Preface About This Manual The technical manual describes the protection, automation, and supervision functions of PCS-924S stub differential relay, and contains operation principle desc
Trang 3Copyright © 2020 NR All rights reserved
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may
be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights
The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice
To the extent required the products described herein meet applicable IEC and IEEE standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly
Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us
Trang 5Preface
About This Manual
The technical manual describes the protection, automation, and supervision functions of PCS-924S stub differential relay, and contains operation principle descriptions, and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data, sorted per function, as well as the hardware of the device The manual can be used as a technical reference during the engineering phase and during normal service In addition, the manual also includes a glossary that lists and defines technical terms used throughout the manual
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment (module or device) However, it comprises important information that must be followed for personal safety, as well as to avoid material damage Information is highlighted and illustrated
as follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will result
in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage
Indicates that property damage can result if the measures specified are not taken
Important information about the device, product handling or a certain section of the documentation which must be given particular attention
Instructions and Warnings
The following hazard statements apply to this device
Disconnect or de-energize all external connections BEFORE opening this
device Contact with hazardous voltages and currents inside this device
Trang 6can cause electrical shock resulting in injury or death
Contact with instrument terminals can cause electrical shock that can result in injury or death
Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment
Have only qualified personnel service this equipment If you are not qualified to service this equipment, you can injure yourself or others, or cause equipment damage
This device is shipped with default passwords Default passwords should
be changed to private passwords at installation Failure to change each default password to a private password may allow unauthorized access
NR shall not be responsible for any damage resulting from unauthorized access
DO NOT look into the fiber (laser) ports/connectors
DO NOT look into the end of an optical cable connected to an optical
output
DO NOT perform any procedures or adjustments that this instruction
manual does not describe
During installation, maintenance, or testing of the optical ports, ONLY use the test equipment qualified for Class 1 laser products!
Trang 7Incorporated components, such as LEDs, transceivers, and laser emitters,
are NOT user serviceable Return units to NR for repair or replacement
Equipment components are SENSITIVE to electrostatic discharge (ESD)
Undetectable permanent damage can result if you do not use proper ESD procedures Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment If your facility is not
equipped to work with these components, contact NR about returning this device and related NR equipment for service
Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables Please use the wiring method recommended in the manual for communication terminals
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power Equipment damage can result otherwise
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure
The firmware may be upgraded to add new features or enhance/modify
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand
Trang 8Document Conventions
⚫ The abbreviations and acronyms in this manual are explained in “Appendix A Glossary” The Glossary also contains definitions of important terms
⚫ Menu path is connected with the arrow "→" and bold
For example: the access path of protection settings is: MainMenu -> Settings -> Protection
Settings
⚫ Settings not in the table should be placed in brackets
For example: the system setting [Opt_SysFreq]
⚫ Cross-references are presented in italics
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
⚫ Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold
For example: press the button "ENT"
Trang 11on the target sections of this manual as your job needs and responsibilities dictate An overview of each manual section and section topics follows
Trang 12Describes the function of various protection elements, gives detailed specifics on protection scheme logic, provides the relevant logic diagrams
6 System Functions
Describes how to perform fundamental operations such as clock synchronization, communicating with the device, switching active setting group, checking relay status, reading event reports and SER (Sequential Events Recorder) records
Appendix A Glossary
Describes the abbreviations adopted in this manual
Document Revision History
PN: ZL_PCS-924S_X_Technical Manual_EN_Overseas General_X
Trang 141
Trang 151
1.1 Application
PCS-924S is a fully numerical stub differential relay which is mainly designed for protecting
T-zone of one and a half breakers arrangement The protection function of PCS-924S comprises
of current differential protection, phase overcurrent protection and feeder line end fault protection
With its flexibility and the powerful PCS-Studio configuration tool, PCS-924S offers future-oriented
T-zone solutions with high investment security and low operating costs
The PCS-924S is widely adopted not only for conventional substations, but also for digital
substations It supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network
interfaces with high real-time performance The process level network supports peer-to-peer (P2P)
mode and networking mode, including single network mode and dual network mode The station
level network could also receive and send MMS messages (such as interlocking signals) or
process level GOOSE messages (such as disconnectors positions and trip signals)
Figure 1.2-1 Functional diagram of PCS-924S
ANSI Protection functions Remark
87S Current differential protection ⚫ Steady-state current differential element (3-terminal
and 2-terminal) 50FLE Feeder line end fault protection ⚫ Definite-time overcurrent element (2 stages)
50P Phase overcurrent protection ⚫ Definite-time overcurrent element (1 stage)
Trang 161
⚫ Trip purpose or alarm purpose
⚫ Current measurement at a 1.2kHz sampling rate
⚫ Current measurement at a 9.6kHz sampling rate
⚫ Differential current calculation
⚫ Sequence component calculation
⚫ Two RS-485 serial ports using IEC 60870-5-103 or Modbus
⚫ One RS-485 serial port for clock synchronization
⚫ Support GOOSE communication module using IEC 61850-8-1 GOOSE
⚫ Full compatibility between IEC 61850 Editions 1 and 2
⚫ Redundancy protocols PRP, HSR and RSTP
⚫ One front RJ-45 port and one rear RJ-45 port for debugging
⚫ Support IEC 61850 MMS Server via extendable electrical or optical Ethernet port
⚫ Support IEC 61850-8-1 GOOSE via extendable electrical or optical Ethernet port
⚫ Support IEC 61850-9-2LE SV via extendable electrical or optical Ethernet port
Trang 171
⚫ Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and
set-point adjustment
⚫ 4 Programmable operator push-buttons with user-configurable labels
⚫ Up to 18 programmable target LEDs with user-configurable labels
⚫ 1 RS-485 rear ports for printer
⚫ Language switchover—English+ selected language
⚫ Configuration tool—PCS-Studio
⚫ User programmable logic
⚫ Fault phase selection
⚫ Switching system phase sequences function (ABC or ACB)
