Nội dung

Copyright © Yokogawa Electric Corporation Example of Graphic builder Ribbon Canvas pane Pan & Zoom pane Layer Window pane Property Grid pane Output Area pane YOKOGAWA VIETNAM CO.LTD...

Trang 1

Copyright © Yokogawa Electric Corporation

<1/7/2011>

June 2012

Yokogawa Electric Corporation

YOKOGAWA VIETNAM CO.LTD

Trang 2

Copyright © Yokogawa Electric CorporationYOKOGAWA VIETNAM CO.LTD

Yokogawa Vietnam Co Ltd Service Department

ENGINEERING COURSE

Trang 4

This document is composed of the following chapters:

• Input documents for Graphic generation

• Graphic Worksheet (optional)

• Graphic Builder

• Graphic Window Display

• Graphic Linked Parts

YOKOGAWA VIETNAM CO,LTD

Trang 5

Copyright © Yokogawa Electric CorporationYOKOGAWA VIETNAM CO.LTD

Example of Graphic builder

Trang 6

Copyright © Yokogawa Electric Corporation

Example of Graphic builder

Ribbon

Canvas pane

Pan & Zoom pane

Layer Window pane

Property Grid pane Output Area pane

YOKOGAWA VIETNAM CO.LTD

Trang 7

Copyright © Yokogawa Electric Corporation

Graphic Builder Mode

Engineering Mode

Start directly from System view

or from other Builder in SW

YOKOGAWA VIETNAM CO,LTD

Standalone Mode

Start as an individual application from the Window Start Menu

Trang 8

Copyright © Yokogawa Electric Corporation

Graphic Builder Mode

YOKOGAWA VIETNAM CO,LTD

Opening Graphic files

Builder file (.edf)Working file (.wkf)Standalone file (.sva)Linked Part files (.lpx)

Standalone file (.sva)Linked part files

(.lpx)

Checking the existence of

function blocks and windows

when saving to a file

User can specify whether

to perform the checking Checking is not performed

Trang 9

Copyright © Yokogawa Electric Corporation

Capacity of Graphic View

YOKOGAWA VIETNAM CO,LTD

Communication Data

Modifier Condition 8 conditions per Object

200 per viewFaceplate Window 16 Faceplate per window

Trang 10

Copyright © Yokogawa Electric Corporation

Graphic Builder File Types

Builder File

The builder files are the master files of graphic builder The extension for this type of file

is edf This type of file can be edited in engineering mode only

YOKOGAWA VIETNAM CO,LTD

Standalone File

When the created graphic file has conflict contents with the builder settings, the builder will display an error and refuse to save and download the graphic file Under this circumstance, you can save the file using this type with a different name the extension for this type of file is sva You can edit this file on graphic builder by importing the sva file on the graphic builder.

Linked parts files

The linked part files are the files of the objects of Graphic View The objects can be simply used

as graphical components for creating a graphic file The object and the linked part files are

closely linked, when you revise the object of the linked part file, the object use in graphic file will change to follow the revision.

Working files

A current created or edited graphic file can be save as a working file (.wkf) A working file

can be created even the file contents conflict with builder settings The working file can be

edited only in engineering mode

Trang 11

Copyright © Yokogawa Electric Corporation

Graphic Builder file Types

YOKOGAWA VIETNAM CO,LTD

File created in the

Trang 12

Copyright © Yokogawa Electric Corporation

Creating Builder (.edf) Files

Graphic Builder is used to create and edit graphic windows to operate and monitor

devices

YOKOGAWA VIETNAM CO.LTD

Trang 13

Copyright © Yokogawa Electric Corporation

Window operation and monitoring authority

Operation/ Monitoring

Authority

Acces

s Level

Trang 14

Copyright © Yokogawa Electric Corporation

Parts of the Graphic builder

Ribbon

Stencil pane

Canvas pane

Pan & Zoom pane

Layer Window pane

Property Grid pane Output Area pane

YOKOGAWA VIETNAM CO.LTD

Trang 15

Copyright © Yokogawa Electric Corporation

Graphic Builder - Ribbon

YOKOGAWA VIETNAM CO,LTD

Home

File

Edit

Trang 16

Copyright © Yokogawa Electric Corporation

Graphic Builder Ribbon File

YOKOGAWA VIETNAM CO,LTD

View

Draw

Tools

Trang 17

Copyright © Yokogawa Electric Corporation

Setting Grid Size & Display Grid

YOKOGAWA VIETNAM CO,LTD

From the Tool Ribbon

Trang 18

Copyright © Yokogawa Electric Corporation

Setting the Cavas Properties

YOKOGAWA VIETNAM CO,LTD

Trang 19

Copyright © Yokogawa Electric Corporation

1 Change display size according to monitor sizeSpecial size can also be set.Change width and height

YOKOGAWA VIETNAM CO,LTD

1

2

Setting the Cavas Properties

2 Change display background color

Trang 20

Copyright © Yokogawa Electric Corporation

Setting the Cavas Properties (Image)

