Preface About This Manual The technical manual describes the protection, automation, control, and supervision functions of PCS S series device for line differential protection, and cont
Trang 3Copyright © 2019 NR All rights reserved
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may
be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights
The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice
To the extent required the products described herein meet applicable IEC and IEEE standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly
Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us
Trang 5Preface
About This Manual
The technical manual describes the protection, automation, control, and supervision functions of PCS S series device for line differential protection, and contains operation principle descriptions, and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data, sorted per function, as well as the hardware of the device The manual can be used as a technical reference during the engineering phase and during normal service In addition, the manual also includes a glossary that lists and defines technical terms used throughout the manual
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment (module or device) However, it comprises important information that must be followed for personal safety, as well as to avoid material damage Information is highlighted and illustrated
as follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage
Indicates that property damage can result if the measures specified are
not taken
Important information about the device, product handling or a certain section of the documentation which must be given particular attention
Instructions and Warnings
The following hazard statements apply to this device
Disconnect or de-energize all external connections BEFORE opening this
Trang 6device Contact with hazardous voltages and currents inside this device can cause electrical shock resulting in injury or death
Contact with instrument terminals can cause electrical shock that can result in injury or death
Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment
Have only qualified personnel service this equipment If you are not qualified to service this equipment, you can injure yourself or others, or cause equipment damage
This device is shipped with default passwords Default passwords should
be changed to private passwords at installation Failure to change each default password to a private password may allow unauthorized access
NR shall not be responsible for any damage resulting from unauthorized access
DO NOT look into the fiber (laser) ports/connectors
DO NOT look into the end of an optical cable connected to an optical
output
DO NOT perform any procedures or adjustments that this instruction
manual does not describe
During installation, maintenance, or testing of the optical ports, ONLY use
Trang 7the test equipment qualified for Class 1 laser products!
Incorporated components, such as LEDs, transceivers, and laser emitters,
are NOT user serviceable Return units to NR for repair or replacement
Equipment components are SENSITIVE to electrostatic discharge (ESD)
Undetectable permanent damage can result if you do not use proper ESD procedures Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment If your facility is not
equipped to work with these components, contact NR about returning this device and related NR equipment for service
Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables Please use the wiring method recommended in the manual for communication terminals
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power Equipment damage can result otherwise
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure
The firmware may be upgraded to add new features or enhance/modify
Trang 8existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand
Document Conventions
The abbreviations and acronyms in this manual are explained in “Appendix A Glossary” The
Glossary also contains definitions of important terms
Menu path is connected with the arrow "→" and bold
For example: the access path of protection settings is: MainMenu→Settings→Protection Settings
Settings not in the table should be placed in brackets
For example: the system setting [Opt_SysFreq]
Cross-references are presented in italics
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold
For example: press the button "ENT"
Trang 11on the target sections of this manual as your job needs and responsibilities dictate An overview of each manual section and section topics follows
