EN 50068:1991PageFigure 21 — Necked out opening 22 Figure 22 — Calculation scheme for Figure 23 — Calculation scheme for Figure 24 — Calculation scheme for adjacent branches in longitudi
Trang 2BS EN 50068:1991
This British Standard, having
been prepared under the
direction of the Power
Electrical Engineering
Standards Policy Committee,
was published under the
authority of the Standards
Board and comes
into effect on
30 September 1991
© BSI 12-1999
The following BSI references
relate to the work on this
standard:
Committee reference PEL/92
Draft announced in BSI News
Amendments issued since publication
Amd No Date Comments
8054 January 1994 Indicated by a sideline in the margin
Trang 3PageCooperating organizations Inside front cover
Trang 4version of EN 50068:1991 and its Amendment A1:1993 “Wrought steel enclosures
for gas-filled high-voltage switchgear and controlgear” published by the European
Committee for Electrotechnical Standardization (CENELEC)
National appendix NA gives the constitution of the committees responsible for
UK participation in the preparation of this standard
National appendix NB gives details of International Standards quoted in this standard for which there is an identical or technically equivalent British Standard
A British Standard does not purport to include all the necessary provisions of a contract Users of British Standards are responsible for their correct application
Compliance with a British Standard does not of itself confer immunity from legal obligations.
Trang 5UDC 621.316.54-213.34-034.14
Descriptors: Enclosure, high-voltage switching device, H.V metal enclosed switchgear and controlgear, pressurized closure, wrought
steel
English version
Wrought steel enclosures for gas-filled high-voltage
switchgear and controlgear
(includes amendment A1:1993)
Enveloppes en acier soudé pour l’appareillage
à haute tension sous pression de gaz
(inclut l’amendment A1:1993)
Kapselungen aus Schmiedestahl für gasgefüllte Hochspannungs- Schaltgeräte und -Schaltanlagen
(enthält Änderungen A1:1993)
This European Standard was approved by CENELEC on 5 March 1990
CENELEC members are bound to comply with the CEN/CENELEC Internal
Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration
Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Central Secretariat or to any
CENELEC member
This European Standard exists in three official versions (English, French,
German) A version in any other language made by translation under the
responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions
CENELEC members are the national electrotechnical committees of Austria,
Belgium, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy,
Luxemburg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and
United Kingdom
CENELEC
European Committee for Electrotechnical StandardizationComité Européen de Normalisation ElectrotechniqueEuropäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B-1050 Brussels
© 1991 Copyright reserved to CENELEC members
Ref No EN 50068:1991 + A1:1993 E
Trang 6EN 50068:1991
© BSI 12-1999
2
Foreword
At the request of CENELEC Technical Committee
TC 17C, the text of the draft EN 50068 prepared by
TC 17C was submitted to the Unique Acceptance
Procedure (UAP)
The text of the draft was approved by CENELEC as
EN 50068 on 5 March 1990
The following dates were fixed:
For products which have complied with the relevant
national standard before 1991-06-01, as shown by
the manufacturer or by a certification body, this
previous standard may continue to apply for
production until 1996-06-01
This document forms a supplement to
EN 50052 (1986): “Cast aluminium alloy enclosures
for gas-filled high-voltage switchgear and
controlgear” and EN 50064 (1989): “Wrought
aluminium and aluminium alloy enclosures for
gas-filled high-voltage switchgear and controlgear”,
concerning welded enclosures for the same type of
switchgear and controlgear but composed of parts
made of wrought steel It is based on the general
specifications given in HD 358 S2 (IEC 517 (1986)
ed 2) which are however not sufficient to satisfy the
conditions for the service allowance of pressurized
high-voltage switchgear and controlgear.)
