PCS-9671S provides the main protection elements, such as: current differential protection and restricted earth fault protection.. 87T Transformer differential protection Biased differe
Trang 3Copyright © 2020 NR All rights reserved
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may
be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights
The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document is subject to change without prior notice
To the extent required the products described herein meet applicable IEC and IEEE standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly
Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us
Trang 5Preface
About This Manual
The manual describes the protection, measurement and supervision functions with the information of relevant hardware for PCS-9671S Transformer Relay
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment (module or device) However, it comprises important information that must be followed for personal safety, as well as to avoid material damage Information is highlighted and illustrated
as follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage
Indicates that property damage can result if the measures specified are
not taken
Important information about the product, please pay attention to avoid undesired result
Instructions and Warnings
The following hazard statements apply to this device
Disconnect or de-energize all external connections BEFORE opening this
device Contact with hazardous voltages and currents inside this device can cause electrical shock resulting in injury or death
Trang 6Contact with instrument terminals can cause electrical shock that can result in injury or death
Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment
Have only qualified personnel service this equipment If you are not qualified to service this equipment, you can injure yourself or others, or cause equipment damage
This device is shipped with default passwords Default passwords should
be changed to private passwords at installation Failure to change each default password to a private password may allow unauthorized access
NR shall not be responsible for any damage resulting from unauthorized access
DO NOT look into the fiber (laser) ports/connectors
DO NOT look into the end of an optical cable connected to an optical
output
DO NOT perform any procedures or adjustments that this instruction
manual does not describe
During installation, maintenance, or testing of the optical ports, ONLY use the test equipment qualified for Class 1 laser products!
Trang 7Incorporated components, such as LEDs, transceivers, and laser emitters,
are NOT user serviceable Return units to NR for repair or replacement
Equipment components are SENSITIVE to electrostatic discharge (ESD)
Undetectable permanent damage can result if you do not use proper ESD procedures Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment If your facility is not
equipped to work with these components, contact NR about returning this device and related NR equipment for service
Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables Please use the wiring method recommended in the manual for communication terminals
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power Equipment damage can result otherwise
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure
The firmware may be upgraded to add new features or enhance/modify
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand
Document Conventions
Trang 8 The abbreviations and acronyms in this manual are explained in “Appendix A Glossary” The
Glossary also contains definitions of important terms
Menu path is connected with the arrow "→" and bold
For example: the access path of protection settings is: MainMenu→Settings→Protection Settings
Settings not in the table should be placed in brackets
For example: the system setting [Opt_SysFreq]
Cross-references are presented in italics
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold
For example: press the button "ENT"
Trang 11An overview of each manual section and section topics follows
Trang 126 System Functions
Describes how to perform fundamental operations such as clock synchronization, communicating with the device, switching active setting group, checking relay status, reading event reports and SER (Sequential Events Recorder) records
Describes the abbreviations adopted in this manual
Document Revision History
PN: ZL_PCS-9671S_X_Technical Manual_EN_Overseas General_X
Current version: R1.11
Corresponding Version
Document Software
R1.00 R1.00 2019-10-25 Form the original manual
R1.10 R1.00 2019-12-09 Update of technical data
Trang 13R1.11 R1.11 2020-06-11
Update of technical data
Improved some description of 87T in Section 3.1
Added PWR plug-in module NR6311A
Added CPU plug-in module NR6106AH
Added CPU plug-in module NR6106AP
Added BIBO plug-in module NR6661A
Trang 15Figure 1.1-1 Two-winding transformer 1-1
Figure 1.1-2 Three-winding transformer 1-1
Figure 1.1-3 Typical application of a 3-winding transformer 1-2
Trang 171
1.1 Application
PCS-9671S can be applied for a two-winding transformer, three-winding transformer,
auto-transformer in any voltage level PCS-9671S provides the main protection elements, such as:
current differential protection and restricted earth fault protection Ancillary functions of fault
diagnostic, disturbance records, event records and communication function are integrated in the
device
PCS-9671S is adaptive to the following 2/3-winding transformers
Figure 1.1-1 Two-winding transformer
Figure 1.1-2 Three-winding transformer
The function diagrams for protecting a 3-winding transformer is shown below
Trang 1887T Transformer differential protection
Biased differential protection with three slopes
Biased DPFC differential protection
Unrestrained instantaneous differential protection
Optional inrush current distinguished principles: harmonic criterion or waveform distortion
Optional harmonic blocking modes: self-adaptive 1Pblk1P mode, 2PBlk3P mode, 1Pblk3P mode
Overexcitation detection: fifth harmonic or third harmonic criterion
Optional transfer methods: △→Y or Y→△
Independent CT saturation criterion
Differential CT circuit failure supervision
64REF Restricted earth-fault protection
CT transient characteristic difference detection
CT saturation detection based on 2 nd and 3 rd
harmonics
Trang 191
50/51P Phase overcurrent protection
2 stages with independent logic by default for each side
Optional definite-time characteristic and inverse-time characteristic for each stage
Trip purpose or alarm purpose for each stage
Harmonic control element for each stage
50/51G Earth fault protection
2 stages with independent logic by default for each side
Optional measured zero-sequence current or calculated zero-sequence current
Optional definite-time characteristic and inverse-time characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
Harmonic control element for each stage
2 Measurement and Metering Functions
Positive sequence currents, zero sequence currents and phase angles
3 Supervision Functions
CT circuit failure supervision (CTS)
Self-diagnostic
Powerful faults recording (max buffer for 10,000 sampled points at 4.8 or 9.6 kHz)
Event Recorder including 1024 disturbance records, 1024 binary events, 1024
supervision events, 256 control logs and 1024 device logs
Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
Single line diagram representation in display
4 Communication Functions
Support of various protocols
Modbus, DNP3.0, IEC 60870-5-103, IEC 61850 Ed.1 & Ed.2, IEC 61850 MMS Server,
IEC 61850-8-1 GOOSE, IEC 61850-9-2LE SV, IEC 62439 Parallel Redundancy Protocol
(PRP), IEC 62439 High-availability Seamless Ring (HSR) Redundancy Protocol, IEEE
802.1w Rapid Spanning Tree Protocol (RSTP)
Up to four 10Base-T/100Base-TX copper Ethernet ports
Up to four 100Base-FX optical Ethernet ports
Two RS-485 serial ports for communication or printer
One RS-485/TTL serial port for clock synchronization
Trang 20 4 Programmable operator pushbuttons with user-configurable labels
Up to 15 programmable target LEDs with user-configurable labels
1 RS-232 or RS-485 rear ports for printer
Language switchover—English+ selected language
Configuration tool—PCS-Studio
6 Additional Functions
User programmable logic
Switching system phase sequences function (ABC or ACB)
Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE 1588: Clock message based on IEEE 1588 via optical fibre interface
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
SNTP (BC): Broadcast SNTP mode via Ethernet network
Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol, Modbus protocol and DNP3.0 protocol
Trang 211
High reliability and redundancy design for drive systems of the sampling circuit and the output
circuit ensure that overall reliability of the device is high Real-time sampling based on dual AD
can mutually check and detect the potential abnormality in the sampling circuit in time The
control power supply of the output relay is independent with the control circuit of trigger signals,
which can prevent from undesired operation caused by the abnormality of drive circuit of
output relays
Various function modules can satisfy various situations according to the different requirements
of users Flexible and universal logic programming, user-defined configuration of BI/BOs,
buttons and LEDs and powerful analog programming are supported
Modularized hardware design makes the device be easily upgraded or repaired by a qualified
service person It can be mixed with different I/O modules, with online self-check and
monitoring function, and the device can be restored from abnormal operation only need to
replace a single abnormal module
Support memory check and error correction function, ensure high reliability and safety
Support the internet communication protocol of native PRP/HSR and RSTP
Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351
communication service, GOOSE communication in station level & process level, SV
communication with multi-sampling rate
Full comply with cyber security standards, including IEC62443, IEC62351, IEEE1686,
NERC-CIP, support role based access control (RBAC), security audit, security encryption
communication and security tool, improve the cyber security capability of devices
Powerful COMTRADE fault and disturbance recording function is supported The whole
recording time is automatically configurable by the fault duration, which is convenient to fault
analysis and replay The recording sample rate is up to 9.6kHz
Settable secondary rated current (1A/5A) and settable voltage threshold of binary input
Support LCD, control and multifunction button
Support flush mounting, semi-flush mounting, surface mounting, wall mounting and other
mounting methods
Cross screw IO, CT/VT terminals can support AWG12 specification connector and 4mm2 lead
Protection class of front side is up to IP54
PCS-Studio is the application software on the user's PC for the interface with PCS S series
devices providing all the related functionality It ranges from device configuration to full
substation design of bay integration
Support IEEE1588, IRIG-B clock synchronization
Support actual system phase sequence, either ABC or ACB, incorrect connection of actual
phase sequence can automatically be verified and relevant protection functions can be
blocked
Trang 221
Equipped with high-speed large capacity output relay, its operation speed is less than 1ms and its break capacity is up to 10A The real-time supervision for output drive circuit can detect the abnormality in advance
Support setup up to 40 users and allow each user to own different password and access authority
The tripping output contacts can be configured by tripping matrix, which is flexible, convenient and suitable to any mode of tripping
Multiple inrush current blocking options are provided Self-adaptive inrush current blocking criterion can ensure the relay fast operation for transformer energized on to a slight fault, meanwhile it will avoid the unwanted operation in the case of the energization inrush current caused by energizing transformer with no load, the recovery inrush current caused by cutting off the transformer external fault, and the sympathetic inrush current
Biased DPFC differential protection is regardless of load current and is sensitive to small internal fault current within the transformer Its anti CT saturation performance is also strong
Trang 232.4.2 Copper Ethernet Port 2-5
2.4.3 Optical Fibre Port 2-6
Trang 242
2.10.1 Clock Performance 2-11 2.10.2 Fault and Disturbance Recording 2-11 2.10.3 Binary Input Signal 2-11
2.11 Protective Functions 2-11
2.11.1 Transformer Current Differential Protection (87T) 2-11 2.11.2 Restricted Earth Fault Protection (64REF) 2-12 2.11.3 Phase Overcurrent Protection (50/51P) 2-12 2.11.4 Earth Fault Overcurrent Protection (50/51G) 2-13
Trang 252
2.1 Electrical Specifications
“System phase sequence”, which can be set by PCS-Studio, this setting
informs the device of the actual system phase sequence, either ABC or ACB CT inputs on the device, labeled as A, B and C, must be connected
to system phase A, B and C for correct operation
Burden <0.05VA/phase @1A, <0.25VA/phase @5A
2.1.2 Power Supply
Standard
IEC 61000-4-11:2017 IEC 61000-4-29:2000
Permissible AC ripple voltage Max 15% of the nominal auxiliary voltage
Burden Quiescent condition Max 15W (default hardware configuration)
Trang 26Quiescent condition Max 1W
Additional for each contact
0.004W @24Vdc 0.008W @48Vdc 0.015W @110Vdc 0.32W @220Vdc 0.41W @250Vdc
Additional for each plug-in binary output (BO) module
Quiescent condition Max 0.1W
Additional for each relay while
2.1.3 Binary Input
Settable pickup voltage and dropout voltage
On value (default set) 69.3~132Vdc 78.75~160Vdc 138.6~264Vdc 157.5~300Vdc
Off value (default set) <55Vdc <62.5Vdc <110Vdc <125Vdc
Maximum permissible voltage 300Vdc
Withstand voltage 2000Vac, 2800Vdc (1min)
Number Up to 34 (ring ferrule), 41 (pin ferrule) binary inputs
Settable pickup voltage and dropout voltage
Maximum permissible voltage 300Vac
Withstand voltage 2000Vac, 2800Vdc (1min)
Number Up to 34 (ring ferrule), 41 (pin ferrule) binary inputs
Settable pickup voltage and dropout voltage
Trang 272
Maximum permissible voltage 300Vdc
Withstand voltage 2000Vac, 2800Vdc (1min)
Number Up to 34 (ring ferrule), 41 (pin ferrule) binary inputs
2.1.4 Binary Output
Tripping/signaling contact
Max system voltage 250Vac, 300Vdc
Pickup time (Typical value) <5ms
Dropout time (Resistive load) <6ms
Breaking capacity (L/R=40ms)
0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc
Cyclic capacity (2.5 cycle/second,
L/R=40ms)
0.5A@48Vdc 0.35A@110Vdc 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc
Short duration current
30A@3s 50A@1s Durability (Loaded contact) 10000 operations
Number Up to 18 (ring ferrule), 22 (pin ferrule) tripping/signal contacts
Trang 282
Heavy-capacity tripping contact
MOV protection (Max voltage) 350Vdc, 275Vac
Pickup time (Typical value) <1ms
Dropout time (Resistive load) <10ms
Breaking capacity (L/R=40ms)
10A@48V 10A@110V 10A@125V 10A@250V
Cyclic capacity (4 cycle/second,
followed by 2 minutes idle for thermal
dissipation)
10A@48V L/R=40ms 10A@110V L/R=40ms 10A@125V L/R=40ms 10A@250V L/R=20ms
Short duration current
30A@3s 50A@1s Durability (Loaded contact) 10000 operations
Number Up to 4 (ring ferrule) heavy-capacity tripping contacts
2.2 Mechanical Specifications
Weight per device Approx 7.36kg (6U, 1/3 × 19")
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated front plate
Protection Class
Front side
IP52 IP54 (valid for surface mounting mode of 6U, 1/3 × 19'' case with
Trang 292
sealing strip)
Rear side, connection terminals IP20
2.3 Ambient Temperature and Humidity Range
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Max transmission distance 500m
Twisted pair Screened twisted pair cable
2.4.2 Copper Ethernet Port
Transmission standard 100Base-TX
Transmission distance Max.100m
Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850
Trang 302
2.4.3 Optical Fibre Port
Characteristic Glass optical fiber
Transmission standard 100Base-FX
Transmission distance Max 2km
2.4.4 Print Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
2.4.5 Clock Synchronization Port
Trang 312
Characteristic Glass optical fiber
Peak optical input power
Logic level HIGH
Logic level LOW
Maximum -40dBm Maximum -10dBm, Minimum -24dBm
2.5 Type Tests
2.5.1 Environmental Tests
Damp heat test, cyclic IEC60068-2-30:2005
2.5.2 Mechanical Tests
Shock and bump IEC 60255-21-2:1988 Class Ⅰ
2.5.3 Electrical Tests
Dielectric tests Test voltage 2kV, 50Hz, 1min
Impulse voltage tests Test voltage 5kV
Trang 322
Electrostatic discharge test
IEC 61000-4-2-2008 class Ⅳ For contact discharge: 8kV For air discharge: 15kV
Radio frequency interference tests
IEC 60255-26:2013 class Ⅲ Frequency sweep
Radiated amplitude-modulated 10V/m (rms), f=80~1000MHz, 1400~2700MHz Spot frequency
Radiated amplitude-modulated 10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Fast transient disturbance tests
IEC 60255-26:2013 Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns
Surge immunity test
IEC 60255-26:2013 Power supply, AC input, I/O port: class Ⅳ, 1.2/50us Common mode: 4kV
Differential mode: 2kV
Conducted RF electromagnetic
disturbance
IEC 60255-26:2013 Power supply, AC, I/O, Comm Terminal: Class Ⅲ , 10V (rms), 150kHz~80MHz
Spot frequency 10V (rms), f=27MHz/68MHz Power frequency magnetic field
Immunity
IEC 61000-4-8: 2009 class Ⅴ, 100A/m for 1min, 1000A/m for 3s
Pulse magnetic field immunity
IEC 61000-4-9:2016 class Ⅴ, 6.4/16μs, 1000A/m for 3s Damped oscillatory magnetic field
immunity
IEC 61000-4-10:2016 class Ⅴ, 100kHz & 1MHz–100A/m Conducted emission IEC 60255-26:2013
Trang 33230MHz~1000MHz: 47dB (μV/m) quasi peak @10m, 57dB (μV/m) quasi peak @3m
Above 1GHz
1GHz~3GHz: 56dB (μV/m) average, 76dB (μV/m) peak @3m
3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m) peak @3m
Auxiliary power supply performance
50ms for interruption without rebooting without energy storage board (Typical configuration) 500ms for interruption without rebooting with energy storage board (Typical configuration)
EMC: 2014/30/EU, EN60255-26:2013
Products safety (LVD): 2014/35/EU, EN60255-27:2014
IEC 61850: Edition 2, Parts 6, 7-1, 7-2, 7-3,7-4 and 8-1
IEC 61850: Edition 2, GOOSE Performance Class P1 (3ms)
Trang 342
IEEE 1588: IEEE Std C37.238TM-2017
DNP: DNP 3.0
PRP: IEC 62439-3 Ed.3 (IS 2016)
HSR: IEC 62439-3 Ed.3 (IS 2016)
2.7 Liquid Crystal Display (LCD)
2.8 Terminals
2.8.1 Ring Ferrule
Grounding (Earthing) Connection BVR type, 0.8~4mm 2 lead M3 0.6~0.8 N·m
2.8.2 Pin Ferrule
Power supply Screw terminals, 0.3~3.3mm 2 lead M2.5 0.4~0.6 N·m Contact I/O Screw terminals, 0.3~3.3mm 2 lead M2.5 0.4~0.6 N·m
2.9 Measurement Scope and Accuracy
Trang 35External time synchronization IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol
2.10.2 Fault and Disturbance Recording
Duration & Recording position
Settable pre-disturbance, post-disturbance and maximum recorded duration
2.10.3 Binary Input Signal
Resolution of binary input signal ≤1ms
Binary input mode Potential-free contact
2.11 Protective Functions
There are some symbols mentioned in the following sections and the meaning of them is given
here
In——CT rated secondary current
p.u.——per unit value of settings and currents for current differential protection
Id——differential current
3I0d——residual differential current
ΔId——DPFC differential current
2.11.1 Transformer Current Differential Protection (87T)
2.11.1.1 Biased Differential Protection
Tolerance of 2 nd and 3 rd harmonic settings 0.01
Tolerance of 5 th harmonic settings 0.02
Tolerance of operating current ≤5% of operating current or 0.02p.u., whichever is greater
Operating time (without blocking criteria) 50Hz: ≤ 30ms (Id>2 times current setting, internal fault)
Trang 362
60Hz: ≤ 25ms (Id>2 times current setting, internal fault)
2.11.1.2 Instantaneous Differential Protection
Tolerance of current setting ≤2.5% of setting or 0.02p.u., whichever is greater
2.11.1.3 DPFC Current Differential Protection
Tolerance of operating current ≤10%
Operating time
50Hz: ≤30ms (ΔId >3 times current setting (the current setting is fixed as 0.2p.u in program), internal fault) 60Hz: ≤30ms (ΔId >3 times current setting (the current setting is fixed as 0.2p.u in program), internal fault)
2.11.2 Restricted Earth Fault Protection (64REF)
Tolerance of operating current ≤5% of operating current or 0.02×In, whichever is greater
2.11.3 Phase Overcurrent Protection (50/51P)
Tolerance of current setting ≤1%×setting or 0.01×In, whichever is greater
Trang 372
Tolerance of pickup time ≤25ms (at 2 times current setting)
Tolerance of operating time
Definite-time: ≤1%×setting or 25ms (at 2 times current setting)
Inverse-time: ≤ 5 % of the calculated value + 1 % of current tolerance, or 35ms (1.2≤I/Ip≤30)
Reset time
Definite-time: ≤1%×setting or 30ms Inverse-time: ≤5% of the calculated value or 30ms
2.11.4 Earth Fault Overcurrent Protection (50/51G)
Tolerance of current setting ≤1%×setting or 0.01×In, whichever is greater
Tolerance of pickup time ≤25ms (at 2 times current setting)
Tolerance of operating time
Definite-time: ≤1%×setting or 25ms (at 2 times current setting)
Inverse-time: ≤ 5 % of the calculated value + 1 % of current tolerance, or 35ms(1.2≤I/Ip≤30)
Reset time
Definite-time: ≤1%×setting or 30ms Inverse-time: ≤5% of the calculated value or 30ms
Trang 403
3.5.2 I/O Signals 3-59 3.5.3 Settings 3-59
List of Figures
Figure 3.1-1 Current compensation calculation process 3-7 Figure 3.1-2 Operation characteristic of sensitive biased differential element 3-9 Figure 3.1-3 Operation characteristic of conventional biased differential element 3-10 Figure 3.1-4 Operation characteristic of biased/instantaneous differential elements 3-11 Figure 3.1-5 Operation characteristic of DPFC biased differential protection 3-14 Figure 3.1-6 Schematic of waveform symmetry principle 3-16 Figure 3.1-7 Logic of inrush current blocking current differential protection 3-19 Figure 3.1-8 Logic of enabling transformer differential protection 3-25 Figure 3.1-9 Pickup logic of transformer differential protection 3-25 Figure 3.1-10 Logic diagram of instantaneous differential element 3-25 Figure 3.1-11 Logic diagram of biased differential element 3-26 Figure 3.1-12 Logic diagram of DPFC biased differential element 3-26 Figure 3.1-13 Logic diagram of CT circuit failure alarm 3-26 Figure 3.2-1 Application for two-winding transformer with one CB at one side 3-29 Figure 3.2-2 Application for two-winding transformer with two CBs at one side 3-29 Figure 3.2-3 Application for auto-transformer 3-29 Figure 3.2-4 REF principle 3-32 Figure 3.2-5 Operation characteristic of REF 3-33 Figure 3.2-6 Logic of enabling restricted earth fault protection 3-36 Figure 3.2-7 Pickup logic of restricted earth fault protection 3-36 Figure 3.2-8 Logic diagram of restricted earth fault protection 3-36 Figure 3.3-1 Logic of enabling phase overcurrent protection 3-38 Figure 3.3-2 Pickup logic of phase overcurrent protection 3-38 Figure 3.3-3 Logic of harmonic control element 3-39 Figure 3.3-4 Definite-time operating curve of phase overcurrent protection 3-40 Figure 3.3-5 Inverse-time operating curve of phase overcurrent protection 3-41