Preface About This Manual This manual describes the configuration scheme in multiple application scenarios for PCS-978S Transformer Relay, including how to connect the device to a compu
Trang 3Copyright © 2020 NR All rights reserved
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may
be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights
The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice
To the extent required the products described herein meet applicable IEC and IEEE standards, but
no such assurance is given with respect to local codes and ordinances because they vary greatly Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us
Trang 5Preface
About This Manual
This manual describes the configuration scheme in multiple application scenarios for PCS-978S Transformer Relay, including how to connect the device to a computer and to configure functions, such as control, protection, measurement and supervision in using of configuration tool
To start using this manual for application configuration, user should know the basic operations of the configuration tool PCS-Studio
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment (module or device) However, it comprises important information that must be followed for personal safety, as well as to avoid material damage Information is highlighted and illustrated as follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage
Indicates that property damage can result if the measures specified are
not taken
Important information about the device, product handling or a certain section of the documentation which must be given particular attention
Instructions and Warnings
The following hazard statements apply to this device
Disconnect or de-energize all external connections BEFORE opening this
device Contact with hazardous voltages and currents inside this device can cause electrical shock resulting in injury or death
Trang 6Contact with instrument terminals can cause electrical shock that can result
in injury or death
Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment
Have only qualified personnel service this equipment If you are not qualified
to service this equipment, you can injure yourself or others, or cause equipment damage
This device is shipped with default passwords Default passwords should
be changed to private passwords at installation Failure to change each default password to a private password may allow unauthorized access NR shall not be responsible for any damage resulting from unauthorized access
DO NOT look into the fiber (laser) ports/connectors
DO NOT look into the end of an optical cable connected to an optical output
DO NOT perform any procedures or adjustments that this instruction
manual does not describe
During installation, maintenance, or testing of the optical ports, ONLY use the test equipment qualified for Class 1 laser products!
Incorporated components, such as LEDs, transceivers, and laser emitters,
Trang 7are NOT user serviceable Return units to NR for repair or replacement
Equipment components are SENSITIVE to electrostatic discharge (ESD)
Undetectable permanent damage can result if you do not use proper ESD procedures Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment If your facility is not
equipped to work with these components, contact NR about returning this device and related NR equipment for service
Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables Please use the wiring method recommended in the manual for communication terminals
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power Equipment damage can result otherwise
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure
The firmware may be upgraded to add new features or enhance/modify
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand
Document Conventions
The abbreviations and acronyms in this manual are explained in “Appendix A Glossary” The
Glossary also contains definitions of important terms
Trang 8 Menu path is connected with the arrow "→" and bold
For example: the access path of protection settings is: MainMenu→Settings→Protection Settings
Settings not in t.he table should be placed in brackets
For example: the system setting [Opt_SysFreq]
Cross-references are presented in italics
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold
For example: press the button "ENT"
Trang 11Three-phase Corresponding Relationship
1 Functions and Applications
Introduces of device functions and typical application scenarios
2 Connection to the Configuration Tool
Introduction of the PCS-Studio configuration tool with the connection method
3 Basic Function
Basic functions configuration methods, including functions selection through MOT, diagram drawing
of LCD display, communication protocol selection and setting, user authority management, configuration of binary inputs and outputs, programmable logic, etc
Trang 12List of abbreviations adopted in this manual
Document Revision History
PN: ZL_PCS-978S_X_Application Manual_EN_Overseas General_X
Trang 13Figure 1.2-3 Typical application of a 2-winding transformer 1-5
Figure 1.2-3 Typical application of a 3-winding transformer 1-6
Figure 1.2-3 Typical application of a auto-transformer 1-7