These specifications are appropriate for pressurized
switchgear enclosures allowing an economic
production without sacrificing aspects of safety For
unusual shapes dictated by electrical conditions
they permit the verification of sound design by proof
tests instead of calculations Nevertheless this
European Standard makes use of many
internationally well acknowledged calculation
rules and the Technical Committee will in
addition pursue the progress in standardization in
CEN/TC 121 and ISO/TC 44 on welding and allied
processes
For the time being reference can only be made to
published International Standards as far as they
are appropriate for the purpose of production of
enclosures to be used in gas-filled switchgear and
controlgear
The present EN has been established as an international specification for the design, construction, testing, inspection and certification of pressurized enclosures used in high-voltage
switchgear and controlgear This standard follows to that extent also Article 2 of the Directive 76/767/EEC
The European Standard contains two normative and one informative technical annexes:
Annex A: Welding procedure and welder performance tests
Annex B: Sample of record form
Annex C: National deviations
List of standards referred to in this standard:
Foreword to Amendment A1
This amendment was prepared by CENELEC Technical Committee TC17C, High-voltage enclosed switchgear and controlgear
The text of the draft was submitted to the voting procedure in March 1993 and was approved by CENELEC as amendment A1 to EN 50068:1991 on July 6, 1993
The following dates were accepted:
— latest date of publication
(IEC 517 (1986) ed 2) Gas-insulated metal-enclosed switchgear
for rated voltages of 72,5 kV and above
ISO 6213:1983 Welding: Items to be
considered to ensure quality
in welding structuresISO 9000:1987 Guidelines for selection and
use of the standards on quality management, quality system elements and quality assurance
ISO/IEC Guide 2:1986 General terms and their definitions concerning
standardization and related activities
ISO 6520:1982 Classification of
imperfections in metallic fusion welds, with explanationsISO/R 373:1964 General principles for
fatigue testing of metals
— latest date of publication
of an identical national standard (dop) 1994-10-01
— latest date of withdrawal
of conflicting national standards (dow) 1994-10-01
Trang 7Text of amendment
2.1 Type of equipment (page 5)
The first paragraph has to be changed as follows
(new text in bold letters);
of high-voltage switchgear and controlgear,
where the gas is used principally for its
dielectric and/or arc-quenching properties,
with rated voltages.
— 1 kV and up to and including 52 kV and
with gas-filled compartments with design
pressure greater than 3 bar (gauge);
— and with rated voltage 72,5 kV and above.
Annex C (page 67) — only English version
6 Manufacture and workmanship 40
7 Inspection and testing 46
8 Pressure relief devices 53
9 Certification and marking 53Annex A Welding procedure and welder
Annex B Sample of record form 65Annex C (informative) National deviations 67Figure 1 to Figure 4 — Typical connections
between cylindrical and conical shells 11Figure 5 — Design factor ¶ and numerical
Figure 6 — Dished end 15Figure 7 — Dished end with branch 15Figure 8 — Dished end with knuckle and
crown of unequal wall thickness 15Figure 9 — Welded joint
outside 0,6Da: v = 0,75 resp 1,0 16Figure 10 — Welded joint
inside 0,6Da: v = 1,0 16Figure 11 — Welded dished end from
crown and knuckle components
inside 0,6Da: v = 1,0 17Figure 12 — Welded dished end from
crown and knuckle components
outside 0,6Da: v = 0,75 resp 1,0 17Figure 13 — Design factor ¶ for dished
ends of the Klöpper type 19Figure 14 — Design factor ¶ for dished
ends of the Korbbogen type 19Figure 15 — Determination of the
Trang 8EN 50068:1991
PageFigure 21 — Necked out opening 22
Figure 22 — Calculation scheme for
Figure 23 — Calculation scheme for
Figure 24 — Calculation scheme for
adjacent branches in longitudinal direction
Figure 25 — Calculation scheme for
adjacent branches in a sphere or in
circumferential direction of a cylinder 25
Figure 26 — Branch and pad reinforcement 26
Figure 27 — Weakening factor vA for
openings and branches perpendicular to
cylindrical and conical shells 27
Figure 28 — Weakening factor vA for
openings and branches perpendicular to
Figure 29 — Circular flange joint 29
Figure 30 — Examples of different
Figure 31 — Forces and moment arms
for flanges with O-ring seal 32
Figure 32 — Hubless flange sections
for stress calculation 32
Figure 33 — Flange with untapered
hub section for stress calculation 33
Figure 34 — The factor “A” as a function
Figure 35 — Graph showing in (Dy/Di)
as a function of m = Dy/Di 36
Figure 36 — Forces and moment arms
