Copyright © Yokogawa Electric Corporation Example of Graphic builder Ribbon Canvas pane Pan & Zoom pane Layer Window pane Property Grid pane Output Area pane YOKOGAWA VIETNAM CO.LTD...
Trang 1Copyright © Yokogawa Electric Corporation
<1/7/2011>
June 2012
Yokogawa Electric Corporation
YOKOGAWA VIETNAM CO.LTD
Trang 2Copyright © Yokogawa Electric CorporationYOKOGAWA VIETNAM CO.LTD
Yokogawa Vietnam Co Ltd Service Department
ENGINEERING COURSE
Trang 4This document is composed of the following chapters:
• Input documents for Graphic generation
• Graphic Worksheet (optional)
• Graphic Builder
• Graphic Window Display
• Graphic Linked Parts
YOKOGAWA VIETNAM CO,LTD
Trang 5Copyright © Yokogawa Electric CorporationYOKOGAWA VIETNAM CO.LTD
Example of Graphic builder
Trang 6Copyright © Yokogawa Electric Corporation
Example of Graphic builder
Ribbon
Canvas pane
Pan & Zoom pane
Layer Window pane
Property Grid pane Output Area pane
YOKOGAWA VIETNAM CO.LTD
Trang 7Copyright © Yokogawa Electric Corporation
Graphic Builder Mode
Engineering Mode
Start directly from System view
or from other Builder in SW
YOKOGAWA VIETNAM CO,LTD
Standalone Mode
Start as an individual application from the Window Start Menu
Trang 8Copyright © Yokogawa Electric Corporation
Graphic Builder Mode
YOKOGAWA VIETNAM CO,LTD
Opening Graphic files
Builder file (.edf)Working file (.wkf)Standalone file (.sva)Linked Part files (.lpx)
Standalone file (.sva)Linked part files
(.lpx)
Checking the existence of
function blocks and windows
when saving to a file
User can specify whether
to perform the checking Checking is not performed
Trang 9Copyright © Yokogawa Electric Corporation
Capacity of Graphic View
YOKOGAWA VIETNAM CO,LTD
Communication Data
Modifier Condition 8 conditions per Object
200 per viewFaceplate Window 16 Faceplate per window
Trang 10Copyright © Yokogawa Electric Corporation
Graphic Builder File Types
Builder File
The builder files are the master files of graphic builder The extension for this type of file
is edf This type of file can be edited in engineering mode only
YOKOGAWA VIETNAM CO,LTD
Standalone File
When the created graphic file has conflict contents with the builder settings, the builder will display an error and refuse to save and download the graphic file Under this circumstance, you can save the file using this type with a different name the extension for this type of file is sva You can edit this file on graphic builder by importing the sva file on the graphic builder.
Linked parts files
The linked part files are the files of the objects of Graphic View The objects can be simply used
as graphical components for creating a graphic file The object and the linked part files are
closely linked, when you revise the object of the linked part file, the object use in graphic file will change to follow the revision.
Working files
A current created or edited graphic file can be save as a working file (.wkf) A working file
can be created even the file contents conflict with builder settings The working file can be
edited only in engineering mode
Trang 11Copyright © Yokogawa Electric Corporation
Graphic Builder file Types
YOKOGAWA VIETNAM CO,LTD
File created in the
Trang 12Copyright © Yokogawa Electric Corporation
Creating Builder (.edf) Files
Graphic Builder is used to create and edit graphic windows to operate and monitor
devices
YOKOGAWA VIETNAM CO.LTD
Trang 13Copyright © Yokogawa Electric Corporation
Window operation and monitoring authority
Operation/ Monitoring
Authority
Acces
s Level
Trang 14Copyright © Yokogawa Electric Corporation
Parts of the Graphic builder
Ribbon
Stencil pane
Canvas pane
Pan & Zoom pane
Layer Window pane
Property Grid pane Output Area pane
YOKOGAWA VIETNAM CO.LTD
Trang 15Copyright © Yokogawa Electric Corporation
Graphic Builder - Ribbon
YOKOGAWA VIETNAM CO,LTD
Home
File
Edit
Trang 16Copyright © Yokogawa Electric Corporation
Graphic Builder Ribbon File
YOKOGAWA VIETNAM CO,LTD
View
Draw
Tools
Trang 17Copyright © Yokogawa Electric Corporation
Setting Grid Size & Display Grid
YOKOGAWA VIETNAM CO,LTD
From the Tool Ribbon
Trang 18Copyright © Yokogawa Electric Corporation
Setting the Cavas Properties
YOKOGAWA VIETNAM CO,LTD
Trang 19Copyright © Yokogawa Electric Corporation
1 Change display size according to monitor sizeSpecial size can also be set.Change width and height
YOKOGAWA VIETNAM CO,LTD
1
2
Setting the Cavas Properties
2 Change display background color
Trang 20Copyright © Yokogawa Electric Corporation
Setting the Cavas Properties (Image)
YOKOGAWA VIETNAM CO.LTD
