1 Communication Modules Introduction of communication interfaces application in different network structures and serial connection modes.. 1 Communication Modules Date: 10 January 2020
Trang 3Copyright © 2020 NR All rights reserved
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may
be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights
The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice
To the extent required the products described herein meet applicable IEC and IEEE standards, but
no such assurance is given with respect to local codes and ordinances because they vary greatly
Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us
Trang 5Preface
Date: 10 January 2020
Preface
About This Document
This manual describes the network structures and the communication protocols supported by the device
To start using this manual, user should have a basic knowledge of communication in substation automation system (SAS) and of the specific communication protocols along with the basic operation methods of the PCS-Studio configuration tool for PCS S series IEDs
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment (module or device) However, it comprises important information that must be followed for personal safety, as well as to avoid material damage Information is highlighted and illustrated as follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will result
in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, could result
in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, may result in
minor or moderate injury or equipment damage
Indicates that property damage can result if the measures specified are not
taken
Important information about the product, please pay attention to avoid undesired result
Instructions and Warnings
The following hazard statements apply to this device
Disconnect or de-energize all external connections BEFORE opening this
device Contact with hazardous voltages and currents inside this device can cause electrical shock resulting in injury or death
Trang 6Contact with instrument terminals can cause electrical shock that can result
in injury or death
Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment
Have ONLY qualified personnel service this equipment If you are not
qualified to service this equipment, you can injure yourself or others, or cause equipment damage
This device is shipped with default passwords Default passwords should
be changed to private passwords at installation Failure to change each default password to a private password may allow unauthorized access
NR shall not be responsible for any damage resulting from unauthorized access
DO NOT look into the fibre (laser) ports/connectors
DO NOT look into the end of an optical cable connected to an optical
output
DO NOT perform any procedures or adjustments that this instruction
manual does not describe
During installation, maintenance, or testing of the optical ports, ONLY use the test equipment qualified for Class 1 laser products!
Trang 7Preface
Date: 10 January 2020
Incorporated components, such as LEDs, transceivers, and laser emitters,
are NOT user serviceable Return units to NR for repair or replacement
Equipment components are SENSITIVE to electrostatic discharge (ESD)
Undetectable permanent damage can result if you do not use proper ESD procedures Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment If your facility is not
equipped to work with these components, contact NR about returning this device and related NR equipment for service
Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage For external circuits, use wiring
of SUFFICIENTLYRATED insulation that will not break down under
abnormal operating conditions
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables Please use the wiring method recommended in the manual for communication terminals
DO NOT connect power to the device until you have completed these
procedures and receive instruction to apply power Equipment damage can result otherwise
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure
The firmware may be upgraded to add new features or enhance/modify
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand
Trang 8Document Conventions
Menu path is connected with the right arrow "→" and bold
For example: the access path of protection settings is: Main Menu → Settings → Protection Settings
Settings out of list should be placed in brackets
For example: the system setting [Opt_SysFreq]
Cross-references are presented in italics
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
Binary input signals, binary output signals, analogue quantities, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold
For example: press the "ENT" button
1 Communication Modules
Introduction of communication interfaces application in different network structures and serial connection modes
2 IEC 61850
Introduction of IEC 61850 protocol, including protocol characteristics and properties
Instantiation application of communication between the client and the server for substation automation via the IEC 61850 Manufacturing Message Specification (MMS) protocol, cross communication between devices via Generic Object-Oriented Substation Event (GOOSE) messages and IEC 61850-9-2 SV implementation
3 DNP3
Instruction of DNP3 protocol characteristics and properties, especially the application layer with implementation information
Trang 9Introduction of Modbus protocol main function codes.
