We cannOI reOOce lhe Firing Rate Control pressure drop pasr our minimum estimated fi\}Jre of 30 percent of the mani 11·97558·1... It we haY'6 5 Regulator Outlet Pressure - Piping Pressu
Trang 1c It point X 1a/(s only a very short disTance to the right
of the diaoonal line, increasing the pressure drop
might allow use of the next smaller valve size
mated lotal pressure drop over bolh SSOVs
5% of 12.0 = O.S in we
To determine lhe extra pressure drop, move upward
to the Pressure Drop Scale fo find the pressure drop
needed for a 2 inch valve In this case, the actual pressure
293
6.4 - 5.4 = 1.0 in we
Using a 2 inch varve may still be p::>ssitJle The actual
wc The diHerence between the eslimatad and actual
manifold to keep the required burner inlet pressure We cannOI reOOce lhe Firing Rate Control pressure drop pasr our minimum estimated fi\}Jre of 30 percent of the mani
11·97558·1
Trang 2FIG 8- PRESSURE DROP VS CAPACI'N FOR A 'NPICAl BUlTERFlY VALVE MAXIMUM OPENING
ANGLES SHOWN 'ARE USEO AS TRIAL SETTINGS WHEN AOJUSTING VALVES FOR HtGH FIRE
sure regul!'llor oullel pre,ssure by O~ in \Of<: to allow for the
additional pressure drcp across the 2 inch SSQVs
pressure regulator SSOVs and Firing Rate Control, plus
repealing the sizing procedure
SIZING CHART FOR FIRING RATE
CONTROL VALVE
Valves SinCe a Butterfly Valve ctleS no! provide light clo
l4)slream
In our ellample the eslimaleO pressure drq:J across the
liring rate control is 6.5 inches wC wilh a capaCity of 10,500
cfh at standard conditions
a If SSOV estimaled <md actual pressure drop are lha
fly Valve pressure drq:J and capacity, X on Fig 8 Use Ihe valve size and opening angle indicaled IYy lhe nearest slanted line below X In this case, ar;ply·
malad pressure droo
Add lhe pressure drq:J difference (0.8 inch we) to the pressure Orq:J available for the Bullerlly Valve 0.8 + 6.5 '" 7.3 in we
y,
nearest slanteO line below In lhis case, we have a 2 inch valve with a 40 degree opening
Trang 3V5055 VALVE SIZING NOMOGRAPH
Non, II ",,",.1 ' "1'0.,10< " " 0."1 ,,~ o J Dr I G) ''0'" ··C~" ~ '0
,k'Q , , _ on• •nd , ' " "t ,~ .1'r " D'QQ·· c -" _, I,.," ,.<h "" '0
0 ',n 0 ',,,,,,.I,, _ ··S «'« <;",,' II_ )-l"
r:o, ',Qn" '0 ' ""'d "Clh G_ fh :· Dr I;., ~ ''0"' "B.,n", Clh," 'h,,,,,"
D.,.,,,,,, 'J) ,.Q ·" .<,(OO.~.,,'"'··O' '"_ , "oeM 01 101 " d I,,,, @ , 1
So ,'· _ _ "",n' "II, bo,_.n , , .>0 ,i,,,.
, _ '~"""'''Q_ aI t,"" (!)
·· C",·· ,.t ,'h' t" ,
The correct size V505 5 Industrial Gas Valve can be
quiCkly selected usinog this nomograph The nomograph is
available in pads at 25 under form number 70-86.27
Valve Sizing Char1
2 Valves Piped in Series
295
For this chart, we need to know the inlel and outlet pressure for the V5055
1 Determine inlet pressure for V5055 When 2 valves are
2 we see thai the V5055 inlel pressure equalS the pres
sure regulator oullet pressure less lhe piping pressure loss from the pressure regulator outlet to the V5Q55 il'lIe! Find the piping lOSS flQJre tram Fig 3 It we haY'6 5
Regulator Outlet Pressure - Piping Pressure Drcp
pressure equals lhe inlel pressure minus the pressure drcp across the valve
71·97558-1
Trang 4"
, ,
NOTE: Since we calculated the corrected capacity
lines 1 and 2 In lhe 1,'5055 Valve Sizif'l;l Chart
direcllol"6
inches we by (he conversion 1aclor1rom IheAPPENPIX
10 gel the correct psi unl!
