Technical Specifications for Cable Bundling Of Exchange
Trang 2Huawei
Objective
To best utilize the cable ties attached to the
delivery to bundle the subscriber and trunk
cables of an exchange
Application:
Exchange and (for reference of) other products
Note:
The figures and the spaces between cable ties
in this course are for reference only.
Trang 3Table of Contents
1 Cable Tie
2 Technical Specifications for Cable Tie Mounting
3 Technical Specifications for Cable Bundling
4 Subscriber Cable
5 Single-core Trunk
6 8-core Trunk
7 Power Cable
8 Power Bus Cable
9 Alarm Indicator Cable
10 Emergency Serial Port Cable
11 Power and Signal Cable of Fan
Trang 5Techinical Specifications for Cable Tie Mounting
1 Mount the cable ties in even spaces and at an appropriate degree of tightness.
2 Cut off the end of each cable tie in a way that no sharp
Trang 6Huawei
Technical Specifications for Cable Bundling
1 Arrange the cables in a bundle closely, straight, and
neatly
2 The cables in a trough may not be bundled Arrange them
neatly They cannot cross each other They cannot overflow the trough
3 Route the signal cables separately from the power cables.
4 Bend a cable, if required, evenly and softly
5 The total thickness of the cables under a floor cannot
exceed 3/4 of the floor height.
6 The cables can cross within one meter after they exit the cabinet.
7 Do not damage the insulation layer of the cables when
bundling them.
8 Do not join cables.
Trang 7Subscriber Cable–inside Cabinet
subrack section of a column and fix them through
baffle rings
lower) using 100M ties.
Trang 8Huawei
bundling on beam–inside Cabinet
using 150I ties
Trang 9bundling along column – inside Cabinet
using 300I ties
Trang 10Huawei
bundling of discrete cables near connectors on
backplane– inside Cabinet
Bundle the discrete cables near the connectors on each backplane at three points (upper, medium and lower) using 100M ties.
Trang 11Subscriber Cable–outside Cabinet (between
Rack and MDF)
A Bundle the cables using 150I and 300I ties.
B Tighten every four cables into one bundle using 150I ties Connect them serially into a square
C Mount cable ties in an even space of 400 mm
(reference).
D Mount 300I ties onto the bending points and to fix the cables on the cabling rack.
Trang 12Huawei
cabling on cabling rack–outside Cabinet
Trang 13cabling ladder–outside Cabinet
Trang 14Huawei
in raised floor–outside Cabinet
Trang 15in raised floor–outside Cabinet
Trang 16Huawei
Subscriber Cable–in MDF
A Bundle the cables using 300I and 100M ties.
B Tighten every four cables into one bundle using 300I ties Connect them serially and fix them on a column in the MDF.
C Mount cable ties in an even space of 150 mm
(reference) or according to the actual situations of the
MDF.
D Bundle the stripped discrete cables using 100M ties.
E Wrap the stripped sections using tapes
Trang 17MDF -discrete cables
Bundle the stripped discrete cables using 100M ties
Trang 18Huawei
MDF -Keep a certain margin 、 stripped sections
Keep a certain margin , Wrap the stripped sections using tape s.
Trang 19MDF - bundling along columnBundle the cables using 300I ties.
Trang 20Huawei Single-core Trunk–inside Cabinet
beam to the column on either side.
subrack section of a column and fix them through baffle rings
backplane using 100M ties.
Trang 21near connectors on backplane – inside Cabinet
Bundle the cables using 100M ties.
Trang 22Huawei
bundling along column – inside Cabinet
Bundle the cables using 300I ties.
Trang 23inside Cabinet
Trang 24Huawei
Single-core Trunk–outside Cabinet
(between Rack and DDF)
A Bundle the cables using 300I ties.
kinked
C Mount cable ties in an even space of 400 mm
(reference).
Trang 25Single-core Trunk–outside Cabinet
(between Rack and DDF)
Trang 26B Mount cable ties in an even space of 150 mm
(reference) or according to the actual situations
of the DDF.
C Bundle the cables near the connectors in the
Trang 27DDF - near the connectors
Bundle the cables near the connectors in the DDF using 100M ties.
Trang 28Huawei
DDF - near the connectors
Trang 29DDF -along a column
Bundle the cables on along a column using 300I ties.
Trang 30Huawei
8-core Trunk–inside Cabinet
and those along a column using 300I ties.
B Fix the subscriber cables of each subrack
along the beam to the column on either side.
C Mount three evenly spaced cable ties along
each subrack section of a column and fix them
through baffle rings
each backplane using 100M ties.
Trang 31near connectors on backplane – inside Cabinet
Bundle the cables using 100M
ties.
Trang 32Huawei
on a beam and along a column – Inside Cabinet
Trang 34Huawei
8-core Trunk–in DDF
A Tighten every four cables into one bundle
using 300I ties Connect them serially into a
square and fix them in the DDF.
B Mount cable ties in an even space of 150 mm (reference) or according to the actual situations
of the DDF.
C Bundle the cables near the connectors in the DDF using 100M ties.
D Similar to the bundling of the single-core
trunk cables in the DDF
Trang 358-core Trunk–in DDF
Trang 36Huawei
Power Cable
A Bundle the cables using 300I ties.