Document Revision History
P/N: ZL_PCS-978S_X_Communication Protocol Manual_EN_Overseas General_X
Trang 111.3 Ethernet Network Structures 1-3
1.3.1 Standardized Ethernet Cable 1-4
1.3.2 Relevant Settings 1-4
1.3.3 Ethernet Interface Setup 1-5
1.3.4 Port Bonding Operation 1-6
Trang 121
Trang 131 Communication Modules
Date: 10 January 2020
1
This section outlines the communication modules of device This device supports a choice of
multiple protocols via rear interfaces on communication modules The protocols are selected and
configured by setting or configuration file via the configuration tool PCS-Studio
It should be noted that the description contained within this manual do not aim to fully detail
protocols The relevant documentation for protocols should be referred to for such goal This
manual serves to describe the specific implementation of protocols in this device
1.1 CPU Module
This device is usually ordered with factory-installed communication modules Yet a communication
module, such as the CPU module or the NET-DSP module, can also be installed and replaced in
the device afterwards
The NR6106 CPU module can be installed on device rack The sub-models of this module
correspond to different communication interfaces or device variants
1
2
3
4
Figure 1.1-1 View of CPU module
1 Ethernet interfaces LAN1 and LAN2
Trang 141 2 Ethernet interfaces LAN3 and LAN4
3 Serial interfaces: 10-terminal connector, 2*EIA-485 ports and 1*EIA-485/TTL port for clock synchronization
4 Debugging interface: RJ45 port
2 × optical Ethernet, 100Base-FX, 1310 nm, duplex LC plug, 2 km via 50 µm or
Trang 151 Communication Modules
Date: 10 January 2020
1 Communication interface
Additional Ethernet protocols and services
HSR (High-availability uninterruptible ring redundancy) ●
1.3 Ethernet Network Structures
The Ethernet interfaces have an integrated switching function This makes it possible to integrate
the device with third-party components into almost all network structures, which are independent
of the communication protocols such as IEC 61850, IEC 60870-5-103 and DNP3
Devices are integrated into superior network structures via switches Each switch provides several
interfaces to connect to devices and other switches in the superior network The superior network
operates on the basis of RSTP (Rapid Spanning Tree Protocol) which leads to a network or a ring
of such network switches This results in a variety of possible structures of superior network
WLAN
Substation LAN
Control Centre LAN
Remote Monitoring
IEDs
Figure 1.3-1 Ethernet network structure
Trang 161 1.3.1 Standardized Ethernet Cable
It is recommended to use screened twisted multi-strand network cable (category 5) as the communication cable
Figure 1.3-2 Ethernet cable
1.3.2 Relevant Settings
The communication settings that are relevant to Ethernet network are listed in the following table Refer to the device technical manual and setting guide for more detail about the parameterization, such as IP address, gateway address, etc
Access path: Main Menu Settings Global Settings Comm Settings General Comm Settings
- - Subnet mask of Ethernet port B
En_LAN2 Enabled Disabled or Enabled - - Put Ethernet port B into service
Trang 171 Communication Modules
Date: 10 January 2020
1
En_LAN4 Disabled Disabled or Enabled - - Put Ethernet port D into service
B01.Opt_NetMode Normal
Normal;
1-2:Normal, 3-4:HSR;
1-2:Normal, 3-4:PRP;
1-2:Normal, 3-4:RSTP;
- - The network method of the CPU
module located in slot No.1
1.3.3 Ethernet Interface Setup
The communication modules and interfaces are available in both electrical and optical versions
There is no difference in interface setup through both versions To communicate with the device
via a PC for monitoring, a connection must be established
Ensure that the device and PC are in the same network segment by setting the IP address
[IP_LAN*] and subnet mask [Mask_LAN*] of corresponding Ethernet interfaces
Trang 181
LAN1 LAN2
LAN3 LAN4
Figure 1.3-3 Ethernet interfaces
For example, to establish a connection between PC and the device first Ethernet interface, set the
IP address and subnet mask of PC to be “198.87.96.102” and “255.255.255.0”.The IP address and subnet mask of device should be [IP_LAN1]= 198.87.96.*** (** can be any integer from 0 to 255 except 102 or any other appeared number), [Mask_LAN1]=255.255.255.0
The logic setting [En_LAN*] must be enabled to activate the corresponding Ethernet interface of device
1.3.4 Port Bonding Operation
