Preface About This Manual The selection guide describes the application overview and the summary of protection, automation, control and supervision functions of PCS-902S.. 1 Functions a
Trang 3Copyright © 2019 NR All rights reserved
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may
be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights
The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice
To the extent required the products described herein meet applicable IEC and IEEE standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly
Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us
Trang 5Preface
About This Manual
The selection guide describes the application overview and the summary of protection, automation, control and supervision functions of PCS-902S Moreover, it provides the explanation about the application option, the firmware option, the software option, the hardware option and etc., and can
be used to indicate how to order a PCS-902S based on expected configurations
1 Functions and Application
Introduces the summary functions of this device, such as the protection, the automation, the control and the supervision Briefly introduces the typical application schemes of PCS-902S
2 MOT Information
Introduces the meaning of the ordering code, and details all options about the application, the firmware, the software, the hardware and etc of PCS-902S
Document Revision History
PN: ZL_PCS-902S_X_Selection Guide_EN_Overseas General_X
Trang 7Figure 1.1-1 Functional overview of PCS-902S 1-1
Figure 1.10-1 Typical application of single circuit breaker 1-8
Figure 1.10-2 Typical application of double circuit breakers 1-8
Trang 81
Trang 91
1.1 Overview
PCS-902S protect overhead and underground lines, feeders and cables on all voltage levels with
highest selectivity possible The large number of protective and automatic functions available
permits their utilization in all areas of line protection The devices contain all important auxiliary
functions that are necessary today for safe network operation This includes control, measurement
and monitoring functions The large number of communication interfaces and communication
protocols satisfies the requirements of communication-based selective protection and of
automated operation Their modular structure permits line protection devices always to be adapted
flexibly to the individual requirements
The functional overview of the device is shown in Figure 1.1-1
Figure 1.1-1 Functional overview of PCS-902S
PCS-902S is a high-speed transmission line distance relay featuring single-pole and three-pole
tripping and reclosing with synchronism check The device features extensive metering and data
recording including high-resolution data capture and reporting PCS-902S features expanded
control equation programming for easy and flexible implementation of custom protection and
control schemes
A simple and robust hardware design features efficient digital signal processing Combined with
extensive self-testing, these features provide device reliability and enhance relay availability
PCS-902S can be configured to support single circuit breaker application or double circuit
breakers application by PCS-Studio If the device is applied to double circuit breakers mode, all
Trang 10Pilot distance protection
Independent pilot zone (forward direction and reverse direction, mho or quadrilateral characteristics)
PUTT, POTT, Blocking, Unblocking, Zone Extension
Current reversal logic
Weak infeed echo or echo&trip
Open breaker echo
Pilot directional earth-fault protection
Directional zero-sequence comparison element for pilot scheme
PTT, Blocking and Unblocking
Current reversal logic
Weak infeed echo or echo&trip
Open breaker echo
Load encroachment for each zone
Power swing blocking and releasing for each zone
Faulty phase selection for each zone 21D DPFC distance protection
Fixed forward direction
High-speed operation
Supplementary for zone 1 of distance protection
67P 50/51P Phase overcurrent protection
Up to 6 stages with independent logic
Voltage control element for each stage
Optional direction element for each stage, including forward direction, reverse direction or non direction
Optional definite-time characteristics and inverse-time characteristics for each stage
Trang 111
Trip purpose or alarm purpose for each stage
Harmonic control element for each stage
67G
50/51G Earth fault protection
Up to 6 stages with independent logic
Optional direction element for each stage, including forward direction, reverse direction or non direction
Optional definite-time characteristics and inverse-time characteristics for each stage
Selectable trip purpose or alarm purpose for each stage
Harmonic control element for each stage
67Q
50/51Q
Negative-sequence overcurrent
protection
Up to 2 stages with independent logic
Optional direction element for each stage, including forward direction, reverse direction or non direction
Optional definite-time characteristics and inverse-time characteristics for each stage
SOTF Switch onto fault
Via distance measurement elements
Via dedicated earth fault element
Via phase overcurrent element
59P Phase overvoltage protection
Up to 2 stages with independent logic
Optional definite-time characteristics and inverse-time characteristics for each stage
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Selectable trip purpose or alarm purpose for each stage
27P Phase undervoltage protection
Up to 2 stages with independent logic
Optional definite-time characteristics and inverse-time characteristics for each stage
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Blocked by instantaneous VT circuit failure
Selectable trip purpose or alarm purpose for each stage
Optional auxiliary criterion, including CB position check and current check
59Q Negative-sequence overvoltage
protection
Up to 2 stages with independent logic
Selectable trip purpose or alarm purpose for each stage
59G Residual overvoltage protection
Up to 2 stages with independent logic
Selectable trip purpose or alarm purpose for each stage
81O Overfrequency protection Up to 6 stages with independent logic
Voltage control element 81U Underfrequency protection Up to 6 stages with independent logic
Trang 121
Voltage control element 81R Rate of change of frequency
