Limit switch open in main JXlwer line or in series with the C{ltroller.. Adiust pilot position so 11ame will ignite main burner.. Pilot line tap on main fuel line is downstream of main p
Trang 1R4138C,D INDUSTRIAL FLAME SAFEGUARD
CONTROLS (FIG 65)
These controls directly replece older R4138A and B
models to meet the lates! rElQJirements They are espe
cially Suitable where Icng petilXi3 01 burner operation with·
out s/'lulc:bwn are normal, such as in heat-treating ovens
and kilns The R4138D is (he same as the R4138Cwl!hthe
adc:lilion 01 a jXl'I'Ver failure override circuit 10 prevent shut
Ing of 1 Second or less) The A4138C is available in 120,
220, and.24O volt rtlOdeIS; the A4138D Is available only in a
120 vol'model
SAFETY FEATURES
The A4138C and D provide a Safe Start Check for a
flame, or a condition simulating a flame, at startup If the
flame"relay 2K is pulled in before the STAAT button is
pressed• 2K.2 is open, preventing the load relay 1K from
pulling in The system cannol be started until the condition
Is corrected and 2K drops PUt
They also prOVide safety shutdown on
- failure to Ignite the pilor (lockout will occur t1the
START button is held in IClIlg9f than the 10ckPUt
switch liming.)
-loss 01 flame during the rUl"l period
-failure in the flame detectiCfl system, If e sell·
cheCking system is' used-see Table II (L.ockoul
will occur it lhe START b rIlon is held in longer
than the lockout switch timinQ.)
On safety shutdown the pilot and main fuel valve(s) are
de-energized 11 used, the exlernal alarm is energized The STAAT bulton must be manu8JJy pressed to restart the
system "the lockout switch trips the load relay 1K drq:>s Oul and the lockout switch must be manually reset to rEtstart the system
OTHER FEATURES
" A plu~in $4.27D Purge Timer is available as an ac· cessory (0 provide e timed purge period prior to the manual startup
" An optionei remole reset assembly allows resetting the lockout switch from a remote location
" Irlcandescent indicator lamps (FLAME OFF, PURGE COMPLETE, FLAME ON) prOVide a visual check: 011he system condl1ion
• The R4138C or D plugs into a subbase or cabinet ElQJiA?OO with quick-connect C'-ontacts
• All field wirinQ (except for the optional remote reset assembly) is connected to a terminal strip on the subbase or In the cabinet The R4138 can be removed easily withoul disconnecting any w·lring
" Clear plastic relay covers help prevent conlamination, damage, end lamperinQ
" An ALARM terminal Is available to operate an exlernalline voltage alarm on salety shutdown
" A zinc-dichromate finish resists the corrosive effects 01 most induslrial atmospheres
KEYED IIECEPTA(L[
FOR PlUG·IN AMPliFIER SPRI",!> CL'P
01'1 CHASSI~
PlUG·I", FlAME SIGNAl
FIG 55-COMPONENTS OF THE R4138C OR O
186
Trang 2- - - -
SEOUENCE OF OPERATION FOR THE R4138C
OR D (FIG 66)
The cperalion orlhe 120voll models oflhe R4138Cand
D win be described Theseq.Jel1ceofoperalion for a 220 or
240 volt model ot the R4138C is the same; it just has an
aci:jitionaltransformer 10 provide 120 volts tor the sMutler
& "'L.CIT UN Ju M; , II:(U_O '0"'" ce OO
'IOCIl """T eAT><I LIN - IT I.SO ~U-"'"
& ' n o' ,"" c""11 D.' "" I"II:UO: ULT
~=,:.~~,':;'~': ':':'~~~'~;;~Uc'=:"~;;.'Jo~~J ~"u."'''- u f l'H€ - ,
& IF • ., " ST••' ' "••""" , roar 0 TH, IT""" ""'TC" ,
FIG 66- SIMPLIFIED SCHEMATIC DIAGRAM OF TME 120 VOLT MODELS OF THE R4138C AND D
SHOWING TYPICAL FIELD WIRING FOR A GAS OR OIL CUTOFF SYSTEM
Trang 3SEQUENCE OF OPERATION FOR THE R4138C, D
NOTE: Italics denote special 8HJlications
NORMAL OPERATION
TO START
" terminal , a The lan(5)
larminal L 1: the plug-in amplifier is 8f\o
ergized
" terminal b The alarm 115 energized, bU1 may be
('tHough the alarm silaneing switl:hl, "
-turned off by opening the alarm si!enc
,
"'""' • app"ed
" terminal 18 ,
open eu1on'lalicalty.)
b • appfled
" terminal 17 tI The purge perod belilins: the lan(s)
~gh the high fire irrtBr1ock) and to
Pow"
lhe mobr ofltle pur~e timer (through bU!l19d fuel and fuel vapor
PT1): 1he purge timer starts
c At the end 01 lhe preset time PT1 , Relay 1 R pulls In: 1 R1 closes to bypass
ctJses, IlPPtyinll power Ie terminal 6 applied Ie the purlle timer (If power is
(Trom terminal L1); the PURGE COM- removed In:m the pur'ile timer, it will
5 Push In the START button and 5 e ~er is applied Ie the i'ilniOOn trans· 5 a Tha i~nrtion transformer Is 9n9r~lZall
statkJn).
shutcbwns when not using
a purge liry'let, wait at lea$!'
minal 6 (II1rou~h the low lire start InlBr
(1l 1K1 ebses applyin'il power to tur· , (1) TI"MI pilot vllive (or 1st sta~e oil
minai'S tro-n terminal 3 valve) • ener~lled The valve
opens and the pilol: (or 191 sta'ila Oil burner) Is I~n~ed
(2) Jt the pilfJl/lnlc lumper wi/1l I'!~s been
clipped fr:T 8 continurxJs (sr~ng)
piJfJl app/iC81ion, the tfame derec
rion circUit fO the amp/if/Sf is com- pleted
(2l 1K2 closes
be'ilins heatin'il (tty autJtransfonner action of 1K thf'OU'ilh 1K3 and 21<2)
,h hea""
d If 8 C7012E cr F PurpJe Peeper U/tfit- pJiffet"Js used, power is applied from ter
d If an Rrn7C DpIarric Self ChecJc Am
vir:itJt FlsmtJ DBtacta (NitI'! seIf-eheck· rrifllll 7 t!roUgl'! Itle Jumper to trJm"inaJ Ing feature) is used, the shtmer is ener·
13, t!roU¢ the sr:iid "'are swircfl in the gized.