Use the setting [Cfg_NetPorts_Bond] to set the channel bonding arrangement of two Ethernet ports in station level communication link In this operating mode, two interfaces of the device are bonding with the same IP and MAC address The 1st interface that detects a connection with switch is active and takes the responsibility of the entire data transmission via such connection The 2nd interface whose link status is monitored operates on standby If the active connection fails, the device switches to the 2nd one rapidly
For redundancy or increased throughput of the communication, dual network structure may be adopted along with channel bonding technology These two bonded interfaces, who share the identical IP address and MAC address, work in Active-Standby mode If the link via active interface
Trang 19The value of this setting represents a 4-bits binary number Each bit represents a corresponding
Ethernet port's bonding status Use the following map to decide the specific setting value
Additionally, the default value "0" means the channel bonding function is deactivated
Ethernet port 1
Setting Value Bit0
1 1 0
0
Ethernet port 1
Setting Value Bit0
1 0 1 0
Ethernet port 1
Setting Value Bit0
1 0 0 1
Ethernet port 2
Setting Value Bit0
0 1 1
0
Ethernet port 2
Setting Value Bit0
0 1 0 1
Ethernet port 3
Setting Value Bit0
0 0 1 1
Ethernet port 1: Bit0, Ethernet port 2: Bit1, Ethernet port 3: Bit2, Ethernet port 4: Bit3
The Active-Standby mode switching logic is:
Take the device Ethernet ports 1 & 2 for example and assume that P1 is connected to NET1 while
P2 is connected to NET2
After the device is powered on, only P1 is activated when both NET1 and NET2 are normal
If NET1 is abnormal, P2 will be activated if NET2 is normal
If NET1 is abnormal, P2 cannot be activated if NET2 is also abnormal The device will keep
trying on P1
If P2 is working, the device will maintain this state even if NET1 has been restored to normal
It will be switched to P1 only if NET2 is abnormal
1.3.5 Star-shaped
Set [B01.Opt_NetMode] to be "Normal" to activate this structure
Only one interface of the device is connected to switch Multiple devices are connected to the switch in
a star-shaped connection
Trang 201
Substation LAN
IEDs
Figure 1.3-4 Star-shaped network
The unique connection provides no redundancy Practically, it is suggested to use another interface to create a dual star network or at least use the port bonding method to enhance the redundancy of network structure
1.3.6 PRP Structure
Set [B01.Opt_NetMode] to be "1-2: Normal, 3-4: PRP" to activate this structure with the device No.3
& 4 Ethernet interfaces
According to IEC 62439-3, the PRP (Parallel Redundancy Protocol) provides communication over two independent networks simultaneously If there is an interruption in communication on either network A or network B, the data exchange continues without problems on the other network Thus, it assures that there is no interruption It is recommended to use a non-PRP device, such as debugging PC, with a Redundancy Box (RedBox) in a PRP network
The PRP nodes connect to two independent networks, and send two copies of the same packet to both networks Both networks transmit these messages to receiving nodes, while receiving nodes accept the first packet and discard the second The receiving nodes make a redundant handling at data link layer to realize redundant message receiving and then transmit data to application layer
Trang 21PRP Activated
LAN A LAN B
PRP Activated
LAN A LAN B
PRP Activated
LAN A LAN B
PRP Activated
IEDs
Figure 1.3-5 PRP structure network
Each node has two interfaces that operate in parallel and that are attached to the same upper
layers of the communication stack through the Link Redundancy Entity (LRE) For the basic
communication, the LRE presents toward its upper layers the same interface as a non-redundant
network adapter, so the upper layers are unaware of redundancy
When receiving a frame from the node’s upper layers, the LRE appends to the frame a
Redundancy Check Trailer (RCT) containing a sequence number and sends the frame through
both its ports at nearly the same time The two frames are nearly identical except for the LAN
identifier (and the checksum)
When receiving frames from the network, the LRE forwards the first received frame of a pair to its
node’s upper layers and discards the duplicate frame (if it arrives) It removes the RCT if required
Trang 221
Figure 1.3-6 Operation mechanism of device PRP interfaces
1.3.7 HSR Structure
Set [B01.Opt_NetMode] to be "1-2: Normal, 3-4: HSR" to activate this structure with the device No.3
& 4 Ethernet interfaces
According to IEC 62439-3, devices operate in hand-in-hand mode in the HSR (High Availability Seamless Redundancy Protocol) structure to form rings with switches If an interruption in communication occurs in a network, a seamless switchover takes place It is recommended to use
