1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

PCS 9613s x technical manual EN overseas general x r1 01

451 25 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề PCS S Series Device
Trường học NR Electric Co., Ltd.
Chuyên ngành Technical Manual
Thể loại Technical Manual
Năm xuất bản 2019
Thành phố P.R. China
Định dạng
Số trang 451
Dung lượng 11,18 MB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Nội dung

This relay is suitable for wall surface mounted indoors or outdoors or flush mounted into a control FR 52 Figure 1.1-1 Functional diagram of PCS-9613S 1.2 Functions 1 Protection funct

Trang 3

Copyright © 2019 NR All rights reserved

NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may

be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights

The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice

To the extent required the products described herein meet applicable IEC and IEEE standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly

Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us

Trang 5

Preface

About This Manual

The technical manual describes the protection, automation, control, and supervision functions of PCS S series device, and contains operation principle descriptions, and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data, sorted per function, as well as the hardware of the device The manual can be used as a technical reference during the engineering phase and during normal service In addition, the manual also includes a glossary that lists and defines technical terms used throughout the manual

Safety Information

This manual is not a complete index of all safety measures required for operation of the equipment (module or device) However, it comprises important information that must be followed for personal safety, as well as to avoid material damage Information is highlighted and illustrated

as follows according to the degree of danger:

Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury

Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury

Indicates a potentially hazardous situation that, if not avoided, may result

in minor or moderate injury or equipment damage

Indicates that property damage can result if the measures specified are

not taken

Important information about the device, product handling or a certain section of the documentation which must be given particular attention

Instructions and Warnings

The following hazard statements apply to this device

Disconnect or de-energize all external connections BEFORE opening this

device Contact with hazardous voltages and currents inside this device

Trang 6

Contact with instrument terminals can cause electrical shock that can result in injury or death

Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment

Have only qualified personnel service this equipment If you are not qualified to service this equipment, you can injure yourself or others, or cause equipment damage

This device is shipped with default passwords Default passwords should

be changed to private passwords at installation Failure to change each default password to a private password may allow unauthorized access

NR shall not be responsible for any damage resulting from unauthorized access

DO NOT look into the fiber (laser) ports/connectors

DO NOT look into the end of an optical cable connected to an optical

output

DO NOT perform any procedures or adjustments that this instruction

manual does not describe

During installation, maintenance, or testing of the optical ports, ONLY use

Trang 7

Incorporated components, such as LEDs, transceivers, and laser emitters,

are NOT user serviceable Return units to NR for repair or replacement

Equipment components are SENSITIVE to electrostatic discharge (ESD)

Undetectable permanent damage can result if you do not use proper ESD procedures Ground yourself, your work surface, and this equipment

BEFORE removing any cover from this equipment If your facility is not

equipped to work with these components, contact NR about returning this device and related NR equipment for service

Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage For external circuits, use wiring

of SUFFICIENTLY RATED insulation that will not break down under

abnormal operating conditions

SEVERE power and ground problems can occur on the communications

ports of this equipment as a result of using non-standard cables Please use the wiring method recommended in the manual for communication terminals

DO NOT connect power to the relay until you have completed these

procedures and receive instruction to apply power Equipment damage can result otherwise

Use of controls or adjustments, or performance of procedures other than

those specified herein, may RESULT IN hazardous radiation exposure

The firmware may be upgraded to add new features or enhance/modify

existing features, please MAKE SURE that the version of this manual is

compatible with the product in your hand

Trang 8

 The abbreviations and acronyms in this manual are explained in “Appendix A Glossary” The Glossary also contains definitions of important terms

 Menu path is connected with the arrow "→" and bold

For example: the access path of protection settings is: MainMenu→Settings→Protection

Settings

 Settings not in the table should be placed in brackets

For example: the system setting [Opt_SysFreq]

 Cross-references are presented in italics

For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1

 Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold

For example: press the button "ENT"