YOKOGAWA VIETNAM CO.LTD

Trang 21

Copyright © Yokogawa Electric Corporation

Setting the Cavas Properties (Image)

To delete the background, click Delete Image

YOKOGAWA VIETNAM CO.LTD

Trang 22

Copyright © Yokogawa Electric Corporation

Setting the Cavas Properties (Image)

YOKOGAWA VIETNAM CO.LTD

Trang 23

Copyright © Yokogawa Electric Corporation

Layer Window Pane

YOKOGAWA VIETNAM CO.LTD

Trang 24

Copyright © Yokogawa Electric Corporation

Inserting Objects from the Home Tab

Trang 25

Copyright © Yokogawa Electric Corporation

Inserting Objects from the Stencil Area

Drag and Drop into

the Cavas Area

YOKOGAWA VIETNAM CO.LTD

Trang 26

Copyright © Yokogawa Electric Corporation

Objects properties - general

1

32

4

1 Customize object position and size

2 Check to make object visible

in the graphic view

3 Enable the target tagname to

be called up from the graphic view

4 Check to enable setting data during debugging

YOKOGAWA VIETNAM CO.LTD

Trang 27

Copyright © Yokogawa Electric Corporation

Objects properties - Line

1

1 Line Style: choose solid line or dashed line

23

45

2 Color: Outline color

3 Transparent: Check to set the outline to be transparent

4 Thickness: Sets the outline Width

5 Hairline: Sets the outline width to the hairline (1point)

YOKOGAWA VIETNAM CO.LTD

Trang 28

Copyright © Yokogawa Electric Corporation

Objects properties - Fill

3 Color: if gradient is selected in Fill type, this option sets the color for both edges of the object

4 Sample: Displays how will the object appear in the graphic view

YOKOGAWA VIETNAM CO.LTD

Trang 29

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

1 Type: Sets the bar type whether Rectangular or cylinder

23

4

2 Growth Direction: Sets the behavior

of the bar during data item increase, whether going up, down, left or right,

3 Reference Point: Sets the reference

of growth, whether endpoint or from the centerpoint

4 Sample: Displays how will the databar appear in the graphic view

Process Data Bar

YOKOGAWA VIETNAM CO.LTD

Trang 30

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

1 Enable Borders: sets whether the bar borders is enable or not Also sets borders type and thickness

2

3

2 Fill: Sets the fill type and color of:

BackgroundBorderbrushForegroundForeground Boderbrush

3 Sample: Displays how will the databar appear in the graphic view.Process Data Bar

YOKOGAWA VIETNAM CO.LTD

Trang 31

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

BoderbrushBackgroundForeground Boderbrush

Foreground

YOKOGAWA VIETNAM CO.LTD

Trang 32

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

1.Sets the datalink of the display bar Sets the tagname.dataitem value Dataitems:

PV,MV,ALRM,Mode…

2

2 Sets the low and high limit value

If left empty, default Low and High limit of the data item range will be set in the data bar display

Process Data Bar

YOKOGAWA VIETNAM CO.LTD

Trang 33

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

1 Execution Mode: sets whether execute one time or continuous execution

2

3

2 Condition: condition formula that will initiate the action of the databar appearance

Conditional format:

tagname.dataitem == dataEx: PIC100.PV >=50.0

Node: upto 8 conditional formula can

Process Data Bar

YOKOGAWA VIETNAM CO.LTD

Trang 34

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

String Percentage

Date Time

3 Use specified Alignment: set to use data character alignment, whether center, left or right.

4 Alignment: Set the alignment type

5 Engineering Unit: user can specify the unit to display When left empty, unit of the data item will be display.

6 Unit length: how many characters are used for the specified unit.

YOKOGAWA VIETNAM CO.LTD

Trang 35

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

1 Fill item: set to specify color of Background, Engineering unit color and Foreground

2

3

Background.

Process Data Character

4 sample: display how will the data character appear in the graphic view

Trang 36

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

1 Label Text String: the text to be displayed in the button.

23

Push Button

4

3 Text Alignment: Center, left or right

4 With Illumination: Enable to changing

of the background color of the push button.

5

2 Text wrapping: Wrap

Wrap with Overflow

No Wrap

5 Attach Guard: when enable, push button must be pressed twice to active, if disabled push button is activated with single click

YOKOGAWA VIETNAM CO.LTD

Trang 37

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

1 Function Type: Call window

23

YOKOGAWA VIETNAM CO.LTD

Trang 38

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

Executable Functions that can be assigned to interactive controls.