81tfJIiffet" (between ampli~B>' tfJi"trlnaJs
16 fIftd 17), 10 ttrrTinaJ 12
Trang 4••
SEQUENCE OF OPERATION FOR THE R4138C 0 (Continued)
NORMAL OPERATION (cOflrinued)
None • The "arne detector detects the nlllT!8 lor llrt stage oiIl1ame) .""
r When the llama is detected relay 2K pull, in
~m8f contact PT2, low nre stan interbck START slam, and inter
nal jumpel" Power will be applied t:I terminal 7 {tmm terminal 3 tt1rcugh 2Kl ID tenninal e, and tI1rough tI1e
STOP stillion and alarm sileJ'ICing
!Witchl tJ tvJld in relay 1K (unl", Ih8 limb open the STOP button il
occurs
Ing
(3) 210 cloS85, applying power lD tar· (3) The aubnatic main fuel vaMl(a) jljI
1Kl) Relay 3K pulls in and the the main burner is ignited The
sys-FLAME ON (WHITE) IlImp Wghts lern is in the run conditbn (If II
mat1lJ8Ify opened vahe i, usBa', fhe
main l:IUmet will not be igrittKi unrif
step 7 is compleuKf.'
, When relay 3K pulls in
terminal 15
ing 110 Relay 11< can pull back in after e fT'OTIenlary power failure if
31< is still pulled in
PI 310 opens, rel'TlOVing _, 18 Th FLAME power fn:m OFF P} Retay 1R drops out and 181 opens
'n" '''"'''.
rerroving power fn:m terminal 5
The PUAGE COMPLETE (GREEN)
self-checking system is used).
bullon
7 Normal operetion
7 Open manual main Iw/ valve(s) 7 The main burlJ8f is igrrlfKi Too system is
TO SIOP'
hold it in until the FLAME OFF b Relay 11< drops out lKl operul re- b The pilol valve (or lsi stage oil valve)
c When relay 31< drops oul
(2) 310 ck:ls&6: ltle FlAME OFF (REO) (2) None
drops out
startup
9 Power ~ retro'tIed from tel'min4l:9 1S end 9 The alarm is
9 Open the alarm silern:ing svwiIch
15
10 Power is rllr1'DWd from tel'miMIs L 1 and '0 The lan(9) stipe end the systIlm is de
10 Open Ihe masler swilr::h
3 The plug n amplifier is de-energized 808I'"glzed
,,"
Trang 5SEQUENCE OF OPERATION FOR THE R4138C, D (Continued)
SAFETY OPERATION
Safe Stan Dleck-A flame, or a condi· Raley 2K puns In when the name (or flame- The system cannot be started unm the con· tion simulating a name, is present be- simulating condition) is detected Contact ditiol'l is
inrJ a.cootinuous (st8flding)
, K1 stays open; no IlOM'I' can be ap • The pilot valw (or 1st stage oil valve) and
• plied D tlIrminals 19 and 20 the automatic main fuel vatve(s) cannot
main closed The FLAME OFF (RED)
lamp remains on The PURGE COM·
PLETE (GREEN) lamp may also cane
No name is detected so relay 2K does not The system c~ be started The ignrtion
The pilot (or 1st stage oil buma" is not
START bbltlDn is released
(lockout II'I'o'itc:h heater) heats until !he The lockout switch must be manually
re-lockout switch 1I1ps (If the START button set to try to restart !he syslem
is held in longer !han the 'Ockout switch timing)
a lS1 opens and relay 1K drops out a The pilot valve (or 1st stalle oil valve)
can-applied to 18nTIinaJ 20
, Relay 3K cannot pull in; 3K1 and 310 , The slerm remains enerllized not be energized,
(RED} lamp remains on
to restart the system,
a When the START button is released, not bypassed When the START but
2K1 stays open: the START station is
the ignition transtormer is de-ener·
fn:m terminal T
b Relay 1K drops out end 1K1 opens, b The pilot valve (or 1st stage oil valve)
System shutdown occurs period
NOTE: Safely operation is the same if
• The pilot vlllve (or 1st stall~ oii valve) and the mllin burner is rxrt ig nired in a • 2K1 opens, removinll power fn:m termi
the automlltic mllin luel vsive(s) are system w;th an interrupted pilot
de-nsls 8 and 7 Relay 1K drops out and 1K1
(obtained only by
opens, removing JXlwer from terminals
lamp goes out
• Thll alarm is energized
The FLAME OFF (RED) lamp lights
• Relay 3K drops out; 3K1 and 310 close
The system shuts down All valves lire
15 All indicator lemps go out and all relays energized, and the valves c!osB The IIlarm drop out 3K1 closes, applying power 10 ler is energized
minal16
190
Trang 6
-~.~ -SEQUENCE OF OPERATION FOR THE R4138C, D (Continued)
SAFETY OPERATION (continued)
Momentaty power "fsHure
B4138C;
Power ~ r9IT'QYed from all tanninals aN lndl
calor lamps go out and all r8l6y, drop out
llill&
Power is rerooved Irem all terminals all indio calor lamps go out, and aU relays except 3K
drop out The charge on capacitor Cl will
hold in 3K tJr about 1 second
• It poWllf' is restored before 3K drops out end before lila plot flame (or 1st
stage oil !IamEI) ~ out
-3K2 will stay cbsed bypassing lK3;
3Kl and 3K3 Will stay open
- rllfey 2K will pUll bacl( in: 2Kl and
2K3 will cbse and 2K2 will open
-the STAAT staliol1 will be bypassed through 2Kl, the STOP statkm, anl:l the alarm silencing switch
- po er .ill be reappliel:l to lerrninal
