⚫ The current settings conversion description is added; ⚫ The setting range of the system setting [Active_Grp] is modified; ⚫ The binary input [87B.BI_ExtBlk] and the alarm signal [87B.
Trang 3Copyright © 2020 NR All rights reserved
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may
be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights
The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice
To the extent required the products described herein meet applicable IEC and IEEE standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly
Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us
Trang 5Preface
About This Manual
The technical manual describes the protection, automation, and supervision functions of PCS-915SC centralized busbar differential relay, and contains operation principle descriptions, and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data, sorted per function, as well as the hardware of the device The manual can be used as a technical reference during the engineering phase and during normal service In addition, the manual also includes a glossary that lists and defines technical terms used throughout the manual
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment (module or device) However, it comprises important information that must be followed for personal safety, as well as to avoid material damage Information is highlighted and illustrated
as follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage
Indicates that property damage can result if the measures specified are
not taken
Important information about the device, product handling or a certain section of the documentation which must be given particular attention
Instructions and Warnings
The following hazard statements apply to this device
Disconnect or de-energize all external connections BEFORE opening this
Trang 6device Contact with hazardous voltages and currents inside this device can cause electrical shock resulting in injury or death
Contact with instrument terminals can cause electrical shock that can result in injury or death
Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment
Have ONLY qualified personnel service this equipment If you are not
qualified to service this equipment, you can injure yourself or others, or cause equipment damage
This device is shipped with default passwords Default passwords should
be changed to private passwords at installation Failure to change each default password to a private password may allow unauthorized access
NR shall not be responsible for any damage resulting from unauthorized access
DO NOT look into the fiber (laser) ports/connectors
DO NOT look into the end of an optical cable connected to an optical
output
DO NOT perform any procedures or adjustments that this instruction
manual does not describe
During installation, maintenance, or testing of the optical ports, ONLY use
Trang 7the test equipment qualified for Class 1 laser products!
Incorporated components, such as LEDs, transceivers, and laser emitters,
are NOT user serviceable Return units to NR for repair or replacement
Equipment components are SENSITIVE to electrostatic discharge (ESD)
Undetectable permanent damage can result if you do not use proper ESD procedures Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment If your facility is not
equipped to work with these components, contact NR about returning this device and related NR equipment for service
Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables Please use the wiring method recommended in the manual for communication terminals
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power Equipment damage can result otherwise
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure
The firmware may be upgraded to add new features or enhance/modify
Trang 8existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand
Document Conventions