14.6 )( 0.0361 = .527 pst
4 Draw line 4 trom 10,370 cfh on the Burner CFH Gas
3, fa the valve site scale 12 inches)
EXAMPLE 2
Determine the 1,'5055 Valve sizQ from lhis job's
5j:lElciflcat ions:
Inlel Pressure Available at 1,'5055 13 Inches wC
Eslimated Pressure Drop
Trang 5••
SOLUTION
calculate cfh required
Gas Flow." This is the adjuslecl gas 110w
3 Draw line 31rom I) inches we on Outlet Pressure scale
107 inches we on the Pressure Droo scale Since the
units
6 In we )( 0.0361 '" .216 psi
Trang 6CONVERSION TO STAHDARD CONDITIONS
STANDARD CONDITIONS
-"'061 valve sizing charts provide coordinates under a
corditlons are:
1 Capacity - cubiC; feel per hour lcfh) ConverSion 10r
CONVERT CAPACITY TO 0.64 SPECIFIC GRAVITY
valve
These condilionsare seldom fOUnd on an actual job To use the valve sizing charts, we must convert the jd:l condi· lions in this BKample to the equivalent cfh gas rating under the standard conditions
CONVERT CAPACITY IN BTUH TO CFH
CftJ =
Btu/cu
CONVERT CAPACITY TO 0.64 SPECIFIC GRAVITY
HOW TO USE CHART
Listed valve·capaciTy ratino;:; ~re based on O.6'llp gr 9U W})en the required cfh ""pa";I~ is kncwn (or 911 of other
specific <:IfavitY it can be convened to the 0.64 'p g< tQw~al~nt by use of correcl multiplying faclor Obtained from
this charI Example; A nfve capacity of 2670 cfh blwd on 0.72 lp <:If gax is ~C1ui~d_ Whit valve capacity based on
0.64 sP \IT ","S will be nlCluved? Solution: On wrtSul sc.&Ie of chart find 0.72 sp gr From that point, move horitonlillly
10 ri'ilhl 10 intenecl the cUJVe; lhen move Itn.ighl down 10 bottom seale and !ud lhe conversion factor, 1.06
Mwtiply the 2670 cfh by the conve";"n factor: 2670 dh" 1.06 = 2830 d'h
When the raled capaeity of ill ulve ror 0.64 'P \IT gas is 'b1own ilS equivalent Cap'C)ty for 'l"" of other <peeific
gravity may be determined by dlvidinq the raled capacitY by Ihe conversion faclor ElIa~ The rated capacifY
of II cenain valve is 3500 cFh What is ill; equivalent capacity lor 0.72 lp \IT gas? Soluticnc 3500 cfh
To find cFh itt .64 op gr, mwtiply cfh at "x" ,p, qt,
iD find "Fh at "J<" sp qt, divide cFh at 64 "p gr by conversi\ln faclor
Trang 7CONVERT CAPACITY TO SEA LEVEL AL TITUOE
CONVERT CAPACITY TO SEA LEVEL ALTITUDE
HOW TO USE CHART
When required valve capacity in cfh at sea levrl is known lilt equivaltnl rtquinod capacity at hiqher elevationJ r.1ay
be dele,mined by use of correct multiplyinq factor obt.tintd from litil chari
Example: A valve capaaty or:sooo dh ill required It 5 ltvel Whll would be the required capacity at an elultion
~t above sea lewl?
Solution: On vertical scale of chart, find 4550 ft From lhat point, move horizontally to riqhl to intersect lile curve;
lilen move straiqht down to bottom scale and read lile conV'trslon flctOt, 1.087 Multiply Ihe 3000 cfh by lil factor;
3000 cfh ill: L087 = 3261 cfh
NOTE: To find the capacity at sea level when the capacity at I hiqhet eltvation is known, ~ the known capacity
by the conve,.,.jon factor 3261 cfh = 00
Trang 8PRESSURE DROP CONVERSION
; 4 in wc 2This conversion IS nol otten needed because rf105t
(Convert
KH0WN PRESSURE UNIT
REOUIRED PRESSURE UNIT POUNDS
PER
SO IN
OUNCES PER
SO IN
MILLlMHRES 0' MERCURY
KILOGRAMS PER
sa CM
INCHES 0' W,o.TER
INCHES 0' MERCURY
FEET 0' W,o.TER
CENTIMETERS 0' WATER
'.