Trang 141
Trang 151
1.1 Functions
PCS-978S transformer relay provides fast and selective protection, control and monitoring for
two-winding transformers, three-two-winding transformers and auto-transformers in any voltage level All
the important auxiliary functions that are necessary today for safe network operation are integrated
in the IED, and the modular structure permits the device always to be adapted flexibly to the
individual requirements
The PCS-978S is applicable not only to conventional substations, but also to digital substations It
supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network interfaces with high
real-time performance The process level network supports peer-to-peer (P2P) mode and
networking mode, including single network mode and dual network mode The station level network
could also receive and send MMS messages (such as interlocking signals) or process level
GOOSE messages (such as trip signals)
1.1.1 Protection Function
87T Transformer differential protection
Biased differential protection with three slopes
Biased DPFC differential protection
Unrestrained instantaneous differential protection
Optional inrush current distinguished principles:
harmonic criterion or waveform distortion
Optional harmonic blocking modes: self-adaptive 1Pblk1P mode, 2PBlk3P mode, 1Pblk3P mode
Overexcitation detection: fifth harmonic or third harmonic criterion
Optional transfer methods: △→Y or Y→△
Independent CT saturation criterion
Differential CT circuit failure supervision
64REF Restricted earth-fault protection
Optional direction element
CT transient characteristic detection
CT saturation detection based on 2nd and 3rd harmonics
87W Winding differential protection
CT transient characteristic detection
CT saturation detection based on 2nd and 3rd harmonics
24 Overexcitation protection
Two stages definite-time overexcitation protection
Stage 1 of definite-time overexcitation protection for trip purpose
Stage 2 of definite-time overexcitation protection for alarm purpose
One stage inverse-time overexcitation protection for both alarm purpose and trip purpose
Trang 161 67P
50/51P Phase overcurrent protection
6 stages with independent logic by default
Voltage control element for each stage
Optional direction element for each stage
Optional definite-time characteristic and inverse-time characteristic for each stage
Trip purpose or alarm purpose for each stage
Harmonic control element for each stage
67G 50/51G Earth fault protection
4 stages with independent logic by default
Optional direction element for each stage
Optional measured zero-sequence current or calculated zero-sequence current
Optional definite-time characteristic and inverse-time characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
Harmonic control element for each stage
67Q 50/51Q
Negative-sequence overcurrent protection
Up to 2 stages with independent logic
Optional direction element for each stage
Optional definite-time characteristic and inverse-time characteristic for each stage
49 Thermal overload protection Two stages thermal overload protection, and one stage
for alarm purpose and the other stage for trip purpose
50BF Breaker failure protection
Up to 6 circuit breakers are supported
Phase-segregated re-trip and three-phases re-trip
Optional current criterion (phase overcurrent element, zero-sequence overcurrent element, negative- sequence overcurrent element)
Optional circuit breaker position check
Two time delays
59P Overvoltage protection
Up to 2 stages with independent logic
Optional definite-time characteristic and inverse-time characteristic for each stage
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Selectable trip purpose or alarm purpose for each stage
27P Undervoltage protection
Up to 2 stages with independent logic
Optional definite-time characteristic and inverse-time characteristic for each stage
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Blocked by instantaneous VT circuit failure
Selectable trip purpose or alarm purpose for each stage
Trang 171
59G Residual overvoltage protection
Up to 2 stages with independent logic
Optional measured zero-sequence voltage or calculated zero-sequence voltage
Optional definite-time characteristic and inverse-time characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
81O Overfrequency protection Up to 2 stages with independent logic
Voltage control element
81U Underfrequency protection Up to 4 stages with independent logic
Voltage control element
1.1.2 Control Functions
Switchgear control
Double point status synthesis
Remote/Local control mode switch
Interlocking logic for control
Direct control
Closing synchronism check with voltage selection
Switchgear trip counter
Tap position indicator and control
1.1.3 Measurement and Metering Functions
CT circuit failure supervision (CTS)
VT circuit failure supervision (VTS)
Self diagnostic
Powerful faults recording (max buffer for 10,000 sampled points at 4.8 or 9.6 kHz)
Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs
Disturbance recorder including 64 disturbance records with waveforms (The file format of
Trang 181
disturbance recorder is compatible with international COMTRADE file.)