7
- relay 1K 111 pull back in thrtluOh LS1 ani:! 3K2
- operation Will re!lJm to normal
• If 3K l:lrops OU1 before power is r&
stored
- 3K2 will open, so 110 will nat be by
passed; 3K1 ani:! 310 will cbse
- relay 1K cannot puU back In since
both 110 8Il1:l 3K2 are open
~ 1K1 stays open so 3K cannal puJf beck In
-!he FLAME OFF (RED) lamp win liOh1 when poWllf' is rr.mred
• II the pilot flame (or 1st staOe oU name)
- relay 2K C8Il1WJ1 pu~ back in 80 2Kl stays open
passel:l
- paMll'" will not be respplied b terml
r.a17
- relay 1K cannot pull be,ck In
- relay 3K willl:lrop out; 3K1 anl:l JIC will close
-lhe FLAME OFF (RED) IM'lp will
light when paMll'" is restJrel:l
The system shut:l down The alarm is aner
llized wherI power Is restored
• If pc:JYIIer is re:Jlored within 1 second llnd the pilot llama (or 1st stage cil
name) is still burning (1l1e \/lWe must
be sbw cbsino), rormal OPer4OOr1 will
be resumed The aJarm 'l¥ill not be en
ergi2ed lIthe main burner name hal
gone out, it will be reionifed by the pilot nama (Power failure override eir·
cuits may ha~e b be al:ll:lel:l b the pilot valve and me,in vaNe(s) b enS\J{e lt1al they 1:10 not close on a mctr\EIntary power interruption)
• The systBrn ~huts llown All valVes are I:IlHIn«gizel:l, anl:l the ~a'- cbse The alarm is 8I18rO~ed lIltlen PQ't¥er is
FLAME DETECTION SYSTEM'
The naome l:Ietec:tion system falle \fIthi1e Relay 2K canrot pull in when the 9)'SI&'n is Safety sl'w.1l'lSoWn occurs LJx:kout'l¥ill occur the system is turnel:l all or l:Iuri~ the startel:l-sarne OperllOOt'l as it lhe pibt (or it the STAAT bllltCn is hell:l in IongBf than
The name l:Ietection system lails
l:Iur-Ino the run periol:l with the bumBf
tiring
Aelay 2K l:lrop~ out-same operation as if
the name goee out
Safety shutdown «CUI'S,
Trang 7This sectlon provides I;lBneral Information about this section does not cover all possible maintenance actroubleshooting and maintaining Flame safeguard sys livlties tllat are req;ired for every system Again, its pur· lems Its PlJrp:lSe is not to allow the service technician to pose Is to help tl'lE! service technician develop ettective perform specifiC troubleshooting q)Elrations, but to help and efficienl preventive mainlenance programs thaI can the technician develop a consistent, analytical approach be applied 10 all installations
to Flame safeguard system troubleshooting Likewise,
T R O U B L E S H O O T l N G - - -
Troubleshooting of control and burner system prob TABLE I-BC7000 SYSTEM ANNUNCIATION AND
Iem6 is made easier Ihrough the BC7000 MicroCorTlJuter DIAGNOSTIC CODES
Burner Control Syslam self-dla\1lOSlic and 1irst-out annun
clallon funclions In addition 10 a line voltal;lB alarm termi
nal (audible armuncialion), the BC7000 Microcomputer
Burner Control System prOVides visual annunciation by
displaying a 3<:ligit alphanumeric code and one or two se
quence status lig,ts
SELF· DIAGNOSTICS of the BC7000 detect and an
nunciatel:xJlh external and internal BC7000 system prob
lems Exlernal faults such.as interlock failure, 11ame
failure, false flame Sib'f\8l, and damper motor problems,
and internal faults associated wllh (he BC7000 chassis,
the PM72Q Program Module, or the flame amplifier are all
reporfed through tl'lE! Multi-function Annunciator Display
FIRST-OUT ANNUNCIATION is aChieved through the
3<:ligit alphanumeric Multi-function Annunciator Display
thaI rep:lrts the cause 01 a safety shutdown, failure to slarl,
or a failure to continue in the burner sequence The cause
of a safety shutdOwn is displayed as an "F" (faulll, fol
lowed by a 2-digil nurTt:ler The cause of failure to ~ontinue
with the burner sequence is displayed as an "H" (hold),
followed by a 2-digil nurTt:ler SElquence status lights
(LEOs) provide pOsilive visual indication of the program
sequence: STANDBY /power on), PREPURGE, HOLD
IGN TRIAL FLAME ON, RUN, POSTPURGE, and safety
shutdown (illuminated reset bullon) Momentary power
loss erases this annunciation and requires resel Safety
shutdown (lockout) is indicated by the illuminated reset
bullon and an "F" (fault) code followed by a 2-digit num
ber safety shutcbwn (lOCkout) d&-energizes all loads en
ergizes the alarm terminal (atter a 1Q second delay) and
requires a rest With this information, most problems can
be diagnosed without axlansive triat-and-error testing
Table 1 shows the codes used to annunciate and dia~
nose system problems with the BC7000 For the Interpre
lation and possible remedies for each code, as well as
SYSTElol MOLD CODES
M70 _ FlAME SIGNAL OURING STANDeY M73 - OPEN PRE-IGNITION INTERLOCK H74 _ OPEN RUNNING I~ERLOCK