Trang 9I N T R O D U C T I O N - - -
DEFINITIONS
1119 firing Crate is Jhe combustion rate II is the rate at
which air, fuel, or snair-fuel mixture Is supplied loaburner
gas or gallons of oil), weight (tons of coal), or heal units
control (or combustion control) is simply a means of regu
ply according to load dernard
PURPOSES
operatioo and to relieve operators from tedious monitoring
dUlies However, their primary purpose is lor economy
To proouca Ihe mosl economical ep8ralion, lh&cOIltrol
system must mainlaln the air-fuel ratio at an optimum
value over the entire load range Usually, The system must
sure, furnace draft, waler level and steam lemperature It
FACTORS AFFECTING THE FIRING RATE
the primary consideration other faclors also affect the fir
much of the lotaf heal produced, opening and closing
The pickup demand or the furnace or boiler also con
sumas part of the heat output When a bJrr.er syslem is
started, the mass of metal that comprises me furnace or
the system, and it also radiales a portion of the heal 10 lhe
surrounding surfaces Finally, lhe efficiency of the fUrnace
or boiler ilself has a bearing on the amOl.n1 at fuel that is
burned The efficiency depends to a great exlent on the
he-at transfer qualities of the boiler or furnace
LIMITATIONS ON THE FIRING RATE
Turndown is lhe ralio or tna maximum firing rate (high
fire) 10 Ihe minimum /iring rate (Jaw fire) al which a burner
will operate satisfactorily It is also expressed as the range
turndown ralio Is particularly desirable for batCh-type fur·
Flame t::Jow-off limilS the maximum firing rate A Ilame moves away from a burner when the velocity at lheair-tuel mixture is greater than the velOCity Of the Ilame front (flame
extinguished
Flashback limils the minimum firing rate A flame
fr el mixinQ lXlinl) when the flame propaoation rale is grealer lhan the velocity of the entering alr'fUel mixlure DRAFT CONSIDERATIONS
Drat!: is lhe movement of air into and through a CON'Ous{ion cflamber, brEl8ctling stack, and chimney
Natural draft results from the difference in density of the heated air rising through the slack or chimney and the
draft are forced and indUCed draft
Forced draft is produced by a fan or blower located at
draft is produced by a partial vacuum within the corrous
cMlTtler
temperature of the atmosphere, height Of the stack, direc· tion and force Oflhe wind, and other environmenlal conditioos Blowers or fans supply a conslanl draft lhat is
independent 01 these conditions Therefor'll, mechanical
draft is used as the main source of air
ber Da"l)f¥s in tl"l& air passages are use::llo control the
draft Darrpar p::lSilions are varied as tne firing rale is varied
FIRING RATE CONTROL METHODS - - -
In large plants, mothodl; of regulating the firing rate are
(1) fland, (2) base load and (3) automatic In hand regula
tion, a fireman allends \0 a ballery of boilers and/or fur
naces He adjusts lhe valves and da,rrp.:lrS manually to
301
keep the pressure ancVor temperature constant In base
load regulation, most Of a gr~ of boilers and/or furnaces are cperated at a ste&'t, hil1l firing rare but one or fTIOfe
71-97558-1
Trang 10automatic regulation, an automatic firing rale control sys
cOl'l'b.Jsl:lon Some of the automatic systems used will be
discussecUn this section
AUTOMATIC FIRING RATE CONTROL
SYSTEMS
vide firing rate control Initially, the syStem is Iriggered by a
disturbanca then causes a sequence of adjl lStJTlentS, In
parallel or in cascade (series), to control the various parts
For exa~le, in a parallel system, a change in steam
speed and 'damper opening to change the airflow, and
pu~ speed and valve opening to control the flow of fu&:
(all) In a cascade system a change in steam pressure
might lnlllate a change In cCllTbuSlion airflow, and the
an adjus1manl of Ihe induced draft, and lhe resulting
ct\aIlgEl in furnace pressure is then corrected by a change
in the forced draft
eral classes-paranat, serieas·fuel, sories-air, or calorime
classes Usually, one particular syslem (or combination)
a healing furnace) generates an error signal The error Sig
pensate for varial.ions in fuel condlion or lor tube foUling in
boilers a ralio regulator (see belOW) is included lO-make