Single line diagram representation in display
1.1.5 Communication Functions
Support of various protocols Modbus, DNP3.0, IEC 60870-5-103, IEC 61850 Ed.1 & Ed.2, IEC 61850 MMS Server, IEC 61850-8-1 GOOSE, IEC 61850-9-2LE SV, IEC 62439 Parallel Redundancy Protocol, IEC 62439 HSR Ring Redundancy Protocol
Up to four 10Base-T/100Base-TX copper Ethernet ports
Up to two 100Base-FX optical Ethernet ports
Two RS-485 serial ports for communication or printer
One RS-485/TTL serial port for clock synchronization
Two RJ45 debugging ports (front and rear)
4 Programmable operator pushbuttons with user-configurable labels
Up to 18 programmable target LEDs with user-configurable labels
1 RS-232 or RS-485 rear ports for printer
Language switchover—English+ selected language
Configuration tool—PCS-Studio
1.1.7 Additional Functions
User programmable logic
Switching system phase sequences function (ABC or ACB)
Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE 1588: Clock message based on IEEE 1588 via optical fibre interface
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
Trang 191
SNTP (BC): Broadcast SNTP mode via Ethernet network
Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol,
Modbus protocol and DNP3.0 protocol
There are three kinds of typical application scenarios, as
Two-winding transformer, single circuit breaker arrangement
Three-winding transformer, single circuit breaker arrangement
Auto-winding transformer, singe circuit breaker arrangement
Figure 1.2-1 Typical application of a 2-winding transformer
This configuration is used in the application scenario of a 2-winding transformer with a single circuit
breaker on both sides The three-phase VT, three-phase CT and the neutral-point CT are used for
Trang 201
protection functions calculation and single-phase busbar VT is used for synchronism check The current differential protection is as the main protection, it provides fast and secure tripping for internal faults Restricted earth fault protection, overexctiation protection, phase overcurrent protection, earth fault protection, phase overvoltage protection, residual overvoltage protection and breaker failure protection are configured as backup protection Negative-sequence overcurrent protection, phase undervoltage protection and frequency protection are also optional for some specific requirements
High voltage circuit breaker synchronism check function is equipped, the circuit breaker, the relevant disconnector switches and earthing switches and the tap position could be controlled by the device Supervision functions of analog input channels, binary input channels, CT secondary circuits, VT secondary circuits, switchgear tripping counter, etc are equipped for the operating reliability and safety of the device Moreover, measurement function including U, I, P, Q, S, Cos, f are available in local HMI and remote representation
52
52
3CT
3VT 3CT
Figure 1.2-2 Typical application of a 3-winding transformer
This configuration is used in the application scenario of a 3-winding transformer with a single circuit breaker on both sides The three-phase VT, three-phase CT and the neutral-point CT are used for protection functions calculation and single-phase busbar VT is used for synchronism check The current differential protection is as the main protection, it provides fast and secure tripping for internal faults Restricted earth fault protection, overexctiation protection, phase overcurrent protection, earth fault protection, phase overvoltage protection, residual overvoltage protection and breaker failure protection are configured as backup protection Negative-sequence overcurrent
Trang 211
protection, phase undervoltage protection and frequency protection are also optional for some
specific requirements
High voltage circuit breaker synchronism check function is equipped, the circuit breaker, the
relevant disconnector switches and earthing switches and the tap position could be controlled by
the device Supervision functions of analog input channels, binary input channels, CT secondary
circuits, VT secondary circuits, switchgear tripping counter, etc are equipped for the operating
reliability and safety of the device Moreover, measurement function including U, I, P, Q, S, Cos, f
are available in local HMI and remote representation
52
52
3CT 3VTs
Figure 1.2-3 Typical application of a auto-transformer
This configuration is used in the application scenario of an auto-winding transformer with a single
circuit breaker on both sides The three-phase VT, three-phase CT and the neutral-point CT are
used for protection functions calculation and single-phase busbar VT is used for synchronism check
The current differential protection is as the main protection, it provides fast and secure tripping for
internal faults Winding differential, restricted earth fault protection, overexctiation protection, phase
overcurrent protection, earth fault protection, phase overvoltage protection, residual overvoltage
protection and breaker failure protection are configured as backup protection Negative-sequence
overcurrent protection, phase undervoltage protection and frequency protection are also optional
for some specific requirements
High voltage circuit breaker synchronism check function is equipped, the circuit breaker, the