SYSTEM FAULTA-OCKOUT CODES FCQ _ FALSE FLAME SIGNAL DURING PREPURGE
FD, _ MIGM FIRE PURGE SWITCH FAULT FlU -_ PRE-IGNITION INTERLOCK OPENEO OURING PREPURGE
F()oO - LOCKOUT/RUNNING INTERLOCK OPENED DUR'NG FREPURGE
FlO _ FALSE FLAlolE SIONAL DURING LOW FI."E HOLD F11 - LOW FIRE START SWITCH FAULT
F'3 - PRE·IGNITION INTERLOCK OPENED DURING LOW FIRE HOLO
Fl" _ LOCKOUT/RUNNING INTERLOCK OPENEO DURING LOW FIRE HOLD
F30 - PILOT (FIRST STAGE OIL) FLAME FAILURE F31 - LOW FIRE START SWITCH OPENED OURING PILOT TRIAL
F34 _ LOCKOUT/RUNNING INTERLOCK OPENEO DURING PJl OT TRIAL
FJ,S _ PILOT FLAr.lE FAILURIO IN TEST r.lODE F4(J _ MAIN FLAME FAILEO TO 'GNITE
F _ LOCKOUT/RUNNING INTERLOCK OPEN EO DURING MAIN FLAME TRIAL
F~ -_ FLAr.lE FAILURE DURING RUN PERIOO F!l4 _ LOCKOUT/RUNNING Ih'TERLOCK OPENED DURING RUN PERIOD
F70 - FALSE FLAME SIGNAL OURING STANDBY F73 - P~E·IGNlnON INTERLOCK FAILED TO CLOSE Fe' _ INTE~lolrnENT (eOUNDING) PRE·IGNITION INTERLOCK
F82 FB.3 F~} INTERr.lITIENT IBOUNCING) BURNER F8!I, Fe7 CONTROLLEAr Ir.lIT
F80 _ INTERr.llrTENT (BOUNDING) LOCKOuT/RUNNING INTERLOCK
FIlO - PROGRAM r.lODULE FAULT FIl7 _ eYNCH~DNIZATION ILiNE FREOUENCYI FAULT F99 - INTERNAL CIRCUIT FAULT
cOf1l)lete systam troubleshooting and CJ;lElrating Instruc
lions, refer to form 65.()()14 trotbleshooling approach presented below is deslgn&d 10 For syslems without self-dia\1lOStic and annunciation; emphasize the similarities involved in troubleshooting dif· (or for problems tllat are not annunciatedl Ihe I;lBneral lerent types 01 systems
'92
Trang 8In any troubleshooting situation, il is necessary to con
sider the entire system-Including not only the burner,
controls, wiring, etc., but also air sUWly, /\Jel sUW1y, and
the condition and characterisllcs 01 the flame Itsel1 In or
der to cover all areas 01' bUrner operallon, lha
troubleshoOting proceoJre is broken down into a series of
specific sleps
The first general step in approaching a system failure is
to doitermine whaiher Ihe shutdown occurs repeatedly or
at random
difl'Ons in the system that can usually be identified by CJb
servation or by a few simple tests
they are caused by marginal or intermittent condiUons (oc
cur one time but not the next), they do not always occur at
atime when they can be observed Frequer1tly, the only
methOO of Identifying them is to be present when they oc
cur and be fortunate enOUQh to see what has h~
Often, a shutdown occurs buttha evidence needed cannot
be obtained TIlis results in the need for repeated attempts
before the correct solution can be found
TIlese two types 01 shutdOwn-recurring and ran
dom-will be discussed separately, since the procedure
lor identifying the causes of each are somewhat different
Recurring Shutdowns are obviously much better suiled to
solution using a step-by·step procedure
RECURRING SHUTDOWNS
After determining the generall'1?9 at failure, determine
the point In the operating cycle al which trouble occurs,
, and the specific symplom To get this informaUoo and to
determine the proper corrective action, aiways complete
the following seven steps;
STEP 1 - KNOW THE SYSTEM AND
EQUIPME~T
Effective troubleshooling requires a knowledge 01 the
complete SyStem and its normal sequence, as well as the
Indi idual devices and equipment that make l4' the sys
tem TIle availability of a schemallc diagram of the syslem
is a necessity A written sequence 01' the normal operation
of the SyStem is also desjr~le
STEP 2-ASK OUESTIONS
Usually, Ihe information available on arrival at the in
stallation consists of a sirrple stalemenl that a burner
shuts down Start by asking all the questions possible of anyone lhat mi~t have some knowle6;)e of what hap
pened When cbeS the shutdown occur? What part of the CYCle? How lonQ after the startup? Does a shutdown occur following every start? How Is the lightoff?
These are only sarrple questions-the lnformation needed will depend on the Individual situation Be sure the operator 01' the SyStem is contacted and questioned RetTlQrrOer, they were present and involved when the shutdown occurred
STEP 3-EVALUATE YOUR INFORMATION Usa Table II, together With your personal experience, to herp evaluate any information you have concernillQ the shutdown The conclusions drawn at this stage only provide an idea of where 10 look tor the exaCI solullon 10 the
prOOlem
STEP 4-MAKE A TRIAL RUN Observe the operation of the burner system through a corrprete cyCle Was each slep of the startup in accordance with the design sequence? Did any deviations occur? Did the shutdown occur exactly as described? Did anything else happen? Have any new facts been established?