adjustmenls in the air-fuel ratio The ralio regulator maybe
device
PARAl.l.El CONTROl SYSTEM (FIG 1)
In the parallel control system, the error signal is sent si·
multaneously to adjust both fuetflow and airllow The ratio
cuit having the greater capacity, so the capaciTy of theboil·
er or furnace will not be reduced if the ratio of fuel 10 air is
decreased Thus, ilthe blower or fans have greater capac
ily than tha fuel feeding equipment, the ratio regulator is
least hardWare II is nol dependent on signals indicative of
the actual flOW of fuel or air Therefore, it is most used in
plants where the fuel buming rate would be difficult to
measure directry, such as a plant using grate firing of coal
SEAlES-FUEl CONTROL SYSTEM (FIG 2)
In the series-fuel control system, lhe error signal con
liq,Jid fuels, and even pulverized coal A series sysIem is generally considered to be very effective in controlling the
the flow requirement of the other
Because airflow Is the dependenl variable, air will not
supply at limes When lhere is a fuel shortage, the system
would deCrease the effectlve heat El\l'9n further
However, if the air SlWly fails or airflOW' Is reduced excessively by a fan failure, there is a danger of filling the furnace with unburned fuel sinCe the error signal can still cause the system to continue fuel flow, Airflow failure will decrease the heat release in the furnace, further aggravat.I,!lg the situation by causing a demand for even mora heat and fuel Electronic circuits may be used to overcome this
by a predelermined amounl Also, a flame safeguard con
combus-RATIO REGULATOR
FUEL FLOW
ERROR SIGNAL
_.J_-,
I ALTERNATE I
'LOCATION •
OF RATIO • : REGULATOR
Trang 11lion Many burners also have airflow interlocks 10 shut
them down if airllow decreases to a predelermined value
SERIES-AIR CONTROL SYSTEM (FIG 3)
"the Series·alr control system overcomes thQ disadvan
IhQ airflow Measuremenl of thQ ail1low then produces a
sig~ that controls the fuel flow Thus if the airf/(lW fails,
readlly measured
CALORIMETER CONTROL SYSTEM (FIG 4)
In lhe calorimeter control system, the error signal CCll'l
produces a signal thai is used 10 control ail1low, The
amount 01 steam produced is proportional to the firing rale
uring steam flow Because stearn flow is substituting for
fuel flow, the ratio regulator is in the steam flow clrcuil
given fuel that will release a certain amount 01 heal If the
rate of heat release is known, the amount of air required
p::>rtionalto the rate of heal release, so a measurement of
heat, the system derives its name from lhe calorimeter, an
apparatus for mensurfng amounts of heat
Steam leaVing the SuPerheater is usually held wilhin
close limits of pressure and temperature so its enerlJll
content per p::>und will not vary appreCiably Therefore,
each p::>und of steam carries the same amount of heat
energy, so steam flow is proportional to the firing rate It steam pressure or temperature vary el'lOUl;1l 10 causa
the system to correct the steam flow for standard conditions
fails A decrease in airllow will decrease the heat release, which will deCrease lhe steam !low, causing a further reduction in airflow Meantime, the system is calUng for more
case, steam flow instead of fuel flow is CClI'1l)3.red with airflow
AIR-FUEL RATIO REGULATORS
control, and (3) flow control All 3 actually keep the flow
sic prq:'l8rty that is controlled direCtly to achieve a cO"lStanl air-fuel ratio
AREA CONTROL (FIG 5)
A simple mechanism is used to cause the opening area
of 2 valves, one controlling airflow anclone controlling ruel flow, to vary in proponion fa each other For 2 varves with identical characteristics, a mechanical connection be
If one valve rolates through a 45 degree angle, the other will also rolate through a45 degree angle: and If this movement causes a 25 percent chaf1Q8 in the flow rate of ona fluid it will cause a 25 percent change in the flow rate of
AIJ'lfLOW
ERROR SIGNAL
FUt:L FLOW
RATIO REGULATOR
AIRfLOW
I
RATIO REGULATOR
"
FIG 3-SERIES-AIR CONTROL SYSTEM
71-97558·1
Trang 12ERROR STEAM
I
RATIO REGULATOR
FIG 5-TYPICAL AIR-FUEL RATIO REGULATOR
~srion Handbook by North Amedcan
MfQ Co., Qeveland, Ohio.)
