sheet cover 0.8mm thk For pipes exposed ceiling only uPVC, PPR pipe Plastic anchor bolt M4x50mm Fire sealant; Depth: 10÷15mm Rockwool 60 kg/m3 Slab Sleeve 10÷15mm 70 mm Detail Installa

Trang 1

Installation Fire Stopping For:

a uPVC, PPR pipes:

1 uPVC, PPR pipes smaller than 50mm

2 uPVC, PPR pipes from 50mm up to 160mm

3 uPVC pipes over 160mm

b Metal pipes and air duct

Trang 2

1 General:

Items: - The Method Statement For Fire Stopping Works

2 Aim:

The objectives is to describe Fire Stopping Works associated with installation

of M&E services in compliance with the contract specification, approved shop drawings, combine and coordinated all services and structural penetration shop drawings

™ For pipe smaller than 50mm: Use Fire Sealant

- Clean the pipe

- Fill rockwool to sleeve (Sleeve size follow table 1)

- Apply fire sealant

- Smooth fire sealant

- Install G.I sheet 0.8mm thk - If the pipes exposed ceiling

Table 1: Sleeves Size for Pipes smaller than 50mm

Trang 3

Wall/Slab Sleeve

Rockwool (60 kg/m3)

Fire sealant uPVC/PPR pipe

Apply Fire Sealant

Fire sealant

Smooth Fire Sealant

Wall/Slab

uPVC, PPR pipe Sleeve

Fire sealant Complete surface

Leave complete seal (The pipes concealed ceiling)

Wall/Slab

uPVC, PPR pipe

Trang 4

G.I sheet cover 0.8mm thk (For pipes exposed ceiling only)

uPVC, PPR pipe

Plastic anchor bolt M4x50mm

Fire sealant; Depth: 10÷15mm

Rockwool (60 kg/m3) Slab

Sleeve

10÷15mm

70 mm

Detail Installation Fire Stopping For uPVC, PPR Pipe Through Slab

G.I sheet cover 0.8mm thk (For pipes exposed ceiling only) Rockwool (60 kg/m3)

10÷15mm

Plastic anchor bolt M4x50mm

Fire sealant; Depth: 10÷15mm uPVC, PPR pipe

70 mm

Wall Sleeve

Detail Installation Fire Stopping For uPVC, PPR Pipe Through The Wall

Trang 5

™ For pipe from 50mm up to 160mm: Use Fire Wrap

- Clean the pipe

- Cut fire wrap to the correct length (See application table)

- Wrap fire wrap around pipe

- Push fire wrap into the annular pace

- Fill all gap of fire wrap by fire sealant (If any)

Wrap fire wrap around pipeCut fire wrap

Fill all gap of fire wrap by fire sealant (If any)

Push fire wrap into the annular pace

Trang 6

Plastic anchor bolt M4x50mm

Fire wrap

70 mm

Detail Installation Fire Wrap For uPVC, PPR Pipe Through The Wall

Detail Installation Fire Wrap For uPVC, PPR Pipe Through Slab

Fire wrap Rockwool (60 kg/m3) uPVC/PPR pipe

Plastic anchor bolt M4x50mm

G.I sheet cover 0.8mm thk (For pipes exposed ceiling only )

25mm 70mm

Slab Sleeve (Sleeve size follow table 2, 3)

Trang 7

Table 2: Sleeves Size for Pipes from 50mm up to 160mm

Condensate Pipe size

Trang 8

™ For uPVC pipe over 160mm: Use Fire Collar

- Make measuring points according to pipe size

- Cut fire collar at marked measuring points according to pipe size

- Ben the intumescent side of the collar until it snap

- Shape the collar to fit the pipe and bevel intumescent edge for close fit

- Wrap the collar around the pipe and clip the first bracket into slots on both ends

- Complete other brackets and fit the collar onto wall/slab

Make measuring points according

to pipe size

Cut fire collar

Ben the intumescent side of the

collar until it snap

Shape the collar to fit the pipe

Trang 9

Wrap the collar around the pipe

and clip the first bracket into slots

Detail Installation Fire Collar For uPVC Through Slab

uPVC pipe

Trang 10

b Metal pipes & Air ducts: Use Fire Sealant

- Clean the pipe, Air duct

- Fill rockwool (60 kg/m3) to sleeve/opening Size of sleeve follow table 4 & 6, size of opening follow table 5

- Apply fire sealant

- Smooth fire sealant

- Install G.I sheet 0.8mm thk- If the pipes, Air duct exposed ceiling

Wall/slab

Rockwool (60 kg/m3)