⚫ Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE 1588: Clock message based on IEEE 1588 via optical fiber interface
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
SNTP (BC): Broadcast SNTP mode via Ethernet network
Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol,
Modbus protocol and DNP3.0 protocol
⚫ Unified software & hardware platform, comprehensive power grid solutions of protection,
measurement and monitoring, easy to use and maintain
⚫ High reliability and redundancy design for drive systems of the sampling circuit and the output
Trang 181
circuit ensure that the overall reliability of the device is high Real-time sampling based on dual
AD can mutually check and detect the potential abnormality in the sampling circuit in time The control power supply of the output relay is independent with the control circuit of trigger signals, which can prevent from undesired operation caused by the abnormality of drive circuit of output relays
⚫ Various function modules can satisfy various situations according to the different requirements
of users Flexible and universal logic programming, user-defined configuration of BI/BOs, buttons and LEDs and powerful analogue programming are supported
⚫ Modularized hardware design makes the device be easily upgraded or repaired by a qualified service person It can be combined with different I/O modules, with online self-check and monitoring function, and the device can be restored from abnormal operation only need to replace a single abnormal module
⚫ Support memory check and error correction function, ensure high reliability and safety
⚫ Support the internet communication protocol of native PRP/HSR and RSTP
⚫ Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351 communication service, GOOSE communication in station level & process level, SV communication with multi-sampling rate
⚫ Fully complies with cyber security standards, including IEC62443, IEC62351, IEEE1686, NERC-CIP, support role based access control (RBAC), security audit, security encryption communication and security tool, improve the cyber security capability of devices
⚫ Powerful COMTRADE fault and disturbance recording function is supported The whole recording time is automatically configurable by the fault duration, which is convenient to fault analysis and replay The recording sample rate is up to 9.6kHz
⚫ Settable secondary rated current (1A/5A) and settable voltage threshold of binary input
⚫ Support flush mounting, semi-flush mounting, surface mounting, wall mounting and other mounting methods
⚫ Cross screw IO, CT terminals can support AWG12 specification connector and 4mm2 lead
⚫ Multiple variants with case size 1/1 or 1/2 × 19"
⚫ Protection class of front side is up to IP54
⚫ PCS-Studio is the configuration tool providing all the related functionality for PCS S series devices It ranges from device configuration to entire substation design of bay integration
⚫ Support IEEE 1588, IRIG-B clock synchronization
⚫ Support actual system phase sequence, either ABC or ACB, incorrect connection of actual phase sequence can automatically be verified and relevant protection functions can be blocked
⚫ Equipped with high-speed large capacity output relay, its operation speed is less than 1ms and
Trang 201
Trang 222.12 Communication Functions 2-13
2.12.1 GOOSE 2-13 2.12.2 SV 2-13
Trang 23Burden <0.05VA/phase @1A, <0.25VA/phase @5A
2.1.2 Power Supply
100Vac/110Vac/115Vac/120Vac 127Vac/220Vac/230Vac/240Vac 250Vac
Permissible voltage range
IEC 61000-4-11:2017 IEC 61000-4-29:2000
Quiescent condition <15W (Default hardware configuration)
Additional for each
Trang 242
0.004W @ 24VDC 0.008W @ 48VDC 0.015W @ 110VDC 0.32W @ 220VDC 0.41W @ 250VDC Additional for each BO
module
Quiescent condition: <0.1W Additional for each energized binary output: <0.44W Additional module for SV