AlSO refer 10 information on measuring the flatTlQ signal during lest runs below
STEP 5-RE-EVALUATE The re-evaluation of availabie facts can often be made during the trial run Mentaily check the possible causes
and eliminate all except those that could b6 resoonsible for lhe shutdown Remember ,that in some instances, more than one factor may be contributing to the prOblem
and must be considered in the solution
STEP 6-VERIFY THE ASSUMED CAUSE BY A TEST RUN
After determining the a,warent causa(s) at eqJipmenl matltnction, perform a second test run to see if the evaluation is cOfree! lithe answer has not been found, a new evaluation must be made that Includes any new In1Drmation thaI has been obtained cllrlng the second lest run More than one ra-evaluation lest may be necessary to get all 01' the information needed to positively Identify the
cause(s) 01 lhe Shutdown
STEP 7-CORRECT THE CONOITION(S)
Trang 9TABLE II-TROUBLESHOOTING RECURRING SHUTDOWNS
To assist In delermining lhe cause of a system shutdown, Ihis tabte lists possible causes and corrective actions for each symptom: For-convenience, lhe lable Is divided inlo sections rapresanling lime perlcxE The problems that could occur during a specific peric:d of the operating cycle are listed in each section If specific information on service of a particular control or piece of equipment is required, refer 10 lhe instructional literature for the particular control
, - - - _ - - - ' - - - I M P O R T A N T - - - ,
Repair or replace all defective comp::lrIents, as necessary
INITIAL STARTUP
A ~nce cbes not
start
1 No JXlMlr
Z L.ockwt (safety) switch tri~
3 Limit switch open (in main JXlwer line or in series with the C(){ltroller)
4 Start or preignition interlock open
5 Process interlock open
6 Wiring open
la O1eck master switch and overload protection (fuse, circuit breaker, etc.) Reset or replace, as necessary
20 Reset- find cause and make necessary repairs
3a Slack damper end switch not made
30 Airflow switch open
3c low-waler-cutoff open
3d Fresh·air dal'11P9r (to boiler room) not open
3e Fuel pressure switch open
31 Other interlocks opErI in JXlwer line
4a Check start or prlHgnition interlocks
sa Check all process controls thaI are interconnected wilh the burner system
6a CheCk wiring for breaks or open splices
FIRST 15 SECONDS AFTER START
B System cbes nol go
10 high fire during
1 Wiring-opens, shorts grounds
2 No JXlMlr at firing rale molor
3 Limit switches in firing rale motor nol made
1 High fire switch open
1, O1eck voltages at the wiring sutbase terminals for firing rate switching
20 Check for JXlwer at T·T terminals on firing rate motor
3a Clean conlacls
1a Check switch
1b AdJlISt linkage
1c Check firing rale motor and its transformer
starfS
2b No airflow Check burner motor (blower) and associated corr-ponenls and circults
2c Plugged air line or filling
194
Trang 10DURING PREPURGE-AFTER 15 SECONDS-BEFORE IGNITION TRIALS
D Flame relay pulis in
(2) Unwanted flame on flame rod
lb Visible light photocell:
(1 ) Light striking cell
(2) Detecting hot felractory
1c Infrared (lead SUlfide) detector:
(1) Electromagnetic piCkl4) on leads Anchor solidly Install coaxial cable if necessary
(2) Unwanted flame being detected
(3) Detecting hal refractory
(3) Defective sensor (replaCe)
le Flame safeguard control:
(1) Defec/ive amplifier (replace)
la 8l.Irner motor (blower) st~
lb Restricted air passage from air d Jct 10 airflow switch
10 Plugged air line or titling
2a Check interlock
LAST FEW SECONDS OF PREPURGE BEFORE IGNITION TRIALS
F 5eq Jence stq:lS 1 Timer switch on flame sat9lJ lard
control set al TEST
la Set switch 10 NORM lXlSilion
2 low fire switch open 2a Check switch
2b Adjust linkage
2c Qleck tiling rate controller (broken polentlometer)
2d Check firing rate motor and its transformer
G No ignition spark 1 No power 10 19lilion transformer
2 HiQh voltage Insulator(sj faulty
3 Ignition elecnode spaf1( gap selling
ta Leadwires cpen, grounded, or not prcperly connected; insulation damagecl
lb Flame saf9lJ lard control not providing power
lc Flame safeguard control recycling
28 Cracked
2b Covered with soot, dir1, or mOisture-causing a shor1to ground
Ja Clean the electrodes
3b SpaCing incorrect-too wide or shorted
3c E!&ctrodeS not prcperly mounted
(cOI1t1nued on IMxt parle)
Trang 11PROBLEM POSSIBLE CAUSE CHECK
G.(conli~ 4 Ignition transformer failure 4<1 High voltage grOi,lnded
4b Transformer defective
H No pilot flame
-1 No fuel sLWly
.2 Pilol valve inoperative
1a Manual pilot shutoff alva should be wide open 1b Fuel line plugged
1c Low or high gas pressure switch open-adjusl pilot
gas pressure regulator
23 No power at flame safeguard control terminals 2b Incorrect or broken wiring
2c Din in valve, or orifice plugged
2d Faulty actuator or valve
I Flame flOl detected
(llame relay does
no! pUll in)
1 Flame detector (general) 1a Dirty lens, filter, or viewing window
1b Dirt in sight pipe
1c Dirty cells
10 Loose cell
1e, Detector moved to poor location
11 Sighting of detector shifled
19 Delector overheated
1h Low or unstable flame signal
1i Defective detector
2 Fire condition 2a smoky fire
2b Fire pallern changed (Ufled or deflectad')
2c Flame adjustment too lean
3 Wiring 3a Poor connection between burner Qround and flame
safeguard control (Run separate ground wire.) 3b Loose connections
3c Excessively long flame detector laadwires
3d Water in condutt with flame detector leadwifes
Sb Ig'lition interference (SLblraCtive)
St Inadequate grOUnd area
5d Irrprcperly tocaled in flame
59 Broken flame ro::l
6 Infrared (lead sulfide) detector Ga Magnetic piCkup ()(l leads (Should be shielded and
anchored to prevent free vibration or swinging.) fib Defectlve cell
I 7 Ultraviolet detector 7a Excessive vibration (can loosen components in
C7012 types.) 7b C7012-faully electron lube(s)
8 Faulty flame signal amplifier Ga Replace (if a plug-in type)
196
Trang 12DURING THE MAIN BURNER FLAME·ESTABLISHING PERIOD
J Main burner does
not light-detective
pilot
1 Pilot flame too small ("soft pilot") la Pilot air vents Clogged
lb Blower inlet clogged
lc Brower housing dirty
ld Blower fan dirty
le Pilot air line dirty
H Blower not running
19 Excessive pilot fuel (ori11ce enlarged)
2 Pilot outage 23 loose connection to pilot valve
2b Main burner air SlWIy blowing out pilot
2c Pilot gas vatve partially closed
3 Pilot not adjusted prcperly 3a Adjust air-fuel ratio
3b Adiust pilot position so 11ame will ignite main burner
K Main burner does
not light - improper
4 Pilot size shrinks 4a Pilot line tap on main fuel line is downstream of
main pressure rSQulator (ShoUld be upstream with separate regulator if one is needecl.)
