Copyright © Yokogawa Electric Corporation Status of Function Block at Start Operation Table: Internal Status of Function Block *1:If a repeated warning alarm occurs at start operation,
Trang 1Copyright © Yokogawa Electric Corporation
<1/7/2011>
June 2012
Yokogawa Electric Corporation
YOKOGAWA VIETNAM CO.LTD
Trang 2CENTUM VP5 ENGINEERING COURSE
Trang 3Control Drawing Builder Day 2
CENTUM VP Engineering Course
Trang 6The start condition determines which method to be used, initial cold start or restart,
to initiate the FCS, upon turning on the power to FCS which was in the power
shutoff status
Trang 7Copyright © Yokogawa Electric Corporation
<1/7/2011>
Status of Function Block at Start Operation
Table: Internal Status of Function Block
*1:If a repeated warning alarm occurs at start operation, process alarm message is output assuming that a new alarm is created As long as the alarm status lasts, the repeated warning alarm message is continuously output at regular intervals If
specified, all alarm messages occurred at initial cold start can be output
The behavior of FCS regarding to function blocks when the FCS is undergoing
Initial Cold Start or Restart is shown as follows.
YOKOGAWA VIETNAM
CO.LTD
Trang 8block mode before the power failure.
Table: List of Function Blocks That Perform MAN Fallback at Initial Cold Start
•At initial cold start
If the function blocks shown below are connected to the process I/O at start operation,
the block mode becomes MAN by the MAN fallback function
MAN fallback of function block differs depending on the type of start operation as
described below.
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 9Copyright © Yokogawa Electric Corporation
<1/7/2011>
Status of Special Function Block at Start Operation
The table below shows the behavior of FCS regarding to the specific function blocks when starting the FCS
Table: Status of Special Function Block
*1:The start operation for sequence table can be changed by changing the
contents of start operation identification switch.
YOKOGAWA VIETNAM
CO.LTD
Trang 10Define whether to receive the values
of global switches under the control
of other stations if
transferred
If the value smaller than 32 bytes is defined for the buffer size of the
present station, global switches will not work.
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 12for the system The station address
is use to identify the
station on the V net,
once set, it cannot be
change anymore.
Component number
are used for wiring and labeling the connection origin or
connection destination
If more information about each station is
required, the station
comment may be input for each station
An alias is an alternative station name of up to 8 alphanumeric characters
A window can be designated to display the station status on the HIS instead of using the HIS station status panel
The name of the higher level process equipment group in plant hierarchy can
be designated or it can be ommitted
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 132 Use when a relative faster response is
required for the process control.
3 Settings related to motor control blocks pulse
Trang 145 Set the optional function block to be
used in the FCS namely:
VPMON
OFFSITE
DIOENH
6 MLD-SW is a Manual Loader Block
with Auto/Man SW to manually operate
final control elements such as control
valves As the lowest downstream block in
the control loops that consist of multiple
function block may be set as CAS or AUT
7 When downloading to an IO module,
the behavior of function blocks connected
to the module maybe specified as IOP
(input open) or not.
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 158 (MOV) specify whether the MV value should
be set to “50%” or “previous value” when
pulses are not output under the conditions the
block mode is in the AUT mode and there is no
feedback input.
If [Centum V Compatible MV Display] is
chosen, the MV value become 50% if PID is in
AUT and there is no feedback.
9 Specify whether “PV value immediately
before holding the output” or “current PV
value” should be used for the previous value
used in the first control calculation after the
output is held in a PI-HLD block.
If [CENTUM-XL Compatible] is checked the
previous PV value used in the first control
calculation after the output is held is overwritten
with the current PV value.
YOKOGAWA VIETNAM
CO.LTD
Trang 165 By checking the check box of [ Suppress system
alarm when CALCU calculation error occurs] the
system alarm messages will not be energized when a
calculation errors occurs in a general-purpose
calculation block (calcu, calcu-c)
7
8
6 For AFV30S or AFV30D, use or not HKU of
system cabinet can be specify.