mixture at others
ual means of adji"lSling their cpenings for setting the air·
tueI ratio Inilially
The L.9Cilream pressurfil!S 01 both air and fuel must be
constant, reqJlring an air blower with a constant pressure
characteristic and a fuel pressure regulalQ{ ahead of Ihe
fuel control valve For all, ils temperalure must be con
variali~
The resistance to flow downsTream trom the clYltrol
sures equal (or proportional), their flow rates are kept pro
IXlrtional thrOU\1lOUI lhe entire turndown range of the
burner This type of ratio regulator works with constant ar·
eas and variable pr8SSUres, which is lTlOre accurate and
usually less expensive lhan the area control msthod
Wl1EIn this type of ratio regulator is in the fuel line, il is
cross-conneclad 10 the air Ii.ne by a small impul6B line, and
vice versa It c.onsi&ts 01 a globe-type valve in which Ihe
plug is-aitached to and movecl by a diaphragm 1'he pres
sure on one side of the diaphragn is proportional to that 01
the air line, and the prassure on the other side is prC4'O'
tional to lhat Of the fuel line If the pressures are not the
same, the urCialance causes the diaphragm to move The
(01' air if the regulalor Is In Ihe air nne) until the pressures are the same
$Ute Is more than the maximum available gas pressure, a
tieed"f is used to permit a cenain amount of leakage1rom the 1l"rpU16B Une 10 ensure tM correci ratio at hiQh firing
used for counlerba.lancing the weights of lhe shaft, plug
ing the plug
When b.Jrning all In low-pressure air atomizing burners,
it is desirable 10 maintain an oil pressure several times
greater than lhe COrTtx.lslion air pressure The air-oil ralio
regulator shown in Fig 7 prOduces a oownslream oil pressure proportional to Ihe pressure elrertecl on the tc:p side of
on the air diaphragn, lending 10 move the valvs shaft as
up on the oil diapnragn, tending 10 raise the valve shaft
to the atmosphere If the area of 111EI air diaphragm is 12 limes [he area oflhe oil diaphragm, the oil pressure has to'
be 12 limes the air pressure in order to balanc9 it The oil valve opens wider untillhe 12:1 pressure ralio is attained
diap,ragms, shaft and valve plug
FLOW CONTROL (FIG 8)
A llow control system actually measures Iheair1/aw and fuei flaw and conlrols the flow 01 one of them accordingly
Trang 13A conslriction, such as an orifice, is plaCed in both the air
striction measures the flow thtough that line Both pres'
d9vJce that adjusts Ihe 'low 0' either the air or fuel to main
tain the desired air-fuel ratio
The alr-gas rallo re(JJtalor shown in Fig 8 conltols the
upstream and downstream Il'Jl=Iulses from an orifice in the
larly', impulseS from the air line act on the air diaphragm so
FIG 6-iYPICAL AIR-GAS RATIO REGULATOR
USING PRESSURE CONTROL, (From
Combustion Handbook try North American
Mfg Co., Cleveland, Ohio.)
relay and crank type cylinder} to the butterfly valve in the air line The butterfly valve moves untillhe now (pressure dif1erenlLal) across the air orifice balances out the flow
that equal pressure drops correspond to the correct ratio
01 flow rates The ratio regulator also has a manual adjust·
,
FIG 7-iYPICAL AIR-OIL RATIO REGULATOR
USING PRESSURE CONTROL (From
Combustion Handbook by North American
Co., GJevs(and, Ohio.)
FIG a-TYPICAL AIR·GAS RATIO REGULATOR USING FLOW CONTROL (From Combustion
Handbook try North Amen'can Mfg Co., Oeveland, Ohio.)