Trang 11

Provides information on viewing fundamental and metering quantities for voltages and currents,

as well as power and energy metering data

6 Supervision

Trang 12

device operation problems

7 System Functions

Describes how to perform fundamental operations such as clock synchronization, communicating with the device, switching active setting group, checking relay status, reading event reports and SER (Sequential Events Recorder) records

8 Hardware

Describes the hardware of the PCS S series device family and provides general information on the product structure and the modules’ information

9 Settings

Provides a list of all PCS-9613S settings and their ranges, unit, steps, defaults The organization

of the settings is similar to the settings organization in the device and in the PCS-Studio configuration tool

Appendix A Glossary

Describes the abbreviations adopted in this manual

Document Revision History

PN: ZL_PCS-9613S_X_Technical Manual_EN_Overseas General_X

Trang 14

1

Trang 15

1

The PCS-9613S relay can provide current differential protection, measurement, control and

monitoring functions for the feeder line in all systems of which the neutral point is effectively

grounded or not effectively grounded Many auxiliary functions such as fault location, fault

recording, event recording, communication functions and etc are also integrated into the device

This relay is suitable for wall surface mounted indoors or outdoors or flush mounted into a control

FR 52

Figure 1.1-1 Functional diagram of PCS-9613S

1.2 Functions

1 Protection functions

ANSI Protection Functions Remark

87 Current differential protection  Steady-state current differential element (2 stages)

 CT saturation detection

Trang 16

1 67P

50/51P Phase overcurrent protection

 Optional direction element for each stage, including forward direction, reverse direction and non-direction

 Optional definite-time characteristic and inverse-time characteristic for each stage

 Selectable trip purpose or alarm purpose for each stage

 Harmonic control element for each stage

67G 50/51G Earth fault protection

 Up to 6 stages with independent logic

 Optional direction element for each stage, including forward direction, reverse direction and non-direction

 Optional measured zero-sequence current or calculated zero-sequence current

 Optional definite-time characteristic and inverse-time characteristic for each stage

 Selectable trip purpose or alarm purpose for each stage

 Harmonic control element for each stage

50/51Q Negative-sequence overcurrent

protection

 Up to 2 stages with independent logic

 Optional direction element for each stage, including forward direction, reverse direction and non-direction

 Optional definite-time characteristic and inverse-time characteristic for each stage

 Selectable trip purpose or alarm purpose for each stage

50/51R RMS overcurrent protection

 Up to 2 stages with independent logic

 Full-current RMS value includes 2nd~11th harmonic component

 Selectable trip purpose or alarm purpose for each stage

37 Undercurrent protection

 Optional blocking condition, including circuit breaker position and current criterion

 Optional “1-out-of-3” logic or “3-out-of-3” logic

 Selectable trip purpose or alarm purpose for each stage

50BF Breaker failure protection

 Breaker failure protection and re-trip function

 Optional current criterion (phase overcurrent element, zero-sequence overcurrent element, negative-sequence overcurrent element)

 It can be initiated by current, circuit breaker position or external binary input

 Two time delays

50PSOTF

50GSOTF Switch-on-to-fault protection

 One stage of phase overcurrent SOTF protection

 One stage of earth fault overcurrent SOTF protection

 Harmonic control element

 Voltage control element for phase overcurrent SOTF protection

Trang 17

1

59P Overvoltage protection characteristic for each stage

 Optional phase voltage or phase-to-phase voltage

 Optional “1-out-of-3” logic or “3-out-of-3” logic

 Selectable trip purpose or alarm purpose for each stage

27P Undervoltage protection

 Up to 2 stages with independent logic

 Optional definite-time characteristic and inverse-time characteristic for each stage

 Optional phase voltage or phase-to-phase voltage

 Optional “1-out-of-3” logic or “3-out-of-3” logic

 Check mode using circuit breaker position and current criterion

 Blocked by instantaneous VT circuit failure

 Selectable trip purpose or alarm purpose for each stage 59Q Negative-sequence overvoltage

protection

 Up to 2 stages with independent logic

 Selectable trip purpose or alarm purpose for each stage 59Pos Positive-sequence overvoltage

protection

 One stage of positive-sequence overvoltage protection

 Selectable trip purpose or alarm purpose 59G Residual overvoltage protection  Up to 2 stages with independent logic