relevant disconnector switches and earthing switches and the tap position could be controlled by
the device Supervision functions of analog input channels, binary input channels, CT secondary
Trang 221
circuits, VT secondary circuits, switchgear tripping counter, etc are equipped for the operating reliability and safety of the device Moreover, measurement function including U, I, P, Q, S, Cos, f are available in local HMI and remote representation
Trang 232.2.1 Via Front RJ45 Port 2-1
2.2.2 Via Ethernet Interface on CPU Module 2-2
2.3 Validation of Configuration 2-2
Trang 252
2.1 Brief Introduction of PCS-Studio
The PCS-Studio is the configuration and debugging software of PCS S series devices It provides
the following configuration functions:
Device information configuration
Viewing and editing project name, user configuration file version, file modification time, etc
Global function configuration
MOT selection, system configuration, function object activation/deactivation, etc
Human-machine interface configuration
Single Line Diagram (SLD) drawing for LCD display, definition of LED indicators, shortcut keys,
user-level waveform recording, etc
Communication configuration
Support of multiple communication protocols, including IEC 61850 (Edition 1 & Edition 2), IEC
60870-5-103, DNP3.0, Modbus, etc
IO signal configuration
Binary inputs, binary outputs, AC and DC analogue inputs, etc
User-defined logic programming
Complete and rich symbol library for user-defined logic programming
On the front panel of the device, there is a multiplex RJ45 port which is the debugging port for
connection to a portable computer Meanwhile, the CPU plug-in module is equipped with several
Ethernet interfaces which may also be used to communicate with debugging computer
2.2.1 Via Front RJ45 Port
By default, the IP address of front debugging port is “100.100.100.100” with the subnet mask
“255.255.255.000” If this address conflicts with any other Ethernet port on CPU module Through
the device front human-machine interface, please call up the modification menu by pressing the
key combination "◄ + ◄ - ENT" under the default LCD display screen and change the default
address
Trang 262
2.2.2 Via Ethernet Interface on CPU Module
Firstly, a connection between the device and the computer must be established by setting the IP address and subnet mask of the corresponding interfaces Configure the IP address and the subnet
mask of corresponding Ethernet interface through MainMenu → Settings → Global Settings →
Comm Settings → General Comm Settings
The IP addresses and the subnet masks of device PC should be in the same network segment Take the second Ethernet interface (LAN2) on CPU module as an example:
LAN enabling setting [En_LAN2] = Enabled
“XXX” can be any value from 0 to 255 except 102
2.3 Validation of Configuration
To take effect of all kinds of offline configuration work through PCS-Studio, it is necessary to regenerate the device configuration file (*.devs) and download it to the device A reboot of device
is obligatory after the download for the validation of any modification
All function configuration described in the following chapters are offline tasks, which requires the “file generation, file downloading and device reboot” process for validation
Trang 273.2.4 Disturbance Fault Recording 3-4
3.3 Human Machine Interface 3-5
3.3.1 Single Line Diagram Display 3-6
3.5.2 Input Signal from BI Module 3-18
3.5.3 Modify Signal Description 3-19
3.5.4 Modify Signal Parameter 3-19
3.6 Binary Outputs 3-20
3.6.1 Selection of BO Module 3-20
3.6.2 Output Signal to BO Module 3-20
3.6.3 Modify Signal Description 3-21
Trang 283
3.7 Output Map 3-23
3.7.1 Introduction 3-23 3.7.2 Configuration Method 3-23
3.8 User-programmable Logic 3-25
3.8.1 Introduction 3-25 3.8.2 Configuration Method 3-26
3.9 User Authority Management 3-28 3.10 Setting Group Switching 3-29
3.10.1 Introduction 3-29 3.10.2 Number of Groups 3-29 3.10.3 Active Group Switching 3-30 3.10.4 Group Number Output 3-31
3.11 GOOSE Communication 3-32
3.11.1 Introduction 3-32 3.11.2 Receiving 3-34 3.11.3 Sending 3-35 3.11.4 Logic Symbols 3-36
3.12 SV Communication 3-37
3.12.1 Introduction 3-37 3.12.2 Receiving 3-37
Trang 293
3.1 Device Information
Please go through the path Project Node → Device Node → Device Setup → Device
Information to view the basic information of device This information is derived from the driver file
when adding the device into project
Some information may be modified to facilitate the device management, including instance name,
config file version, config time, etc The length of user-defined information “User Information” is
limited to 106 bytes
When generating the driver file, the configuration tool will package user-defined information and
MOT information After downloading the driver file to the device, the information will be analyzed
and displayed on device LCD
3.2 Global Configuration
3.2.1 MOT Selection
Usually, the device Market Ordering Table (MOT) is defined during the project ordering phase
Please check and adapt to the MOT code to verify the device functions configuration in specific
project design The MOT selection path is: Project Node → Device Node → Device Setup →
Global Config → MOT
The MOT code and the detailed option information are displayed on the page Please double click