a non-HSR device, such as debugging PC, with a Redundancy Box (RedBox) in an HSR network
HSR nodes send a copy of data to application layer The data is copied at data link layer and is transmitted from Port A and Port B via different physical link
HSR ring transmission through two-way link ensures the redundancy of data When a link fails, a message can be transmitted to the receiving device from another loop, and there is no network reconstruction time There is no switching network, and forwarding through the device However, forwarding device has a forwarding delay time per level, so the total forwarding delay is great
Trang 23HSR Activated
LAN A LAN B
HSR Activated
LAN A LAN B
HSR Activated
IEDs
Substation LAN
Figure 1.3-7 HSR structure network
Each HSR node has two interfaces arranged in a ring Source nodes send packets over both
interfaces Each node transmits unreceived frames from interface A to interface B and vice versa
The source node removes frames it receives that it injected into the ring
Each HSR node receives two copies of the same packet, and accepts the first packet and discards
the second The accepted packet is transmitted to application layer
For P2P messages (e.g TCP messages), receiving node will stop transmitting after receiving the
message For multicast or broadcast message, if the message comes from itself, receiving node
will stop transmitting after receiving the message If the message comes from other nodes,
receiving node will transmit it to another interface after receiving the message, i.e., receiving
message from interface A and transmitting message to interface B
1.3.8 RSTP Ring Structure
Set [B01.Opt_NetMode] to be "1-2: Normal, 3-4: RSTP" to activate this structure with the device No.3
& 4 Ethernet interfaces
Devices participate in a ring structure via two interfaces Data is transmitted one by one in the ring
until it reaches its intended destination If the ring structure breaks at a point, stars show up upon
the switch quantity Thanks to RSTP mechanism, the communication may function continuously
without interruption However, a second fault in one star cannot be ignored
Trang 24RSTP Activated
LAN A LAN B
RSTP Activated
LAN A LAN B
1.4.1 Relevant Settings
The communication settings that are relevant to serial connection are listed in the following table Refer to the device technical manual and setting guide for more detail about the parameterization, such as protocol option, address, baud rate, etc
Access path: Main Menu Settings Global Settings Comm Settings General Comm Settings
Trang 25- - Communication protocol of rear RS-485 serial port 1
Protocol_RS485-2 IEC103
IEC103 Modbus DNP
- - Communication protocol of rear RS-485 serial port 2
- bps Baud rate of rear RS-485 serial port 2
Addr_RS485-1 100 0~255 1 - Communication address between the device and the
SCADA or RTU via RS-485 serial port 1
Addr_RS485-2 100 0~255 1 - Communication address between the device and the
SCADA or RTU via RS-485 serial port 2
1.4.2 EIA-485 Interface
Each EIA-485 port has three terminals (two for data transmission and one for signal grounding) It
provides a half-duplex fully isolated serial connection to the device The connection is polarized
and whilst the connection diagram indicates the polarization of terminals Notice that there is no
agreed definition of which terminal is which If the master is unable to communicate with the device
and the communication settings match, it is possible that the two-wire connection is reversed
Trang 271 Communication Modules
Date: 10 January 2020
1
topology is not part of the EIA-485 standard and is forbidden
Two-core screened cable is recommended The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate Total cable length must
not exceed 500m The screen must be continuous and grounded at only one end (normally at the
master connection point) For both safety and noise reasons, it is important to avoid circulating
current, especially when the cable runs between buildings
The signal grounding connection must have continuity for the benefit of all devices connected to
the bus At no stage must it be connected to the cables screen or to the device chassis This is for
both safety and noise reasons
1.4.2.3 Biasing
It may also be necessary to bias the signal wires to prevent jabber Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven This may occur
when all slaves are in receiving mode and the master is slow to turn from receiving mode to
transmitting mode This may be because the master purposefully waits in receiving mode, or even
