1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

PCS 978s x application manual EN overseas general x r1 00

127 14 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề PCS-978S Transformer Relay Application Manual
Trường học NR Electric Co., Ltd.
Chuyên ngành Electrical Engineering
Thể loại manual
Năm xuất bản 2020
Thành phố P.R. China
Định dạng
Số trang 127
Dung lượng 5,62 MB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Nội dung

Preface About This Manual This manual describes the configuration scheme in multiple application scenarios for PCS-978S Transformer Relay, including how to connect the device to a compu

Trang 3

Copyright © 2020 NR All rights reserved

NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may

be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights

The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice

To the extent required the products described herein meet applicable IEC and IEEE standards, but

no such assurance is given with respect to local codes and ordinances because they vary greatly Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us

Trang 5

Preface

About This Manual

This manual describes the configuration scheme in multiple application scenarios for PCS-978S Transformer Relay, including how to connect the device to a computer and to configure functions, such as control, protection, measurement and supervision in using of configuration tool

To start using this manual for application configuration, user should know the basic operations of the configuration tool PCS-Studio

Safety Information

This manual is not a complete index of all safety measures required for operation of the equipment (module or device) However, it comprises important information that must be followed for personal safety, as well as to avoid material damage Information is highlighted and illustrated as follows according to the degree of danger:

Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury

Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury

Indicates a potentially hazardous situation that, if not avoided, may result

in minor or moderate injury or equipment damage

Indicates that property damage can result if the measures specified are

not taken

Important information about the device, product handling or a certain section of the documentation which must be given particular attention

Instructions and Warnings

The following hazard statements apply to this device

Disconnect or de-energize all external connections BEFORE opening this

device Contact with hazardous voltages and currents inside this device can cause electrical shock resulting in injury or death

Trang 6

Contact with instrument terminals can cause electrical shock that can result

in injury or death

Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment

Have only qualified personnel service this equipment If you are not qualified

to service this equipment, you can injure yourself or others, or cause equipment damage

This device is shipped with default passwords Default passwords should

be changed to private passwords at installation Failure to change each default password to a private password may allow unauthorized access NR shall not be responsible for any damage resulting from unauthorized access

DO NOT look into the fiber (laser) ports/connectors

DO NOT look into the end of an optical cable connected to an optical output

DO NOT perform any procedures or adjustments that this instruction

manual does not describe

During installation, maintenance, or testing of the optical ports, ONLY use the test equipment qualified for Class 1 laser products!

Incorporated components, such as LEDs, transceivers, and laser emitters,

Trang 7

are NOT user serviceable Return units to NR for repair or replacement

Equipment components are SENSITIVE to electrostatic discharge (ESD)

Undetectable permanent damage can result if you do not use proper ESD procedures Ground yourself, your work surface, and this equipment

BEFORE removing any cover from this equipment If your facility is not

equipped to work with these components, contact NR about returning this device and related NR equipment for service

Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage For external circuits, use wiring

of SUFFICIENTLY RATED insulation that will not break down under

abnormal operating conditions

SEVERE power and ground problems can occur on the communications

ports of this equipment as a result of using non-standard cables Please use the wiring method recommended in the manual for communication terminals

DO NOT connect power to the relay until you have completed these

procedures and receive instruction to apply power Equipment damage can result otherwise

Use of controls or adjustments, or performance of procedures other than

those specified herein, may RESULT IN hazardous radiation exposure

The firmware may be upgraded to add new features or enhance/modify

existing features, please MAKE SURE that the version of this manual is

compatible with the product in your hand

Document Conventions

 The abbreviations and acronyms in this manual are explained in “Appendix A Glossary” The

Glossary also contains definitions of important terms

Trang 8

 Menu path is connected with the arrow "→" and bold

For example: the access path of protection settings is: MainMenu→Settings→Protection Settings

 Settings not in t.he table should be placed in brackets

For example: the system setting [Opt_SysFreq]

 Cross-references are presented in italics

For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1

 Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold

For example: press the button "ENT"