8 If this option is checked, user can change the
mode of a regulatory control block to Primary Direct
(PRD) mode even the block in calibration mode.
When this option is not checked (default): not allow
changing to PRD when block is in CAL.
7 If this option is checked, a process alarm will be
initiated when calibration mode (CAL) is applied to
or released from a function block
When the option is checked: alarm will be initiated
When not: alarm will no be initiated (default)
5
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 171 When the FCS database is a type of database
for unit configuration, state transition matrix
can be defined.
A state transition matrix to be applied in this
FCS can be selected from the state transition
matrix list of this project.
YOKOGAWA VIETNAM
CO.LTD
Trang 18TO ANOTHER STEP
PAUSE
RESTART
PSTART END
ABORT ABORT
SUSPEND
END
RESTART SUSPEND
END
RESET ABORT
END
Trang 191 The IP address on the control bus are
used to logically identify the station for
communication among other station on
the control bus
YOKOGAWA VIETNAM
CO.LTD
Trang 20Copyright © Yokogawa Electric Corporation
<1/7/2011>
FIO Module Configuration
YOKOGAWA VIETNAM CO,LTD
ENGINEERING DEPARTMENT
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 2164 channels
Trang 2232 Channels (16 input/16 output)
16 Channels (8 input/8 output)
Trang 23Copyright © Yokogawa Electric CorporationYOKOGAWA VIETNAM CO.LTD
IO Classification
Isolated channels Isolated
Safety
Non-Isolated
Trang 24Ethernet Serial
RS 232 RS422/485
Trang 261-5 V DC, 1-10 V DC -10 V to +10 V DC RTDs
Pt100, JPt100, Pt1000, JPt1000 Thermocouples
JIS R, J, K, E, T, B, S Pulse
Trang 28AAI135 4 to 20 mA, 8-Channel, Isolated Channels
AAI141 4 to 20 mA, 16-Channel, Non-Isolated
AAI143 4 to 20 mA, 16-Channel, Isolated
8-Channel Input/8-Channel Output, Non-Isolated
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 29No of channels 16, non-isolated 16, isolated 8, isolated
channels Input signal 4-20mA DC 4-20mA DC 4-20mA DC Allowable input
Trang 31AAV141 1 to 5 V, 16-Channel, Non-Isolated
AAV142 -10 to 10V, 16-Channel, Non-Isolated
AAV144 -10 to 10V, 16-Channel, Isolated
Analog Output
AAV542 -10 to 10V, 16-Channel, Non-Isolated
AAV544 -10 to 10V, 16-Channel, Isolated
Hybrid (AI/AO)
AAB841 1 to 5 V Input, 4 to 20 mA Output,
8-Channel Input/8-Channel Output, Non-Isolated
YOKOGAWA VIETNAM COMPANY LTD YOKOGAWA VIETNAM CO.LTD
Trang 33N/mV: -100 to 150 mV, 16-Channel, Isolated ChannelsYOKOGAWA VIETNAM
CO.LTD
Trang 35AAP849 Pulse Input/Analog Output Module compatible for PAC
Pulse Count, 4 to 20 mA output,
8-Channel Input/8-Channel Output, Non-Isolated
YOKOGAWA VIETNAM
CO.LTD
Trang 36ADV151 Digital Input Module (32-Channel, 24 V DC, Isolated)
ADV141 Digital Input Module (16-Channel, 100 V AC, Isolated)
ADV142 Digital Input Module (16-Channel, 220 V AC, Isolated)
ADV157 Digital Input Module (32-Channel, 24 V DC, Isolated)
ADV161 Digital Input Module (64-Channel, 24 V DC, Isolated)
ADV159 Digital Input Module for Compatible ST3 (32-Channel Input, Isolated Channels)
ADV169 Digital Input Module for Compatible ST6 (64-Channel Input, Isolated, Common Minus Side
Every 16-Channel)
Digital Output
ADV551 Digital Output Module (32-Channel, 24 V DC, Isolated)
ADV557 Digital Output Module (32-Channel, 24 V DC, Pressure Clamp Terminal Support Only,
(Isolated)
ADV561 Digital Output Module (64-Channel, 24 V DC, Isolated)
ADR541 Relay Output Module (16-Channel, 24 to 110 V DC/100 to 240 V AC, Isolated)
ADV559 Digital Output Module for Compatible ST4 (32-Channel Output, Isolated Channels)