Trang 14FIRING RATE
TIle size and aw1icalion 01 a burner determines how II
iG fired Ditlerent rnel!nds 01 flrino result In various prepurge configurations An a,wrovall:lOC¥ may require a specifiC prepurge COnfiq.Jtalion for a given awlica1ion
The swilching required fa achieve a certain prepurge corr
guard pr~ammlng conlrol programmer)
er"lCJl 91 heat This is the most efficient method because
trols ars requlrec:l, so It is also less expansive initially Orr
01'1' filing is used mostly on warm air turnaces in residential and corrmerclal buildings, and also for residential awn
aness such as hot waler healers
HIGH-LOW FIRING
Hig-.-Iow firing provid9s 2 firing rates, high fire and low
tained by simultaneously PJs!tioning lhe dampers 10 aO'nil more combustion air and the fuel valve to admit more fuel
more fuel.l High·low firing is used on large, commerCial
firing rare is r8QUired than Is safe for on-off firing, so the burner must light off at low fire to al/Oid a possible eKp1o
wnile This melhQj has been found 10 save 10 to 15 per·
Cent of the fuel required 101 modulalac:l firing
MODULATED FIRING Modulaled firing provides a gradually varying firing
marlCt The burner lights off at low tire 1l1en a controller
variable (usually prBSSUre or temperalurel at the controllEi"
sel PJlnt Modulaled firing provides precise coolrol, but it
is the least efficienl because it is ditficull 10 keep the air
fuel ratio conSlanl over the entire mlX1Jlating range It is used on industrial furnaces or bOilers 'or applicatlOflS re
quiring close pressure or temperature tolerances, such as
PREPURGE CONFIGURATIONS
oorner Iighl-otl, to remove any fuel or fuel vapors that may
methOOS at tiring The ~high fire" Is really a l!!i~().I!I.!§Ir
Is that the darrper controUing corrbustion air is c:penac:lto lis maximum ~ition to move> as much air as possIble thrDU~ the combuslion chamber This position is thE!
period when the burner Is firing
heat, the prepurge period aclually COOls the system OOwn
flrinQ are summarized in Table I Insurance comp9.r'1ies in
causing loss of productior'1 It they requIre safely controls thal causa urnecessary down lime they pay, Since they reqUire cerlain firing rate contrOls, you can see the imper·
tance of IheS4 controls to the safety of the Ourner system
STANDARD ON-OFF PREPURGE
No firing rate SwilCtling is rElQJired The amount 01 air admiUed during the prepurge pariod is Itle same as the amount of combuslion air provided during the run period witr the burner firing
OPEN DAMPER PREPURGE Firing rale swilChlne in fhe programmer drives a 2-posi
low fire p.:lSihon before ignition trials, and drives il back
open 10 high fire for the run period
LOW FIRE PREPURGE
used anymore in flame safeguard awlicalions Firing rate
er motor at ils low fire position until after i'7lillOn trials,
control of a series 90 pressure or temperature conlroller
Trang 15TABLE I-PAEPURGE CONFIGURAnONS
1-wireb
UL Modulating
(2-stage firing)
R4181A1042,-A1059
<&"-Factory Mutual requirements
IAI-Industrial Risk Insurers (formerly F.I.A.) requirements
b Firing rate motor mUSI close by itselt (spring-return) when power is removed
d Low fire switch stops sequence before ignition trials until low fire position is proven
I Switching returns firing rale motor to its low tire position when the run period is OVer
LOW-HIGH-LOW PREPURGE
controller lor the run period The programmer has provi
sions for a proved 10w-firl;l-5tart interlock Oow fire switch),
which stops the sequence before ignition trials until the
LOW-HIGH-LOW PROVEN PREPURGE
This is the same as lOw-high-low prepurge, excepl that
Ihe programmer also has provisions for a proved high fire
interlock (high fIre switch), which slops the sequence near
PROVED LOW-FIRE-START INTERLOCK
which is outdated and seldom used anymore) This inl9f
maximum) betote the burner can be iglited This is usually
SWitCh) mounted on the drive Shaft or the firing rale motor The auxiliary switCh is wired inlo the safety conlrol (programmer) circuit
PROVED HIGH FIRE INTERLOCK