Trang 11

Three-phase Corresponding Relationship

1 Functions and Applications

Introduces of device functions and typical application scenarios

2 Connection to the Configuration Tool

Introduction of the PCS-Studio configuration tool with the connection method

3 Basic Function

Basic functions configuration methods, including functions selection through MOT, diagram drawing

of LCD display, communication protocol selection and setting, user authority management, configuration of binary inputs and outputs, programmable logic, etc

Trang 12

List of abbreviations adopted in this manual

Document Revision History

PN: ZL_PCS-978S_X_Application Manual_EN_Overseas General_X

Trang 13

Figure 1.2-3 Typical application of a 2-winding transformer 1-5

Figure 1.2-3 Typical application of a 3-winding transformer 1-6

Figure 1.2-3 Typical application of a auto-transformer 1-7

Trang 14

1

Trang 15

1

1.1 Functions

PCS-978S transformer relay provides fast and selective protection, control and monitoring for

two-winding transformers, three-two-winding transformers and auto-transformers in any voltage level All

the important auxiliary functions that are necessary today for safe network operation are integrated

in the IED, and the modular structure permits the device always to be adapted flexibly to the

individual requirements

The PCS-978S is applicable not only to conventional substations, but also to digital substations It

supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network interfaces with high

real-time performance The process level network supports peer-to-peer (P2P) mode and

networking mode, including single network mode and dual network mode The station level network

could also receive and send MMS messages (such as interlocking signals) or process level

GOOSE messages (such as trip signals)

1.1.1 Protection Function

87T Transformer differential protection

 Biased differential protection with three slopes

 Biased DPFC differential protection

 Unrestrained instantaneous differential protection

 Optional inrush current distinguished principles:

harmonic criterion or waveform distortion

 Optional harmonic blocking modes: self-adaptive 1Pblk1P mode, 2PBlk3P mode, 1Pblk3P mode

 Overexcitation detection: fifth harmonic or third harmonic criterion

 Optional transfer methods: △→Y or Y→△

 Independent CT saturation criterion

 Differential CT circuit failure supervision

64REF Restricted earth-fault protection

 Optional direction element

 CT transient characteristic detection

 CT saturation detection based on 2nd and 3rd harmonics

87W Winding differential protection

 CT transient characteristic detection

 CT saturation detection based on 2nd and 3rd harmonics

24 Overexcitation protection

 Two stages definite-time overexcitation protection

 Stage 1 of definite-time overexcitation protection for trip purpose

 Stage 2 of definite-time overexcitation protection for alarm purpose

 One stage inverse-time overexcitation protection for both alarm purpose and trip purpose

Trang 16

1 67P

50/51P Phase overcurrent protection

 6 stages with independent logic by default

 Voltage control element for each stage

 Optional direction element for each stage

 Optional definite-time characteristic and inverse-time characteristic for each stage

 Trip purpose or alarm purpose for each stage

 Harmonic control element for each stage

67G 50/51G Earth fault protection

 4 stages with independent logic by default

 Optional direction element for each stage

 Optional measured zero-sequence current or calculated zero-sequence current

 Optional definite-time characteristic and inverse-time characteristic for each stage

 Selectable trip purpose or alarm purpose for each stage

 Harmonic control element for each stage

67Q 50/51Q

Negative-sequence overcurrent protection

 Up to 2 stages with independent logic

 Optional direction element for each stage

 Optional definite-time characteristic and inverse-time characteristic for each stage

49 Thermal overload protection  Two stages thermal overload protection, and one stage

for alarm purpose and the other stage for trip purpose

50BF Breaker failure protection

 Up to 6 circuit breakers are supported

 Phase-segregated re-trip and three-phases re-trip

 Optional current criterion (phase overcurrent element, zero-sequence overcurrent element, negative- sequence overcurrent element)

 Optional circuit breaker position check

 Two time delays

59P Overvoltage protection

 Up to 2 stages with independent logic

 Optional definite-time characteristic and inverse-time characteristic for each stage