 Selectable trip purpose or alarm purpose for each stage 81O Overfrequency protection  Up to 6 stages with independent logic

 Voltage control element 81U Underfrequency protection  Up to 6 stages with independent logic

 Voltage control element 81R Frequency rate-of-change

protection

 Up to 6 stages with independent logic

 Voltage control element 32R Reverse power protection  Up to 2 stages with independent logic

 Selectable trip purpose or alarm purpose for each stage

25 Synchro-check  Independent logic for auto-reclosing and manually closing

VTS Voltage transformer supervision

TCS Tripping circuit supervision

2 Control functions

 Circuit breaker & disconnector control (Remote/Local)

 Synchronism check for remote and manual closing

3 Measurement functions

Trang 18

 DC power supply supervision

 System frequency supervision

 Two RS-485 serial ports using IEC 60870-5-103

 One RS-485 serial port for clock synchronization

 Support GOOSE communication module using IEC 61850-8-1 GOOSE

 Full compatibility between IEC 61850 Editions 1 and 2

 Redundancy protocols PRP and HSR

 One front RJ45 port for debugging

Trang 19

1

 Up to 15/18 (1/3U or 1/2U chassis) programmable target LEDs with user-configurable

labels

 1 RS-232 or RS-485 rear ports for printer

 Language switchover—English+ selected language

 Configuration tool—PCS-Studio

7 Additional functions

 User programmable logic

 Fault location

 Fault phase selection

 System phase sequences rotation function (ABC or ACB)

 Clock synchronization

 IRIG-B: IRIG-B via RS-485 differential level or TTL level

 PPS: Pulse per second (PPS) via RS-485 differential level or binary input

 PPM: Pulse per minute (PPM) via RS-485 differential level or binary input

 IEEE1588: Clock message based on IEEE1588 via optical fiber interface

 SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network

 SNTP (BC): Broadcast SNTP mode via Ethernet network

 Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol,

Modbus protocol and DNP3.0 protocol

 Unified software and hardware platform, comprehensive power grid solutions of protection,

control, measurement and monitoring, easy to use and maintain

 High reliability and redundancy design for drive systems of the sampling circuit and the output

circuit ensure that overall reliability of the device is high Real-time sampling based on dual AD

Trang 20

1 which can prevent from undesired operation caused by the abnormality of drive circuit of

output relays

 Various function modules can satisfy various situations according to the different requirements

of users Flexible and universal logic programming, user-defined configuration of BI/BOs, buttons and LEDs and powerful analogue programming are supported

 Modularized hardware design makes the device be easily upgraded or repaired by a qualified service person It can be combined with different I/O modules, with online self-check and monitoring function, and the device can be restored from abnormal operation only need to replace a single abnormal module

 Support memory check and error correction function, ensure high reliability and safety

 Support the internet communication protocol of native PRP/HSR and RSTP

 Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351 communication service, GOOSE communication in station level & process level, SV communication with multi-sampling rate

 Fully comply with cyber security standards, including IEC62443, IEC62351, IEEE1686, NERC-CIP, support role based access control (RBAC), security audit, security encryption communication and security tool, improve the cyber security capability of devices

 Powerful COMTRADE fault and disturbance recording function is supported The whole recording time is automatically configurable by the fault duration, which is convenient to fault analysis and replay The recording sample rate is up to 9.6kHz

 Settable secondary rated current (1A/5A) and settable voltage threshold of binary input

 Support small size and large size LCD, control and multifunction button

 Support flush mounting, semi-flush mounting, surface mounting, wall mounting and other mounting methods

 Cross screw IO, CT/VT terminals can support AWG12 specification connector and 4mm2 lead

 Multiple variants with case size 1/3 or 1/2 × 19"

 Protection class of front side is up to IP54

 PCS-Studio engineering tool is the application software on the user's PC for the interface with PCS S series devices providing all the related functionality It ranges from device configuration

to entire substation design of bay integration

 Support IEEE1588, IRIG-B clock synchronization

 Support actual system phase sequence, either ABC or ACB, incorrect connection of actual phase sequence can automatically be verified and relevant protection functions can be