Trang 126 System Functions
Describes how to perform fundamental operations such as clock synchronization, communicating with the device, switching active setting group, checking relay status, reading event reports and SER (Sequential Events Recorder) records
Describes the abbreviations adopted in this manual
Document Revision History
PN: ZL_PCS-994S_X_Technical Manual_EN_Overseas General_X
Trang 13Figure 1.1-1 Typical applications of PCS-994S 1-1
Figure 1.1-2 Function diagram of PCS-994S 1-1
Trang 151
1.1 Application
PCS-994S frequency and voltage controller provides fast and selective generation shedding and
load shedding due to the frequency or voltage abnormality in the power network, for avoiding the
system crash and a large area blackout, maintaining the stability of the system voltage and
frequency The device contains all important auxiliary functions that are necessary today for safe
network operation This includes measurement and monitoring functions The large number of
communication interfaces and communication protocols satisfies the requirements of
communication-based selective control and of automated operation Their modular structure
permits the device always to be adapted flexibly to the individual requirements
PCS-994S applies to double-bus scenarios and single bus with bus section scenarios
PCS-994S
Bus1 Bus2
PCS-994S
Figure 1.1-1 Typical applications of PCS-994S
The function diagram for protecting a double-bus is shown below
Figure 1.1-2 Function diagram of PCS-994S
The PCS-994S is applicable not only to conventional substations, but also to digital substations It
supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network interfaces with high
real-time performance The process level network supports peer-to-peer (P2P) mode and
networking mode, including single network mode and dual network mode The station level
network could also receive and send MMS messages (such as interlocking signals) or process
level GOOSE messages (such as trip signals)
Trang 161
1.2 Functions
1 Protection Functions
81U Under-frequency protection
Up to 5 basic stage of under-frequency load shedding
Up to 2 accelerated stage of under-frequency load shedding
Up to 3 special stage of under-frequency load shedding
Under-voltage blocking element
df/dt blocking element
Frequency over-range blocking element
81O Over-frequency protection
Up to 5 basic stage of over-frequency generation shedding
Under-voltage blocking element
Frequency over-range blocking element
81R Rate-of-change of frequency
protection
Up to 5 stages with independent logic
Optional positive or negative change of frequency for each stage
Under-voltage blocking element
27 Under-voltage protection
Up to 5 basic stage of under-voltage load shedding
Up to 2 accelerated stage of under-voltage load shedding
Up to 3 special stage of under-voltage load shedding
Under-voltage blocking element
dU/dt blocking element
VT circuit failure blocking
59 Over-voltage protection Up to 3 basic stage of over-voltage system splitting
2 Measurement and Metering Functions
Powerful faults recording (max buffer for 10,000 sampled points at 4.8 or 9.6 kHz
Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision events, 256 control logs and 1024 device logs
Disturbance recorder including 64 disturbance records with waveforms (The file format of disturbance recorder is compatible with international COMTRADE file.)
Trang 171
Single line diagram representation in display
4 Communication Functions
Support of various protocols
Modbus, DNP3.0, IEC 60870-5-103, IEC 61850 Ed.1 & Ed.2, IEC 61850 MMS Server,
IEC 61850-8-1 GOOSE, IEC 61850-9-2LE SV, IEC 62439 Parallel Redundancy Protocol,
IEC 62439 HSR Ring Redundancy Protocol
Up to four 10Base-T/100Base-TX copper Ethernet ports
Up to four 100Base-FX optical Ethernet ports
Two RS-485 serial ports for communication or printer
One RS-485/TTL/ST port for clock synchronization
Two RJ45 debugging ports (front and rear)
5 User Interfaces
Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and
set-point adjustment
Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management
4 Programmable operator pushbuttons with user-configurable labels
Up to 18 programmable target LEDs with user-configurable labels
1 RS-485 rear port for printer
Language switchover—English+ selected language
Configuration tool—PCS-Studio
6 Additional Functions
User programmable logic
Switching system phase sequences function (ABC or ACB)
Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE1588: Clock message based on IEEE1588 via optical fibre interface
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
