Air Duct Seal: 50 Seal TDC joint Bolt hole 10mm Air Duct 50 Angle flange joint Bolt hole 8mm Seal Air Duct Figure 09: Position of Seal for TDC Joint Figure 10: Possition of Seal for
Trang 1General
Aim
Scope of works
Methodology
I Duct Installation Works
1 Air Duct Connection
2 Air Duct Seal
3 Air Duct Insulation
II Air Devices Installation Works
1 Volume Dampers (VD), Volume Control Dampers (VCD), Fire Dampers (FD)
2 Diffuser, Grille
3 Plenum Chamber, Silencer Chamber
4 Flexible Duct, Canvas Joints
5 Louver, Access Door, Outdooor Hood
Trang 2General:
Items: - The Method Statement for Air Distribution Installation Works
Aim:
The aim of works is to describe mechanical works associated with installation of Air Distribution Installation Works and to ensure compliance with contract requirements, specification and quality control
Scope of Works:
The scope of work for this method statement shall include all the Ductworks for the
SAIGON M&C TOWER Project.
Methodology:
I Duct Installation Works:
Table1: Rectangular Duct Thickness Schedule
1 Air Duct Connection:
Table 2: Regulation for air duct connection Schedule
Corner Angle Duct Connection Companion Angle Duct
Duct size
largest
dimension
(mm)
Rivet Maximum Spacing on
Largest Dimension (mm) Duct Size (L max) Up to 400 600 800 ~ 1250 1600 ~ 2500 Above 2500
Trang 3Table 3: Support, hanger, spacing schedule
Duct size Less than
400 400 ~ 999 1000 ~1999
2000 ~
2500 Over 2500
Angle steel V-30x30x2.5 V30x30x2.5 V-40x40x3
V-50x50x3.5
U-80x38x3.5 Round bar 2 x Φ8 2 x Φ10 2 x Φ10 2 x Φ10 2 x Φ12 Hanger
Angle steel V-30x30x2.5 V30x30x2.5 V-40x40x3
V-50x50x3.5
U-80x38x3.5
Vertical
support
1.1 Duct size over 1500mm:
) For duct size largest dimension over 1500mm show be as Figure 01:
) Detail A show be as Figure 02, Figure 03:
Figure 01: Typical duct connection detail (using flange joint)
Figure 02: Detail of bolt spacing for flange joint
100
Angle steel flange
(see table 02)
Bolt hole 8mm Sealed
100
100
Concrete slab
Air Duct
Detail A L ≤ 1200
Hanger rod M10
Angle steel (see table 3)
Anchor bolt
W
Trang 41.2 Duct size under 1500mm:
) For duct size largest dimension under 1500mm show be as Figure 04
) Detail B show be as Figure 05, Figure 06, Figure 07
Figure 05: Detail of Cross Aim Brace Spacing
Figure 03: Detail of connection angle for flange
Figure 4: Branch duct connection detail (using Transverse Duct Connector (TDC) joint)
A ≤ 150 mm
B ≤ 200 mm
100 mm ≤ C ≤ 150 mm
C
B
C
A
4 holeΦ10
Air duct
Cross aim brace
W Air flow
Air flow
L = 0.25W; L≥150mm
L
Main duct
Detail B Branch duct
Change between section
Air flow
Rivet 3.2mm
5mm thk
Width: 25mm, 5mm thk
Air Duct
Angle steel flange (see table 02) Bolt & Nut 8mm
Trang 5Table 4: Size, Thickness and Spacing of TDC Joint Schedule
Duct Size largest dimension (mm) Less than 700 700~1200 1200~1500
Thickness of Cross Arm Brace (minimum)(mm) 1.0 1.0 1.0
Max 1100
Bolt M10
Cross Aim Brace (see table 4)
Air Duct TDC Corner (see table 4) Figure 06: Cross Aim Brace detail
Bolt M10
TDC corner 1.2mm thk TDC duct end