On value (default set) 69.3~132Vdc 78.75~160Vdc 138.6~264Vdc 157.5~300Vdc
Off value (default set) <55Vdc <62.5Vdc <110Vdc <125Vdc
Maximum permissible voltage 300Vdc
Withstand voltage 2000Vac, 2800Vdc (1 min)
Number
Up to 84 (6U, 1/2 × 19'', ring ferrule), 105 (6U, 1/2 × 19'', pin ferrule),
259 (6U, 1/1 × 19'', ring ferrule) or 329 (6U, 1/1 × 19'', pin ferrule) binary inputs according to various hardware configurations
Settable pickup voltage and dropout voltage
Maximum permissible voltage 300Vac
Withstand voltage 2000Vac, 2800Vdc (1 min)
Number Up to 84 (6U, 1/2 × 19'', ring ferrule), 105 (6U, 1/2 × 19'', pin ferrule),
Trang 25Maximum permissible voltage 300Vdc
Withstand voltage 2000Vac, 2800Vdc (1 min)
Number
Up to 84 (6U, 1/2 × 19'', ring ferrule), 105 (6U, 1/2 × 19'', pin ferrule),
259 (6U, 1/1 × 19'', ring ferrule) or 329 (6U, 1/1 × 19'', pin ferrule) binary inputs according to various hardware configurations
2.1.4 Binary Output
Tripping/signaling contact
Max system voltage 250Vac, 300Vdc
Pickup time (Typical value) <5ms
Dropout time (Resistive load) <6ms
Breaking capacity (L/R=40ms)
0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc
Cyclic capacity (2.5 cycle/second,
L/R=40ms)
0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc
Trang 262
0.15A@250Vdc
Short duration current
30A@3s 50A@1s Durability (Loaded contact) 10000 operations
Number
Up to 44 (6U, 1/2 × 19'', ring ferrule), 56 (6U, 1/2 × 19'', pin ferrule),
135 (6U, 1/1 × 19'', ring ferrule) or 175 (6U, 1/1 × 19'', pin ferrule) binary outputs according to various hardware configurations
Heavy-capacity tripping contact
MOV protection (maximum voltage) 350Vdc, 275Vac
Pickup time (Typical value) <1ms
Dropout time (Resistive load) <10ms
Breaking capacity (L/R=40ms)
10A@48V L/R=40ms 10A@110V L/R=40ms 10A@125V L/R=40ms 10A@220V L/R=20ms 10A@250V L/R=20ms
Cyclic capacity (4cycles in 1 second,
followed by 2 minutes idle for thermal
dissipation)
10A@48V L/R=40ms 10A@110V L/R=40ms 10A@125V L/R=40ms 10A@220V L/R=20ms 10A@250V L/R=20ms
Short duration current
30A@3s 50A@1s Durability (Loaded contact) 10000 operations
Number
Up to 12 (6U, 1/2 × 19'', ring ferrule or pin ferrule) or 40 (6U, 1/1 × 19'', ring ferrule or pin ferrule) binary outputs according to various hardware
Trang 272
configurations
2.2 Mechanical Specifications
Weight per device
Approx 8.66kg (6U, 1/2 × 19'') Approx 13.88kg (6U, 1/1 × 19'')
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated frontplate
Protection Class
Front side
IP52 IP54 (valid for surface mounting mode of 6U, 1/2 × 19'' case with sealing strip)
Rear side, connection terminals IP20
2.3 Ambient Temperature and Humidity Range
Trang 282
2.4 Communication Port
2.4.1 EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Max transmission distance 500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
2.4.2 Ethernet Port
Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850
Safety level Isolation to ELV level
2.4.3 Optical Fibre Port
For Station Level and Process Level
Characteristics Glass optical fiber
Maximum transmission distance 2km
Minimum receiving power -31dBm
2.4.4 Print Port
Trang 292
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Safety level Isolation to ELV level
2.4.5 Clock Synchronization Port
Peak optical input power
Logic level HIGH
Logic level LOW
Maximum -40dBm Maximum -10dBm, Minimum -24dBm
Trang 302
Damp heat test, cyclic IEC60068-2-30:2005
2.5.2 Mechanical Tests
Shock and bump IEC 60255-21-2:1988 Class Ⅰ
2.5.3 Electrical Tests
Dielectric tests Test voltage 2kV, 50Hz, 1min
Impulse voltage tests Test voltage 5kV
Electrostatic discharge test
IEC 61000-4-2-2008 class Ⅳ For contact discharge: 8kV For air discharge: 15kV
Radio frequency interference tests
IEC 60255-26:2013 class Ⅲ Frequency sweep
Radiated amplitude-modulated 10V/m (rms), f=80~1000MHz, 1400~2700MHz Spot frequency
Radiated amplitude-modulated 10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Fast transient disturbance tests