ADV569 Digital Output Module for Compatible ST7 (64-Channel Output, Isolated, Common Minus
Side Every 16-Channel)
Hybrid (DI/DO)
ADV859 Digital I/O Module for Compatible ST2 (16-Channel Input/16-Channel Output, Isolated
Channels)
ADV869 Digital I/O Module for Compatible ST5 (32-Channel Input/32-Channel Output, Isolated,
Common Minus Side Every 16-Channel)
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 39AD R - 5 41
DC Power Supply
or
YOKOGAWA VIETNAM
CO.LTD
Trang 40Connection Types of Field Wiring
Three types of field connection can be chosen
– Direct wiring for the Weidmueller (pressure clamp) terminals
– Connect through the field terminal assemblies (Terminal boards) or the signal conditioners
• Dedicated system connection cables are also needed.
– Connect with MIL cables
Each module has three types of front assembly to choose the field
connection type
– Terminal board for Foundation Fieldbus module is available
– Redundant configuration is available except MIL cable connection
MIL connector Weidmuller
terminals KS cable adapter
Trang 42(2-Port, 1200 bps to 115.2 kbps) ALF111 Foundation Fieldbus communication Module
(FF-H1) (4-Port, 31.25 kbps) ALE111 Ethernet communication module (1-Port, 10 Mbps) ALP111 PROFIBUS-DPV1 communication module
YOKOGAWA VIETNAM COMPANY LTD YOKOGAWA VIETNAM CO.LTD
SERVICE DEPARTMENT
Trang 491 Control IOs – upper node
2 Monitoring IOs – after Control IOs
3 Subsystems – last node
YOKOGAWA VIETNAM COMPANY LTD YOKOGAWA VIETNAM CO.LTD
Trang 51If card fails, ALL control loops
on the card are affected!
YOKOGAWA VIETNAM
CO.LTD
Trang 52Copyright © Yokogawa Electric Corporation
<1/7/2011>
IO Loading Considerations
If active card fails, control
is shifted to backup card at
Trang 53YOKOGAWA VIETNAM
CO.LTD
Trang 54ANB10x-xx0, ANB11x-xx0 and ANR10x-xx0: Hazardous Area
Installation of modules in any one of ANB10S, ANB10D,ANR10S, ANR10D nodes and Compact Field Control Unit for FIO (AVF10X,AFV30X, AFV40X) imposes a limitation on the total number of modules considering the power supply.
ANB10, ANB11 and ANR10: Non-Hazardous Area
ANB10x-xx-3, ANB11x-xx-3 and ANR10x-xx-3: Hazardous Area
Note: - 0 Basic Type, -3 with ISA G3(hazardous area with corrosive chemicals)
Trang 55AFV10D, AFV30D and AFV40D
For application to Non-Hazardous Area or Hazardous Area
AFV10S, AFV30S and AFV40S
For application to Non-Hazardous Area or Hazardous Area
AFV10D, AFV30D: Hazardous Area
Trang 57AAI143: Factor B Device
AAI543: Factor B Device
Power Factor Rating
Trang 58AAI143: Factor B Device
AAI543: Factor B Device
Power Factor Rating
Trang 59Copyright © Yokogawa Electric Corporation
<1/7/2011>
Power Supply Restrictions
Hazardous Area with
corrosive chemicals
AAI143: Factor B Device
Power Factor Rating
Trang 60AGS813/AGP813 modules Max 8 units/FCS (max 4 pair for dual- redundant operation
dual-redundant operation
No of all the communication modules Max 30 modules/FCS
AFV30D/AFV40D + Node Expansion (V1)
No of ALR111/ALR121/ALE111/ALP121/
AGS813/AGP813 modules Max 16 units/FCS (max 8 pair for dual- redundant operation
dual-redundant operation
No of all the communication modules Max 48 modules/FCS
Trang 61AGS813/AGP813 modules Max 32 units/FCS (max 16 pair for dual- redundant operation
dual-redundant operation
No of all the communication modules Max 64 modules/FCS
Trang 62AGS813/AGP813 modules Max 8 units/FCS (max 4 pair for dual- redundant operation
dual-redundant operation
No of all the communication modules Max 30 modules/FCS
AFV10D (Extended Type)
No of ALR111/ALR121/ALE111/ALP121/
AGS813/AGP813 modules Max 16 units/FCS (max 8 pair for dual- redundant operation