Metal pipe/Air duct

Fill Rockwool To Sleeve

Trang 11

Table 4: Sleeve size for metal pipes (w/o Insulation) Service Pipe size

Opening Sizes (mm) with Insulation Wide (WD) High (HD) Wide (WO) High (HO) Wide (WO) High (HO)

Trang 12

Table 6: Sleeve size for chiller pipes

Service Pipe size

Trang 13

Fire sealant Complete surface

Leave complete seal

Trang 14

G.I sheet cover 0.8mm thk (For pipes exposed ceiling only) Plastic anchor bolt M4x50mm

Fire sealant; Depth: 10÷15mm Rockwool (60 kg/m3)

Metal pipe

Slab Sleeve

10÷15mm

70 mm

Detail Installation Fire Stopping Metal Pipe Through Slab

G.I sheet cover 0.8mm thk (For pipes exposed ceiling only) Rockwool (60 kg/m3)

10÷15mm

Plastic anchor bolt M4x50mm

Fire sealant; Depth: 10÷15mm Metal pipe

70 mm

Wall Sleeve

Detail Installation Fire Stopping For Metal Pipe Through The Wall

Trang 15

Fire protection pipes

G.I sheet cover 0.8mm thk

Detail Installation Fire Stopping For Fire Protection Pipes

Exposed Ceiling Through The Wall

Rockwool (48 kg/m3) Insulation

(For pipes exposed ceiling only) Wall

Detail Installation Fire Stopping For Chiller Pipes Through The Wall

70mm Chiller insulation

Rockwool (60 kg/m3)

Plastic anchor bolt M4x50mm

Fire sealant; Depth: 10÷15mm Chiller pipe

10÷15mm

Sleeve

Trang 16

Plastic anchor bolt M4x50mm

Rockwool (48 kg/m3) Insulation

70mm

G.I sheet cover 0.8mm thk (For pipes exposed ceiling only)

Rockwool (60 kg/m3) Fire sealant; Depth: 10÷15mm

Trang 17

G.I sheet cover 0.8mm thk (For pipes exposed ceiling only) Plastic anchor bolt M4x50mm

Fire sealant; Depth: 10÷15mm Rockwool (60 kg/m3)

Air duct

Slab Opening

10÷15mm

70 mm

Detail Installation Fire Stopping Air duct Through Slab

G.I sheet cover 0.8mm thk (For pipes exposed ceiling only) Rockwool (60 kg/m3)

10÷15mm

Plastic anchor bolt M4x50mm

Fire sealant; Depth: 10÷15mm Air duct

70 mm

Wall Opening

Detail Installation Fire Stopping For Air duct Through The Wall

Trang 18

c Electrical conduits: Use Fire Sealant

- G.I conduits: Method statement installation fire stopping for G.I

conduit through the wall/slab is the same Method statement installation fire stopping for metal pipes

- PVC conduits: Method statement installation fire stopping for

PVC conduit through the wall/slab is the same Method statement installation fire stopping for uPVC, PPR pipes smaller than 50mm through wall/slab

d Electric trunking, cable tray, ladder: Use Fire Cement

- Clean electric trunking, cable tray, ladder

- Install form work to side opening (For wall opening)

- Install form work to bottom opening (For floor opening)

- Apply fire cement to opening (Opening size follow table 4)

- Take-out form work

- Clean electric trunking, cable tray, ladder out-side the wall/slab (If any)

Opening size max

Trunking

Detail Installation Fire Cement For Cable Trunking, Cable Tray Through Wall

Trang 19

≤ 600mm Cable tray Cable trunking

Fire cement

Floor opening Slab

≥ 105mm

Detail Installation Fire Cement For Cable Trunking,

Cable Tray Through Slab

Detail Installation Fire Cement For Cable

Trunking Through SlabDetail Installation Fire Cement For Cable

Trunking and Cable Through The Wall

Trang 20

Busduct system: Use Rocwool and G.I Sheet

- Install G.I sheet 0.8mm thk to side opening (For wall opening)

- Install G.I sheet 0.8mm thk to bottom opening (For floor opening)

- Apply rockwool to opening

- Install G.I sheet 0.8mm thk to other side opening (For wall opening)

- Install G.I sheet 0.8mm thk to top opening (For floor opening)

- Clean busduct, working area

Trang 21

G.I sheet cover 0.8mm thk

Busduct

Detail Installation Fire Stopping For Busduct Through

Slab ( Bottom View)

Busduct

Rockwool (60 kg/m3)

Detail Installation Fire Stopping For Busduct Through Slab

(Top View – Befor Install G.I Sheet Cover)

Trang 22

Detail Installation Fire Stopping For Busduct Through The Wall

70mm