IEC 60255-26:2013 Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns
Trang 312
Surge immunity test
IEC 60255-26:2013 Power supply, AC input, I/O port: class Ⅳ, 1.2/50μs Common mode: 4kV
Differential mode: 2kV
Conducted RF Electromagnetic
Disturbance
IEC 60255-26:2013 Power supply, AC, I/O, Comm Terminal: Class Ⅲ, 10V (rms), 150 kHz~80MHz
Spot frequency 10V (rms), f=27MHz/68MHz Power Frequency Magnetic Field
Immunity
IEC 61000-4-8: 2009 class Ⅴ, 100A/m for 1min, 1000A/m for 3s
Pulse Magnetic Field Immunity
IEC 61000-4-9:2016 class Ⅴ, 6.4/16μs, 1000A/m for 3s Damped oscillatory magnetic field
immunity
IEC 61000-4-10:2016 class Ⅴ, 100kHz & 1MHz–100A/m
Conducted emission
IEC 60255-26:2013 0.15MHz~0.50MHz: 79dB (μV) quasi peak, 66dB (μV) average 0.50MHz~30MHz: 73dB (μV) quasi peak, 60dB (μV) average
Radiated emission
IEC 60255-26:2013
Below 1GHz
30MHz~230MHz: 40dB (μV/m) quasi peak @10m, 50dB (μV/m) quasi peak @3m
230MHz~1000MHz: 47dB (μV/m) quasi peak @10m, 57dB (μV/m) quasi peak @3m
Above 1GHz
1GHz~3GHz: 56dB (μV/m) average, 76dB (μV/m) peak @3m
3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m) peak @3m
Auxiliary power supply performance IEC 60255-26:2013
Trang 32⚫ EMC: 2014/30/EU, EN60255-26:2013
⚫ Products safety (LVD): 2014/35/EU, EN60255-27:2014
⚫ IEC 61850: Edition 2, Parts 6, 7-1, 7-2, 7-3,7-4 and 8-1
⚫ IEC 61850: Edition 2, GOOSE Performance Class P1 (3ms)
⚫ IEEE 1588: IEEE Std C37.238TM-2017
⚫ DNP: DNP 3.0
⚫ PRP: IEC 62439-3 Ed.3 (IS 2016)
⚫ HSR: IEC 62439-3 Ed.3 (IS 2016)
2.7 Liquid Crystal Display (LCD)
Trang 332
2.8 Terminals
2.8.1 Ring Ferrule
Connection Type Wire Size Screw Type Torque
Grounding (Earthing) connection BVR type, 0.8~4mm 2 lead M3 0.6~0.8 N·m
2.8.2 Pin Ferrule
Connection Type Wire Size Screw Type Torque
Power supply Screw terminals, 0.3~3.3mm 2 lead M2.5 0.4~0.6 N·m
Contact I/O Screw terminals, 0.3~3.3mm 2 lead M2.5 0.4~0.6 N·m
2.9 Measurement Scope and Accuracy
Item Range Accuracy
Trang 342
2.10.2 Fault and Disturbance Recording
Duration & Recording position
Settable pre-disturbance, post-disturbance and maximum recorded duration
2.10.3 Binary Input Signal
Resolution of binary input signal ≤1ms
Binary input mode Potential-free contact
2.11 Protective Functions
2.11.1 Current Differential Protection
Current setting accuracy ≤2.5% of setting or 0.02In whichever is greater
Pickup time ≤30ms (at 2times current setting)
Maximum operating time ≤30ms (at 4 times current setting)
Minimum operating time ≤20ms (at 4 times current setting)
2.11.2 Feeder Line End Fault Protection
Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater
Pickup time ≤25ms (at 2 times current setting)
Operating time accuracy ≤1%×Setting or 25ms (at 2 times current setting)
2.11.3 Phase Overcurrent Protection
Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater
Pickup time ≤25ms (at 2 times current setting)
Operating time accuracy ≤1%×Setting or 25ms (at 2 times current setting)
Trang 35Receiving Control Block (RCB) Max 16 (Typical configuration: 50×FCD+200×BOOL+16×FLOAT)
Sending Control Block (SCB) Max 8 (Typical configuration: 100×BOOL)
Receiving route delay Max 2ms
Sending route delay Max 3ms
The capacity of GOOSE receiving and sending is determined by the number of configured boards and protection functions
2.12.2 SV
Receiving Control Block (RCB) Max 6 (per board)
Receiving route delay Max 2ms
The capacity of SV receiving is determined by the number of configured boards and protection functions
Trang 362
Trang 383
3.5.5 Settings 3-17
3.6 Trip Logic 3-18
3.6.1 Function Description 3-18 3.6.2 Function Block Diagram 3-18 3.6.3 I/O Signals 3-18 3.6.4 Logic 3-19 3.6.5 Settings 3-19
List of Figures