Trang 21Copyright © Yokogawa Electric Corporation
Setting the Cavas Properties (Image)
To delete the background, click Delete Image
YOKOGAWA VIETNAM CO.LTD
Trang 22Copyright © Yokogawa Electric Corporation
Setting the Cavas Properties (Image)
YOKOGAWA VIETNAM CO.LTD
Trang 23Copyright © Yokogawa Electric Corporation
Layer Window Pane
YOKOGAWA VIETNAM CO.LTD
Trang 24Copyright © Yokogawa Electric Corporation
Inserting Objects from the Home Tab
Trang 25Copyright © Yokogawa Electric Corporation
Inserting Objects from the Stencil Area
Drag and Drop into
the Cavas Area
YOKOGAWA VIETNAM CO.LTD
Trang 26Copyright © Yokogawa Electric Corporation
Objects properties - general
1
32
4
1 Customize object position and size
2 Check to make object visible
in the graphic view
3 Enable the target tagname to
be called up from the graphic view
4 Check to enable setting data during debugging
YOKOGAWA VIETNAM CO.LTD
Trang 27Copyright © Yokogawa Electric Corporation
Objects properties - Line
1
1 Line Style: choose solid line or dashed line
23
45
2 Color: Outline color
3 Transparent: Check to set the outline to be transparent
4 Thickness: Sets the outline Width
5 Hairline: Sets the outline width to the hairline (1point)
YOKOGAWA VIETNAM CO.LTD
Trang 28Copyright © Yokogawa Electric Corporation
Objects properties - Fill
3 Color: if gradient is selected in Fill type, this option sets the color for both edges of the object
4 Sample: Displays how will the object appear in the graphic view
YOKOGAWA VIETNAM CO.LTD
Trang 29Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
1 Type: Sets the bar type whether Rectangular or cylinder
23
4
2 Growth Direction: Sets the behavior
of the bar during data item increase, whether going up, down, left or right,
3 Reference Point: Sets the reference
of growth, whether endpoint or from the centerpoint
4 Sample: Displays how will the databar appear in the graphic view
Process Data Bar
YOKOGAWA VIETNAM CO.LTD
Trang 30Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
1 Enable Borders: sets whether the bar borders is enable or not Also sets borders type and thickness
2
3
2 Fill: Sets the fill type and color of:
BackgroundBorderbrushForegroundForeground Boderbrush
3 Sample: Displays how will the databar appear in the graphic view.Process Data Bar
YOKOGAWA VIETNAM CO.LTD
Trang 31Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
BoderbrushBackgroundForeground Boderbrush
Foreground
YOKOGAWA VIETNAM CO.LTD
Trang 32Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
1.Sets the datalink of the display bar Sets the tagname.dataitem value Dataitems:
PV,MV,ALRM,Mode…
2
2 Sets the low and high limit value
If left empty, default Low and High limit of the data item range will be set in the data bar display
Process Data Bar
YOKOGAWA VIETNAM CO.LTD
Trang 33Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
1 Execution Mode: sets whether execute one time or continuous execution
2
3
2 Condition: condition formula that will initiate the action of the databar appearance
Conditional format:
tagname.dataitem == dataEx: PIC100.PV >=50.0
Node: upto 8 conditional formula can
Process Data Bar
YOKOGAWA VIETNAM CO.LTD
Trang 34Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
String Percentage
Date Time
3 Use specified Alignment: set to use data character alignment, whether center, left or right.
4 Alignment: Set the alignment type
5 Engineering Unit: user can specify the unit to display When left empty, unit of the data item will be display.
6 Unit length: how many characters are used for the specified unit.
YOKOGAWA VIETNAM CO.LTD
Trang 35Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
1 Fill item: set to specify color of Background, Engineering unit color and Foreground
2
3
Background.
Process Data Character
4 sample: display how will the data character appear in the graphic view
Trang 36Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
1 Label Text String: the text to be displayed in the button.
23
Push Button
4
3 Text Alignment: Center, left or right
4 With Illumination: Enable to changing
of the background color of the push button.
5
2 Text wrapping: Wrap
Wrap with Overflow
No Wrap
5 Attach Guard: when enable, push button must be pressed twice to active, if disabled push button is activated with single click
YOKOGAWA VIETNAM CO.LTD
Trang 37Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
1 Function Type: Call window
23
YOKOGAWA VIETNAM CO.LTD
Trang 38Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
Executable Functions that can be assigned to interactive controls.