B Mount cable ties in an even space of 400 mm Tighten every four cables into one bundle
Trang 37Power Cable -inside PDF
Trang 38Huawei
Power Cable -inside PDF
Trang 39Power Cable -outside Cabinet
Trang 40Huawei
Power Cable -outside Cabinet
Trang 41Power Bus Cable ( 95 mm2)
B Mount cable ties in an even space of 500
mm.
Trang 42Huawei
Power Bus Cable ( 95 mm2)
Trang 43Alarm Indicator Cable(1)
Keep the cables away from the heat dissipation hole in cabinet top.
A The row and column indicator control cables include a row indicator signal cable, column indicator signal cable, and row indicator cascade cable They drive the row and column
indicators on top of the cabinet.
B A row indicator signal cable and a column indicator signal cable share the same structure They have a 4PIN connector at one end and six UT soldering flakes at the other Fix the three soldering flakes on the three black cables to one side of the
three row and column indicators Fix the other three soldering flakes on the red, yellow, and green cables to the other side of the red, yellow, and green row and column indicators.
Trang 44Huawei
Alarm Indicator Cable(2)
C For C841AMD (widely used in the previous
cabinets) insert the row indicator in J8 and the
column indicator in J9 in the AMD in the power
distribution box J6 and J7 are connected using the
row indicator cascade cable.
D For CB01AMD (used in the later assembled
cabinets) insert the row indicator in J6 and the
column indicator in J7 in the power distribution
box J4 and J5 are connected using the row
indicator cascade cable The row indicator cascade
cable has a 4PIN connector at either end.
Trang 45Alarm Indicator Cable
Keep the cables away from the heat dissipation hole in cabinet top.
Trang 46Huawei Emergency Serial Port Cable
The emergency serial ports refer to the serial data
paths throughout the entire AM/CM and SPM system
They have connection with all subracks except CKM
They are applicable for status data report of PWS,
alarm data report of AMD, and data report and
equipment maintenance of other boards in emergency
cases The entire emergency serial port system
consists of the serial port cables in various lengths
and the connected communication nodes The cables
inside a cabinet have already been installed before the
delivery The cables between cabinets need be
installed on the site There are the following two
categories of serial port cables:
Common emergency serial port communication
cable
Trang 47Emergency Serial Port Cable
Common emergency serial port communication cable
1 All common emergency serial port communication
cables have a 4PIN connector at either end They connect
the nodes in AM/CM and SPM, including the CB01AMD in
the power distribution box and the backplanes of the
subracks.
2 There are two serial ports in the upper right (seen from
the back) of the backplane of each subrack that requires
emergency serial connection Connect the two ports in
parallel All of the ports can be connected with one serial
bus.
3 JT1 and JT2 are the serial ports in a backplane J12 and
J13 are the serial ports in AMD.
4 There are five types of emergency serial port
communication cable according to the length: 0.4-m cable, 0.8-cable, 1.2-m cable, 2.5-m cable and 4-m cable.
Trang 48Huawei Emergency Serial Port Cable
Emergency serial port communication cable of BAM
1 An emergency serial port communication cable of
BAM connects the serial port in AMD in the BAM with
the emergency serial port in the basic cabinet.
2 An emergency serial port communication cable
has a 4PIN connector at either end Insert one end in
the serial port J12 in CB01AMD in the main control
subrack, and the other end in the serial port J12 (or
J13) in CB01AMD in the BAM.
Trang 49Power and Signal Cable of Fan
The power and signal cable of fan supplies working
power for the fans and reporting the status signals of
the fans to the monitor unit It has a blue power
connector, a black power connector, and a fan signal
connector The power connectors are inserted in a
busbar The fan signal connector is inserted in J2 in
CB01AMD(or J1.7 in C841AMD) in the power
distribution box They have been inserted before the
delivery Pay attention to the power connector polarity
when changing the connectors on the site.
Trang 50B The cables of an alarm box include a signal cable and a
Trang 51Alarm Box
D The power cable supplies –48V power for the alarm box.
E The DIP switches S1 and S3 are used for setting the working mode The two RS232 ports P1 and P2 serve the serial
.
Trang 52Huawei
Clock Cable
A The clock cables provide 8K and 2M reference clock
sources for the subracks.
B The clock cables are routed from the CKM subrack to
the subracks that require the reference clock sources.
C A clock cable is a four-pair twisted cable Its connectors are: 2 5PIN + 2 2 5PIN.
Trang 53Network Cable Terminal
A The terminal system of AM/CM is a distributed and
hierarchical Server/Client architecture The Server side consists of the BAM Server and Switch There is a WS on the side of a Client.
B Tighten the screws on the connector of a load cable.
Trang 54Huawei
Network Cable
Trang 55Network Cable
Trang 56Huawei
Tail Fiber
A Protect the tail fibers outside the cabinet in tubes.
B Tail fiber coiling diameter 8 cm
Trang 57tail fibers - excess tail fibers
A coil of excess tail fibers shall be greater than 8cm in
diameter Fix it on a beam or tail fiber frame.
Trang 58Huawei
tail fibers -on backplane
Bundle the tail fibers using 100M ties.
Trang 59tail fibers -on backplane
Trang 6161
Trang 62Huawei
Trang 6363
Trang 64Huawei