in a high impedance state, until it has something to transmit Jabber causes the receiving device(s)
to miss the first bits of the first character in the packet, which results in rejecting message and no
consequential responding of slave The symptoms of these are poor response time (due to retries),
increasing message errors, erratic communication and even a complete failure of communication
Biasing requires that the signal wires be weakly pulled to a defined voltage level of approximate 1V
There should only be one bias point on the bus, which is best situated at the master connection
point The DC source used for the bias must be clean, otherwise noise will be injected Note that
some devices may (optionally) be able to provide the bus bias, in which case external components
will not be required
It is extremely important that the 120Ω termination resistors are fitted
Failure to do so will result in an excessive bias voltage that may damage the devices connected to the bus
As the field voltage is much higher than that required, NR cannot assume responsibility for any damage that may occur to a device connected to the network as a result of incorrect application of this voltage
Ensure that the field voltage is not being used for other purposes (i.e
powering logic inputs) as this may cause noise to be passed to the communication network
Trang 281
Trang 292.3 MMS Communication Network Deployment 2-4
2.3.1 Dual-net Full Duplex Mode Sharing the Same RCB Instance 2-5
2.3.2 Dual-net Hot-standby Mode Sharing the Same RCB Instance 2-6
2.3.3 Dual-net Full Duplex Mode with 2 Independent RCB Instances 2-7
2.4 Server Data Organization 2-8
2.4.1 Digital Status Values 2-8
2.4.2 Analog Values 2-8
2.4.3 Protection Logical Nodes 2-10
2.4.4 LLN0 and Other Logical Nodes 2-10
2.5 Server Features and Configuration 2-11
2.6.1 For IEC 61850 Edition 1 2-19
2.6.2 For IEC 61850 Edition 2 2-25
2.7 Logical Nodes Table 2-31
2.7.1 For IEC 61850 Edition 1 2-32
2.7.2 For IEC 61850 Edition 2 2-36
Trang 302
Trang 312 IEC 61850
2
Date: 10 January 2020
The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic
equipment to produce standardized communications systems It is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards The complete set includes:
IEC 61850-1: Introduction and overview
IEC 61850-2: Glossary
IEC 61850-3: General requirements
IEC 61850-4: System and project management
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-6: Configuration description language for communication in electrical substations
related to IEDs
IEC 61850-7-1: Basic communication structure for substation and feeder equipment–
Principles and models
IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment–
Common data classes
IEC 61850-7-4: Basic communication structure for substation and feeder equipment–
Compatible logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
IEC 61850-10: Conformance testing
These documents can be obtained from the IEC (https://www.iec.ch) It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set
Trang 322
IEC 61850 Ed1&2 MMS GOOSE
IEC 61850-9-2 SV GOOSE
RTU SCADA
Optical
Electronic CT/VT
Merging Unit
Electrical or Optical
Figure 2.3-1 Application of IEC 61850 in substation
2.1 Relevant Settings
For the adoption of IEC 61850 as the communication protocol of this device, select the option
“Basic + IEC 61850 (Edition 1.0 or Edition 2.0)” in the following path through the PCS-Studio configuration tool: Project Name → IED Name → Device Setup → Global Config → MOT → S3 Protocol
Use the "Edition" option to determine the IEC 61850 protocol edition through the path: Project Name → Communication → IEC61850
Trang 332 IEC 61850
2
Date: 10 January 2020
Besides the general Ethernet network settings, such IP address, MAC address, the settings that
are relevant to this protocol are listed in the following table Refer to the device technical manual
and setting guide for more detail about the parameterization, such as IED name, dual network
operation mode, etc
Access path: Main Menu Settings Global Settings Comm Settings IEC61850
ThAbs_Measmt 0.02 0.001~0.5 0.001 - Measurement values zero drift
Opt_DualNetMode_MMS SingleNet
SingleNet HotStdby ColdStdby
It is used to select the network mode of MMS network for the communication with SCADA
SingleNet: Single network HotStdby: Hot standby mode (always two ports in service)
ColdStdby: Cold standby mode (only one port in service)
IEDNAME TEMPLATE - - - Logical device name in IEC 61850
Trang 342
2.2 Communication Profiles
This device supports IEC 61850 server services over TCP/IP communication protocol stacks The TCP/IP profile requires the device to have an IP address to establish communications These addresses are located in the path: Main Menu → Settings→ Global Settings→ Comm Settings