SNTP (BC): Broadcast SNTP mode via Ethernet network
Trang 18 Various function modules can satisfy various situations according to the different requirements
of users Flexible and universal logic programming, user-defined configuration of BI/BOs, buttons and LEDs and powerful analog programming are supported
Modularized hardware design makes the device be easily upgraded or repaired by a qualified service person It can be mixed with different I/O modules, with online self-check and monitoring function, and the device can be restored from abnormal operation only need to replace a single abnormal module
Support memory check and error correction function, ensure high reliability and safety
Support the internet communication protocol of native PRP/HSR and RSTP
Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351 communication service, GOOSE communication in station level & process level, SV communication with multi-sampling rate
Full comply with cyber security standards, including IEC62443, IEC62351, IEEE1686, NERC-CIP, support role based access control (RBAC), security audit, security encryption communication and security tool, improve the cyber security capability of devices
Powerful COMTRADE fault and disturbance recording function is supported The whole recording time is automatically configurable by the fault duration, which is convenient to fault analysis and replay The recording sample rate is up to 9.6kHz
Settable secondary rated current (1A/5A) and settable voltage threshold of binary input
Trang 191
Support small size and large size LCD, control and multifunction button
Support flush mounting, semi-flush mounting, surface mounting, wall mounting and other
mounting methods
Cross screw IO, CT/VT terminals can support AWG12 specification connector and 4mm2
lead
Multiple variants with case size 1/1 or 1/2 × 19"
Protection class of front side is up to IP54
PCS-Studio is the application software on the user's PC for the interface with PCS S series
devices providing all the related functionality It ranges from device configuration to full
substation design of bay integration
Support IEEE1588, IRIG-B clock synchronization
Support actual system phase sequence, either ABC or ACB, incorrect connection of actual
phase sequence can automatically be verified and relevant protection functions can be
blocked
Equipped with high-speed large capacity output relay, its operation speed is less than 1ms and
its break capacity is up to 10A The real-time supervision for output drive circuit can detect the
abnormality in advance
Support setup up to 40 users and allow each user to own different password and access
authority
The PCS-994S can accelerated load shedding to prevent power system collapse when the
system’s voltage or the frequency decreases sharply Thus, the voltage or frequency can be
restored back to optimal operating range quickly
Since the decrease of three-phase voltage due to insufficient reactive power is basically
symmetric, and no large sudden variation occurs, the under-voltage element of this controller
makes judgments based on positive-sequence voltage If a negative-sequence voltage
exceeds 0.15Un or a positive-sequence voltage changes suddenly, the under-voltage load
shedding function is blocked Therefore, the controller will not execute system-splitting during
faults
The power swing blocking function, based on the analysis of df/dt and du/dt, can prevent
mal-operation caused by short-circuit fault or abnormal conditions of voltage and frequency
The adaptive floating threshold method is adopted, which only reflects the frequency
component deviation of power supply This measuring element improves the protection
sensitivity and stability under load fluctuation and system disturbance conditions
Unique two-out-two logic is adopted in the hardware design to improve security, while the
redundant scheme improves dependability The two independent data acquisition channels
are provided to prevent mal-operation caused by component failure One works as a fault
detector and the other is designed for protection logic
Trang 222.11 Communication Functions 2-11
2.11.1 GOOSE 2-11 2.11.2 SV 2-12 2.11.3 IEC61850-9-2 Transmission Parameters 2-12 2.11.4 Sampled Value Accuracy 2-12
Trang 232
2.1 Electrical Specifications
“System phase sequence”, which can be set by PCS-Studio, this setting
informs the device of the actual system phase sequence, either ABC or ACB VT inputs on the device, labeled as A, B and C, must be connected
to system phase A, B and C for correct operation
600V 660V
Phase-to-phase 519V