1 Manual main fuel shutoff valve closed
la Open it
fuel supply
2 Safety shutoff valves not opening 2a No power at actuator or at valve terminal on llama
2b Valve stuck in closed p::lSition
2c Defective valve or actuator
2d Check gas pressure switch (see causes 4 and 5)
3 vent valve cpen 3a Power at valve actuator
3b Valve stuck open
3c Check for proper operation of valve and actuator
4 Low gas pressure switch open 4a Check location of low gas pressure switch in gas
line May open when main gas valve closes
4b Adjust gas pressure regulator
5 High gas pressure switch open sa A pressure regulating valve that does not close off
tight will allow line pressure to build up ahead of the main valve Opening the valve allows excess
pressure in line
Sb Adjust gas pressure regUlator
6 Improper air·fuel ratio Ga Adjust as necessary
6b Check burner motor (blower) cperation
7 Low fueltemperalure (oil) 7a O1eck temperature of oil from oil heater (heavy
oils)
7b Defective oil temperature control
7c Defective wiring
8 Faulty fuel system Ba Fuel line downstream from main fuel valve is too
long-requires eltCessive lime to get fuel to the burner
Bb Plugged or dirty fuel line
8c Out of fuel (Oil)
Sd Low atomizing steam or air prSSSlJre (Oil)
(continued on next page)
Trang 13PROBLEM POSSIBLE CAUSE CHECK
L Main burner lights,
but QOel5 out
1 Main burner flame nol detected 1a Deleclor has pool' view 01 main burner 11ame
(sightil'lQ plIol but not main flame)
1b Detector shifted
1e Smoke in r:ombustlon eharrber
1d Oil ~apors screening deteclor from flame
2 Imprcper air-fuel ratio 2a Flame unstable-poor shape, quallly or position
Adjust air-fuel ratio
.2b Cheek burner motor (blower) operalion
';
3 Faulty fuel system 3a Low fuel pressure
3b Fuel spray patlem distone:1
Je Oil lank nearly amply Pump is pullin~ air atter a small inilialflow
3d Cold oil in line belween healef and burner Try a reslan
36 AtomiZing sleam or air SlWly pressure 100 low (oil)
DURING A CHANGE IN THE FIRING RATE
M Flame goes oot
du(lng firing rate
charge
1 P~r sUl+Ily voltage drq:l
2 Conditions in combus:ion charrber
1a AcXjed electriea\ load on jXJWer sU~Iy when lirirg rate changes-check circuilry and cO"Inections_
2a Smoke screen between delector and ftame
2b Change in alr·fuel rallo
2c Change in flame paHern
2d Change in oil spray pattern
2e Reclrculalion ol atornlzedoil
N Flame QOes oul , _ Power sUWly ~ariation " Line ~oltage drop due to on-off switching 01 a heavy
electrical load,
1b Power failure
2 Failure In lhe flame deLeclion 2a Check flame signal amplifier Replace amplifier 'f it
2b Clreck 11ame deleclOr
2c If using a 'lame 100, make sure it is nol louching hot re1ractory AlSO check the tempera lure at its
Insulator - if more lhan SOO F [2f>O C], move 11ane rod to a cooler location
2d 11 using an infrared deteclor, chack for hot refractory saluration-make sure that radiation from hot refraclory does not mask the 11ickering radiation of the flame UseN'
38 Delermine cause(s) and correct the condition(s) 3b It airilow switch Is cpen, check burner motor tb!ov'ler) and i!s associaled componenls and circuitry
3 Limil or interlock op8'ls
~
" Check tor improper wiring or deteriorated lead -ires
4b Check: operalion of the val~e and aclualor
4 safety shutoft val~e closes
5• Clean fuel line
5 Plugged 1I.Je1 line
Trang 14RANDOM SHUTDOWNS
The same general step-by-step procedure is followed
"when troubleshooting random shutdowns as outlined lor
S',ep 1 - Know the system and
Step 2-Ask
Step
S Slep"6- Verify the assumed cause by a test
When troubleshooting random shuldoVoTlS, slep
2-asking questions-becomes an especlallv important
step since the troubleshooter may nof be able to actually
witness a burner shutdOwn Important questions that
might be asked are:
- Has the startup period been complelely
normal-including pilot ignition and main burner Iightoff?
- Have both pilot and main buHlsr flames been burning
properly? At all firing rates? Does the air-fuel ratio
seem satisfactory?
- How has the flame Signal been? Stable or oscillating,
and at what level? (Be sure to verify during trial runs:
check detector sighting)
- How iong since the burner has been serviced and
what was done? Was the detector lens, f\\ter, viewing
window, and sighting pipe cleaned? Flama signal
checked?
- How 10nQ had the burner been running continuously
when the last shutdown occurred, and what was the
firing rate?
- Was there anything different tram normal when the
shutdown occurred?
- Has any eqUipment been 1~IaCed recently? If so,
what an.:::l why?
- Has anything in the system been changed, r~laced,
or worked-on, no mailer hOw unrelated it may seem?