→ General Comm Settings
MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper (application) layer for transfer of real-time data This protocol has been in existence for a number of years and provides a set of services suitable for the transfer of data within a substation LAN environment IEC 61850-7-2 abstract services and objects are mapped to actual MMS protocol services in IEC 61850-8-1
Client/server
This is a connection-oriented type of communication The connection is initiated by the client, and communication activity is controlled by the client IEC 61850 clients are often substation computers running HMI programs or SOE logging software Servers are usually substation equipment such as protection relays, meters, RTUs, transformer, tap changers, or bay controllers
Peer-to-peer
This is a non-connection-oriented, high speed type of communication usually between substation equipment, such as protection relays, intelligent terminal GOOSE is the method of peer-to-peer communication
Substation configuration language (SCL)
A substation configuration language is a number of files used to describe IED configurations and communication systems according to IEC 61850-5 and IEC 61850-7 Each configured device has an IED Capability Description (ICD) file and a Configured IED Description (CID) file The substation single line information is stored in a System Specification Description (SSD) file The entire substation configuration is stored in a Substation Configuration Description (SCD) file The SCD file is the combination of the individual ICD files and the SSD file, moreover, add communication system parameters (MMS, GOOSE, control block, SV control block) and the connection relationship of GOOSE and SV to SCD file
2.3 MMS Communication Network Deployment
In order to enhance the stability and reliability of SAS, dual-MMS Ethernet is widely adopted This section is applied to introduce the details of dual-MMS Ethernet technology Generally, single-MMS Ethernet is recommended to be adopted in the SAS of 110kV and lower voltage levels,
Trang 35Client-server mode is adopted: clients (SCADA, control centre and etc.) communicate with the
IEDs via MMS communication network, and the IEDs operate as the servers IEDs are connected
to clients passively, and they can interact with the clients according to the configuration and the
issued command of the clients
Three modes for dual-MMS Ethernet (abbreviated as dual-net) are provided as below
Hereinafter, the normal operation status of net means the physical link and TCP link are both ok The abnormal operation status of net means physical link or TCP link is broken
2.3.1 Dual-net Full Duplex Mode Sharing the Same RCB Instance
Client
IED (Server)
Report Control Block
Report Instance 1 RptEna = true
Abnormal operation status
Figure 2.3-1 Dual-net full duplex mode sharing the RCB block instance
Net A and Net B share the same report control block (abbreviated as RCB) enabled by the client
IED sends undifferentiated date through dual-net to the clients If one net is physically
disconnected, the flag of RCB instance (i.e.: “RptEna” in above figure) is still “true” Only when
both Net A and Net B are disconnected, the flag of the RCB instance will automatically change to
“false”
In normal operation status of this mode, IED provides the same MMS service for Net A and Net B
If one net is physically disconnected (i.e.: “Abnormal operation status” in above figure), the
working mode will switch to single-net mode seamlessly and immediately Network communication
Trang 362
supervision is unnecessary here, and Buffered Report Control Block (abbreviated as BRCB) need not to be used On the other net, date alternation works normally Therefore, MMS service can interact normally without interruption This mode ensures no data loss during one net is in abnormal operation status
In this mode, one report will be transmitted twice via dual nets for the same report instance, so the client needs to distinguish whether two reports are same according to corresponding EntryIDs
2.3.2 Dual-net Hot-standby Mode Sharing the Same RCB Instance
Client
IED (Server)
Report Control Block
Report Instance 1 RptEna = true
TCP Link Main MMS Link
Normal operation status
Client
IED (Server)
Report Control Block
Report Instance 1 RptEna = true
Abnormal operation status
Standby MMS Link
Figure 2.3-2 Dual-net hot-standby mode sharing the same RCB instance
In this mode, the MMS service is provided on main MMS link, no MMS service interacts on the standby MMS link The definitions of two links are as follows:
Main MMS Link: Physically connected, TCP level connected, MMS report service available
Standby MMS Link: Physically connected, TCP level connected, MMS report service not available
If the main net fails to operate (i.e.: “Abnormal operation status” in the above figure), the IED will set “RptEna” to “false” Meanwhile the client will detect the failure by heartbeat message or
“keep-alive”, it will automatically enable the RCB instance by setting “RptEna” back to “true” through standby MMS link By the buffer function of BRCB, the IED can provide uninterrupted MMS service on the standby net However, the differences of BRCB standards among different manufacturers may cause data loss Moreover, if duration of net switch is too long, the data loss is positively as the capacity of BRCB’s buffer function is limited
Trang 37For example, if the subnet mask is “255.255.0.0”, network prefix of Net A is
“198.120.0.0”, network prefix of Net B is “198.121.0.0”, Net A IP address of the IED is “198.120.1.2”, and then Net B IP address of the IED must be configured as “198.121.1.2”, i.e., Net A IED host address =1x256+2=258, Net B IED host address =1x256+2=258, Net A IED host address equals to Net B IED host address
2.3.3 Dual-net Full Duplex Mode with 2 Independent RCB Instances
Client
IED (Server)
Report Control Block
Report Instance 1 RptEna = true
Report Instance 2 RptEna = true
Figure 2.3-3 Dual-net full duplex mode with 2 independent RCB instances
In this mode, IED provides 2 report instances for each RCB, Net A and Net B work independently
from each other, failures of any net will not affect the other net at all Tow report instances are
required for each client Therefore, the IED may be unable to provide enough report instances if
there are too many clients
Net A and Net B send the same report separately when they operate normally To ensure no
repeated data is saved into database, massive calculation is required for the client
Moreover, accurate clock synchronization of the IED is required to distinguish whether 2 reports
are the same report according to the timestamps Clock synchronization error of the IED may lead
to report loss/redundancy
As a conclusion, for the second mode, it’s difficult to realize seamless switchover between dual
nets, however, for the third mode, the IED may be unable to provide enough report instances if too
Trang 382
many clients are applied on site Considering client treatment and IED implementation, the first mode (Dual-net full duplex mode sharing the same report instance) is recommended for MMS communication network deployment
2.4 Server Data Organization
IEC61850 defines an object-oriented approach to data and services An IEC61850 physical device can contain one or more logical device(s) (for proxy) Each logical device can contain many logical nodes Each logical node can contain many data objects Each data object is composed of data attributes and data attribute components Services are available at each level for performing various functions, such as reading, writing, control commands, and reporting
Each IED represents one IEC 61850 physical device The physical device contains one or more logical device(s), and the logical device contains many logical nodes The logical node LPHD contains information about the IED physical device The logical node LLN0 contains common information about the IED logical device
2.4.1 Digital Status Values
The GGIO logical node is available in this device to provide access to digital status points (including general I/O inputs and warnings) and associated timestamps and quality flags The data content must be configured before the data can be used GGIO provides digital status points for access by clients It is intended that clients use GGIO in order to access digital status values from
in this device Clients can utilize the IEC61850 buffered reporting features available from GGIO in order to build sequence of events (abbreviated as SOE) logs and HMI display screens Buffered reporting should generally be used for SOE logs since the buffering capability reduces the chances of missing data state changes All needed status data objects are transmitted to HMI clients via buffered reporting, and the corresponding buffered reporting control block (abbreviated
as BRCB) is defined in LLN0
2.4.2 Analog Values
Most of analog measured values are available through the MMXU logical nodes, and metering values in MMTR, the else in MMXN, MSQI and so on Each MMXU logical node provides data from an IED current/voltage “source” There is one MMXU available for each configurable source MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides data from CT/VT source 2 (usually for monitor and display purpose) All these analog data objects are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding unbuffered reporting control block (URCB) is defined in LLN0
