Tiêu đề Amendment No. 1/2002 to AS/ACIF S009:2001 installation requirements for customer cabling (wiring rules)
Thể loại Amendment
Năm xuất bản 2002
Định dạng
Số trang 1
Dung lượng 97,46 KB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Nội dung

1/2002AUSTRALIAN COMMUNICATIONS INDUSTRY FORUM Amendment No.. 1/2002 to AS/ACIF S009:2001 Installation requirements for customer cabling Wiring Rules REVISED TEXT The 2001 edition of AS/

Trang 1

AS/ACIF S009:2001 Amdt No 1/2002

AUSTRALIAN COMMUNICATIONS INDUSTRY FORUM

Amendment No 1/2002

to AS/ACIF S009:2001 Installation requirements for customer cabling (Wiring Rules)

REVISED TEXT The 2001 edition of AS/ACIF S009 is amended as follows; the amendments should be inserted in the

appropriate places

SUMMARY: This Amendment applies to Clauses 5.5.3.4

Published 9 December 2002

Approved for publication on 6 December 2002

Gazetted on 18 December 2002 and commenced on that day

ISBN 1 74000 228 8

AMDT

No 1

DEC.

2002

Page 36 Clause 5.5.3.4

Delete Clause 5.5.3.4 and replace with the following:

5.5.3.4 Cable type

5.5.3.4.1 Cable installed underground shall be compliant, underground cable

whether or not the cable is installed in conduit

5.5.3.4.2 Underground cable installed after 1 January 2004 shall meet the

requirements of AS/ACIF S008

5.5.3.4.3 Blown-fibre tube systems installed underground shall—

(a) be contiguous between access points;

(b) have access points appropriately located or sealed to prevent the ingress of moisture; and

(c) be appropriately installed or plugged when entering a building to prevent the passage of fluid or gas into the building from any pit or access hole

This Amendment forms part of the Standard on publication.

- End of Amendment No