protection
Up to 6 stages with independent logic
Voltage control element 32R Reverse power protection
Up to 2 stages with independent logic
Selectable trip purpose or alarm purpose for each stage
50BF Breaker failure protection
Phase-segregated re-trip and three-phases re-trip
Optional current criterion (phase overcurrent element, zero-sequence overcurrent element, negative-sequence overcurrent element)
Optional circuit breaker position check
Two time delays 50DZ Dead zone protection Clear the dead zone faults between CT and the circuit
breaker
62PD Pole discrepancy protection
Initiated by three auxiliary contacts of phase-segregate circuit breaker
Optional auxiliary criterion (zero-sequence current element or negative-sequence current element) 46BC Broken conductor protection
Adopt the ratio of negative-sequence current to positive-sequence current (Ι2/Ι1) to detect the broken conductor
25 Synchrocheck Independent logic for auto-reclosing and manually
closing
79 Auto-reclosing
One shot or multi-shot
1-pole AR, 3-pole AR or 1/3-pole AR
Optional trigger mode, including protection operating and external binary input
Support synchro-check and voltage check
FL Fault location
Single-end fault location
Double-end fault location
Zero-sequence mutual coupling compensation for parallel lines
DPFC is the abbreviation of deviation of power frequency component
Trang 131
1.3 Control Functions
Circuit breaker & disconnector control (Remote/local)
Synchronism check for remote and manual closing
Event Recorder including 1024 disturbance records, 1024 binary events, 1024
supervision events, 256 control logs and 1024 device logs
Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
Pilot communication channel supervision
DC power supply supervision
Channel status statistic
System frequency supervision
1.6 Pilot Channel Scheme
Optional single- or dual- pilot channels (fiber optic)
Support G.703 and C37.94
Trang 14 Two RS-485 serial ports using IEC 60870-5-103 or Modbus
One RS-485 serial port for clock synchronization
Support GOOSE communication module using IEC 61850-8-1 GOOSE
Full compatibility between IEC 61850 Editions 1 and 2
Redundancy protocols PRP, HSR and RSTP
One front RJ-45 port and one rear RJ-45 port for debugging
4 Programmable operator pushbuttons with user-configurable labels
Up to 18 programmable target LEDs with user-configurable labels
1 RS-485 rear ports for printer
Language switchover—English+ selected language
Configuration tool—PCS-Studio
1.9 Additional Functions
User programmable logic
Fault location
Fault phase selection
Parallel line compensation for fault location
Switching system phase sequences function (ABC or ACB)
Clock synchronization
Trang 151
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE1588: Clock message based on IEEE1588 via optical fibre interface
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
SNTP (BC): Broadcast SNTP mode via Ethernet network
Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol,
Modbus protocol and DNP3.0 protocol
There are several typical applications for different application situation
2-terminal transmission line
Trang 1681R 81O
81R 81O
Trang 172.2.2 Application Scenario (U Field) 2-2
2.2.3 Firmware Type (A Field) 2-3
2.2.4 Firmware Version (R Field) 2-3
2.2.5 Software Functions (S Field) 2-3
2.2.6 Chassis Structure and Installation (C Field) 2-5
2.2.7 Power Supply Plug-in Module (PWR Field) 2-16
2.2.8 Plug-in Module Configuration (H Field) 2-17
2.2.9 MOT Version 2-23
Trang 182
Trang 192
2
2.1 Ordering Code
PCS S series device can select the hardware configuration and software functions of the device
through the auxiliary tool “PCS-Torch”, and a corresponding MOT (Market Ordering Table) serial
code will be generated
The MOT serial code consists of 9 parts, including:
Device type: indicates the device type
U field: indicates application scenario
A field: indicates firmware type, which can be standard version or regional version
R field: indicates firmware version
S field: indicates software functions
C field: indicates chassis structure and installation
PWR field: indicates the voltage level of power supply plug-in module
H field: indicates plug-in module configuration
MOT version: indicates MOT version
The display format is shown as below:
H field
MOT version
Click the button "Default", all options will be chosen as default value directly Click the button
Trang 202
"Import", an existing MOT file (*.xls) can be directly imported into the corresponding device type of
PCS-Torch
After selecting the specific function, click the button “Complete” to display the currently selected
configuration information, is shown as below:
Click the button "Copy", MOT (Market Ordering Table) serial code based on selected information will be copy to the clipboard Click the button "Export", MOT and hardware configuration can be
exported as a file (*.xls)
2.2 Selection Information
A MOT serial code consists of several bits, and the specific meaning of each bit is as below
2.2.1 Device Type
For a specific device, the device type is fixed, such as PCS-902S, so it is not need to be chosen
2.2.2 Application Scenario (U Field)
The corresponding application scenarios are selected according to the actual protected objects by
the device Only one kind of application is available, so it is chosen as "2 terminal line" fixedly
Trang 212
2
2.2.3 Firmware Type (A Field)
The firmware type is used to select between the standard version program and the regional
version program Only the standard version program is available, so it is chosen as "Standard"
fixedly
2.2.4 Firmware Version (R Field)
The firmware version is used to select required program version If there is no special version
requirement, the latest version can be chosen, i.e., “Latest version” Otherwise, the specified
version can be chosen
2.2.5 Software Functions (S Field)
The software functions are determined by four parts: "Software", "Language", "Protocol" and
"Sampling mode"
1 Software
The option is used to select the required protection functions, which is used in conjunction with the
application scenario option
Different options correspond with different combinations of protection functions, which can be
viewed through the button "Software Functions" in PCS-Torch