a cell in the “Option” column to switch the option from drop-down box for device functional and
hardware specifications modification When the contents of the cell is changed, the corresponding
contents in the "Description" and "Code" columns and the corresponding bit of ordering code will
Trang 303
change synchronously
Between some options, coercive and mutually exclusive relations may exist For a coercive relation, one option is fixed to be selected; for a mutually exclusive relation, one option is impossible to be selected
Click on the “Software Function” button to view the device function scheme in different application
scenarios
Click on the “Show Back View” button to view the device rear panel modelled and composed of
user configured plug-in modules
3.2.2 System Configuration
File Downloading Mode
To respond to the cybersecurity requirements, the downloading operation of device firmware or configuration file could be checked for user authority
Please view and modify the downloading mode through the path: Project Node → Device Node
→ Device Setup → Global Config → System Config → Download mode of config file
Transformer connection
To set the number of branches for each side of transformer through the path: Project Node →
Trang 313
Device Node → Device Setup → Global Config → System Config → Transformer connection
The total number of branches on each side shall not be more than 6, and the number of branches at high voltage side shall not be 0 The default configuration is two branches at each side
Device Maintenance Mode
During the factory test or site commissioning phase, user could put this device into “Maintenance”
state in order to block signal noise in station communication network The enabling mode of this
state could be activated by a local terminal of binary input or by the logic device “MODE” in IEC
61850 communication protocol
Please view and modify the mode through the path: Project Node → Device Node → Device
Setup → Global Config → System Config → Mode of IED maintenance source
3.2.3 Function Group
Through the page "Function Group", all protection functions and control functions can be enabled
or disabled sorted by the secondary menu, as shown in figure below Double-click the cell in the
"Option" column to switch the option from drop-down box
Trang 323
3.2.4 Disturbance Fault Recording
Through the path Project Node → Device Node → HMI Setup → DFR Setup, user can configure
the triggering conditions (“Trigger”) and recorded analog (“Analog Record”) and binary (“Binary
Record”) quantities of the disturbance recording function
Certain default variables have been set by default If the “Deletable” attribute is “No”, the variable
is fixed to be recorded Otherwise, it can be removed from the recording function User could pick
up variables from the right column: Variable DB → Source → Function_Logic → Page : XXXX
to customize the recording variable list
Some attributes could be set for the variables in different recording groups:
“Trigger Type” in “Trigger”
This attribute could be set as “High_Level_Trigger”, “Low_Level_Trigger”,
“Rising_Edge_Trigger”, “Falling_Edge_Trigger” and “Bilateral_Trigger”
Trang 333
“Phase” in “Analog Record”
After setting the phase identification, the phase field corresponding to the channel in waveform
recording file (*.CFG) will be filled with the phase By default, the phase field is empty
“Record in Wave File” in “Analog Record” and “Binary Record”
This attribute is used to involve the corresponding analog channels and binary variables into
waveform recording function
3.3 Human Machine Interface
The human machine interface (HMI) module is installed on the front panel of this device It is used
to observe the running status and event information on the LCD, and configure the protection
settings and device operation mode It provides a convenient and friendly access interface to help
user to know the device status and detailed event information easily
As shown in the following figures, this device provides two variants (6U height, 1/2 and 1/1 × 19
inch width) whose HMI elements on front panel are similar
Trang 341 Local LCD screen for device status and information display
2 Easy-to-use keypad aiding simple navigation and set-point adjustment
3 Push buttons for opening/closing operation and switching of local/remote control mode
4 Push button for user login/logout of authority management
5 Push buttons with configurable labels for user-programmable functions
6 Front RJ45 multiplex port for debugging
7 Push button for target reset of all signals
8 Two LED indictors for device running status
9 Up to 18 programmable LED indicators with configurable labels
3.3.1 Single Line Diagram Display
The device local LCD screen supports Single Line Diagram (SLD) display of protected primary equipment with relevant information, such as switchgears and transformers For controllable equipment, control operations via the SLD is possible
For 6U 1/1 and 1/2 variants, the large LCD resolution is 320×240 pixels with up to 15 lines and 40 characters per line A display exceeding the screen scale may continue in the next page