⚫ The abbreviations and acronyms in this manual are explained in “Appendix A Glossary” The Glossary also contains definitions of important terms
⚫ Menu path is connected with the arrow "→" and bold
For example: the access path of protection settings is: MainMenu -> Settings -> Protection Settings
⚫ Settings not in the table should be placed in brackets
For example: the system setting [Opt_SysFreq]
⚫ Cross-references are presented in italics
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
⚫ Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold
For example: press the button "ENT"
Trang 11An overview of each manual section and section topics follows
Trang 12The content of this manual has been compiled for information purposes only Although NR has done its best to ensure that the document remains the most precise and the most up-to-date as possible, NR shall not assume any liability for defects and damage which result through use of the information contained herein
Document Revision History
PN: ZL_PCS-915SC_X_Technical Manual_EN_Overseas General_X
Current version: R1.20
Trang 13⚫ The current settings conversion description is added;
⚫ The setting range of the system setting [Active_Grp] is modified;
⚫ The binary input [87B.BI_ExtBlk] and the alarm signal [87B.Alm_BI_ExtBlk] are deleted;
⚫ The logics of 87B, 50DZ, 50SOTF are modified
⚫ The binary input [@Bayn.BI_En_Force_52b] is added;
⚫ The Section “Busbar Protection Operation Mode
Identification” in Chapter 3 is modified;
⚫ BC/BS dead zone differential protection is added;
⚫ Phase overvoltage protection and phase undervoltage protection are added;
⚫ Overfrequency protection, underfrequency protection and frequency rate-of-change protection are added;
⚫ Breaker failure protection logic is modified;
⚫ VT circuit supervision function is modified
⚫ The busbar differential protection settings [87B.t_Dly1_Biased] and [87B.t_Dly2_Biased] are added;
⚫ The dead zone fault protection settings [BC.50DZ.En_Blk50BF] and [Fdr.50DZ.En_Blk50BF] are added;
⚫ The supervision setting [Opt_CBPosChk] is added;
⚫ The logic of breaker failure protection is modified
⚫ The front view, the typical rear view and the typical hardware configuration of the extended unit PCS-915SC-EU are added
Trang 14R1.20 R1.23 2020-07-02
⚫ Section 3.3 and Section 3.4 are added;
⚫ Many signals are added for each protection element;
⚫ The setting [50DZ.En_BlkDPFC] is added;
⚫ The logic diagram of BC/BS dead zone fault protection and feeder dead zone fault protection are modified;
⚫ The logic diagram of BC/BS dead zone differential protectionis modified;
⚫ The logic of breaker failure protection is modified;
⚫ The bay CT circuit failure function is added;
⚫ External binary input trip busbar function is modified;
⚫ Section 3.22.2 is modified;
⚫ Section 6.1 is modified;
⚫ Section 6.3.6 is added;
⚫ The device setting [En_PopupRecord_Blk] is added;
⚫ Label settings are modified
Trang 161
Trang 171
1.1 Application
PCS-915SC centralized busbar relay integrates busbar differential protection, bus coupler/section
protection (includes overcurrent protection, switch-on-to-fault protection, dead zone fault
protection, dual CTs BC/BS dead zone differential protection and breaker failure protection),
feeder protection (includes overcurrent protection, dead zone fault protection and breaker failure
protection), voltage protection (phase overvoltage protection and undervoltage protection) and
frequency protection (overfrequency protection, underfrequency protection and frequency
rate-of-change protection) With its flexibility and the powerful PCS-Studio configuration tool,
PCS-915SC offers future-oriented busbar solutions with high investment security and low
operating costs
The PCS-915SC is widely adopted not only for conventional substations, but also for digital
substations It supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network
interfaces with high real-time performance The process level network supports peer-to-peer (P2P)
mode and networking mode, including single network mode and dual network mode The station
level network can also receive and send MMS messages (such as interlocking signals) or process
level GOOSE messages (such as circuit breakers or disconnectors positions and trip signals)
3 CTs
* 52
The functions of this relay include protective functions and auxiliary testing functions, and the
functions of this relay are listed in the following tables
1 Busbar differential protection ⚫ Steady-state percentage restraint busbar 87B
Trang 181
differential protection
⚫ DPFC percentage restraint busbar differential protection
2 Bus coupler/section protection
⚫ Breaker failure protection (50BF)
⚫ Dead zone fault protection (50DZ)
⚫ Dead zone differential protection (87DZ)
⚫ Switch-on-to-fault protection (50SOTF)
⚫ Overcurrent protection (50/51)
50BF 50DZ 87DZ 50SOTF 50/51
3 Feeder protection
⚫ Breaker failure protection (50BF)
⚫ Dead zone fault protection (50DZ)
⚫ Overcurrent protection (50/51)
50BF 50DZ 50/51
4 Voltage protection
⚫ Phase overvoltage protection
⚫ Phase undervoltage protection
59P 27P
6 Auxiliary function
⚫ Dynamic busbar replica
⚫ CT circuit supervision
⚫ VT circuit supervision
⚫ Disconnector position alarm
DPFC is the abbreviation of “deviation of power frequency component” When a fault occurs in the power system, the fault current consists of three parts: the pre-fault power frequency components, the power frequency variables during the fault and the transient variables during the fault DPFC
is the power frequency variables during the fault
2 Measurement functions
⚫ Phase angle measurement
Trang 191
⚫ Differential current calculation
⚫ Sequence component calculation
⚫ Event recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs
⚫ Disturbance recorder including 32 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file)
⚫ Two RS-485 serial ports using IEC 60870-5-103 or Modbus
⚫ One RS-485 serial port for clock synchronization
⚫ Support GOOSE communication module using IEC 61850-8-1 GOOSE
⚫ Full compatibility between IEC 61850 Editions 1 and 2
⚫ Redundancy protocols PRP and HSR
⚫ One RS-485 serial port for clock synchronization
5 Digital interface
⚫ Support IEC 61850 MMS Server via extendable electrical or optical Ethernet port
⚫ Support IEC 61850-8-1 GOOSE via extendable electrical or optical Ethernet port
⚫ Support IEC 61850-9-2LE SV via extendable electrical or optical Ethernet port
6 User Interface
Trang 201
⚫ Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and set-point adjustment
⚫ 4 programmable operator pushbuttons with user-configurable labels
⚫ Up to 18 programmable target LEDs with user-configurable labels
⚫ 1 RS-232 or RS-485 rear ports for printer
⚫ Language switchover—English+ selected language
⚫ Configuration tool—PCS-Studio
7 Additional functions
⚫ User programmable logic
⚫ Fault phase selection
⚫ System phase sequences rotation function (ABC or ACB)
⚫ Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fiber interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE1588: Clock message based on IEEE1588 via optical fiber interface
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
SNTP (BC): Broadcast SNTP mode via Ethernet network
Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol, Modbus protocol and DNP3.0 protocol
Trang 211
circuit ensure that overall reliability of the device is high Real-time sampling based on dual AD
can mutually check and detect the potential abnormality in the sampling circuit in time The
control power supply of the output relay is independent with the control circuit of trigger signals,
which can prevent from undesired operation caused by the abnormality of drive circuit of
output relays
⚫ Various function modules can satisfy various situations according to the different requirements