MMXUx logical nodes provide the following data for each source:
MMXU.MX.TotW: three-phase active power
Trang 392 IEC 61850
2
Date: 10 January 2020
MMXU.MX.TotVAr: three-phase reactive power
MMXU.MX.VA: three-phase apparent power
MMXU.MX.TotPF: three-phase power factor
MMXU.MX.Hz: frequency
MMXU.MX.PPV.phsAB: phase AB voltage magnitude and angle
MMXU.MX.PPV.phsBC: phase BC voltage magnitude and angle
MMXU.MX.PPV.phsCA: Phase CA voltage magnitude and angle
MMXU.MX.PhV.phsA: phase AG voltage magnitude and angle
MMXU.MX.PhV.phsB: phase BG voltage magnitude and angle
MMXU.MX.PhV.phsC: phase CG voltage magnitude and angle
MMXU.MX.A.phsA: phase A current magnitude and angle
MMXU.MX.A.phsB: phase B current magnitude and angle
MMXU.MX.A.phsC: phase C current magnitude and angle
MMXNx logical nodes provide the following data for each source:
MMXN.MX.Vol: single-phase voltage magnitude and angle
MMXN.MX.Hz: single-phase voltage frequency
MMXN.MX.Amp: single-phase current magnitude and angle
MSQIx logical nodes provide the following data for each source:
MSQI.MX.SeqV.c1: positive sequence voltage magnitude and angle
MSQI.MX.SeqV.c2: negative sequence voltage magnitude and angle
MSQI.MX.SeqV.c3: zero sequence voltage magnitude and angle
MSQI.MX.SeqA.c1: positive sequence current magnitude and angle
MSQI.MX.SeqA.c2: negative sequence current magnitude and angle
MSQI.MX.SeqA.c3: zero sequence current magnitude and angle
MSQI.MX.ImbZroV: zero sequence voltage unbalance rate
MSQI.MX ImbZroA: zero sequence current unbalance rate
RSYNx logical nodes provide the following data for each source:
RSYN.MX.DifVClc: voltage difference
RSYN.MX DifHzClc: frequency difference
Trang 402
RSYN.MX DifAngClc: phase angle difference
2.4.3 Protection Logical Nodes
The following list describes the protection elements of this device The specified device will contain
a subset of protection elements from this list
RBRF: Breaker failure
RREC: Automatic reclosing
The protection elements listed above contain start (pickup) and operate flags, instead of any element has its own start (pickup) flag separately, all the elements share a common start (pickup) flags “PTRC.ST.Str.general” The operate flag for PTOC1 is “PTOC1.ST.Op.general” These flags take their values from related module for the corresponding element Similar to digital status values, the protection trip information is reported via BRCB, and BRCB also locates in LLN0
2.4.4 LLN0 and Other Logical Nodes
Logical node LLN0 is essential for an IEC 61850 based IED This LN shall be used to address common issues for Logical Devices In this device, most of the public services, the common settings, control values and some device-oriented data objects are available here The public services may be BRCB, URCB and GSE control blocks and similar global defines for the whole device; the common settings include all the setting items of communication settings, system settings and some of the setting items, which can be configured to 2 or more logical nodes In LLN0, the item Loc is a device control object, this Do item indicates the local operation for complete logical device, when it is true, all the remote control commands to the IED will be blocked and those commands make effective until the item Loc is changed to false Besides the logical nodes we describe above, there are some other logical nodes below in the IEDs
MMXU: This LN shall be used to acquire values from CTs and VTs and calculate measurands such as RMS values for current and voltage or power flows out of the acquired voltage and current samples These values are normally used for operational purposes such as power flow supervision and management, screen displays, state estimation, etc The requested accuracy for these functions has to be provided
CILO: This LN shall be used to “enable” a switching operation if the interlocking conditions are fulfilled One instance per switching device is needed At least all related switchgear positions have to be subscribed The interlocking algorithm is a local issue
This LN is used for the interlocking function at station level and/or at bay level
Interlocking may be totally centralized or totally decentralized Since the interlocking rules are basically the same on bay and station level and based on all related position indications, the different interlocking LNs may be seen as instances of the same LN class Interlocking (IL)