Trang 21

1

abnormality in advance

 Support setup up to 40 users and allow each user to own different password and access

authority

 Fully integrates multi functions into one device and can realize the protection and monitoring

function of feeder line

 Current differential protection

 Two-terminal transmission line application

 Phase-segregated differential protection employs steady quantities as protection criteria,

easy to set, quick to clear the fault, high sensitivity and immune to power swing and load

fluctuation

 Current differential protection has the excellent resistance to CT saturation when external

fault As long as the correct transfer time is no less than 3ms, current differential

protection will ensure fast clearance of internal fault and non-operation of external fault

 Current differential protection supports double fiber channel, parallel and independent,

either can be selected as main channel and seamlessly switched to standby channel

when main channel is abnormal

 Unique and reliable differential logic and it can be set non-operation when CT circuit

failure under normal conditions

 Both dedicated fiber channel and multiplexing fiber channel are supported, and single mode

and multi-mode channel combination operation mode is enable Communication rate supports

64kbit/s and 2Mbit/s, and communication protocol supports C37.94 and G.703

 Comprehensive functionality includes phase overcurrent protection, earth fault overcurrent

protection, negative-sequence overcurrent protection, overvoltage protection, undervoltage

protection, frequency protection, reverse power protection, breaker failure protection,

undercurrent protection etc The breaker failure, reclosing, measuring, monitoring and control

function are supported

 The overcurrent protection is combined with harmonic blocking logic, which can prevent

mal-operation affected by inrush current while the transformer is no-load energized

 Selectable IEC, ANSI inverse-time characteristic curves that can be defined by users, and the

inverse-time drop-out curve selection is supported

 Overvoltage and undervoltage protection support single phase and three phase operation

criteria setting, phase voltage and phase-to-phase voltage measurement mode are selectable,

which can be for various applications

 Complete event recording function is provided: 64 latest protection operation reports, 1024

Trang 22

1

Trang 24

2

2.10.2 Clock Performance 2-12 2.10.3 Fault and Disturbance Recording 2-12 2.10.4 Binary Input Signal 2-12

2.11 Protective Functions 2-12

2.11.1 Fault Detector (FD) 2-12 2.11.2 Current Differential Protection (87L) 2-13 2.11.3 Phase Overcurrent Protection (50/51P) 2-13 2.11.4 Earth Fault Protection (50/51G) 2-14 2.11.5 Negative-sequence Overcurrent Protection (50/51Q) 2-15 2.11.6 RMS Overcurrent Protection (50/51R) 2-16 2.11.7 Phase Overvoltage Protection (59P) 2-16 2.11.8 Residual Overvoltage Protection (59G) 2-16 2.11.9 Negative-sequence Overvoltage Protection (59Q) 2-16 2.11.10 Positive-sequence Overvoltage Protection (59Pos) 2-17 2.11.11 Phase Undervoltage Protection (27P) 2-17 2.11.12 Overfrequency Protection (81O) 2-17 2.11.13 Underfrequency Protection (81U) 2-17 2.11.14 Frequency Rate-of-change Protection (81R) 2-18 2.11.15 Reverse Power Protection (32R) 2-18 2.11.16 Undercurrent Protection (37) 2-18 2.11.17 Breaker Failure Protection (50BF) 2-19 2.11.18 Switch-on-to-Fault Protection (SOTF) 2-19 2.11.19 Auto-reclosing (79) 2-19 2.11.20 Transient Overreach 2-19 2.11.21 Fault Locator 2-20

Trang 25

2

“System phase sequence”, which can be set by PCS-Studio, this setting

informs the device of the actual system phase sequence, either ABC or ACB CT and VT inputs on the device, labelled as A, B and C, must be connected to system phase A, B and C for correct operation

Number Up to 4 current inputs according to various applications

600V 660V

Phase-to-phase 519V

1038V 1141V

Trang 26

Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage

Burden

Quiescent condition <15W (Default hardware configuration)