of users Flexible and universal logic programming, user-defined configuration of BI/BOs,
buttons and LEDs and powerful analogue programming are supported
⚫ Modularized hardware design makes the device be easily upgraded or repaired by a qualified
service person It can be combined with different I/O modules, with online self-check and
monitoring function, and the device can be restored from abnormal operation only need to
replace a single abnormal module
⚫ Support memory check and error correction function, ensure high reliability and safety
⚫ Support the internet communication protocol of native PRP/HSR and RSTP
⚫ Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351
communication service, GOOSE communication in station level & process level, SV
communication with multi-sampling rate
⚫ Fully comply with cyber security standards, including IEC62443, IEC62351, IEEE1686,
NERC-CIP, support role based access control (RBAC), security audit, security encryption
communication and security tool, improve the cyber security capability of devices
⚫ Powerful COMTRADE fault and disturbance recording function is supported The whole
recording time is automatically configurable by the fault duration, which is convenient to fault
analysis and replay The recording sample rate is up to 9.6kHz
⚫ Settable secondary rated current (1A/5A) and settable voltage threshold of binary input
⚫ Support flush mounting and rack mounting methods
⚫ Cross screw IO, CT/VT terminals can support AWG12 specification connector and 4mm2 lead
⚫ Protection class of front side is up to IP54
⚫ PCS-Studio configuration tool is the application software on the user’s PC for the interface
with PCS S series devices providing all the related functionality It ranges from device
configuration to entire substation design of bay integration
⚫ Support IEEE1588, IRIG-B clock synchronization
⚫ Support actual system phase sequence, either ABC or ACB, incorrect connection of actual
phase sequence can automatically be verified and relevant protection functions can be
blocked
⚫ Equipped with high-speed large capacity output relay, its operation speed is less than 1ms and
its break capacity is up to 10A The real-time supervision for output drive circuit can detect the
abnormality in advance
Trang 226 busbars and 36 bays
⚫ Comprehensive functionality including phase segregated current differential protection, breaker failure protection, overcurrent protection and dead zone protection, etc
⚫ The phase segregated differential protection adopts both of deviation of power frequency component (DPFC) and steady-state component, that can guarantees fast and reliable performance during CT saturation It can ensure no mal-operation of external fault and fast operation of internal fault in the case of the correct transfer time of CT is no less than 3ms
⚫ With patented adaptive-weight anti-saturation algorithm and harmonic restrain algorithm, the DPFC differential protection operates fast and not affected by load current, the typical operation time is within 15ms
⚫ Voltage blocking is an option for the current differential protection and breaker failure protection, which will improve the reliability of current differential protection and breaker failure protection
⚫ With CT circuit supervision function, once CT circuit failure is detected, the user can choose discrimination zone or check zone differential protection blocking
⚫ Both of phase segregated and three phase breaker failure binary inputs can be connected for breaker failure protection, users can choose whether or not blocked by the current criterion The overcurrent element of breaker failure protection have been especially treated, the drop-off time of it is no more than 12ms
⚫ Selectable IEC, ANSI inverse-time characteristic curves that can be defined by users and the inverse-time drop-out curve selection is supported