1038V 1141V
Burden at rated <0.10VA/phase @100V
2.1.2 Power Supply
100Vac/110Vac/115Vac/120Vac 127Vac/220Vac/230Vac/240Vac 250Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
Trang 242
Settable pickup voltage and dropout voltage
On value (default set) 69.3~132Vdc 78.75~160Vdc 138.6~264Vdc 157.5~300Vdc
Off value (default set) <55Vdc <62.5Vdc <110Vdc <125Vdc
Maximum permissible voltage 300Vdc
Withstand voltage 2000Vac, 2800Vdc (continuously)
Settable pickup voltage and dropout voltage
Maximum permissible voltage 300Vac
Withstand voltage 2000Vac, 2800Vdc (continuously)
Settable pickup voltage and dropout voltage
Maximum permissible voltage 300Vdc
Withstand voltage 2000Vac, 2800Vdc (continuously)
2.1.4 Binary Output
Tripping/signaling contact
Max system voltage 250Vac, 300Vdc
Pickup time (Typical value) <5ms
Trang 252
Dropout time (Resistive load) <6ms
Breaking capacity (L/R=40ms)
0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc
Cyclic Capacity (2.5 cycle/second,
L/R=40ms)
0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc
Short duration current
30A@3s 50A@1s Durability (Loaded contact) 10000 operations
Heavy-capacity tripping contact
MOV Protection (maximum voltage ) 350Vdc, 275Vac
Pickup time (Typical value) <1ms
Dropout time (Resistive load) <10ms
Breaking capacity (L/R=40ms)
10A@48V 10A@110V 10A@125V 10A@250V
Cyclic Capacity (4 cycles in 1 second,
followed by 2 minutes idle for thermal
dissipation)
10A@48V L/R=40ms 10A@110V L/R=40ms 10A@125V L/R=40ms 10A@250V L/R=20ms
Trang 262
Short duration current
30A@3s 50A@1s Durability (Loaded contact) 10000 operations
2.2 Mechanical Specifications
Weight per device
Approx 5.86kg (6U, 1/2) Approx 9.22kg (6U, 1/1)
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated front plate
Protection Class
Rear side, connection terminals IP20
2.3 Ambient Temperature and Humidity Range
Trang 272
Max transmission distance 500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
2.4.2 Copper Ethernet Port
Transmission standard 100Base-TX
Max transmission distance 100m
Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850
Safety level Isolation to ELV level
2.4.3 Optical Port
Optical Port: For Station Level and Process Level
Characteristic Glass optical fiber
Transmission distance Maximum 2km
Transmission power 50μm: Minimum -24dBm 62.5μm: Minimum -20dBm
Optical Port: For Clock Synchronization
Characteristic Glass optical fiber
Trang 282
Peak optical input power
Logic level HIGH
Logic level LOW
Maximum -40dBm Maximum -10dBm, Minimum -24dBm
2.4.4 Print Port
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Safety level Isolation to ELV level
2.4.5 Clock Synchronization Port
Damp heat test, cyclic IEC60068-2-30:2005
2.5.2 Mechanical Tests
Shock and bump IEC 60255-21-2:1988 Class Ⅰ
2.5.3 Electrical Tests
Dielectric tests Test voltage 2kV, 50Hz, 1min
Trang 29Electrostatic discharge test
IEC 61000-4-2-2008 class Ⅳ For contact discharge: 8kV For air discharge: 15kV
Radio frequency interference tests
IEC 60255-26:2013 class Ⅲ Frequency sweep
Radiated amplitude-modulated 10V/m (rms), f=80~1000MHz, 14000~2700MHz Spot frequency
Radiated amplitude-modulated 10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Fast transient disturbance tests
IEC 60255-26:2013 Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns
Surge immunity test
IEC 60255-26:2013 Power supply, AC input, I/O port: class Ⅳ, 1.2/50us Common mode: 4kV
Differential mode: 2kV
Conducted RF Electromagnetic
Disturbance
IEC 60255-26:2013 Power supply, AC, I/O, Comm Terminal: Class Ⅲ , 10Vrms, 150 kHz~80MHz
Spot frequency
Trang 302
10V/m (rms), f=27MHz/68MHz Power Frequency Magnetic Field
Immunity
IEC 61000-4-8: 2009 class Ⅴ, 100A/m for 1min, 1000A/m for 3s
Pulse Magnetic Field Immunity
IEC 61000-4-9:2016 class Ⅴ, 6.4/16μs, 1000A/m for 3s Damped oscillatory magnetic field
immunity
IEC 61000-4-10:2016 class Ⅴ, 100kHz & 1MHz–100A/m
Conducted emission
IEC 60255-26:2013 0.15MHz~0.50MHz: 79dB (μV) quasi peak, 66dB (μV) average 0.50MHz~30MHz: 73dB (μV) quasi peak, 60dB (μV) average
Radiated emission
IEC 60255-26:2013
Below 1GHz
30MHz~230MHz: 40dB (μV/m) quasi peak @10m, 50dB (μV/m) quasi peak @3m
230MHz~1000MHz: 47dB (μV/m) quasi peak @10m, 57dB (μV/m) quasi peak @3m
Above 1GHz
1GHz~3GHz: 56dB (μV/m) average, 76dB (μV/m) peak @3m
3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m) peak @3m
Auxiliary power supply performance
50ms for interruption without rebooting without energy storage board (Typical configuration) 500ms for interruption without rebooting with energy storage board (Typical configuration)