 Optional phase voltage or phase-to-phase voltage

 Optional “1-out-of-3” logic or “3-out-of-3” logic

 Selectable trip purpose or alarm purpose for each stage

27P Undervoltage protection

 Up to 2 stages with independent logic

 Optional definite-time characteristic and inverse-time characteristic for each stage

 Optional phase voltage or phase-to-phase voltage

 Optional “1-out-of-3” logic or “3-out-of-3” logic

 Blocked by instantaneous VT circuit failure

 Selectable trip purpose or alarm purpose for each stage

Trang 17

1

59G Residual overvoltage protection

 Up to 2 stages with independent logic

 Optional measured zero-sequence voltage or calculated zero-sequence voltage

 Optional definite-time characteristic and inverse-time characteristic for each stage

 Selectable trip purpose or alarm purpose for each stage

81O Overfrequency protection  Up to 2 stages with independent logic

 Voltage control element

81U Underfrequency protection  Up to 4 stages with independent logic

 Voltage control element

1.1.2 Control Functions

 Switchgear control

 Double point status synthesis

 Remote/Local control mode switch

 Interlocking logic for control

 Direct control

 Closing synchronism check with voltage selection

 Switchgear trip counter

 Tap position indicator and control

1.1.3 Measurement and Metering Functions

 CT circuit failure supervision (CTS)

 VT circuit failure supervision (VTS)

 Self diagnostic

 Powerful faults recording (max buffer for 10,000 sampled points at 4.8 or 9.6 kHz)

 Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision

events, 256 control logs and 1024 device logs

 Disturbance recorder including 64 disturbance records with waveforms (The file format of

Trang 18

1

disturbance recorder is compatible with international COMTRADE file.)

 Single line diagram representation in display

1.1.5 Communication Functions

 Support of various protocols Modbus, DNP3.0, IEC 60870-5-103, IEC 61850 Ed.1 & Ed.2, IEC 61850 MMS Server, IEC 61850-8-1 GOOSE, IEC 61850-9-2LE SV, IEC 62439 Parallel Redundancy Protocol, IEC 62439 HSR Ring Redundancy Protocol

 Up to four 10Base-T/100Base-TX copper Ethernet ports

 Up to two 100Base-FX optical Ethernet ports

 Two RS-485 serial ports for communication or printer

 One RS-485/TTL serial port for clock synchronization

 Two RJ45 debugging ports (front and rear)

 4 Programmable operator pushbuttons with user-configurable labels

 Up to 18 programmable target LEDs with user-configurable labels

 1 RS-232 or RS-485 rear ports for printer

 Language switchover—English+ selected language

 Configuration tool—PCS-Studio

1.1.7 Additional Functions

 User programmable logic

 Switching system phase sequences function (ABC or ACB)

 Clock synchronization

 IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface

 PPS: Pulse per second (PPS) via RS-485 differential level or binary input

 PPM: Pulse per minute (PPM) via RS-485 differential level or binary input

 IEEE 1588: Clock message based on IEEE 1588 via optical fibre interface

 SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network

Trang 19

1

 SNTP (BC): Broadcast SNTP mode via Ethernet network

 Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol,

Modbus protocol and DNP3.0 protocol

There are three kinds of typical application scenarios, as

 Two-winding transformer, single circuit breaker arrangement

 Three-winding transformer, single circuit breaker arrangement

 Auto-winding transformer, singe circuit breaker arrangement

Figure 1.2-1 Typical application of a 2-winding transformer

This configuration is used in the application scenario of a 2-winding transformer with a single circuit

breaker on both sides The three-phase VT, three-phase CT and the neutral-point CT are used for

Trang 20

1

protection functions calculation and single-phase busbar VT is used for synchronism check The current differential protection is as the main protection, it provides fast and secure tripping for internal faults Restricted earth fault protection, overexctiation protection, phase overcurrent protection, earth fault protection, phase overvoltage protection, residual overvoltage protection and breaker failure protection are configured as backup protection Negative-sequence overcurrent protection, phase undervoltage protection and frequency protection are also optional for some specific requirements