⚫ With the disconnector position status monitor and memory function, the device can check the rationality of the memorized disconnector position status and automatically correct the error
⚫ Users can disable the discrimination zone differential element by the external binary input during the busbar maintenance Also the bay can be disabled by the external binary input when it is in maintenance
⚫ LCD can display real-time main wiring diagram, the number of each bay, the state of each breaker and disconnector, current and power flow, etc
Trang 242
2.10.1 Clock Performance 2-10 2.10.2 Fault and Disturbance Recording 2-11 2.10.3 Binary Input Signal 2-11
2.11 Protective Functions 2-11
2.11.1 Current Differential Protection (87B/87DZ) 2-11 2.11.2 Dead Zone Fault Protection (50DZ) 2-11 2.11.3 Switch-on-to-fault Protection (50SOTF) 2-11 2.11.4 Breaker Failure Protection (50BF) 2-11 2.11.5 Phase Overcurrent Protection (50/51P) 2-11 2.11.6 Earth Fault Protection (50/51G) 2-12 2.11.7 Phase Overvoltage Protection (59P) 2-12 2.11.8 Phase Undervoltage Protection (27P) 2-12 2.11.9 Overfrequency Protection (81O) 2-13 2.11.10 Underfrequency Protection (81U) 2-13 2.11.11 Frequency Rate-of-change Protection (81R) 2-13
2.12 Communication Functions 2-14
2.12.1 GOOSE 2-14 2.12.2 SV 2-14
Trang 25Burden <0.05VA/phase @1A, <0.25VA/phase @5A
600V 660V
Phase-to-phase 519V
1038V 1141V
Burden at rated <0.10VA/phase @100V
2.1.3 Power Supply
Rated voltage 110Vdc/125Vdc/220Vdc/250Vdc
100Vac/110Vac/115Vac/120Vac 127Vac/220Vac/230Vac/240Vac 250Vac
Permissible voltage range
IEC 61000-4-11:2017 IEC 61000-4-29:2000
Trang 26Quiescent condition <30W (Default hardware configuration)
Additional for each energized SFP socket
Additional for each binary output (BO) module
Quiescent condition: <0.1W Additional for each energized relay: <0.44W Additional module for SV
On value (default set) 69.3~132Vdc 78.75~160Vdc 138.6~264Vdc 157.5~300Vdc
Off value (default set) <55Vdc <62.5Vdc <110Vdc <125Vdc
Maximum permissible voltage 300Vdc
Withstand voltage 2000Vac, 2800Vdc (1 min)
Trang 272
Settable pickup voltage and dropout voltage
Maximum permissible voltage 300Vac
Withstand voltage 2000Vac, 2800Vdc (1 min)
Settable pickup voltage and dropout voltage
Maximum permissible voltage 300Vdc
Withstand voltage 2000Vac, 2800Vdc (1 min)
2.1.5 Binary Output
Tripping/signalling contact
Maximum system voltage 250Vac, 300Vdc
Pickup time (Typical value) <5ms
Drop-off time (Resistive load) <6ms
Breaking capacity (L/R=40ms)
0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc Cyclic capacity (2.5 cycle/second,
L/R=40ms)
0.5A@48Vdc 0.35A@110Vdc
Trang 282
0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc
Short duration current
30A@3s 50A@1s Durability (Loaded contact) 10000 operations
Heavy-capacity tripping contact
MOV Protection (Maximum voltage) 350Vdc, 275Vac
Pickup time (Typical value) <1ms
Drop-off time (Resistive load) <10ms
Breaking capacity
10A@48V L/R=40ms 10A@110V L/R=40ms 10A@125V L/R=40ms 10A@220V L/R=20ms 10A@250V L/R=20ms
Cyclic capacity (4cycles in 1 second,
followed by 2 minutes idle for thermal
dissipation)
10A@48V L/R=40ms 10A@110V L/R=40ms 10A@125V L/R=40ms 10A@220V L/R=20ms 10A@250V L/R=20ms
Short duration current
30A@3s 50A@1s Durability (Loaded contact) 10000 operations
2.2 Mechanical Specifications
Weight per device Approx 23kg (6U, 1/1 × 19")
Trang 292
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated front-plate
Protection Class
Rear side, connection terminals IP20
2.3 Ambient Temperature and Humidity Range
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Maximum transmission distance 500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
2.4.2 Ethernet Port
Trang 302
Maximum transmission
distance
500m (50/125μm) 300m (62.5/125μm)
Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850
Safety level Isolation to ELV level