for flanges with O-ring seal 37
Figure 37 — Flange with large fillet
radius sections for stress calculation 38
Figure 38 — Flange with tapered
hub sections for stress calculation 39
Figure 39 — Flange with flat circular
cover and O-ring seal 40
Figure 40 — Butt welds in plates of
unequal thickness with approximately
coincident middle lines 47
Figure 41 — Butt welds in plates of
unequal thickness with offset of
(not exhaustive; other steels may be used from national standards) 8Table 2 — Design factor ¶ for conical
shells and numerical factors
Table 3 — The factor “A” as a function
Table A.2 — Number of test
Trang 91 Introduction
This standard covers the requirements for the design, construction, testing, inspection and certification
of gas-filled enclosures for use specifically in high-voltage switchgear and controlgear or for associated gas-filled equipment Special consideration is given to these enclosures for the following reasons
a) The enclosures usually form the containment of electrical equipment, thus their shape is determined
by electrical rather than mechanical considerations
b) The enclosures are installed in restricted access areas and the equipment is operated by experts and instructed persons only
c) As the thorough drying of the inert, non-corrosive gas-filling medium is fundamental to the
satisfactory operation of the electrical equipment it is periodically checked For this reason, no internal corrosion allowance is required on the wall thickness of these enclosures
d) The enclosures are subjected to only small fluctuations of pressure as the gas-filling density shall be maintained within close limits to ensure satisfactory insulating and arc-quenching properties
Therefore, the enclosures are not liable to fatigue due to pressure cycling
e) The operating pressure is relatively low
For the foregoing reasons, and to ensure the minimum disturbance hence reducing the risk of moisture and dust entering the enclosures which would prevent correct electrical operation of the switchgear, no pressure tests shall be carried out after installation and before placing in service and no periodic inspection
of the enclosure interiors or pressure tests shall be carried out after the equipment is placed in service
2 Scope and field of application
Busbars and connections
The scope also covers pressurized components such as the centre chamber of live tank switchgear, gas-insulated current transformers, etc
2.2 Production
The production of the enclosures shall be in accordance with documented welding procedures which shall
be carried out by well trained and supervised welding personnel Where International Standards (ISO or CEN) are not available national standards may be used
NOTE The standard will be revised as soon as possible when ISO or CEN standards covering the various aspects are available.
NOTE Reference should be made to the ISO 9000 series of standards for quality systems.
Trang 10design pressure (of an enclosure)
pressure used to determine the thickness of the enclosure It is at least the upper limit of pressure reached within the enclosure at the design temperature HD 358 S2 = IEC 517 (1986) ed 2
3.6
design temperature (of an enclosure)
highest temperature reached by the enclosure which can occur under service conditions This is generally the upper limit of ambient air temperature increased by the temperature rise due to the flow of rated normal current HD 358 S2 = IEC 517 (1986) ed 2
NOTE Solar radiation should be taken into account when it has a significant effect on the temperature of the gas and on the mechanical properties of some materials Similarly, the effects of low temperatures on the properties of some materials should be considered.
Trang 11the materials given in clause 4.
The rules take into account that these enclosures are subjected to particular operating conditions (clause 1)
which distinguish them from compressed air receivers and similar storage vessels
The thicknesses determined by the various equations are minima and therefore the specific nominal thickness shall be increased by the amount of any negative tolerance permitted by the material
In the case of such an enclosure or an enclosure for which calculations are not made, a proof test of the individual housing is necessary before the internal parts are added
Trang 12Table 1 — Examples of materials (not exhaustive; other steels may be used from national standards)
NFA 36 – 601
[forgings]
A37 – CP A37 – AP A37 – FP A42 – CP A42 – AP A42 – FP A48 – CP A48 – AP A48 – FP
SS14 13 30-01SS14 14 30-01SS14 14 32-01SS14 21 06-01SS14 21 17-01
SS 142333
SS 142343
UN1 5869-75UN1 7382-75UN1 7070-82UN1 8317-81UN1 7660-77[forgings]
Trang 13When designing an enclosure, account shall be taken of the following, if applicable.