High voltage circuit breaker synchronism check function is equipped, the circuit breaker, the relevant disconnector switches and earthing switches and the tap position could be controlled by the device Supervision functions of analog input channels, binary input channels, CT secondary circuits, VT secondary circuits, switchgear tripping counter, etc are equipped for the operating reliability and safety of the device Moreover, measurement function including U, I, P, Q, S, Cos, f are available in local HMI and remote representation

52

52

3CT

3VT 3CT

Figure 1.2-2 Typical application of a 3-winding transformer

This configuration is used in the application scenario of a 3-winding transformer with a single circuit breaker on both sides The three-phase VT, three-phase CT and the neutral-point CT are used for protection functions calculation and single-phase busbar VT is used for synchronism check The current differential protection is as the main protection, it provides fast and secure tripping for internal faults Restricted earth fault protection, overexctiation protection, phase overcurrent protection, earth fault protection, phase overvoltage protection, residual overvoltage protection and breaker failure protection are configured as backup protection Negative-sequence overcurrent

Trang 21

1

protection, phase undervoltage protection and frequency protection are also optional for some

specific requirements

High voltage circuit breaker synchronism check function is equipped, the circuit breaker, the

relevant disconnector switches and earthing switches and the tap position could be controlled by

the device Supervision functions of analog input channels, binary input channels, CT secondary

circuits, VT secondary circuits, switchgear tripping counter, etc are equipped for the operating

reliability and safety of the device Moreover, measurement function including U, I, P, Q, S, Cos, f

are available in local HMI and remote representation

52

52

3CT 3VTs

Figure 1.2-3 Typical application of a auto-transformer

This configuration is used in the application scenario of an auto-winding transformer with a single

circuit breaker on both sides The three-phase VT, three-phase CT and the neutral-point CT are

used for protection functions calculation and single-phase busbar VT is used for synchronism check

The current differential protection is as the main protection, it provides fast and secure tripping for

internal faults Winding differential, restricted earth fault protection, overexctiation protection, phase

overcurrent protection, earth fault protection, phase overvoltage protection, residual overvoltage

protection and breaker failure protection are configured as backup protection Negative-sequence

overcurrent protection, phase undervoltage protection and frequency protection are also optional

for some specific requirements

High voltage circuit breaker synchronism check function is equipped, the circuit breaker, the

relevant disconnector switches and earthing switches and the tap position could be controlled by

the device Supervision functions of analog input channels, binary input channels, CT secondary

Trang 22

1

circuits, VT secondary circuits, switchgear tripping counter, etc are equipped for the operating reliability and safety of the device Moreover, measurement function including U, I, P, Q, S, Cos, f are available in local HMI and remote representation

Trang 23

2.2.1 Via Front RJ45 Port 2-1

2.2.2 Via Ethernet Interface on CPU Module 2-2

2.3 Validation of Configuration 2-2

Trang 25

2

2.1 Brief Introduction of PCS-Studio

The PCS-Studio is the configuration and debugging software of PCS S series devices It provides

the following configuration functions:

 Device information configuration

Viewing and editing project name, user configuration file version, file modification time, etc

 Global function configuration

MOT selection, system configuration, function object activation/deactivation, etc

 Human-machine interface configuration

Single Line Diagram (SLD) drawing for LCD display, definition of LED indicators, shortcut keys,

user-level waveform recording, etc

 Communication configuration

Support of multiple communication protocols, including IEC 61850 (Edition 1 & Edition 2), IEC

60870-5-103, DNP3.0, Modbus, etc

 IO signal configuration

Binary inputs, binary outputs, AC and DC analogue inputs, etc

 User-defined logic programming

Complete and rich symbol library for user-defined logic programming

On the front panel of the device, there is a multiplex RJ45 port which is the debugging port for

connection to a portable computer Meanwhile, the CPU plug-in module is equipped with several

Ethernet interfaces which may also be used to communicate with debugging computer

2.2.1 Via Front RJ45 Port

By default, the IP address of front debugging port is “100.100.100.100” with the subnet mask

