages with independent logic
Voltage control element
1.3 Control Functions
Switchgear control
Double point status synthesis
Remote/Local control mode switch
Interlocking logic for control
Direct control
Closing synchronism check with voltage selection
Switchgear trip counter
Tap position indicator and control
1.4 Measurement and Metering Functions
Trang 231
1.5 Supervision Functions
CT circuit failure supervision (CTS)
VT circuit failure supervision (VTS)
Self diagnostic
Powerful faults recording (max buffer for 10,000 sampled points at 4.8 or 9.6 kHz)
Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs
Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
Single line diagram representation in display
1.6 Communication Functions
Support of various protocols
Modbus, DNP3.0, IEC 60870-5-103, IEC 61850 Ed.1 & Ed.2, IEC 61850 MMS Server, IEC
61850-8-1 GOOSE, IEC 61850-9-2LE SV, IEC 62439 Parallel Redundancy Protocol, IEC
62439 HSR Ring Redundancy Protocol
Up to four 10Base-T/100Base-TX copper Ethernet ports
Up to fourteen 100Base-FX optical Ethernet ports
Up to four 1000Base-SX optical Ethernet ports
Two RS-485 serial ports for communication or printer
One RS-485/TTL serial port for clock synchronization
Two RJ45 debugging ports (front and rear)
1.7 User Interfaces
Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and set-point
adjustment
Push buttons for open/close, switch for selection between local and remote control, and user's
login and logout authority management
4 Programmable operator pushbuttons with user-configurable labels
Up to 18 programmable target LEDs with user-configurable labels
1 RS-232 or RS-485 rear ports for printer
Language switchover—English+ selected language
Configuration tool—PCS-Studio
Trang 241
1.8 Additional Functions
User programmable logic
Switching system phase sequences function (ABC or ACB)
Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE 1588: Clock message based on IEEE 1588 via optical fibre interface
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
SNTP (BC): Broadcast SNTP mode via Ethernet network
Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol, Modbus protocol and DNP3.0 protocol
Up to 36 analog inputs can be provided and configured flexibly
The tripping output contacts can be configured by tripping matrix, which is flexible, convenient and suitable to any mode of tripping
The relay supports at most 6 branches differential protection The transformer angle can be adjusted flexibly, and any transformer angle compensation mode is supported and any side can be chosen as the reference side of differential protection
Reliable differential CT circuit failure supervision The relay can detect multi-phase CT wire-break, multi-side CT wire-break, short-circuit, and other complex situation The corresponding logic setting can be used to select blocking differential protection or not, in case
of CT circuit failure
Multiple inrush current blocking options are provided Self-adaptive inrush current blocking
Trang 251
criterion can ensure the relay fast operation for transformer energized on to a slight fault,
meanwhile it will avoid the unwanted operation in the case of the energization inrush current
caused by energizing transformer with no load, the recovery inrush current caused by cutting
off the transformer external fault, and the sympathetic inrush current
Biased DPFC differential protection is regardless of load current and is sensitive to small
internal fault current within the transformer Its anti CT saturation performance is also strong
Trang 282
2.9 Measurement Scope and Accuracy 2-13 2.10 Management Function 2-13
2.10.1 Control Performance 2-13 2.10.2 Clock Performance 2-13 2.10.3 Fault and Disturbance Recording 2-14 2.10.4 Binary Input Signal 2-14
2.11 Protective Functions 2-14