dual-redundant operation
No of all the communication modules Max 48 modules/FCS
Trang 64Copyright © Yokogawa Electric Corporation
<1/7/2011>
Create a New Node
Select a project from your system view
1 Creating a New Node: FFCS
A node for installing an I/O module must be created prior to creating an I/O module A node for holding I/O modules can be created
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 71Copyright © Yokogawa Electric Corporation
<1/7/2011>
Software Switch Configuration
&
Message Definition
YOKOGAWA VIETNAM
CO.LTD
Trang 73For CS3000 /CENTUM VP R4 up to 4000 common switches are available with
%SW0001 to %SW0400 being System Reserved.
For CENTUM VP R5 up to 9000 common switches are available with
%SW8000 to %SW9000 being system Reserved.
Changing the number of system common switches can be performed on FCS
properties sheet by checking the option box [ Increase Number of System Common Switches] By default setting, this option is checked
Trang 74assigned to each station The defined value is broadcasted to each station in the
system via control bus scan transmission when data transfer to other stations is
defined at Scan Transmission Definition on the FCS Constants Builder.
When the values of global switches under the control of other stations are sent via scan transmission, the global switch on the present station is updated when data
receipt is defined at Scan Transmission Definition on the FCS Constants Builder.
The values of global switches are updated by 100 ms, which is fixed
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 77Copyright © Yokogawa Electric Corporation
<1/7/2011>
Message Types
The following messages have system-fixed identification numbers and contents:
• System Alarm Messages
• Process Alarm Messages
YOKOGAWA VIETNAM
CO.LTD
Trang 78Copyright © Yokogawa Electric Corporation
<1/7/2011>
Message Types
System Alarm Messages
System alarm messages notify the operator of the hardware errors in the control station or an HIS as well as errors in communication The type and contents of the system alarm are
predetermined
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 79Copyright © Yokogawa Electric Corporation
<1/7/2011>
Message Types
Process Alarm Messages
Process alarm message is used to notify the status of a process alarm to the operator
YOKOGAWA VIETNAM
CO.LTD
Trang 80Copyright © Yokogawa Electric Corporation
<1/7/2011>
Annunciator Message (%AN)
Annunciator message outputs
store alarm-occurrence statuses
as logical values.
The HIS annunciator function simulates the annunciator instrument panel
These special message outputs are
used to simulate the annunciator
panels of the instrument panels
Figure: Flow of Annunciator Message Processing
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 82Copyright © Yokogawa Electric Corporation
<1/7/2011>
Annunciator Message (%AN)
Annunciator message is used to notify the operator of errors in the process.
Up to 24 alphanumeric characters are used.
1000 Annunciator Messages (FFCS-L)
YOKOGAWA VIETNAM
CO.LTD
SERVICE DEPARTMENT
Trang 83Copyright © Yokogawa Electric Corporation
<1/7/2011>
Operator Guide Message (%OG)
Operator guide messages are triggered by the sequence control of the control
station.
When the Operation and
Monitoring Functions detect an
operator guide message, a
character string that corresponds
to the message number is
displayed in the Operator Guide
view, then the operator guide
message is saved to the
historical message log file.
Figure: Flow of Operator Guide Message Processing
YOKOGAWA VIETNAM
CO.LTD