EXAMPLES: A new bOiler installed in the next build
ing; another healer or boiler connected to the
same stack or breaching
If the cause Of the problem has not been positively iden
Ilfied after completing the step-by-st~ trOUbleshOOting
procedures, perform routine maintenance on \he burner
Be sure to clean the flame delector, detector mounl, and
any viewino~ windows Check the detector to be sure it has
not shifted in its mount Clean blowers, air dampers, etc
Check the condmon of the pilot and main burner flame,
and adjust as necessary Perform other routine mainte
nance checks on the oorner eqUipment as req.Jired Make
a trial (un to be certain that the burner is cperating
correctly
If the problem recurs after the service call, it is best to
connect a memory type tester to the system to monitor
burner operation and plSilively pinpoint the cause of shut·
dovm
LOCKOUT (SAFETY) SWITCH INDICATION The type of failure Indicated by whether the namesafeguard conlrol is locked out or not dependS on the control design and on the particular awllcation
Some name safeguard primary controls-such as lhe R485-do not have a lockout switch Others-suc:' as the A4138-have a lockout switch that will lock out only on failure 10 ignite Masl automatic primary controls, progammars and microcOl'T"Puter systems- RA890, R4795 R4140, A41SO A4126, R4127, R41al BC7QOO-w\U lock out on either failure to ignite or flame failure during the run period
In addition they may be designed to lock out in other circumstances, or they may permil the installer to determine whether a lockout will occur in a given situation The RAB90G primary conlrol, for exal1l'le, will lock out
it a flame-Simulating failure occurs during stancby II is also typically connected to lock out on limit action Olher controls such as some models of the R4140 Programmer, have a special lockout interlock circuH; they wUllock out on the action of critical interlocks but will recycle on \he action
ot other limits Even If a special circuit is not prOVided, criticallimils may be wired to cut off oorner flame on limit action, causing a flameout that resulls in tripping the lockout switch
In QBneral, safety lockout will indicate a Shutcbwn that
conditions Exal1l'les or such conditions are:
- Poor f\ame characteristics poor pilot, unreliable igni tion source
- FaUlty flame delection system; dirty lens or sighting pipe, burned off or drCllXling flame rod shifted detec
lor mount, overheated detector, loose comJXlflents
- Flame signal al1l'lifier failure
- Operation of critical inlerlocks (dependS upon the application)
Shutdowns which do not result in safely lockout are
generally caused by conditions resulting in momentalf power failure:
- Loss of line VOltage
- Bad ~ces or loose connections,
- Worn or damaged wiring
- Opening of noncritical limits (dependS upon lhe
awlication)
On automatIc systems, the flame sa1eguard control will recycle and make a restart allerJ1)t semiautomatic sys
tems will stqJ and rEqJire a manual reslart
Random shutdowns for the most part may be categorized under 3 main headings:
1 Failure to ignite 01' detect the pilot
Z Failure to light or delect the main bUrner flame
3 Flameout after igniling the pliot or maIn nama Shutdowns of types 1 and 2 occur during iQ'lition trials; type 3 Shutdowns occur during the run period Hcpetully, the cperator will be able to say at what point in the cycle the 1ailure occurred 11 not, all possibilities must be checked In Table m, PJSSibl8 causes are grouped under
these 3 main headings
Trang 15TABLE 111_ TROUBLESHOOTING RANDOM SHUTDOWNS
DURING IGNITION TRIALS P"ROBLEM
A FaHure 10 ignita or
detect the pilOt
CHECK
1 Limit or Interlock open 1a Loose, worn, or damaged wiring
1b Temporary condillon Find and correct the condilion(s) causing the limit or interlock 10 open
2b Worn or damaged high voltage leadwires
Ja Manual pilot shutoff valve parity closed
3b Temporarily Clogged orifice in the pilot valve 3c Temporarily pinched or clogged pilaf fuel line
.:la Air register dirty
4b Air damper loose, causing temporary closing of air register
4c Diny or restricted air passages In the burf'\9r
4d Air s\.Wly line pinched, or temporarily restricted
by dirl or scale
48 Diny rotor, passages or housing in lhe burner motor (blower)
detector - may be te"'lXlrarily open or grounded
Sb Loose flame deteclor-shifted its position so it Cba5n't sighl the pilot flame properly
Sc Dirl on the delector lens, filter, or viewing window,
or in the sighting pipe
50 Temporary hot spot in the combLlstion chamber, causing overheating of the detector
se If using a Ilame rod: intermi\lent vibrations causing flame rod to be grounded; dirty or craCked insulator
S! If using a C7012 detector: power SUJ:Ply 1luctuation
Sg Inlermittent circuit in the flame signal amplifier (replace If it is a plug-in type)
5h Loose component(s) in the flame detector
Ga Too smoky Check ail·tuel ralio
6b Flame patlern changed
6c Change in c~ition of fuel
1a lcx:ls9, worn, or damaged Wiring
1b, Temporary condition; correct it
2a Perform checkS under causes 3 and 4 in section
3 Inadaq.Jale fuel suJ:Ply
B Failure to light the
main burner or 10
detect 1119 main
flame
1 Limit or interlock open
2 Inadequate pilot flame
corroustlon chamber
(continued on neld page)
200
Trang 16PROBLEM POSSiBLE CAUSE CHECK
B:.(continued) 3 Marginal air·fuel ralio fer maIn
burner
3a Adjust as necessary
3b Check bUrner motor (blower) cperatlon
3c Perform checks under causes 3 and 4 In section
A abOve (for main burner Une and ~al\les)
3d Low fuel temperature (heavy all)
-
4 Main burner flame nof defected-faulty flame detection system
5 Main burner flame not detected-combustion chamber conditions
Perform checks under cause 5 In seetlon A above (for main flame detector)
sa Perform checks under cause 6 in seclion A abo\le
Sb Oil bumers-\lapors intermittently screen the detector from the lIame
DURING THE RUN PERIOD
C Flame goes Out
,
1 Power SUWly fluctuation 1 Line ~oltage drc:p due to on-oH switching of a
heavy electrical load
1b Power failure
2 Limit or interlock open 2a Loose, worn, or damaged wiring
2b Tem!Xlrary condition; correct it
3 Safety shutoH \la!\le closes :la Loose, worn, or damaged wiring
4 Marginal flame signal 4a Unstable flame-adjust air-fuel ratio; check
com!Xlsition of fuel
40 Main fuel line le~rarily clogged or pinched 4c Decrease in air SUWly -perform checks urder cause 4 in sacho.' A abo\Ie (for main burner) 4d Faulty flame 09leclion system -perform checks uncIer cause 5 in section A atxwe (for main flame detector)
48 Smoky corrbustion chamber; check air-fIJel ralio and CCllllXJSition of fuel
41 Oil bumers-\lapors intermittently screen the detector from the flame
prepurge (no flame)
1 Stray currents induced in lIame detector leadwires
1a Shorten the leadwires (l1'IO\le the flame safeguard control closer to the burner)
1b Use Shielded leadwires and ground Ihe shield at the wiring sutbase
1c Run the leadwires alone In a separate cor"'dJit, and groond the cordJit at the wiring $I tJbase
(conrinU&d on flfJxt page)
Trang 17,-
MEASURING THE FLAME SIGNAL firing rale from low tire 10 hi~ fire and back cbwn and _
while modulating in between (if awlicabJe) Table IV inter
DURING TEST RUNS
preis abnormalllame signal raadinQS that are Indicative of During IrOLbleshOOling, il Is strongly recommended problems.