2.6 Certifications
ISO9001:2015
Trang 31 EMC: 2014/30/EU, EN60255-26:2013
Products safety (LVD): 2014/35/EU, EN60255-27:2014
IEC 61850: Edition 2, Parts 6, 7-1, 7-2, 7-3,7-4 and 8-1
IEC 61850: Edition 2, GOOSE Performance Class P1 (3ms)
IEEE 1588: IEEE Std C37.238TM-2017
DNP: DNP 3.0
PRP: IEC 62439-3 Ed.3 (IS 2016)
HSR: IEC 62439-3 Ed.3 (IS 2016)
2.7 Liquid Crystal Display (LCD)
2.8 Terminals
2.8.1 Ring Ferrule
Grounding (Earthing) Connection BVR type, 0.8~4mm2 lead M3 0.6~0.8 N·m
2.8.2 Pin Ferrule
Power supply Screw terminals, 0.3~3.3mm2 lead M2.5 0.4~0.6 N·m
Contact I/O Screw terminals, 0.3~3.3mm2 lead M2.5 0.4~0.6 N·m
Trang 32External time synchronization IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol
2.9.2 Fault and Disturbance Recording
Duration & Recording position
Settable pre-disturbance, post-disturbance and maximum recorded duration
2.9.3 Binary Input Signal
Resolution of binary input signal ≤1ms
2.10 Protective Functions
2.10.1 Under-frequency Protection (81U)
Tolerance of frequency setting ≤0.01Hz
Tolerance of operating time ≤1%×setting or 60ms
2.10.2 Over-frequency Protection (81O)
Tolerance of frequency setting ≤0.01Hz
Tolerance of operating time ≤1%×setting or 60ms
Trang 332
2.10.3 Frequency Rate-of-change Protection (81R)
Tolerance of frequency rate-of-change setting ≤0.02Hz/s
Tolerance of operating time ≤1%×setting or 60ms
2.10.4 Under-voltage Protection (27)
Tolerance of voltage setting ≤1.5% or 0.1V, whichever is greater
Tolerance of operating time ≤1%×setting or 30ms
2.10.5 Over-voltage Protection (59)
Tolerance of voltage setting ≤1.5% or 0.1V, whichever is greater
Tolerance of operating time ≤1%×setting or 30ms
Sending Control Block (SCB) Max 16
Trang 342
2.11.2 SV
Receiving Control Block (RCB) Max 12
2.11.3 IEC61850-9-2 Transmission Parameters
Transmission frame interval jitter < 300ns
2.11.4 Sampled Value Accuracy
Voltage accuracy for measurement
Accuracy class 0.2 class Amplitude (Typical) < 0.1% @ Un Angle (Typical) < 5’ @ Un
Voltage accuracy for protection
Amplitude (Typical) < 0.1% @ Un Angle (Typical) < 5’ @ Un
Trang 363
3.5.1 Function Description 3-22 3.5.2 Function Block Diagram 3-23 3.5.3 I/O Signal 3-23 3.5.4 Logic 3-23 3.5.5 Settings 3-23
List of Figures
Figure 3.1-1 Logic diagram of load over-shedding by stage 2 of under-frequency protection 3-4 Figure 3.1-2 Function block of basic stages of under-frequency protection 3-4 Figure 3.1-3 Function block of accelerated stages of under-frequency protection 3-4 Figure 3.1-4 Function block of special stages of under-frequency protection 3-4 Figure 3.1-5 Logic of basic stages of under-frequency protection 3-5 Figure 3.1-6 Logic of accelerated stages of under-frequency protection 3-6 Figure 3.1-7 Logic of special stages of under-frequency protection 3-6 Figure 3.2-1 Logic of over-frequency protection 3-11 Figure 3.3-1 Logic of frequency rate-of-change protection 3-13 Figure 3.4-1 Schematic of blocking and unblocking upon short circuit 3-17 Figure 3.4-2 Function block of basic stages of under-voltage protection 3-17 Figure 3.4-3 Function block of accelerated stages of under-voltage protection 3-18 Figure 3.4-4 Function block of special stages of under-voltage protection 3-18 Figure 3.4-5 Logic of basic stages of under-voltage protection 3-19 Figure 3.4-6 Logic of accelerated stages of under-voltage protection 3-19 Figure 3.4-7 Logic of special stages of under-voltage protection 3-20 Figure 3.5-1 Logic of over-voltage protection 3-23
List of Tables
Table 3.1-1 I/O signals of basic stages of under-frequency protection 3-5 Table 3.1-2 I/O signals of accelerated stages of under-frequency protection 3-5 Table 3.1-3 I/O signals of special stages of under-frequency protection 3-5
Trang 373
Table 3.1-4 Settings of under-frequency protection 3-7
Table 3.2-1 I/O signals of over-frequency protection 3-10
Table 3.2-2 Settings of over-frequency protection 3-11
Table 3.3-1 I/O signals of frequency rate-of-change protection 3-13
Table 3.3-2 Settings of frequency rate-of-change protection 3-13
Table 3.4-1 I/O signals of basic stages of under-voltage protection 3-18
Table 3.4-2 I/O signals of accelerated stages of under-voltage protection 3-18
Table 3.4-3 I/O signals of special stages of under-voltage protection 3-18
Table 3.4-4 Settings of under-voltage protection 3-20
Table 3.5-1 I/O signals of over-voltage protection 3-23
Table 3.5-2 Settings of over-voltage protection 3-23
Trang 393
3.1 Under-frequency Protection (81U)
Frequency is an important index of the power quality, which can reflect the balance of the output