2.11.1 Transformer Current Differential Protection (87T) 2-14 2.11.2 Restricted Earth Fault Protection (64REF) 2-15 2.11.3 Winding Differential Protection (87W) 2-15 2.11.4 Reactor Differential Protection (87R) 2-16 2.11.5 Inter-turn Fault Protection (21IT) 2-16 2.11.6 Overexcitation Protection (24) 2-16 2.11.7 Phase Overcurrent Protection (50/51P, 67P) 2-17 2.11.8 Earth Fault Overcurrent Protection (50/51G, 67G) 2-17 2.11.9 Negative-sequence Overcurrent Protection (50/51Q, 67Q) 2-18 2.11.10 Thermal Overload Protection (49) 2-19 2.11.11 Breaker Failure Protection (50BF) 2-19 2.11.12 Overvoltage Protection (59P) 2-19 2.11.13 Residual Overvoltage Protection (59G) 2-20 2.11.14 Undervoltage Protection (27P) 2-20 2.11.15 Overfrequency Protection (81O) 2-20 2.11.16 Underfrequency Protection (81U) 2-20
2.12 Communication Functions 2-21
2.12.1 GOOSE 2-21 2.12.2 SV 2-21
Trang 292
2.1 Electrical Specifications
“System phase sequence”, which can be set by PCS-Studio, this setting
informs the device of the actual system phase sequence, either ABC or ACB CT and VT inputs on the device, labeled as A, B and C, must be connected to system phase A, B and C for correct operation
Number Up to 24 (6U, 1/2 × 19") or 36 (6U, 1/1 × 19") AC current inputs
600V 660V
Phase-to-phase 519V
1038V 1141V
Trang 30Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
Quiescent condition Max 1W
Additional for each contact
0.004W @24Vdc 0.008W @48Vdc 0.015W @110Vdc 0.32W @220Vdc 0.41W @250Vdc
Additional for each plug-in binary output (BO) module
Quiescent condition Max 0.1W Additional for each relay while
operating
Max 0.44W
Additional for each plug-in
SV sampling (NET-DSP) module
Number Up to 8 (ring ferrule) or 12 (pin ferrule) channels of DC analogue inputs,
all of the channels can be set as 0~±20mA or 0~±10Vdc
Trang 312
2.1.5 Binary Input
Settable pickup voltage and dropout voltage
On value (default set) 69.3~132Vdc 78.75~160Vdc 138.6~264Vdc 157.5~300Vdc
Off value (default set) <55Vdc <62.5Vdc <110Vdc <125Vdc
Maximum permissible voltage 300Vdc
Withstand voltage 2000Vac, 2800Vdc (1min)
Number
Up to 84 (6U, 1/2 × 19", ring ferrule), 105 (6U, 1/2 × 19", pin ferrule), 234 (6U, 1/1 × 19", ring ferrule), or 297 (6U, 1/1 × 19", pin ferrule) binary inputs
Settable pickup voltage and dropout voltage
Maximum permissible voltage 300Vac
Withstand voltage 2000Vac, 2800Vdc (1min)
Number
Up to 84 (6U, 1/2 × 19", ring ferrule), 105 (6U, 1/2 × 19", pin ferrule), 234 (6U, 1/1 × 19", ring ferrule), or 297 (6U, 1/1 × 19", pin ferrule) binary inputs
Settable pickup voltage and dropout voltage
Maximum permissible voltage 300Vdc
Withstand voltage 2000Vac, 2800Vdc (1min)
Number Up to 84 (6U, 1/2 × 19", ring ferrule), 105 (6U, 1/2 × 19", pin ferrule), 234
(6U, 1/1 × 19", ring ferrule), or 297 (6U, 1/1 × 19", pin ferrule) binary
Trang 32Maximum permissible voltage 121Vdc
Withstand voltage 2000Vac, 2800Vdc (1 min)
Number Up to 5 (6U, 1/2 × 19", pin ferrule) or 15 (6U, 1/1 × 19", pin ferrule) MR
Maximum permissible voltage 137.5Vdc
Withstand voltage 2000Vac, 2800Vdc (1 min)
Maximum permissible voltage 242Vdc
Withstand voltage 2000Vac, 2800Vdc (1 min)
Number
Up to 5 (6U, 1/2 × 19", pin ferrule) or 15 (6U, 1/1 × 19", pin ferrule) MR inputs
Trang 332
2.1.6 Binary Output
Tripping/signaling contact
Pickup time (Typical value) <5ms
Dropout time (Resistive load) <6ms
Breaking capacity (L/R=40ms)
0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc
Cyclic Capacity (2.5 cycle/second,
L/R=40ms)
0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc
Short duration current
30A@3s 50A@1s Durability (Loaded contact) 10000 operations
Number
Up to 44 (6U, 1/2 × 19", ring ferrule), 56 (6U, 1/2 × 19", pin ferrule), 122 (6U, 1/1 × 19", ring ferrule), or 158 (6U, 1/1 × 19", pin ferrule) tripping/signal contacts
Heavy-capacity tripping contact
MOV Protection (Max voltage ) 350Vdc, 275Vac
Pickup time (Typical value) <1ms
Dropout time (Resistive load) <10ms
Trang 342
Breaking capacity (L/R=40ms)
10A@48V 10A@110V 10A@125V 10A@250V
Cyclic Capacity (4 cycle/second,