In a SLD screen, up to 20 objects (switchgear, transformer, etc.) could be displayed per page For each object, its different status, description labels and relevant measured quantities are configurable Meanwhile, this device supports object customization based on basic symbols, such
as circle, direct line, rectangle, etc The configuration steps are:
Enter the configuration page through the path in PCS-Studio: Project Node → Device Node
→ HMI Setup → LCD Graph
Trang 353
Drag objective symbols to the red grid zone, adjust their location and use "Line" to connect
them
Double click a symbol to set its attributes in the pop-up window (if available) Different
configuration tabs may be displayed for different symbols
On “Graphics” tab of a disconnector, select a graphical symbol of equipment
On “Display” tab of a disconnector or a breaker, set the equipment display mode by
Trang 363
selecting its relevant variable and display condition
On “Control” tag of a disconnector or a breaker, build a relation between the control object
and a control output by selecting a known output from the default drop-down box or by
clicking the “Advance” button and selecting a predefined enabling/disabling function
output
3.3.2 LED Indicators
This device provides 2 default fixed LEDs “HEALTHY” and “ALARM” to indicate device running
Trang 373
status and abnormal status Additionally, it provides 18 programmable LEDs with user-configurable
labels
Each programmable LED could be set to ON or OFF in one of the three colours: red, yellow and
green with or without the “Latched” status After being lighten up, a latched LED would not
extinguish along with the corresponding signal recovery User needs to reset the LED by a
command from the device LCD menu or by pressing the “TARGET RESET” button on the front HMI
panel The configuration steps are:
Enter the configuration page through the path in PCS-Studio: Project Node → Device Node
→ Program → Function_Logic → UserPage_20LED
Drag a variable from the "Source" tab in the right “Variable DB” Use "Link line" in the tool
bar to connect the variable with one LED The value of variable determines the LED ON/OFF
state The variable may be a logic output calculated by other logical elements and gates
Double click the LED table to define the LED attributes, such as “Latched” status, colour and
description name
Trang 383
3.3.3 Shortcut Keys
This device provides the following keys on the front HMI panel to quickly realize frequently-used functions
Closing operation of control function for local control mode Only valid when single line diagram is drawn and the control
configuration between output and position indication signal of the object switchgear is completed
Opening operation of control function for local control mode
Switching of Remote and Local control mode for control function
Two LEDs are equipped to indicate current remote/local control
mode Please refer to the configuration method in Section 6.1.3
Remote/Local Control Mode
User login/logout for authority management
One LED is equipped to indicate the use logged in/out state Please
refer to Section 3.9 User Authority Management for the configuration method
Reset of latched LED indicators (by default)
In device default configuration, this button is the triggering signal to
reset the LED indicators other than "HEALTHY" and "ALARM"
User may customize another logic that is triggered by the press of this button, such as clearing log, resetting trip counter, etc
3.3.4 Function Keys
This device provides four keys (F1, F2, F3 and F4) for programmable rapid functions, such as a quick execution of menu command or a direct access to sub-level menu path The configuration steps are:
Enter the configuration window through the path in PCS-Studio: Project Node → Device Node → HMI Setup → Function Key
Trang 393
Double click on the “Function” column to select an associated function from the drop-down
box
Unlatched signal (500ms pulse, programmable)
Latched signal (flip-flop mechanism, programmable)
The above two kinds of signals are configurable through programmable logics which are usually realized in a customized logic
user-configuration page created under the path: Project Node → Device Node
→ Program → Function_Logic → Customized Page Name
Drag a LCD signal under the path: "Variable DB → Source → CPU →
Page:PPC → Component:LCD", and drag a variable under the path
"Variable DB → Destination → Function_Logic → Page:**" Connect the source and the destination signals with "Link line" to create a customized
logic
Trang 40to remove it
In the “LED Colour” column, configure the LED light in three colours: green, yellow and red
Each function key is equipped with a LED indicator Associate a source signal in the column
“LED Associated Signal” to control the ON/OFF status of this LED A source signal could be
a binary output of device function If the source signal is configured, the LED ON/OFF depends
on the signal state Otherwise, if the “LED Associated Signal” field is empty, the LED ON/OFF
status depends on the configured function
For a latched/unlatched signal, the LED shows its corresponding status;
For a menu access, the LED flashes regularly
3.3.5 Labels on Front Panel
On the front HMI panel, this device provides two slots for user-defined labels of LED indicators and
function keys The labels are configured and printed by the PC tool “Panel Label Printer” The
configuration steps are: