INTRODUCTION This basic design report has been prepared on the basis of identifying the criteria, assumptions, design data, feasible structural options and design approach for the selec
Trang 1HOI AN SOUTH DEVELOPMENT LIMITED
NKC CONSULTANCY CO LTD
NOVEMBER 2017
Trang 2STRUCTURAL BASIC
DESIGN REPORT
STRUCTURAL, INFRASTRUCTURE &
MEPF DESIGN SERVICES
Email: consulting.engineer@nkc.com.vn
Approved by:
Dr Vinh Tran – Chairman Date: 11 / 2017
Trang 3
INVESTOR
HOI AN SOUTH DEVELOPMENT LIMITED
Duy Hai Commune – Duy Xuyen District
Quang Nam Province
GENERAL DIRECTOR
CONSULTANT
STRUCTURAL, INFRASTRUCTURE &
MEPF DESIGN SERVICES
A1-00.01 Complex M1,
74 Nguyen Co Thach, An Loi Dong Ward,
District 2, Ho Chi Minh City Tel:+(84.8) 3744 6801; Fax:+(84.8) 3744 6851
Email:consulting.engineer@nkc.com.vn
Website:www.nkc.com.vn
CHAIRMAN
Dr VINH TRAN
Trang 4
SUMMARY OF ISSUES
Trang 6
APPENDICES
APPENDIX E TYPICAL PILE CAP DESIGN
APPENDIX F TYPICAL TIE BEAM DESIGN
APPENDIX G TYPICAL FLOOR SLAB DESIGN
Trang 7
1 INTRODUCTION
This basic design report has been prepared on the basis of identifying the criteria, assumptions, design data, feasible structural options and design approach for the selection of the optimum option for the development of next phase of the project
2 THE PROJECT
2.1 Project Description
This project is titled as “Staff Village”, located in Duy Hai Commune, Duy Xuyen District, Quang Nam Province, Viet Nam The development consists of 6 tower in which 2 towers have 8 storeys, 4 towers having 9 storeys, and a two-storey main building for administration and facilities
2.2 Partners
Design & Build Contractor Cofico Construction Joint Stock Company No 1 C&S and MEP Consultant NKC Consultancy Co Ltd
3 STANDARDS FOR STRUCTURAL DESIGN
3.1 Applicable Codes and Standards
The project shall be designed based on Vietnamese standards for all structural elements except columns and core wall are designed based on Eurocodes standards
Structural Design Standards
Standards For Design of Reinforcement Concrete Structures TCVN 5574: 2012 Piled Foundations – Vietnamese Design Standard TCVN 10304 : 2014
3.2 Computer Programs
The following computer programs will be used for the analysis and design of the structure:
ETABS Version 13.1.2 Analysis of general space structure
SAFE Version 12.3.1 Analysis and Design of foundation
PLAXIS Version 8.0 Analysis and Design of diaphragm wall
Excel spread sheet Design of reinforced concrete elements
ADSEC Version 8.0 Design of reinforcement for columns/ walls
4 GEOTECHNICAL DATA
4.1 Introduction
This report establishes the general basis for the geotechnical design of the project
The design criteria, design assumptions, design data and analysis methodology for the geotechnical design of the project is identified This report will form part of the guideline and control document for the detailed design and analysis of the porject which will be developed later on
Trang 8
4.2 Borehole Location Plan
Total of 5 boreholes In which, the boreholes CBH20 to CBH24 are depth 80m, it is necessary for the extraction of soil samples and execution of tests
4.2.1 Borehole Log
Summary below is the illustrated composition of the borehole log CBH20 to CBH24 as recorded in the Soil Investigation Report prepared by South Branch of Vietnam Institute for Building Science and Technology untertaken in September 2016
BOREHOLE LOG LOCATION LAYOUT
Trang 9
BOREHOLE LOG SECTION CBH20 TO CBH24
Trang 104.2.4 Geotechincal Parameters
The principle geotechnical parameters considered most appropriate for use in the geotechnical
design of this project are summarised in Table below
Trang 12
5 FOUNDATION DESIGN
5.1 Proposed Foundations
The proposed foundation systems is the precast prestressed circular piles with the diameter of 400mm
to provide the support for the lift core walls and the columns/shear walls of the buildings
The isolated columns/ shear walls of the building are supported by isolated pile caps with 2 or more piles The isolated pile caps are connected and stabilised by the orthogonal tie beams system
Loading from the upper floors are transferred to the columns/shear walls and the walls systems, from wihich they are in turn transferred down to the pile caps and hence to the ground via the friction and end bearing capacities of the piles
Trang 13
PILE CAPS AND TIE BEAMS LAYOUT
7 9' 9 10 11 11' 12 13 14 15
8
Trang 14
3D PILE CAP MODEL
5.2 Design Limit states
Piles and foundations shall be based on two limit states, namely Limit states 1 and 2 as below:
Limit State 1: includes calculations
+ Ultimate capacity of pile follow soild strength
+ Ultimate Capacity of pile and pile cap follow pile material
+ Stability of bored pile and pile cap
Basic load combination and special load combination (seimic load, wind load ) shall be applied in Limit sate 1
Limit State 2: includes calculations
+ Settlements of bored pile and foundation
+ Transverse displacement of pile and foundation
+ Formation and development crack of pile and pile cap
Basic load combination and service load combination shall be applied in limit state 2
5.3 Design Methodology
The design methodology used to determination of the load capacity of the bored piles and
diaphragm wall panels will be based on Vietnamese Standard TCVN 10304: 2014 The site
supervision work, control the entire construction process and workmanship have also been
addressed in the design
5.4 Analysis of Differential Settlement
Differential settlement has often caused damages to the structures and the remedial works have often mounted to very figures and difficulties Therefore estimation and overcome the possibility of differential settlement is necessary rightaway during the design period Differential settlement can be overcome by the following methods:
Foundations must be appropriately designed to ensure the settlements of the foundations are comparable
Trang 15
Relatively even distribution of building weight on plan
Use deep foundation technique to transfer loads into the good soil layers, this would minimise the foundation settlements
Design of the superstructure to be flexible in order to cater for certain amount of differential settlement, if occurs
Provide additional reinforcement at locations where the differential settlement is likely to occur
Trang 167 9' 9 10 11 11' 12 13 14 15
8
Trang 17
6 LATERAL STABILITY SYSTEM - COLUMNS / STAIR WALLS
Lateral stability of the building is provided by a Columns–Stair walls System The system consists of reinforced concrete stair walls and columns which are mostly located on orthogonal axes The stair walls are located around the staircase shafts to form the end-core system and the columns are located around the perimeter and along the central corridor of the building Refer to relevant structural drawings for further details In order to optimise the design, columns/walls are designed such that their sizes reducing with height, however the ease of construction dictates that there should be many changes in columns/walls dimensions within the building, therefore the columns/ walls are arranged into zones, within each zone the columns/walls sizes are unchanged
Stair walls are linked by spandrel beams, which are arranged above the location of door openings Spandrel beams are very important in terms of distribution of forces between the walls The size of spandrel beams must be arranged such that to be appropriate with architectural and services system’s requirements
7 SUPERSTRUCTURE DESIGN
7.1 Level 1 Floor to Roof
Based on the architectural drawings in terms of layout and spacing between columns, the structural system for the ground floors is traditional reinforced concrete beam/ slab system This floor consists of pile caps having depth of 1000mm, tie beams having dimensions of 500X700mm The slab thickness is 200mm sitting on top of 100mm blinding concrete
Dead load and live load from the floors above will be transmitted to the stair walls and columns system This vertical structural system is mainly reinforced concrete structure will in turn transmit the floor loading
to the foundations
Finishes inside the ground floor, in general, to be 50mm for the floors and the toilet areas, a step down
of 50mm is provided in the toilet areas
General arrangement of a typical floor for level 2 to roof is shown as below.General arrangement of a typical ground floor is shown as below
Floor Level (FFL)
Floor height Column size Core wall
Trang 187 9' 9 10 11 11' 12 13 14 15
8
Trang 197 9' 9 10 11 11' 12 13 14 15
8
Trang 207 9' 9 10 11 11' 12 13 14 15
8
Trang 218 STRUCTURAL DESIGN DATA
8.1 Design Loadings
8.1.1 Gravity load
The dead load which includes the self-weight of the structure and super imposed dead load (finishes,
partition and services) will be assessed based on the Architect’s specification
8.1.2 Live Load and Finishes
Based on TCVN 2737: 1995 and tabulated in details in Appendix B for each area based on functional
requirements
Live load reduction
Live Loads on Horizontal Elements
For load items 1-5 in Table 3 of TCVN 2737, live load on horizontal elements, such as floor slabs main
and secondary beams, may be reduced by a factor below:
1 1
6 0 4 0
A / A
.
A > A2 = 36m2)
2 2
5 0 5 0
A / A
.
For load items 1-5 in Table 3 of TCVN 2737, live load on vertical elements, such as columns and
walls, and foundation may be reduced by a factor below:
Trang 228.1.3 Effect of Temperature Changes
Thermal Coefficient of concrete: 1.0x10-5/ oC
Change in outside temperature: 15 oC
The effect of temperature changes can be directly analysed by Etabs computer program via the
material properties, and can be disregarded for this building
8.1.4 Wind load
Wind load to be calculated based on:
TCVN 2737 -1995: Design loadings and Impacts
TCXD 229 - 1999: Guideline for the calculation of the Dynamic Component of the Wind Loads
Wind Load = Wind Coeff x Design Wind Pressure x Frontal area Based on TCVN 2737, wind load consist of two components, namely static and dynamic The
derivation of these two components are illustrated below:
Static Component:
The standard value of the static component of wind load W at height Z from the base level is
determined from the following formula:
w = wo x k x c
in which:
wo - Values of wind load determined from the zoning map in Appendices D, E and F of TCVN
2737 The value of Duy Xuyen District, Quang Nam province is taken as 0.95 kPa (category B) as in Table 4 of TCVN 2737.
II-k - Coefficient involving changes in height of wind pressure as stipulated in Table 5 of TCVN 2737
(Terrain type: A- Open terrain, with no onstructions higher than 1.5m (coasts, large fields without plants, lake surfaces, etc.)
c - Coefficient for aerodynamic effect as derived in Table 6 of TCVN 2737 and is taken as 1.4.
Trang 23Dynamic Component:
Dynamic component of wind load have to be included in the wind load calculation where the building
exceeds the 40m in high (Cl 6.2 of TCVN 2737) In addition, for high rise and slender structures,
aerodynamic instability has to be checked
Limit value of vibration frequency f1 (Table 9 of TCVN 2737)
f1 = 0.3 (RC structure)
fL = 1.3Hz (Wind pressure zone II)
Where frequency of fundamental mode f1 is less than the limit value of vibration frequency fL (Cl 6.13.3
of TCVN 2737):
Wp(ji) = Wj x ξi x i x yji Where:
Mj - Concentrated mass of the jth floor of the structure, tonnes;
ξi - Dynamic coefficient corresponding to the ith mode of vibration and the parameter derived from
Figure 2 of TCVN 2737;
γ - Reliability coefficient of wind load;
Wo – Wind pressure (N/mm2)
f1 – Frequency of the fundamental mode of vibration
yji – Transverse displacement of the centre of gravity of the jth floor diaphragm of ith mode of
vibration;
WFj - Standard value of the dynamic component of the wind load on the jth floor, corresponding to
different modes of vibration, kN:
WFj = Wj x ξi x ξj x
- For the first mode of vibration, = 1, whilst for other modes of vibration, = 1;
Sj - Windward area of jth floor (m2);
ξi - Dynamic pressure coefficient at height Z from the base level as stipulated in Table 8 of TCVN
2737.
For detailed provisions of the ablove calculation procedure, refer to Cl 4.3 to 4.5 of TCXD 299: 1999
The corrective coefficient for building structures with a design life of 100 years is taken as 1.37 in
accordance with Table 4.3 of QC 02: 2009
Combination of the Static and Dynamic components
The internal forces and displacements derived according to the above procedures shall be combined
in accordance with the following formula (Cl 4.12 of TCXD 229):
Trang 24Where:
X - moment, shear force, axial force and displacement;
X1 - moment, shear froce, axial force and displacement inducd by the static component of the wind
load;
moment, shear force, axial force and displacement induced by the dynamic component of the wind load in the ith mode of vibration;
s - number of modes of vibration
Coefficient of correction for design life more than 100 years has been taken as 1.37 as below
(according to QC 02: 2009 BXD)
8.1.4.1 Displacement Limitation at Top of Building
Requires for the column/wall system, the maximum displacement at the top of the building is H/500,
where H is the building height
Total displacement at the top of the building from the analysis model:
Since f < [ f ] Satisfy the displacement limitation at top
8.1.4.2 Storey Drift Limitation
Storey Drift Limitation = dr/hs ≤ 1/500 (Clause C5.4 – TCVN 5574: 2012)
in which h is the floor height
Tables below shows the comparison between actual calculated storey drifts for various storey heights:
Trang 25
Story Load Point Item Drift (dr/hs) X (mm) Y Z Check
Trang 26Story Load Point Item Drift (dr/hs) X (mm) Y Z Check
Trang 27Story Load Point Item Drift (dr/hs) X (mm) Y Z Check
Trang 28Story Load Point Item Drift (dr/hs) X (mm) Y Z Check
Trang 298.1.5 Seismic load
Seismic design based on TCVN 9386: 2012
From Appendix H, peak ground acceleration: agR = 0.0263g (Duy Xuyen District, Quang Nam
Province)
Extract from TCVN9386-2012 below indicate that in the vicinity of the staff village site the ground
acceleration is less than 0.04g, therefor, there is no need to design the structure subjected to seismic
8.1.6 Structural Data Check
8.1.6.1 Overturning Stability Check
Coefficient of safety against overturning FoS = Mr / M over > 1.5 (TCXD 198: 1997 Clause 2.6.3)
Stabilising Moment Mr
Overturning Moment M over
Table calculates overturning stability about axes X& Y:
Calculation of Stability against wind
Factor of safety against overturning
FoS = Mr / M over = 5680411 / 29334 = 193.64 > 1.5 OK
Factor of safety against overturning
Moment overturning Direction OX (KNm) Story
Floor
elevation
(m)
Story height (m)
Dead Load (KN)
X Centre of Mass (m)
1 Story Cumulative 1 Story Cumulative
(KN)
Moment overturning Direction OY (KNm) Story
Floor
elevation
(m)
Story height (m)
Dead Load (KN)
Y Centre of Mass (m) dx (m)
Trang 30FoS = Mr / M over = 1207942 / 133865 = 9.02 > 1.5 OK
LOCATION OF CENTRE OF MASS
8.1.7 Summary of Design Criteria
Stability against
overturing Wind–Y: Coef of Safety = 9.02
> 1.5 (TCXD 198: 1997 Item 2.6.3)
Storey drift due to
Period
Mode 1, T = 1.906s, i.e f = 0.525 Hz Mode 2, T = 1.496s, i.e f = 0.668 Hz Mode 3, T = 1.169s, i.e f = 0.855 Hz
Trang 318.2.2 Reinforcement
Reinforcement will be either hot rolled high yield or mild steel to Vietnamese strandard
Locally produced based on JIS G 3112 – 1991 or equivalent quality:
High yield steel CB500
fy = 500 N/mm² (10 < đường kính <= 18 mm), ký hiệu T Mild steel CB250
fy = 250 N/mm² (đường kính <= 10 mm), ký hiệu R
8.2.3 Concrete cover
Fire Resistance Period (FRP) will be referred to the architectural drawings and the design of structural
elements will ensure that sufficient concrete cover will be provided to meet the required FRP The cover
the the outermost reinforcing bars are shown on Table below:
Concrete cover to the edge of the main rebar(mm) (Based on section, 5.3, 5.4 of EN1992: 2004 and Appendix F of QCVN 06: 2010/BXD)
Trang 32Minimum cover to reinforcement shall be the values as shown in the above table or the bar diameter
whichever is the greater one
Minimum cover to reinforcement of element cast directly against soil to be 50mm
Cover to bottom reinforcement of pile cap to be 100mm
Minimum cover to reinforcement of water tank element or watertight construction to be 40mm
8.3 Load cases and load combinations
The following load cases and load combinations shall be used for the design of structural elements:
SDL: Super Dead load
LL: Live load all level except commercial carpark area
LL1: Live load apply for commercial carpark area
Wx Wind load in X-direction
Wxx Wind load in –X-direction
Wy Wind load in Y-direction
Wyy Wind load in –Y-direction
8.4 Load combinations
8.4.1 Load combinations for columns/ walls
EN 1992:
2004 Eurocode – Basis of Structural Design
Trang 338.4.2 Load Combinations for other elements
Combinations of forces for the design other elements such as beams, slabs, pile caps, pile reactions
and pile reinforcement
TCVN 2737:1995
Trang 34APPENDIX A - BUILDING STOREY PARAMETERS
Floor Level (FFL)
thickness
Finishes Structural
Slab Level (SSL)
Column size wall Thick Core wall
Trang 35APPENDIX B - FLOOR LOADING
Khu vực / Area Cấu tạo / Structure
Dày / thickness (mm)
Tĩnh Tải / Dead load (KN/m 2 )
Hoạt Tải / Live Load (KN/m 2 )
Trần treo / Hanging Ceiling
Trần treo / Hanging Ceiling
TẢI TƯỜNG - WALL LOADING
Tường xây 100 / Wall 100 THK
Tường xây 200 / Wall 200 THK
1.803.60
Trang 36APPENDIX C - 3D ANALYSIS MODEL
Trang 37APPENDIX D - WIND LOADING
Trang 39APPENDIX E - TYPICAL PILE CAP DESIGN
Trang 40LEVEL 1 FLOOR PLAN