“255.255.255.000” If this address conflicts with any other Ethernet port on CPU module Through

the device front human-machine interface, please call up the modification menu by pressing the

key combination "◄ + ◄ - ENT" under the default LCD display screen and change the default

address

Trang 26

2

2.2.2 Via Ethernet Interface on CPU Module

Firstly, a connection between the device and the computer must be established by setting the IP address and subnet mask of the corresponding interfaces Configure the IP address and the subnet

mask of corresponding Ethernet interface through MainMenu → Settings → Global Settings →

Comm Settings → General Comm Settings

The IP addresses and the subnet masks of device PC should be in the same network segment Take the second Ethernet interface (LAN2) on CPU module as an example:

LAN enabling setting [En_LAN2] = Enabled

“XXX” can be any value from 0 to 255 except 102

2.3 Validation of Configuration

To take effect of all kinds of offline configuration work through PCS-Studio, it is necessary to regenerate the device configuration file (*.devs) and download it to the device A reboot of device

is obligatory after the download for the validation of any modification

All function configuration described in the following chapters are offline tasks, which requires the “file generation, file downloading and device reboot” process for validation

Trang 27

3.2.4 Disturbance Fault Recording 3-4

3.3 Human Machine Interface 3-5

3.3.1 Single Line Diagram Display 3-6

3.5.2 Input Signal from BI Module 3-18

3.5.3 Modify Signal Description 3-19

3.5.4 Modify Signal Parameter 3-19

3.6 Binary Outputs 3-20

3.6.1 Selection of BO Module 3-20

3.6.2 Output Signal to BO Module 3-20

3.6.3 Modify Signal Description 3-21

Trang 28

3

3.7 Output Map 3-23

3.7.1 Introduction 3-23 3.7.2 Configuration Method 3-23

3.8 User-programmable Logic 3-25

3.8.1 Introduction 3-25 3.8.2 Configuration Method 3-26

3.9 User Authority Management 3-28 3.10 Setting Group Switching 3-29

3.10.1 Introduction 3-29 3.10.2 Number of Groups 3-29 3.10.3 Active Group Switching 3-30 3.10.4 Group Number Output 3-31

3.11 GOOSE Communication 3-32

3.11.1 Introduction 3-32 3.11.2 Receiving 3-34 3.11.3 Sending 3-35 3.11.4 Logic Symbols 3-36

3.12 SV Communication 3-37

3.12.1 Introduction 3-37 3.12.2 Receiving 3-37

Trang 29

3

3.1 Device Information

Please go through the path Project Node → Device Node → Device Setup → Device

Information to view the basic information of device This information is derived from the driver file

when adding the device into project

Some information may be modified to facilitate the device management, including instance name,

config file version, config time, etc The length of user-defined information “User Information” is

limited to 106 bytes

When generating the driver file, the configuration tool will package user-defined information and

MOT information After downloading the driver file to the device, the information will be analyzed

and displayed on device LCD

3.2 Global Configuration

3.2.1 MOT Selection

Usually, the device Market Ordering Table (MOT) is defined during the project ordering phase

Please check and adapt to the MOT code to verify the device functions configuration in specific

project design The MOT selection path is: Project Node → Device Node → Device Setup →

Global Config → MOT

The MOT code and the detailed option information are displayed on the page Please double click

a cell in the “Option” column to switch the option from drop-down box for device functional and

hardware specifications modification When the contents of the cell is changed, the corresponding

contents in the "Description" and "Code" columns and the corresponding bit of ordering code will

Trang 30

3

change synchronously

Between some options, coercive and mutually exclusive relations may exist For a coercive relation, one option is fixed to be selected; for a mutually exclusive relation, one option is impossible to be selected

Click on the “Software Function” button to view the device function scheme in different application

scenarios

Click on the “Show Back View” button to view the device rear panel modelled and composed of

user configured plug-in modules

3.2.2 System Configuration

 File Downloading Mode

To respond to the cybersecurity requirements, the downloading operation of device firmware or configuration file could be checked for user authority

Please view and modify the downloading mode through the path: Project Node → Device Node