Display HIS window
Performing a system function
Controlling trend data acquisition
Controlling LED’s on the HIS console
Performing an instrument command
Starting a program or opening a file
Displaying a data input dialog box
Display a menu dialog box
Display a data-menu item dependent menu dialog box
Playing back a sound file
Printing a report
Displaying a panel set
Calling up a frame
Switching view in a frame
Using parameters to start system-specific functions
YOKOGAWA VIETNAM CO.LTD
Trang 39Copyright © Yokogawa Electric Corporation
Assigning Function- call window
Window assignable to call Window Function
Logic Chart Status
Control Drawing Status
Advance Alarm Filter
Product Control (unit name specification)
YOKOGAWA VIETNAM CO.LTD
Trang 40Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
Key Name
2
Push Button & Touch Target
Execute System Function
Trang 41Copyright © Yokogawa Electric Corporation
System Function Keys
System Function Key
Hard Copy Prints all windows displayed on the main monitor
screen including Windows-based application windowsPrint Prints an active window This is enable only when the
print function is available for the active window to be printed
Message Printout Prints all messages using all message printers
Buzzer Reset Resets buzzer
Silence sound output Turn off the sound upon acknowledgement by the
operatorPanel set Actives the panel set associated with the graphic
windowIsolate Prevents a window from being activated by other HIS
consoles You can switch the isolation status…
YOKOGAWA VIETNAM CO.LTD
Trang 42Copyright © Yokogawa Electric Corporation
System Function Keys
System Function Key
Window down Moves the window at the top of the cascade to the
bottom This function excludes the main window
Window up Moves the window at the bottom of the cascade to the
top This function excludes the main window
Focus Switches the focus between windows This is enable
only in full screen mode
Main window focus Brings the main window into focus This is enabled
only in full screen mode
Circulate Witches the focus of the windows, including
Windows-based application windows, sequentiallyAcknowledge Performs alarm acknowledgement on alarms related to
the active window/
Close window Close all display windows
YOKOGAWA VIETNAM CO.LTD
Trang 43Copyright © Yokogawa Electric Corporation
System Function Keys
System Function Key
History call Send Displays previously displayed windows one at time,
starting from the oldestHistory call return Displays previously displayed windows at one time,
starting from the newestNavigator Displays a navigator Window
User in Display a log-in dialog box
Clear Cancels a selection or data input
Message monitor
window
Displays a message monitor window
Shift Screen Shifts the HIS standard windows displayed in main
monitor to the secondary window
YOKOGAWA VIETNAM CO.LTD
Trang 44Copyright © Yokogawa Electric Corporation
System Function Keys
System Function Key
Delete Monitor
Specified Screen (*) Removes windows from a monitor screen by according to the monitor number specified
YOKOGAWA VIETNAM CO.LTD
Trang 45Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
Window name ex: TG0101
YOKOGAWA VIETNAM CO.LTD
Trang 46Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
number in the Operation Keyboard
as target of the command
2
Push Button & Touch Target
Flash/Light/Turn off the LED
1 Function Type: Flash/light/Turn off the LED
3
3 Parameter: Specify command action
Flashing ON
OFF
YOKOGAWA VIETNAM CO.LTD
Trang 47Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
5 Command Data: Value of the data field.2
Push Button & Touch Target
Instrument Command Operation
4 Acknowledgement: Specify to enable with Acknowledgement
54
2 Data type: Specify the data type as target of the command
1 Function Type: Instrument command Operation
7 Condition Formula Ex: LIC100.Mode==“MAN”
The target command will only be executed when the above condition satisfied
6 Check when input: enable condition testing before command execution
6
7
YOKOGAWA VIETNAM CO.LTD
Trang 48Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
file name of the program or file You can enter a maximum of 46 characters.
program name: BKHCAMS_SON.EXE Parameter: FCS0101
Suppress alarms for FCS0101
2
Push Button & Touch Target
Execute Program by File Name
1 Function Type: Execute the program by File Name
Trang 49Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
2 Data type: specify the data type as target of the command
2
Push Button & Touch Target
Call Data Input Dialog
1 Function Type: call data dialog box
Trang 50Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
5
Push Button & Touch Target
Call Data Input Dialog
7
6
6 Condition Formula Ex: LIC100.Mode==“MAN”
The target command will only be executed when the above condition satisfied
5 Check when input: enable condition testing before command execution
7 Data entry Dialog style:
choose between normal or INC/DEC
YOKOGAWA VIETNAM CO.LTD
Trang 51Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
Process data recipe Data (unit name specification) Recipe Data (Batch ID specification)
2
Push Button & Touch Target
Call Menu Dialog
1 Function Type: Call menu dialog
Trang 52Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
1
2 Display position: Specify menu position when displayed
2
Push Button & Touch Target
Call Menu Dialog
as either:
Specified data Menu number Label text string
3
3 label: Insert menu item label
4 Data insert: Insert menu data item
4
YOKOGAWA VIETNAM CO.LTD
Trang 53Copyright © Yokogawa Electric Corporation
Buttons and Data Display Properties
saved in the HIS from the path:
C:\CENTUMVP\his\Media\User
2
Push Button & Touch Target
Execute the Multimedia Function
1 Function Type: execute Multimedia Function
3
4 Number of Execution: if Play is selected, specify how many times it will be played.