followed by 2 minutes idle for thermal
dissipation)
10A@48V L/R=40ms 10A@110V L/R=40ms 10A@125V L/R=40ms 10A@250V L/R=20ms
Short duration current
30A@3s 50A@1s Durability (Loaded contact) 10000 operations
Number
Up to 12 (6U, 1/2 × 19", ring ferrule), or 36 (6U, 1/1 × 19", ring ferrule) heavy-capacity tripping contacts
MR (Mechanical Relay) contact
Pickup time (Typical value) <10ms
Dropout time (Resistive load) <10ms
Breaking capacity (L/R=40ms)
1.00A@48Vdc 0.50A@110Vdc 0.40A@125Vdc 0.25A@220Vdc 0.20A@250Vdc
Short duration current
12A@3s 15A@1s 20A@0.5s 30A@0.2s
Trang 352
Durability (Loaded contact) 10000 operations
Number Up to 15 (6U, 1/2 × 19", pin ferrule) or 45 (6U, 1/1 × 19", pin ferrule) MR
outputs
2.2 Mechanical Specifications
Weight per device
Approx 8.66kg (6U, 1/2 × 19") Approx 15.27kg (6U, 1/1 × 19")
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated front plate
Protection Class
Front side
IP52 IP54 (valid for surface mounting mode of 6U 19" × 1/2 case with sealing strip)
Rear side, connection terminals IP20
2.3 Ambient Temperature and Humidity Range
Trang 362
2.4 Communication Port
2.4.1 EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Transmission distance Max 500m
2.4.2 Copper Ethernet Por
Transmission standard 100Base-TX
2.4.3 Optical Ethernet Port
Transmission standard 100Base-FX
Transmission distance Max 2km
Trang 372
Transmission standard 1000Base-SX
Transmission distance
Max 500m (50/125μm) Max 300m (62.5/125μm)
2.4.4 Print Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
2.4.5 Clock Synchronization Port
Damp heat test, cyclic IEC60068-2-30:2005
2.5.2 Mechanical Tests
Shock and bump IEC 60255-21-2:1988 Class Ⅰ
Trang 382
2.5.3 Electrical Tests
Dielectric tests Test voltage 2kV, 50Hz, 1min
Impulse voltage tests Test voltage 5kV
Electrostatic discharge test
IEC 61000-4-2-2008 class Ⅳ For contact discharge: 8kV For air discharge: 15kV
Radio frequency interference tests
IEC 60255-26:2013 class Ⅲ Frequency sweep
Radiated amplitude-modulated 10V/m (rms), f=80~1000MHz, 1400~2700MHz Spot frequency
Radiated amplitude-modulated 10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Fast transient disturbance tests
IEC 60255-26:2013 Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns
Surge immunity test
IEC 60255-26:2013 Power supply, AC input, I/O port: class Ⅳ, 1.2/50us Common mode: 4kV
Differential mode: 2kV Conducted RF electromagnetic IEC 60255-26:2013
Trang 392
disturbance Power supply, AC, I/O, Comm Terminal: Class Ⅲ , 10V (rms),
150kHz~80MHz Spot frequency 10V (rms), f=27MHz/68MHz Power frequency magnetic field
Immunity
IEC 61000-4-8: 2009 class Ⅴ, 100A/m for 1min, 1000A/m for 3s
Pulse magnetic field immunity
IEC 61000-4-9:2016 class Ⅴ, 6.4/16μs, 1000A/m for 3s Damped oscillatory magnetic field
immunity
IEC 61000-4-10:2016 class Ⅴ, 100kHz & 1MHz–100A/m
Conducted emission
IEC 60255-26:2013 0.15MHz~0.50MHz: 79dB (μV) quasi peak, 66dB (μV) average 0.50MHz~30MHz: 73dB (μV) quasi peak, 60dB (μV) average
Radiated emission
IEC 60255-26:2013
Below 1GHz
30MHz~230MHz: 40dB (μV/m) quasi peak @10m, 50dB (μV/m) quasi peak @3m
230MHz~1000MHz: 47dB (μV/m) quasi peak @10m, 57dB (μV/m) quasi peak @3m
Above 1GHz
1GHz~3GHz: 56dB (μV/m) average, 76dB (μV/m) peak @3m
3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m) peak @3m
Auxiliary power supply performance
50ms for interruption without rebooting without energy storage board (Typical configuration)
500ms for interruption without rebooting with energy
Trang 40 EMC: 2014/30/EU, EN60255-26:2013
Products safety (LVD): 2014/35/EU, EN60255-27:2014
IEC 61850: Edition 2, Parts 6, 7-1, 7-2, 7-3,7-4 and 8-1
IEC 61850: Edition 2, GOOSE Performance Class P1 (3ms)
IEEE 1588: IEEE Std C37.238TM-2017
DNP: DNP 3.0
PRP: IEC 62439-3 Ed.3 (IS 2016)
HSR: IEC 62439-3 Ed.3 (IS 2016)
2.7 Liquid Crystal Display (LCD)
2.8 Terminals
2.8.1 Ring Ferrule
Connection Type Wire Size Screw Type Torque