Figure 3.3-1 3-terminal application 3-5 Figure 3.3-2 Operation characteristic curve of 3-terminal current differential protection 3-6 Figure 3.3-3 Operation characteristic curve of 3-terminal current differential protection 3-7 Figure 3.3-4 Logic of current differential protection 3-11 Figure 3.4-1 Logic of feeder line end fault protection 3-14 Figure 3.5-1 Logic of phase overcurrent protection 3-17 Figure 3.6-1 Simplified tripping logic 3-19
List of Tables
Table 3.1-1 Input/Output signals of three-phase current element 3-1 Table 3.1-2 Settings of three-phase current element 3-2 Table 3.2-1 Input/Output signals of fault detector 3-5 Table 3.3-1 I/O signals of current differential protection 3-8 Table 3.3-2 Settings of current differential protection 3-12 Table 3.4-1 I/O signals of feeder line end fault protection 3-13 Table 3.4-2 Settings of feeder line end fault protection 3-15 Table 3.5-1 I/O signals of phase overcurrent protection 3-16 Table 3.5-2 Settings of phase overcurrent protection 3-17 Table 3.6-1 I/O signals of trip logic 3-18 Table 3.6-2 Settings of trip logic 3-19
Trang 393
3.1 Three-phase Current Element (TCUR3P)
Three-phase current element is responsible for pre-processing the sampled value of three-phases
currents and calculating sequence components, amplitudes and phase angles of three phase
currents, etc All calculated information of three-phase current element is used for protection logic
calculation
3.1.1 Function Description
Three-phase current element has following functions:
1 Pre-process three phase currents
2 Calculate information related to three-phase current
When any phase current is greater than 0.04In, the input current signals are valid and the valid
signal will be used by programmable logic application
3.1.2 Function Block Diagram
TCUR3P
CTx.Ia_Sec CTx.Ib_Sec CTx.Ic_Sec
CTx.I2_Sec CTx.3I0_Cal_Sec CTx.I1_Sec
CTx.Ang(Ia-Ib) CTx.Ang(Ib-Ic) CTx.Ang(Ic-Ia) CTx.Ang(Ia)
CTx.Ang(Ic) CTx.Ang(3I0_Cal) CTx.Ang(Ib)
CTx.Flg_OnLoad
CTx.in_ia CTx.in_ib CTx.in_ic
3.1.3 I/O Signals
Table 3.1-1 Input/Output signals of three-phase current element
No Input Signal Description
1 CTx.in_ia Sampled value of phase-A current of CTx
Trang 403
2 CTx.in_ib Sampled value of phase-B current of CTx
3 CTx.in_ic Sampled value of phase-C current of CTx
No Output Signal Description
1 CTx.Ia_Sec The amplitude of phase-A current of CTx (secondary value)
2 CTx.Ib_Sec The amplitude of phase-B current of CTx (secondary value)
3 CTx.Ic_Sec The amplitude of phase-C current of CTx (secondary value)
4 CTx.I1_Sec The amplitude of positive-sequence current of CTx (secondary value)
5 CTx.I2_Sec The amplitude of negative-sequence current of CTx (secondary value)
6 CTx.3I0_Cal_Sec The amplitude of calculated residual current of CTx (secondary value)
7 CTx.Ang(Ia-Ib) Phase angle between phase-A and phase-B currents of CTx
8 CTx.Ang(Ib-Ic) Phase angle between phase-B and phase-C currents of CTx
9 CTx.Ang(Ic-Ia) Phase angle between phase-C and phase-A currents of CTx
10 CTx.Ang(Ia) Phase angle of phase-A current of CTx
11 CTx.Ang(Ib) Phase angle of phase-B current of CTx
12 CTx.Ang(Ic) Phase angle of phase-C current of CTx
13 CTx.Ang(3I0_Cal) Phase angle of the calculated residual current of CTx
14 CTx.Flg_OnLoad A flag indicating that any phase current of CTx is greater than 0.04In
3.1.4 Settings
⚫ Access path:
MainMenu Settings Global Settings System Settings
Table 3.1-2 Settings of three-phase current element
No Settings Range Unit Step Default
value Remark
1 CT1.I1n 0~9999 A 1 1000 Primary rated current value of CT1 (i.e the CT
of CB1)
2 CT1.I2n 1 or 5 A - 1 Secondary rated current value of CT1
3 CT2.I1n 0~9999 A 1 1000 Primary rated current value of CT2 (i.e the CT
of CB2)
4 CT2.I2n 1 or 5 A - 1 Secondary rated current value of CT2
5 CT3.I1n 0~9999 A 1 1000 Primary rated current value of CT3 (i.e the CT
Enabled: make connected current polarity reversed
8 CT2.En_RevCT Disabled
Enabled - - Disabled
It is used to adjust the current polarity of CT2 Disabled: keep connected current polarity unchanged
Enabled: make connected current polarity