power of the generator and the active power of the load The decrease of frequency indicates that
the output power of the system is much less than that of the load When the system frequency is
less than the predefined setting, the under-frequency protection will operate for shedding some
part of loads from the system
3.1.1 Function Description
The device can provide five basic stages, two accelerated stage, and three special stages of
under-frequency load shedding If the system frequency is less than the setting, under-frequency
protection will operate to shedding some part of loads from the system Under-frequency
protection is with definite-time characteristics and with instantaneous dropout characteristics
3.1.1.1 Discriminated Equations of Under-frequency Load Shedding
There are two kinds of operation sequences for basic stages, independent and sequential
For the logic that the five basic stages operate independently, the discriminated equations
are,
When f≤ f_Pkp_UF & t≥0.05s FD (fault detector) of under-frequency protection will pick up,
then
If f≤[81U1.f_Set] & t≥[81U1.t_Op], basic stage 1 of under-frequency will operate;
If f≤[81U2.f_Set] & t≥[81U2.t_Op], basic stage 2 of under-frequency will operate;
If f≤[81U3.f_Set] & t≥[81U3.t_Op], basic stage 3 of under-frequency will operate;
If f≤[81U4.f_Set] & t≥[81U4.t_Op], basic stage 4 of under-frequency will operate;
If f≤[81U5.f_Set] & t≥[81U5.t_Op], basic stage 5 of under-frequency will operate
(Where, f is the frequency of the selected voltage, f_Pkp_UF is the internal pickup setting, it
follows the rule as below:
If [81U.f_Pkp]≠0.00Hz, f_Pkp_UF = [81U.f_Pkp], where [81U.f_Pkp] is the under-frequency
pick up setting;
Else if [81U.f_Pkp]=0.00Hz, f_Pkp_UF=MAX{[81U1.f_Set], [81U2.f_Set]… [81U5.f_Set]…
[81US3.f_Set]} + 0.1Hz, t is the time delay)
For the logic that the five basic stages operate sequentially, the discriminated equations are,
When f≤f_Pkp_UF & t≥0.05s fault detector of under-frequency protection will pick up, then
If f≤[81U1.f_Set] & t≥[81U1.t_Op], basic stage 1 of under-frequency will operate
↓ if f≤[81U2.f_Set] & t≥[81U2.t_Op], basic stage 2 of under-frequency will operate
↓ if f≤[81U3.f_Set] & t≥[81U3.t_Op], basic stage 3 of under-frequency will operate
Trang 403
↓ if f≤[81U4.f_Set] & t≥[81U4.t_Op], basic stage 4 of under-frequency will operate
↓ if f≤[81U5.f_Set] & t≥[81U5.t_Op], basic stage 5 of under-frequency will operate (Where, “↓” means the above conditions have been met and realized.)
The discriminated equations of the two accelerated stages are shown as below
When f≤[f_Pkp_UF] & t≥0.05s fault detector of under-frequency protection will pick up, then
If f≤[81U1.f_Set] & {[81UAcc2.df/dt_Set]≤-df/dt<[81U.df/dt_H_Blk]} & t≥[81UAcc2.t_Op], stage 1 of under-frequency will trip and stage 2 will be accelerated to trip
If f≤[81U1.f_Set] & {[81UAcc2-3.df/dt_Set]≤ - df/dt < [81U.df/dt_H_Blk]} & t≥[81UAcc2-3.t_Op], stage 1 of under-frequency will trip, and stage 2 and stage 3 will be accelerated to trip
The discriminated equations of the three special stages are shown as below
When f≤f_Pkp_UF & t≥0.05s fault detector of under-frequency protection will pick up, then
If f≤[81US1.f_Set] & t≥[81US1.t_Op], special stage 1 of under-frequency will operate
If f≤[81US2.f_Set] & t≥[81US2.t_Op], special stage 2 of under-frequency will operate
If f≤[81US3.f_Set] & t≥[81US3.t_Op], special stage 3 of under-frequency will operate
3.1.1.2 Blocking Measures to Prevent Maloperation
In order to prevent possible device maloperation in conditions of high harmonics, voltage circuit failure and so on, such blocking measures are carried out as follows:
1 Voltage control element (under-voltage blocking)
If the positive voltage U1<[81.U_VCE] (the under-voltage blocking setting), the under-frequency protection will be blocked
2 df/dt blocking element
If -df/dt ≥ [81U.df/dt_H_Blk], the under-frequency protection will be blocked The df/dt blocking effect will be released automatically until the system frequency returns to be greater than the pickup setting of under-frequency load shedding
3 Frequency over-range blocking element
When any one of the following inequality is met, the device will take the system frequency as abnormality
For the 50Hz system, f<33Hz or f>65Hz
For the 60Hz system, f<40Hz or f>72Hz
In parallel operation condition, if the device detect that the system frequency calculated from one bus voltage is abnormal or the voltage is close to zero, it will switch over-voltage sampling source
to the other bus; if the voltages of both buses are all detected to be close to zero or both of the