Additional for each energized SFP

0.25W ~ 0.35W

Additional for each BI module

Quiescent condition : <1W Additional for each energized binary input:

0.004W @ 24VDC 0.008W @ 48VDC 0.015W @ 110VDC 0.32W @ 220VDC 0.41W @ 250VDC Additional for each BO

module

Quiescent condition: <0.1W Additional for each energized binary output: <0.44W Additional module for SV

Trang 27

2

Maximum permissible voltage 300Vdc

Withstand voltage 2000Vac, 2800Vdc (continuously)

Number

Up to 34 (6U, 1/3, ring ferrule), 41 (6U, 1/3, pin ferrule), 84 (6U, 1/2, ring ferrule) or 105 (6U, 1/2, pin ferrule) binary inputs according to various hardware configurations

Settable pickup voltage and dropout voltage

Maximum permissible voltage 300Vac

Withstand voltage 2000Vac, 2800Vdc (continuously)

Number

Up to 34 (6U, 1/3, ring ferrule), 41 (6U, 1/3, pin ferrule), 84 (6U, 1/2, ring ferrule) or 105 (6U, 1/2, pin ferrule) binary inputs according to various hardware configurations

Settable pickup voltage and dropout voltage

Maximum permissible voltage 300Vdc

Withstand voltage 2000Vac, 2800Vdc (continuously)

Number

Up to 34 (6U, 1/3, ring ferrule), 41 (6U, 1/3, pin ferrule), 84 (6U, 1/2, ring ferrule) or 105 (6U, 1/2, pin ferrule) binary inputs according to various hardware configurations

Trang 28

2

Tripping/signalling contact

Pickup time (Typical value) <5ms

Dropout time (Resistive load) <6ms

Breaking capacity (L/R=40ms)

0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc

Cyclic Capacity (2.5 cycle/second,

L/R=40ms)

0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc

Short duration current

30A@3s 50A@1s Durability (Loaded contact) 10000 operations

Number

Up to 18 (6U, 1/3, ring ferrule), 22 (6U, 1/3, pin ferrule), 44 (6U, 1/2, ring ferrule) or 56 (6U, 1/2, pin ferrule) binary outputs according to various hardware configurations

Heavy-capacity tripping contact

MOV Protection (maximum voltage ) 350Vdc, 275Vac

Trang 29

2

Breaking capacity (L/R=40ms)

10A@48V 10A@110V 10A@125V 10A@250V

Cyclic Capacity (4cycles in 1 second,

followed by 2 minutes idle for thermal

dissipation)

10A@48V L/R=40ms 10A@110V L/R=40ms 10A@125V L/R=40ms 10A@250V L/R=20ms

Short duration current

30A@3s 50A@1s Durability (Loaded contact) 10000 operations

Number

Up to 4 (6U, 1/3, ring ferrule) or 12 (6U, 1/2, ring ferrule) heavy-capacity binary outputs according to various hardware configurations

2.2 Mechanical Specifications

Weight per device

Approx 8.66kg (6U, 1/2) Approx 6.93kg (6U, 1/3)

Location of terminal Rear panel of the device

Device structure Plug-in modular type @ rear side, integrated front plate

Protection Class

Rear side, connection terminals IP20

Trang 30

Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s

2.4.2 Ethernet Port

Trang 31

2

For Station Level and Process Level

Transmission power 50μm: Minimum -24dBm 62.5μm: Minimum -20dBm

Minimum receiving power Minimum -31dBm

For Differential Communications

2.4.4 Print Port

Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s

2.4.5 Clock Synchronization Port

Trang 32

Damp heat test, cyclic IEC60068-2-30:2005

2.5.2 Mechanical Tests

2.5.3 Electrical Tests

Dielectric tests Test voltage 2kV, 50Hz, 1min

Impulse voltage tests Test voltage 5kV

Electrostatic discharge test

IEC 61000-4-2:2008 class Ⅳ For contact discharge: 8kV

Trang 33

2

Radio frequency interference tests

Frequency sweep Radiated amplitude-modulated 10V/m (rms), f=80~1000MHz, 14000~2700MHz Spot frequency