thallhe 11arne signal be measured throughouf all test runs
NOTE: To find oul hOw 10 measure the flame signal, refer Flame sit;;Jl31 measurements provide valuable information I.Q the Checkout section of the applicable instruction
on system operation The flame signal should be ctlserved sheet
for the flame safeguard control
from slart~ 10 shutdown, including dJring changes in the PREVENTIVl: MAINTENANCE - - -
A prS"venliv8 maintenance program should be estab eralion, and actual maintenance procedures
lished for the bumer and lis associated oquipmenl 10 en Whenever a service technician is engaged in either of
sure maximum availability of the burner, PrevenlivB thBSIJ endeavors, they 6hould keep in mind the following maintenance is divided inlo 2 parts-checking system op- • Ten Commancrnents.·
1 Always close all manual fuel valves anlordisconnectthe wiring from all aL1lomatlc fuel valves before starting a checkoL11
of a burner syslem
2 Visually jnspect every combuslion charrt>er and assure YOL1rsetf that lhere is no accumulation of combustibles before allempting to start a burner system
4 Never p JSh in relays (unless the manufacturer's inslruclions tell you to)
S Nevar permanently hold In relays wllh rul:lber bands, slicks, or other devices
6 Never change the 10ckd\Jt (safety) swllch liming of a flame safeg ard control If lhe system is locking oul, cure the dis
ease, not the sy~om
7 Never permanenlly jumper or bypass any safety interlocks or limit switches, This is extremely dangerous
8 Conducl a Pilot Turndown Test on every new iob before putting the burner Into service, and periodically thereafter
9 Conducl all required Salety Shutdown Tests (inCluding a Flame Failure Response Test) on every burner al startup and
at least once a year thereafter
10 Regard every burner shutoown as a safety 6huloown until provsn otherwise
CHECKING SYSTEM OPERATION
System operalion should be checked 01"1 a regular ba·
sis Normally a schedule of onc~ a month is satisfactory, but this may be riloc:Iifled depending on the operating con
dition 01 the burner and the Importance of maintaining burner operation In process awlicatlons, et;lElratlon migl'lt
be checked on a conlinuOU! or daily baSis, Accurate records should be kept on all Cbservalions
By corrparing performance wllh records of past condi
tions, potentially trOUblesome ChanQBS can be identified and corrective Slaps taken
FLAME SIGNAL MEASUREMENT
"The flama signal is the most important Indlcalor of 1lamecondition A drop In the Ilameslgnal, or a shift from a steady (stable) to an unsteady reading, indicates the need
tor corrective action to avert a 6hulOOwn Ideally, the flame Si "al should be checked for all of lhe following conditions:
a During prepurge (A flame siQnal during prepurge indicates a Slray current Induced in the leadwires, a component failure simulating a flame, response 10 hoi refractory, or an unwanted flame present In the combustion chamber This signal must be eliminated.)
b Al the beginning of Ignition Trials with only the ignition on (A flame signal indicates response to the ignition spark and must be elimlnaled.)
c Pilot wllh eleclric ignition on
d Pilot with eleclric iQnltlon off
e Main burner flame and pilot oolh on
f Main burner flame on, pllol off (interrupted pilot) Measurements d and f (pilol alone and main burner flame alone) are particularly useful as indicators of general system condillons Table IV liSts corrective aclions for abnormal flame signal readinl;J>
CONDITION OF THE PILOT AND MAIN BURNER FLAMES
"The general condition-hard, medium, or soft-ol ooth pll01 and main burner flames shOUld be checked On mOC1Jlaring burners, main flame conditions should be cbS9NecI throughout the full 1Iring range Any awarent Change in lhe air-fuel ralio when the firing rale changes should be investigated On mUltiple stage burners, the flame should be checked at each firing rate It is possible thaI there will be a momentary change In the flame quality resL1l1ing In a very short smoky period as the burner goes
from one slage to anolher This can usually be ignored If the fire recovers to a clean condition promplly
202
Trang 18(more than 1/2 micre>arT1J)
when ignition is turned off
and only the pilot is on
D Unsleadi (unstable), or
less than the minimum
acceptable current (when
measuring (he pilot alone,
the main burner flame
alone, or bolh 10000therO
NOTE: Flame signal
requirements vary:
Consult the label on the
plug-in flame signal
amplifier, or the CheckOut
seclion 01 the Instruction
sheet 'for lhe flame
sa1ElQJC!rd control
TABLE IV-INTERPRETATION OF FLAME SIGNAL READINGS
DURING IGNITION TRIALS ABNORMAL
1 (continued)
2 Flame-simulaling componenl failure
3 Flame deteclor responding
to hot refractory (rectifying photocell or in1rared detector)
4 Unwanted flame in combustion chamber
1 Flame deleclor responding
to ignitiO/l spark (ultraviolet detectors)
1 Iglilion interference (flame reds)
1 Unslable flame
1d Keep the exposed wires at the ends of the shield or conduit as short as p:>ssible, and lwist them before making connections
le Anchor leadw'ires and conduit at close intervals to avoid noise pickup due 10 vibrations
23 Check flame signal amplifier: replace if defective (plug-in type)
2b Check flame detector; replace i1 defective
3a Add orifice ahead of cell to restrict viewing area 3/) Resighl detector at a cooler, more distant part ot the comoustion chamber
3c Inlrared detector: lengthen the sighting pipe or decrease the pipe size (diameter)
4a Correct the condilion(s} causing the flame
'a Resight lhe detector farther away from the spark or
lb II may be necessary to construcl a barrier 10 shield
lhe spark from the detector
lc Continue adjustmenls until the flama signal due to lhe spark is less lhan 1/4 micr~
1a Make sure there is enough grOlind area
lb Be sure the ignition electrode and flame roo are on q:;p::lSile sides of the ground area
lc Check for correct spacing on the ignition electrode: ,6,000 voll systems~ 1/16 10 3132
ld Make sure the flame rod and i",ilion teadwlres are not too close 10000ther anywhere; replace ant worn
or damaged leadw'ires
le If the problern cannot be eliminated, you may have
to ctJar"9! to an ultraviolet nama delec\ion system
la Adjust air-fuel ratio
lb_ CheCk burner motor (blower) operatlm
lc ~just pressure reg.Jlators
ld Make sure manual fuel shutoff valves are wide q:l9I"I 1e Check fuel line- it may be dirty or pinched
1f Clean the air register, air supply line, air passages,
and blower
lQ Q1eck thaI the composition of the fuel has noe changed
1h Oil burners: adjust oil spray pattern; increase fuel
lerrperature (heavy oil)
(conlinUfld on non page)