→ Device Setup → Global Config → System Config → Download mode of config file

 Transformer connection

To set the number of branches for each side of transformer through the path: Project Node →

Trang 31

3

Device Node → Device Setup → Global Config → System Config → Transformer connection

The total number of branches on each side shall not be more than 6, and the number of branches at high voltage side shall not be 0 The default configuration is two branches at each side

 Device Maintenance Mode

During the factory test or site commissioning phase, user could put this device into “Maintenance”

state in order to block signal noise in station communication network The enabling mode of this

state could be activated by a local terminal of binary input or by the logic device “MODE” in IEC

61850 communication protocol

Please view and modify the mode through the path: Project Node → Device Node → Device

Setup → Global Config → System Config → Mode of IED maintenance source

3.2.3 Function Group

Through the page "Function Group", all protection functions and control functions can be enabled

or disabled sorted by the secondary menu, as shown in figure below Double-click the cell in the

"Option" column to switch the option from drop-down box

Trang 32

3

3.2.4 Disturbance Fault Recording

Through the path Project Node → Device Node → HMI Setup → DFR Setup, user can configure

the triggering conditions (“Trigger”) and recorded analog (“Analog Record”) and binary (“Binary

Record”) quantities of the disturbance recording function

Certain default variables have been set by default If the “Deletable” attribute is “No”, the variable

is fixed to be recorded Otherwise, it can be removed from the recording function User could pick

up variables from the right column: Variable DB → Source → Function_Logic → Page : XXXX

to customize the recording variable list

Some attributes could be set for the variables in different recording groups:

“Trigger Type” in “Trigger”

This attribute could be set as “High_Level_Trigger”, “Low_Level_Trigger”,

“Rising_Edge_Trigger”, “Falling_Edge_Trigger” and “Bilateral_Trigger”

Trang 33

3

“Phase” in “Analog Record”

After setting the phase identification, the phase field corresponding to the channel in waveform

recording file (*.CFG) will be filled with the phase By default, the phase field is empty

“Record in Wave File” in “Analog Record” and “Binary Record”

This attribute is used to involve the corresponding analog channels and binary variables into

waveform recording function

3.3 Human Machine Interface

The human machine interface (HMI) module is installed on the front panel of this device It is used

to observe the running status and event information on the LCD, and configure the protection

settings and device operation mode It provides a convenient and friendly access interface to help

user to know the device status and detailed event information easily

As shown in the following figures, this device provides two variants (6U height, 1/2 and 1/1 × 19

inch width) whose HMI elements on front panel are similar

Trang 34

1 Local LCD screen for device status and information display

2 Easy-to-use keypad aiding simple navigation and set-point adjustment

3 Push buttons for opening/closing operation and switching of local/remote control mode

4 Push button for user login/logout of authority management

5 Push buttons with configurable labels for user-programmable functions

6 Front RJ45 multiplex port for debugging

7 Push button for target reset of all signals

8 Two LED indictors for device running status

9 Up to 18 programmable LED indicators with configurable labels

3.3.1 Single Line Diagram Display

The device local LCD screen supports Single Line Diagram (SLD) display of protected primary equipment with relevant information, such as switchgears and transformers For controllable equipment, control operations via the SLD is possible

For 6U 1/1 and 1/2 variants, the large LCD resolution is 320×240 pixels with up to 15 lines and 40 characters per line A display exceeding the screen scale may continue in the next page

In a SLD screen, up to 20 objects (switchgear, transformer, etc.) could be displayed per page For each object, its different status, description labels and relevant measured quantities are configurable Meanwhile, this device supports object customization based on basic symbols, such

as circle, direct line, rectangle, etc The configuration steps are:

 Enter the configuration page through the path in PCS-Studio: Project Node → Device Node

→ HMI Setup → LCD Graph

Trang 35

3

 Drag objective symbols to the red grid zone, adjust their location and use "Line" to connect

them

 Double click a symbol to set its attributes in the pop-up window (if available) Different

configuration tabs may be displayed for different symbols

On “Graphics” tab of a disconnector, select a graphical symbol of equipment

On “Display” tab of a disconnector or a breaker, set the equipment display mode by