a) The possible evacuation of the enclosures as part of the filling process
For enclosures of this type it is usually necessary to evacuate the air before introducing gas pressure, this ensures purity of the gas The evacuated condition is therefore not an operational condition and in most cases enclosures designed for internal pressure will be suitable for the evacuated condition without buckling
For certain long lengths and large diameters of busbar sections, however, it is possible that the
enclosure will buckle due to external pressure In such cases the design should be checked for external pressure and the enclosure strengthened if necessary Since this is not an operational condition it is not
a matter of safety
b) The full differential pressure possible across the enclosure wall
c) Superimposed loads and vibrations by external effects
d) Stresses caused by temperature differences including transient conditions and by differences in coefficients of thermal expansion
e) Effects of solar radiation
NOTE Pressure stresses due to an internal electrical fault are not considered in the design of an enclosure since after such an occurrence the enclosure would be carefully checked and, if necessary, replaced.
For the case of arcing due to an internal fault, reference is made to HD 358 S2 (IEC 517 (1986) ed 2)
5.4 Design pressure
The design is based on the design pressure as defined in clause 3.5.
5.5 Design temperature
The selection of material and the determination of the design stress depend upon the highest wall
temperature which can be expected during service at the design pressure (p).
5.6 Design stress basis
The nominal design strength K shall be selected from the material standard, where
K = yield strength or 0,2 % proof stress at the design temperature.
(For austenitic steels the 1 % proof stress may be used)
The safety factor against yield strength, 0,2 % proof stress or 1 % proof stress, is S = 1,5 Hence it follows the permissible design stress B = K/1,5.
5.7 Calculation of shells, dished ends, openings, screws and bolts
For the purpose of calculation of shells, dished ends, bolts, screws and openings the following specific symbols are used:
di internal diameter of openings and branches mm
tA required wail thickness at openings mm
x distance over which the governing stress is assumed to act mm
h1 height of the straight flange of dished ends mm
Trang 14EN 50068:1991
5.7.1 Cylindrical shells
The required wall thickness is:
The minimum permissible wall thickness of cylindrical shells is 3 mm
Pi loading of an area (A) with regard to internal pressure N
¶ design factor
n number of screws per flange joint Ps/Pi = —
clamping force per screw = Ps/n N
(Equation 1)
Ps´/P´i
P´
P´s
Trang 155.7.2 Spherical shells
The required wall thickness is:
The minimum permissible wall thickness of spherical shells is 3 mm
Figure 1 to Figure 4 — Typical connections between cylindrical and conical shells
(Equation 2)
Trang 16thickness calculated according to 5.7.3.1 or 5.7.3.2 is to be taken into consideration For the shallow conical
shells with an angle of slope to the axis of the cone Î1 > 70° the wall thickness shall be determined according
to 5.7.3.3 even if smaller wall thicknesses as according to 5.7.3.1 and 5.7.3.2 are found.
In equations 3 and 7 the weld joint factor (v) refers to the circumferential joint and in equation 6 to the
longitudinal joint
If the distance between the circumferential joint and the knuckle is at least 0,5x then the equations 3 and 7
is the weld joint factor v = 1,0.
The minimum permissible wall thickness of conical shells is 3 mm
5.7.3.1 Calculation based on the stress in meridional direction
The required wall thickness is:
The design factor ¶ is to be taken from Table 2 or Figure 5 depending on the difference Ó between the angles of slope of two adjoining shells
and the ratio of the knuckle radius by the external diameter of the shell r/Da
A Shells with knuckle (Figure 1 and Figure 2)
If the wide end of a conical shell is flanged to a knuckle then the wall thickness in the knuckle shall be determined according to equation 3 and shall be maintained away from the knuckle in the conical section over a distance of at least
and along the cylindrical section over a distance of at least 0,5x.
B Shells without knuckle (Figure 4)
Conical shells may be connected with each other or with cylindrical shells by means of welded butt joints providing the following is met:
a) Ó k 30°;
b) joints welded from both sides;
c) the length of the two shells shall be at least 2x according to equation 5.