(see table 4)
Rubber gasket (see figure 08) Nut M10
Nut M10
TDC flange
Rubber gasket (see figure 08)
Rubber gasket (see figure 08)
Figure 07: Typical TDC assembly detail
Air duct
Corner plate
(see detail)
TDC joint
Trang 6) Note:
? Support, hanger will be concerned on method statement of M&E Support System Installation Work: ME - REE - T+ - MS – G+ - GEN - 003
2 Air Duct Seal:
50
Seal TDC joint
Bolt hole 10mm
Air Duct
50
Angle flange joint Bolt hole 8mm
Seal
Air Duct Figure 09: Position of Seal for TDC Joint
Figure 10: Possition of Seal for Angle Flange Joint
Bolt hole 8mm
Rubber gasket Width: 25mm
Figure 08: Typical rubber gasket installation detail
Trang 7
3 Air Duct Insulation:
Table 5: Duct Insulation Specification Schedule
Supply air chambers
and sound
attenuation fittings
Figure 11: Possition of Sealant for Duct Seam
Figure 12: Typical smoke exhause duct insulation detail
Seam
Board insulation 50mm (see table 5)
Alu Sheet Cladding
(if any) Metal clips
Air duct
Pin Φ1.6mm
(see figure 15)
Adhesive
Attached Alu Tape (Width 50mm)
Seal (Inside Only) Air Duct
Seal
Trang 8Metal clip Alu foil facing
Alu sheet cladding
Rockwool for smoke exhaust duct Glasswool for AC duct
Air duct
`
Pin Φ1.6mm (see figure 15)
Figure 14: Insulation detail for supply air chambers and sound attenuation fitings
Figure 13: Ducting insulation layer detail
Pins Φ1.6mm (see figure 14)
Metal clips Air duct
Glasswool 25mm thk Glass cloth
Trang 9Max 300mm Max 300mm
Figure 15: Shape & distance of pins
Metal clip Pin Φ1.6mm
Insulated duct
Bare duct Max 300mm
Max 300mm
Trang 10Page 11 Figure 17: Detail of typical insulation for diffuser box
50mm
50mm
Figure 16: Typical insulation menthod for TDC joint & flange joint
Plan view
Ceiling
Glasswool 25mm thk (outside duct) Aluminum tape 25mm
Glasswool 25mm thk (outside duct) Glasswool 25mm thk
(inside diffuser box)
Screw
Air flow Chamber box
Front view
TDC joint 25mm
Metal slip
Glasswool 25mm thk
Attached alu tape 25mm
25mm
Flange joint
Pin Φ 1.6mm
Attached alu tape 25mm
TDC or Flange joint
25mm
Trang 11II Air Devices Installation Works:
1 Volume Dampers (VD), Volume Control Dampers (VCD), Fire Damer (FD):
Table 6: Quantity of hanger rods for Fire Damper
Rectangular Duct Spiral Duct Duct size or Diameter (mm) Less than 300 Over 300 Less than 300 Over 300
Figure 19: Detail of setting damper
Figure 18: Detail of typical insulation for grille (VHS type)
Glasswool 25mm thk (outside duct)
Wall Screw
Frame
Tapping Air duct
TDC joint
Air flow
L = 8D D: diameter of air duct
Concrete foundation
L
D
Air Fan
VD
VD Air duct
Concrete slab
Trang 12Anchor bolt Concrete floor slab
Angle steel
Insulation 25mm Rubber pad
Bolt M8
Wall Fire damper
Vertical duct
Wall Concrete floor slab
Fire damper
VCD Access door FD
V-Angle steel
Rockwool 50mm
Duct elbow Insulation 25mm
V-Angle steel Anchor bolt
Hanger rod
Vertical duct Bolt M8
Figure 20: Typical damper installation detail
PLAN VIEW
FRONT VIEW
Trang 132 Diffusers, Registers:
Ceiling
SUPPLY AIR CHAMBER BOX
Glasswool 25mm thk