Trang 36

3

selecting its relevant variable and display condition

On “Control” tag of a disconnector or a breaker, build a relation between the control object

and a control output by selecting a known output from the default drop-down box or by

clicking the “Advance” button and selecting a predefined enabling/disabling function

output

3.3.2 LED Indicators

This device provides 2 default fixed LEDs “HEALTHY” and “ALARM” to indicate device running

Trang 37

3

status and abnormal status Additionally, it provides 18 programmable LEDs with user-configurable

labels

Each programmable LED could be set to ON or OFF in one of the three colours: red, yellow and

green with or without the “Latched” status After being lighten up, a latched LED would not

extinguish along with the corresponding signal recovery User needs to reset the LED by a

command from the device LCD menu or by pressing the “TARGET RESET” button on the front HMI

panel The configuration steps are:

 Enter the configuration page through the path in PCS-Studio: Project Node → Device Node

→ Program → Function_Logic → UserPage_20LED

 Drag a variable from the "Source" tab in the right “Variable DB” Use "Link line" in the tool

bar to connect the variable with one LED The value of variable determines the LED ON/OFF

state The variable may be a logic output calculated by other logical elements and gates

Double click the LED table to define the LED attributes, such as “Latched” status, colour and

description name

Trang 38

3

3.3.3 Shortcut Keys

This device provides the following keys on the front HMI panel to quickly realize frequently-used functions

Closing operation of control function for local control mode Only valid when single line diagram is drawn and the control

configuration between output and position indication signal of the object switchgear is completed

Opening operation of control function for local control mode

Switching of Remote and Local control mode for control function

Two LEDs are equipped to indicate current remote/local control

mode Please refer to the configuration method in Section 6.1.3

Remote/Local Control Mode

User login/logout for authority management

One LED is equipped to indicate the use logged in/out state Please

refer to Section 3.9 User Authority Management for the configuration method

Reset of latched LED indicators (by default)

In device default configuration, this button is the triggering signal to

reset the LED indicators other than "HEALTHY" and "ALARM"

User may customize another logic that is triggered by the press of this button, such as clearing log, resetting trip counter, etc

3.3.4 Function Keys

This device provides four keys (F1, F2, F3 and F4) for programmable rapid functions, such as a quick execution of menu command or a direct access to sub-level menu path The configuration steps are:

 Enter the configuration window through the path in PCS-Studio: Project Node → Device Node → HMI Setup → Function Key

Trang 39

3

Double click on the “Function” column to select an associated function from the drop-down

box

 Unlatched signal (500ms pulse, programmable)

 Latched signal (flip-flop mechanism, programmable)

The above two kinds of signals are configurable through programmable logics which are usually realized in a customized logic

user-configuration page created under the path: Project Node → Device Node

→ Program → Function_Logic → Customized Page Name

Drag a LCD signal under the path: "Variable DB → Source → CPU →

Page:PPC → Component:LCD", and drag a variable under the path

"Variable DB → Destination → Function_Logic → Page:**" Connect the source and the destination signals with "Link line" to create a customized

logic

Trang 40

to remove it

In the “LED Colour” column, configure the LED light in three colours: green, yellow and red

 Each function key is equipped with a LED indicator Associate a source signal in the column

“LED Associated Signal” to control the ON/OFF status of this LED A source signal could be

a binary output of device function If the source signal is configured, the LED ON/OFF depends

on the signal state Otherwise, if the “LED Associated Signal” field is empty, the LED ON/OFF

status depends on the configured function

 For a latched/unlatched signal, the LED shows its corresponding status;

 For a menu access, the LED flashes regularly

3.3.5 Labels on Front Panel

On the front HMI panel, this device provides two slots for user-defined labels of LED indicators and

function keys The labels are configured and printed by the PC tool “Panel Label Printer” The

configuration steps are:

Ngày đăng: 13/07/2021, 10:50

TỪ KHÓA LIÊN QUAN