If deviating from b) the butt joints are to be welded from one side only, then equivalence with joints welded from both sides shall be demonstrated by a welding procedure test
(Equation 3)
(Equation 5)
Trang 17Table 2 — Design factor ¶ for conical shells and numerical factors cos Î and 1/cos Î
The wall thickness for both shells at the butt joint shall be determined under consideration of the bending stress in the circumferential seam according to equation 3
Figure 5 — Design factor ¶ and numerical factor 1/cos Î
AngleÎ
resp. Ó
¶for a ratio ofr/Da
cos Î 0,01 0,02 0,03 0,04 0,06 0,08 0,10 0,15 0,2 0,3 0,4 0,5
1,21,72,23,35,18,010,7
1,21,62,03,04,77,29,5
1,11,41,82,64,06,07,7
1,11,31,72,43,55,37,0
1,11,21,62,23,24,96,3
1,11,11,41,92,84,25,4
1,11,11,31,82,53,74,8
1,11,11,11,42,02,73,1
1,11,11,11,11,41,72,0
1,11,11,11,11,11,11,1
0,9850,9400,8660,7070,5000,3420,259
1,0151,0641,1551,4142,0002,9203,861
1 cos Î
Trang 18
-EN 50068:1991
5.7.3.2 Calculation based on the stress in tangential direction
The required wall thickness is:
where the weld joint factor (v) is the efficiency of the longitudinal joint and the numerical factor 1/cos Î1
has been taken from Table 2 or Figure 5
The design diameter (Dk) is to be determined according to Figure 1 to Figure 4 and the distance x according
to equation 5
In the case of conical shells connected with each other the wall thickness shall be calculated for each shell with its individual angle of slope to the axis (Î1 or Î2) of the enclosure
5.7.3.3 Shallow conical shells (:1 > 70°)
The required wall thickness is:
If the distance between knuckle and circumferential joint is at least:
then the weld joint factor is v = 1,0.
Provided the requirements for shells without knuckle are met (see 5.7.3.1), conical shells with different
angles of slope may be joined by butt welds This requires a knuckle radius of r = 0 in equation 7.
5.7.4 Dished ends subject to internal pressure
C Hemispherical dished ends
Other configurations for dished ends may be used with appropriate calculation or proof test
Up to a wall thickness of 50 mm the height of the straight flange (h1) need not exceed 150 mm With hemispherical dished ends no straight flange is required
Trang 19Shorter straight flanges (h1) are acceptable provided the circumferential joint between dished end and cylindrical shell is non-destructively tested to the same extent as a fully strengthened butt joint with a design stress level equal to the permissible design stress level.
If a dished end is welded together from crown and knuckle components, the joint shall be at a sufficient distance from the knuckle The distance shall be regarded to be sufficient, if in the case where
a) crown and knuckle are of different thickness (see Figure 8)
b) crown and knuckle are of equal thickness (see Figure 6)
x = 3,5t for dished ends of the Klöpper type
x = 3,0t for dished ends of the Korbbogen type
with a minimum however of at least 100 mm
NOTE When determining the transition from the knuckle to the crown of a dished end the starting point shall be the internal
diameter With thin-walled dished ends of the Klöpper type the transition is about 0,89Di, and with thin-walled dished ends of the
Korbbogen type it is about 0,86Di These factors get less as the wall thickness increases.