In addition 10 a proved low-flrl;l-5tart interlock, Factory Mutual and In:iJstrlal Risk Insurers (formerly F.l.A.) also
!hrOU<tl the combustion charrber The hit;1'l tire swllch Is usually also an auxll1ary switch on the firing ratelOOlOf'
Trang 16FIRING RATE SWITCHING IN PROGRAMMERS -
By means of simpllfiod schematic dlagrams and timer seq Jente charts, we wlU show how fhe PfOlJfammers ae
CCllT'9liSh firing rate switching For simpliCity, only the cir·
cuits and conlaCts nec~ry 10 de6Cribe the basic
operation are shown For a complete description ollhe 0p
R4140L"'-4"7 (form 60-{)4.44)
TImer contacts are oesicnaled M1B, M3A, etc Termi·
nals L1 and l2 are the -hoi- and ~common· terminals 01
ttle power SLWly External oevices are shown in 001(95
Operation 01 the firing rale motor Is deScribed in detail In
the seedndpar1 of this section covering Honeywell Control
Systems '
',WIRE (OPEN DAMPER) FIRING RATE SWITCHING
figs 9 and 10 show the firing rala swilching of the
o1lhe lOY\' fire provIng cjrcuil Is not shown because II is similar 10 the operation tor 4·wire switching, which will be d9scrlbed later
A 2-posJl!on, spting·t~um llcluator is used to control
position
"flow is e!tab\ished, Ihe airtlow switch close's, er'oergili~
switch, jurrper, and M108) TIle actuator drives the darrq>
er open ~o high lire ~ition)
s:ops the timer until the low fire swilCh closes, proving thai the daf1lJ9r is in ils low fire position before ignition trials
closed during most of this period Near lhe end of ignition trials, al ti9.5 seconds, M108 closes The damp€lf actuator
& ~T""To AM , ,~ 5"' v ""''' lOON IUAC S.CC"""
& , -A , T ,.UA"lICI.""ffN U 'NAU" .O
A IN CA""~ ACTUATM ,S"IlC,
11A'·I'O:I'''''''._'''~·.I'''''N AUU.HOII " D rocoorr"OL tNE
FIG '0- TYPICAL TIMER SEQUENCE CHART
FOR '-WIRE (OPEN DAMPER) FIRING RATE SWITCHING
and I'" damper stays open during the run period
closed
3-WIRE FIRING RATE SWITCHING
type, 3-wire R4150L Programmers Operation 01 the high fire and lOW fire proving circuits is nOI shown because it is similar to the opera.tion for 4-Wire switching, whiCh follows
awly power to lhe motor, but cnly shorts between molar and c()l"(roller terminals, or opens them
A proportioning, sptfng-return or spring·biased motor
-FIG, 11- TYPICAL 3-WIRE FIRING RATE
SWITCHING
FIRING RATE SWITCHING,
Trang 17FIG 12-TYPICAl TIMER SEQUENCE CHART
FOR 3-WIRE FIRING RATE SWITCHING
the molor 10 its closed position The spring·tiased molDl'
has a spring allached\o ilsbalancing relay When the "R"
leg is coened, the spring pulls the balancing rela.y to its
closed position, and the molor is than electrically returned
to ils closed posilion
Or'lOs, M98 closes, shorting between terminals 10 and' 1
on lheprogrammer and between terminals Rand B on the
firing rate molor The motor dlives the damper cpen 10 its
high fire posi\ion At 7 seconds internal prCJgrammer
switching stops lhe timer unlillhe high fire switch closes,
prOVing that the damper is open 10 provide maximum air·
At 42 secondS, M9B opens, opening Ihe • R· leg of the
motor circuit The spring (or spring-bias) drives the motor
and darnpel' closed At 60 seconds, internal prCJgrammer
switching stops the timer until the lOW fire switch closes,
proving that the damper is in its low fire position before ig
nition trials
connecting the A terminals of the molar ar.d controller
The firing rate motor is released to mcx:::Iulate under conlrol
period
the timer slarts Al 118 seconds, M9A opens, cpening the
drives the molar and damper closed
4-WIRE FIRING RATE SWITCHING
a firing rate molar .ith a spring-return or spring-biasecl
balanCing relay Therefore newer A4150G ard Lmcdels,
FiQS 13, 14, and 15 show the firing rale switching 01 a
I'T'ICX1els have provisions only for the low 11re switch
motDl" (Fig 14) Is energiZed IhroU(1l MJA Al 3 seconds,
minals Rand B on lhe 1iring rate motor The motor drives
provide maximum airtlow during prepurge, the timer motor
prspurga continues
At 20 secondS, M3B closes (Fig 14), bypassing the high fire switch At 26 seconds, M10A opens (Fig 13)
FIG 14- T'(PICAL OPERATION OF HIGH FIRE
AND LOW FIRE PROVING CiRCUITS