 Display HIS window

 Performing a system function

 Controlling trend data acquisition

 Controlling LED’s on the HIS console

 Performing an instrument command

 Starting a program or opening a file

 Displaying a data input dialog box

 Display a menu dialog box

 Display a data-menu item dependent menu dialog box

 Playing back a sound file

 Printing a report

 Displaying a panel set

 Calling up a frame

 Switching view in a frame

 Using parameters to start system-specific functions

YOKOGAWA VIETNAM CO.LTD

Trang 39

Copyright © Yokogawa Electric Corporation

Assigning Function- call window

Window assignable to call Window Function

 Logic Chart Status

 Control Drawing Status

 Advance Alarm Filter

 Product Control (unit name specification)

YOKOGAWA VIETNAM CO.LTD

Trang 40

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

Key Name

2

Push Button & Touch Target

Execute System Function

Trang 41

Copyright © Yokogawa Electric Corporation

System Function Keys

System Function Key

Hard Copy Prints all windows displayed on the main monitor

screen including Windows-based application windowsPrint Prints an active window This is enable only when the

print function is available for the active window to be printed

Message Printout Prints all messages using all message printers

Buzzer Reset Resets buzzer

Silence sound output Turn off the sound upon acknowledgement by the

operatorPanel set Actives the panel set associated with the graphic

windowIsolate Prevents a window from being activated by other HIS

consoles You can switch the isolation status…

YOKOGAWA VIETNAM CO.LTD

Trang 42

Copyright © Yokogawa Electric Corporation

System Function Keys

System Function Key

Window down Moves the window at the top of the cascade to the

bottom This function excludes the main window

Window up Moves the window at the bottom of the cascade to the

top This function excludes the main window

Focus Switches the focus between windows This is enable

only in full screen mode

Main window focus Brings the main window into focus This is enabled

only in full screen mode

Circulate Witches the focus of the windows, including

Windows-based application windows, sequentiallyAcknowledge Performs alarm acknowledgement on alarms related to

the active window/

Close window Close all display windows

YOKOGAWA VIETNAM CO.LTD

Trang 43

Copyright © Yokogawa Electric Corporation

System Function Keys

System Function Key

History call Send Displays previously displayed windows one at time,

starting from the oldestHistory call return Displays previously displayed windows at one time,

starting from the newestNavigator Displays a navigator Window

User in Display a log-in dialog box

Clear Cancels a selection or data input

Message monitor

window

Displays a message monitor window

Shift Screen Shifts the HIS standard windows displayed in main

monitor to the secondary window

YOKOGAWA VIETNAM CO.LTD

Trang 44

Copyright © Yokogawa Electric Corporation

System Function Keys

System Function Key

Delete Monitor

Specified Screen (*) Removes windows from a monitor screen by according to the monitor number specified

YOKOGAWA VIETNAM CO.LTD

Trang 45

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

Window name ex: TG0101

YOKOGAWA VIETNAM CO.LTD

Trang 46

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

number in the Operation Keyboard

as target of the command

2

Push Button & Touch Target

Flash/Light/Turn off the LED

1 Function Type: Flash/light/Turn off the LED

3

3 Parameter: Specify command action

Flashing ON

OFF

YOKOGAWA VIETNAM CO.LTD

Trang 47

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

5 Command Data: Value of the data field.2

Push Button & Touch Target

Instrument Command Operation

4 Acknowledgement: Specify to enable with Acknowledgement

54

2 Data type: Specify the data type as target of the command

1 Function Type: Instrument command Operation

7 Condition Formula Ex: LIC100.Mode==“MAN”

The target command will only be executed when the above condition satisfied

6 Check when input: enable condition testing before command execution

6

7

YOKOGAWA VIETNAM CO.LTD

Trang 48

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

file name of the program or file You can enter a maximum of 46 characters.

program name: BKHCAMS_SON.EXE Parameter: FCS0101

Suppress alarms for FCS0101

2

Push Button & Touch Target

Execute Program by File Name

1 Function Type: Execute the program by File Name

Trang 49

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

2 Data type: specify the data type as target of the command

2

Push Button & Touch Target

Call Data Input Dialog

1 Function Type: call data dialog box

Trang 50

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

5

Push Button & Touch Target

Call Data Input Dialog

7

6

6 Condition Formula Ex: LIC100.Mode==“MAN”

The target command will only be executed when the above condition satisfied

5 Check when input: enable condition testing before command execution

7 Data entry Dialog style:

choose between normal or INC/DEC

YOKOGAWA VIETNAM CO.LTD

Trang 51

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

Process data recipe Data (unit name specification) Recipe Data (Batch ID specification)

2

Push Button & Touch Target

Call Menu Dialog

1 Function Type: Call menu dialog

Trang 52

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

1

2 Display position: Specify menu position when displayed

2

Push Button & Touch Target

Call Menu Dialog

as either:

Specified data Menu number Label text string

3

3 label: Insert menu item label

4 Data insert: Insert menu data item

4

YOKOGAWA VIETNAM CO.LTD

Trang 53

Copyright © Yokogawa Electric Corporation

Buttons and Data Display Properties

saved in the HIS from the path:

C:\CENTUMVP\his\Media\User

2

Push Button & Touch Target

Execute the Multimedia Function

1 Function Type: execute Multimedia Function

3

4 Number of Execution: if Play is selected, specify how many times it will be played.

Ngày đăng: 05/03/2017, 16:33

TỪ KHÓA LIÊN QUAN