Radiated amplitude-modulated 10V/m (rms), f=80MHz/160MHz/450MHz/900MHz

Fast transient disturbance tests

IEC 60255-26:2013 Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns

Surge immunity test

IEC 60255-26:2013 Power supply, AC input, I/O port: class Ⅳ, 1.2/50μs Common mode: 4kV

Differential mode: 2kV

Conducted RF Electromagnetic

Disturbance

IEC 60255-26:2013 Power supply, AC, I/O, Comm Terminal: Class Ⅲ, 10Vrms, 150 kHz~80MHz

Spot frequency 10V/m (rms), f=27MHz/68MHz Power Frequency Magnetic Field

Immunity

IEC 61000-4-8: 2009 class Ⅴ, 100A/m for 1min, 1000A/m for 3s

Pulse Magnetic Field Immunity

IEC 61000-4-9:2016 class Ⅴ, 6.4/16μs, 1000A/m for 3s Damped oscillatory magnetic field

immunity

IEC 61000-4-10:2016 class Ⅴ, 100kHz & 1MHz–100A/m

Conducted emission

IEC 60255-26:2013 0.15MHz~0.50MHz: 79dB (μV) quasi peak, 66dB (μV) average 0.50MHz~30MHz: 73dB (μV) quasi peak, 60dB (μV) average

Trang 34

2

Below 1GHz

50dB (μV/m) quasi peak @3m 230MHz~1000MHz: 47dB (μV/m) quasi peak @10m, 57dB (μV/m) quasi peak @3m

Above 1GHz

1GHz~3GHz: 56dB (μV/m) average, 76dB (μV/m) peak @3m

3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m) peak @3m

Auxiliary power supply performance

500ms for interruption without rebooting with energy storage board (Typical configuration)

 EMC: 2014/30/EU, EN60255-26:2013

 Products safety (LVD): 2014/35/EU, EN60255-27:2014

2.7 Liquid Crystal Display (LCD)

Trang 35

2

2.8 Terminals

2.8.1 Ring Ferrule

Connection Type Wire Size Screw Type Torque

Grounding (Earthing) Connection BVR type, 0.8~4mm2 lead M3 0.6~0.8 N⋅m

2.8.2 Pin Ferrule

Connection Type Wire Size Screw Type Torque

2.9 Measurement Scope and Accuracy

Item Range Accuracy

≤ 2.0% of rating (0.05~1.00In, 0.05~1.00Un)

≤ 1.0% of applied quantities (1.00~4.00In, 1.00~1.50Un)

Reactive power (VAr)

0.05~1.50Un 0.05~4.00In

≤ 2.0% of rating (0.05~1.00In, 0.05~1.00Un)

≤ 1.0% of applied quantities (1.00~4.00In, 1.00~1.50Un)

Trang 36

2

0.05~4.00In ≤ 1.0% of applied quantities (1.00~4.00In, 1.00~1.50Un)

Energy (Wh)

0.05~1.50Un 0.05~4.00In

≤ 2.0% of rating (0.05~1.00In, 0.05~1.00Un)

≤ 1.0% of applied quantities (1.00~4.00In, 1.00~1.50Un)

Energy (VAh)

0.05~1.50Un 0.05~4.00In

≤ 2.0% of rating (0.05~1.00In, 0.05~1.00Un)

≤ 1.0% of applied quantities (1.00~4.00In, 1.00~1.50Un)

2.10 Management Function

2.10.1 Control Performance

Response time of local control ≤1s

Response time of remote control ≤3s

2.10.2 Clock Performance

Real time clock accuracy ≤1s/day

Accuracy of GPS synchronization ≤1ms

External time synchronization IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol

2.10.3 Fault and Disturbance Recording

Duration & Recording position Settable pre-disturbance, post-disturbance and maximum recorded

duration

2.10.4 Binary Input Signal

Resolution of binary input signal ≤1ms

Binary input mode Potential-free contact

2.11 Protective Functions

2.11.1 Fault Detector (FD)

2.11.1.1 DPFC Current Element

Trang 37

2

Current setting accuracy ≤2.5%×Setting or 0.02In, whichever is greater

2.11.2 Current Differential Protection (87L)

Current setting accuracy ≤2.5%×Setting or 0.01In, whichever is greater

Pickup time ≤30ms (at 2 times current setting)

Maximum operating time (at 4 times

current setting)

<30ms (Steady-state current differential element)

Minimum operating time (at 4 times

current setting)

<20ms (Steady-state current differential element)

2.11.3 Phase Overcurrent Protection (50/51P)

Without direction controlled element

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy

(Definite-time characteristics) ≤1%×Setting or 25ms (at 2 times current setting)

Operating time delay accuracy

(Inverse-time characteristics) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)

Dropout time accuracy (Definite-time

Dropout time accuracy (Inverse-time

characteristics) ≤5% of calculated value or 30ms

With direction controlled element

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Trang 38

2

Operating time delay accuracy

(Definite-time characteristics) ≤1%×Setting or 40ms (at 2 times current setting)

Operating time delay accuracy

(Inverse-time characteristics) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30) Dropout time accuracy (Definite-time

Dropout time accuracy (Inverse-time

characteristics) ≤5% of calculated value or 30ms

2.11.4 Earth Fault Protection (50/51G)

Without direction controlled element

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy

(Definite-time characteristics) ≤1%×Setting or 25ms (at 2 times current setting)

Operating time delay accuracy

(Inverse-time characteristics) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30) Dropout time accuracy (Definite-time

Dropout time accuracy (Inverse-time

characteristics) ≤5% of calculated value or 30ms

With direction controlled element

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤40ms (at 2 times current setting)

Operating time delay accuracy

(Definite-time characteristics) ≤1%×Setting or 40ms (at 2 times current setting)

Operating time delay accuracy

≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)

Trang 39

2

characteristics) ≤5% of calculated value or 30ms

2.11.5 Negative-sequence Overcurrent Protection (50/51Q)

Without direction controlled element

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy

(Definite-time characteristics) ≤1%×Setting or 25ms (at 2 times current setting)

Operating time delay accuracy

(Inverse-time characteristics) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)

Dropout time accuracy (Definite-time

Dropout time accuracy (Inverse-time

characteristics) ≤5% of calculated value or 30ms

With direction controlled element

Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤40ms (at 2 times current setting)

Operating time delay accuracy

(Definite-time characteristics) ≤1%×Setting or 40ms (at 2 times current setting)

Operating time delay accuracy

(Inverse-time characteristics) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)

Dropout time accuracy (Definite-time

Dropout time accuracy (Inverse-time

characteristics) ≤5% of calculated value or 30ms

Trang 40

2

Current setting accuracy ≤2.5%×Setting or 0.01In, whichever is greater

Pickup time ≤25ms (at 2 times current setting)

Operating time delay accuracy ≤1%×Setting or 25ms (at 2 times current setting)

Dropout time accuracy ≤1%×Setting or 30ms

2.11.7 Phase Overvoltage Protection (59P)

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤35ms (at 1.1 times voltage setting)

Operating time delay accuracy

(Definite-time characteristics) ≤1%×Setting or 35ms (at 1.1 times voltage setting)

Operating time accuracy

(Inverse-time characteristics) ≤5% of calculated value + 1% voltage tolerance or 40ms (1.1≤U/Up≤2) Dropout time accuracy ≤1%×Setting or 30ms

Dropout ratio Settable 0.93~1.00, default value: 0.98

2.11.8 Residual Overvoltage Protection (59G)

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤35ms (at 1.1 times voltage setting)

Operating time delay accuracy ≤1%×Setting or 35ms (at 1.1 times voltage setting)

Dropout ratio Settable 0.93~1.00, default value: 0.98

2.11.9 Negative-sequence Overvoltage Protection (59Q)

Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater

Pickup time ≤35ms (at 1.1 times voltage setting)

Ngày đăng: 13/07/2021, 10:51

TỪ KHÓA LIÊN QUAN