2.4.3 Optical Fiber Port
For Station Level
Characteristic Glass optical fiber
Maximum transmission distance 2km
Minimum receiving power -31dBm
2.4.4 Print Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Safety level Isolation to ELV level
2.4.5 Clock Synchronization Port
Trang 312
2.5 Type Tests
2.5.1 Environmental Tests
Damp heat test, cyclic IEC60068-2-30:2005
2.5.2 Mechanical Tests
Shock and bump IEC 60255-21-2:1988 Class Ⅰ
2.5.3 Electrical Tests
Dielectric tests Test voltage 2kV, 50Hz, 1min
Impulse voltage tests Test voltage 5kV
Electrostatic discharge test
IEC 61000-4-2-2008 class Ⅳ For contact discharge: 8kV For air discharge: 15kV
Radio frequency interference tests
IEC 60255-26:2013 class Ⅲ Frequency sweep
Radiated amplitude-modulated 10V/m (rms), f=80~1000MHz, 1400~2700MHz Spot frequency
Radiated amplitude-modulated 10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Trang 322
Fast transient disturbance tests
IEC 60255-26:2013 Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns
Surge immunity test
IEC 60255-26:2013 Power supply, AC input, I/O port: class Ⅳ, 1.2/50μs Common mode: 4kV
Differential mode: 2kV
Conducted RF electromagnetic
disturbance
IEC 60255-26:2013 Power supply, AC, I/O, Comm Terminal: Class Ⅲ, 10V(rms), 150 kHz~80MHz
Spot frequency 10V (rms), f=27MHz/68MHz Power frequency magnetic field
immunity
IEC 61000-4-8: 2009 class Ⅴ, 100A/m for 1min, 1000A/m for 3s
Pulse magnetic field immunity
IEC 61000-4-9:2016 class Ⅴ, 6.4/16μs, 1000A/m for 3s Damped oscillatory magnetic field
immunity
IEC 61000-4-10:2016 class Ⅴ, 100kHz & 1MHz–100A/m
Conducted emission
IEC 60255-26:2013 0.15MHz~0.50MHz: 79dB (μV) quasi peak, 66dB (μV) average 0.50MHz~30MHz: 73dB (μV) quasi peak, 60dB (μV) average
Radiated emission
IEC 60255-26:2013
Below 1GHz
30MHz~230MHz: 40dB (μV/m) quasi peak @10m, 50dB (μV/m) quasi peak @3m
230MHz~1000MHz: 47dB (μV/m) quasi peak @10m, 57dB (μV/m) quasi peak @3m
Above 1GHz
1GHz~3GHz: 56dB (μV/m) average, 76dB (μV/m) peak @3m
3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m)
Trang 33500ms for interruption without rebooting with energy storage board (Typical configuration)
⚫ EMC: 2014/30/EU, EN60255-26:2013
⚫ Products safety (LVD): 2014/35/EU, EN60255-27:2014
⚫ IEC 61850: Edition 2, Parts 6, 7-1, 7-2, 7-3,7-4 and 8-1
⚫ IEC 61850: Edition 2, GOOSE Performance Class P1 (3ms)
⚫ IEEE 1588: IEEE Std C37.238TM-2017
⚫ DNP: DNP 3.0
⚫ PRP: IEC 62439-3 Ed.3 (IS 2016)
⚫ HSR: IEC 62439-3 Ed.3 (IS 2016)
2.7 Liquid Crystal Display (LCD)
Trang 342
2.8 Terminals
2.8.1 Ring Ferrule
Grounding (Earthing) connection BVR type, 0.8~4mm 2 lead M3 0.6~0.8 N⋅m
2.8.2 Pin Ferrule
Power supply Screw terminals, 0.3~3.3mm 2 lead M2.5 0.4~0.6 N⋅m Contact I/O Screw terminals, 0.3~3.3mm 2 lead M2.5 0.4~0.6 N⋅m
2.9 Measurement Scope and Accuracy
Trang 352
2.10.2 Fault and Disturbance Recording
Duration & Recording position Settable pre-disturbance, post-disturbance and maximum recorded
duration
2.10.3 Binary Input Signal
Resolution of binary input signal ≤1ms
Binary input mode Potential-free contact
2.11 Protective Functions
2.11.1 Current Differential Protection (87B/87DZ)
Current accuracy ≤2.5% of setting or 0.02In whichever is greater
Voltage accuracy ≤2.5% of setting or 0.01Un, whichever is greater
2.11.2 Dead Zone Fault Protection (50DZ)
Current accuracy ≤2.5% of setting or 0.02In whichever is greater
Time delay accuracy ≤1%xSetting + 40ms
2.11.3 Switch-on-to-fault Protection (50SOTF)
Current accuracy ≤2.5% of setting or 0.02In whichever is greater
2.11.4 Breaker Failure Protection (50BF)
Current accuracy ≤2.5% of setting or 0.02In, whichever is greater
Time delay accuracy ≤1%×Setting or 25ms (at 2 times current setting)
Voltage accuracy ≤2.5% of setting or 0.01Un, whichever is greater
2.11.5 Phase Overcurrent Protection (50/51P)
Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater
Pickup time ≤25ms (at 2 times current setting)
Operating time delay accuracy
(Definite-time characteristics) ≤1%×Setting or 25ms (at 2 times current setting)
Operating time delay accuracy ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30)
Trang 362
(Inverse-time characteristics)
Dropout time accuracy (Definite-time
characteristics) ≤1%×Setting or 30ms
Dropout time accuracy (Inverse-time
characteristics) ≤5% of calculated value or 30ms
2.11.6 Earth Fault Protection (50/51G)
Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater
Pickup time ≤25ms (at 2 times current setting)
Operating time delay accuracy
(Definite-time characteristics) ≤1%×Setting or 25ms (at 2 times current setting)
Operating time delay accuracy
(Inverse-time characteristics) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30) Dropout time accuracy (Definite-time
characteristics) ≤1%×Setting or 30ms
Dropout time accuracy (Inverse-time
characteristics) ≤5% of calculated value or 30ms
2.11.7 Phase Overvoltage Protection (59P)
Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater
Pickup time ≤35ms (at 1.1 times voltage setting)
Operating time delay accuracy
(Definite-time characteristics) ≤1%×Setting or 35ms (at 1.1 times voltage setting)
Operating time accuracy
(Inverse-time characteristics) ≤5% of calculated value + 1% voltage tolerance or 40ms (1.1≤U/Up≤2) Drop-out time accuracy ≤1%×Setting or 30ms
Drop-out ratio Settable 0.93~1.00, default value: 0.98
2.11.8 Phase Undervoltage Protection (27P)
Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater
Pickup time ≤35ms (at 0.9 times voltage setting)
Trang 372
Operating time delay accuracy
(Definite-time characteristics) ≤1%×Setting or 35ms (at 0.9 times voltage setting)
Drop-out time accuracy (Inverse-time
characteristics) ≤5% of calculated value + 1% voltage tolerance or 50ms (U/Up≤0.9)
Drop-out time accuracy ≤1%×Setting or 30ms
Drop-out ratio Settable 1.00~1.20, default value: 1.03
2.11.9 Overfrequency Protection (81O)
Frequency setting accuracy ≤ 0.01Hz
Time delay accuracy ≤1%×Setting+70ms
Drop-out time accuracy ≤40ms
Drop-out frequency 1.0×Setting
2.11.10 Underfrequency Protection (81U)
Frequency setting accuracy ≤ 0.01Hz
Time delay accuracy ≤1%×Setting+70ms
Drop-out time accuracy ≤40ms
Drop-out frequency 1.0×Setting
2.11.11 Frequency Rate-of-change Protection (81R)
Frequency rate-of-change setting
Time delay accuracy ≤1%×Setting+70ms
Drop-out time accuracy ≤40ms
Drop-out frequency 1.0×Setting
Trang 38Receiving route delay Max 2ms
Sending route delay Max 3ms
The capacity of GOOSE receiving and sending is determined by the number of configured boards and control & protection functions
2.12.2 SV
Receiving Control Block (RCB) Max 12
Receiving route delay Max 2ms
The capacity of SV receiving is determined by the number of configured boards and control & protection functions
Trang 393
3 Protection Functions
Table of Contents
3.1 Overview 3-1
3.2 Supported Busbar Arrangements 3-1
3.3 Three-phase Current Element (TCUR3P) 3-7
Trang 403
3.7.2 Function Block Diagram 3-47 3.7.3 I/O Signal 3-48 3.7.4 Logic 3-49 3.7.5 Settings 3-51
3.8 Feeder Dead Zone Fault Protection (50DZ) 3-52
3.8.1 Function Description 3-53 3.8.2 Function Block Diagram 3-54 3.8.3 I/O Signal 3-54 3.8.4 Logic 3-56 3.8.5 Settings 3-56
3.9 BC/BS Switch-on-to-fault (SOTF) Protection (50SOTF) 3-58
3.9.1 Function Description 3-58 3.9.2 Function Block Diagram 3-58 3.9.3 I/O Signal 3-59 3.9.4 Logic 3-59 3.9.5 Settings 3-60
3.10 Breaker Failure Protection (50BF) 3-61
3.10.1 Function Description 3-62 3.10.2 Function Block Diagram 3-67 3.10.3 I/O Signal 3-67 3.10.4 Logic 3-70 3.10.5 Settings 3-72
3.11 Phase Overcurrent Protection 3-75
3.11.1 Function Description 3-76 3.11.2 Function Block Diagram 3-82 3.11.3 I/O Signal 3-82 3.11.4 Logic 3-83 3.11.5 Settings 3-83
3.12 Earth Fault Overcurrent Protection 3-85
3.12.1 Function Description 3-86