Glass wool 25mm thk
Insulation (outside) Opposed blade damper
Glass wool 25mm thk Insulation (outside)
Insulation (inside)
(if any)
Figure 21: Example of connection with chamber & duct
Connection with chamber box
H, W: Dimension of Diffusers opening size for ceiling (mm)
d : Diameter of flexible duct (mm)
Flexible
K = 150 ~ 300mm
D+50mm
Connection with Duct
Figure 22: Detail of typical installation for supply air diffuser
K
W×H
Ceiling
Air duct W+50mm
H+50mm
D
W×H
K Ceiling
Chamber box
D Flexible
H+50mm
100mm or over
Trang 14RETURN AIR CHAMBER BOX
Ceiling
Screw Glass wool 25mm thkInsulation (outside)
Glasswool 25mm thk Insulation (inside)
EXHAUST AIR CHAMBER BOX
Opposed blade damber
Ceiling
Screw
(if any)
3 Plenum Chamber, Silencer Chamber:
? Sound Absorber for Chamber shall be used glasswool 50mm thk, 48 kg/cm3 density
Table 7: Galvanized steel sheet thickness for Chamber
Longest Dimension of Chamber (mm) Chamber Size (L max) (mm) Less than 800 800 ~ 1500 1500 or Over
Figure 24: Detail of typical connection for exhause air grille Figure 23: Detail of typical installation for return air grille
Trang 15
Figure 25: Silencer Elbow Chamber Detail
Figure 26: Silencer Chamber Detail
Sound Absorber by glasswool 50mm thk
R
A
L
A
Silencer Elbow
A
B
Silencer Chamber
Sound Absorber by glasswool 50mm thk
Detail D
Detail E
Detail E
Pin Φ 1.6mm
GI sheet cover 0.6mm thk 25~50mm
Air Duct
Sound Absorber by glasswool 50mm thk
Trang 164 Flexible Duct, Canvas Joints
a) Flexible Duct:
Bolt M6
AIR DUCT FLEXIBLE DUCT
Screw 3.2Ø
G.I.sheet 0.6mm thk Steel band
Ceiling
SUPPLY AIR CHAMBER BOX
Opposed blade damper Glass wool 50mm thk Insulation (outside) G.I.sheet 0.6mm thkSteel band
Glasswool 25mm thk Insulation (inside)
Insulation (outside)
(if any) Glasswool 25mm thk
Figure 27: Chamber Jointing Detail
Figure 28: Detail of typical connection between flexible duct & chamber box
PinΦ1.6mm
100~150mm 75mm
25~50mm
Sound Absorber by glasswool 50mm thk
Trang 17b) Canvas Joints:
RETURN CHAMBER BOX
Flange joint (refer to detail G) Glasswool 25mm thk
Insulation (outside)
Glasswool 25mm thk Insulation (inside)
AIR DUCT
Screw
Figure 29: Canvas Joint Detail
Figure 30: Detail of typical connection between canvas & chamber box
L = 200 ~ 250 (mm)
Detail F
Galvanized steel sheet ( same as duct thickness)
Angle steel flange Rubber gasket (width:5mm)
Cuff 5mm or more
Rivet 3.2mm Bolt and nut M8
Canvas Joint
Washer Air duct
L Flange joint
Air duct Air duct
Duct canvas
Detail F
Trang 185 Louver, Access door, Outdoor Hood:
a) Louver:
Figure 31: Typical Louver Installation Detail
Concrete slab
box
Anchor bolt
Access door (see figure 32)
Hanger rod
Wall
500mm
Angle steel (see table 3)
Trang 19b) Access door:
Sach lock Air duct
Aluminium
Screw 3.2Ø Steel plate
Steel plate
Sach lock Aluminium
c) Outdoor Hood:
Figure 33: Typical Outdoor Hood Installation Detail
Chamber box Outdoor hood
GI sheet cover 0.6 mm thk
Air duct Wall
Insect Screen (if any)
Mortar Sealant
Rockwool 60kg/m3 Screw
Figure 32: Typical Access Door Installation Detail