(Equation 12)
Figure 6 — Dished end
Figure 7 — Dished end with branch
Figure 8 — Dished end with knuckle and crown of unequal wall thickness
Trang 20EN 50068:1991
5.7.4.2 Percentage of the permissible design stress level in joints
A weld joint factor v = 1,0 may be applied, if the extent of testing corresponds to that specified for a design
stress level equal to the permissible design stress level or if the dished end is made from one plate
A weld joint factor v = 1,0 may also be applied in the case of welded dished ends (with the exception
of hemispherical dished ends) regardless of the extent of testing provided the welded joint intersects
the crown area of 0,6Da (see Figure 10 and Figure 11) If the welded joint does not intersect the
crown area of 0,6Da, the weld joint factor is v = 0,75 or v = 1,0 according to the extent of testing
(see Figure 9 and Figure 12)
5.7.4.3 Weakening due to openings and branches (Figure 7)
Openings in the crown are of 0,6Da of dished ends of the Korbbogen and Klöpper type and in hemispherical
dished ends are to be checked for adequate reinforcement according to 5.7.5 without taking into account
the design factor ¶ In the case of pad reinforcement the pad shall not go beyond 0,8Da with dished ends of
the Klöpper type and 0,7Da with dished ends of the Korbbogen type
Figure 9 — Welded joint outside 0,6Da : v = 0,75 resp 1,0
Figure 10 — Welded joint inside 0,6Da : v = 1,0
Trang 21For openings outside the crown area of 0,6Da increased design factors ¶ according to Figure 13 and
Figure 14 apply Where the ligament between adjacent openings is not entirely within 0,6Da then the minimum width of the ligament shall be at least equal to the sum of half the opening diameters
measured on the distance between the centres of the openings
5.7.4.4 Calculation rules
The required wall thickness of the crown is:
The required wall thickness of the knuckle is:
The design factors ¶ for dished ends (with or without openings and branches) are to be taken from;a) Figure 13 for dished ends of the Klöpper type
b) Figure 14 for dished ends of the Korbbogen type
as a function of t/Da and di/Da
Figure 11 — Welded dished end from crown and knuckle components inside 0,6Da : v = 1,0
Figure 12 — Welded dished end from crown and knuckle
components outside 0,6Da : v = 0,75 resp 1,0
(Equation 13)
(Equation 14)
Trang 22EN 50068:1991
The curves with di/Da > 0 apply for reinforced openings in the whole crown and knuckle area The design factor ¶ = 1,1 applies regardless of the wall thickness to hemispherical dished ends in a distance of:
adjacent to the welded joint
With dished ends of the Klöpper type and Korbbogen type subject to internal pressure an additional check
is required to make sure whether the knuckle is adequately dimensioned to prevent elastic buckling (the
formation of folds in the knuckle) This is the case where the buckling pressure (pB) according to Figure 15
is equal or higher than 1,5 times the design pressure (p).
The minimum permissible wall thickness of dished ends is 3 mm
The stress distribution due to internal pressure in dished ends of the Korbbogen and Klöpper type is determined by means of the elastic analysis (see Annex A)
5.7.5 Openings in cylindrical, conical and spherical shells subject to internal pressure
5.7.5.1 General
These rules apply for circular openings in cylindrical, conical and spherical shells subject to internal pressure and for their compensation
These rules cover ratios of di/Da k 1,0
NOTE Experience has shown that in the case of great diameter ratios, stresses occur in the cross section perpendicular to the enclosure axis (gusset area).
The results available from research work in this field are not sufficient as to establish general design rules Generally, these stresses
do not result in failure as long as no creep occurs and damage by cyclic loading is not expected.
Additional external forces and moments are not covered by these rules and are therefore to be considered separately
For conical shells these rules apply only if the wall thickness is determined by the circumferential stress.These rules permit plastic deformations of up to 1 % at highly stressed local areas during pressure test Therefore openings shall be designed carefully Abrupt changes of geometry should be avoided
5.7.5.2 Compensation methods
A Increased wall thickness of the shell
Openings are reinforced by increasing the wall thickness of the shell (see Figure 16 and Figure 17)
B Local increase of the wall thickness
Openings are reinforced by means of a set-in or set-on ring or pad (see Figure 18 and Figure 19)
C Increased wall thickness of the branch
Openings are reinforced by increasing the wall thickness of the branch (see Figure 20 and Figure 21)
(Equation 15)
Trang 23Figure 13 — Design factor ¶ for dished ends of the Klöpper type
Figure 14 — Design factor ¶ for dished ends of the Korbbogen type
Trang 25Figure 16 — Increased thickness of a cylindrical shell
Figure 17 — Increased thickness of a conical shell
Figure 18 — Local increase by reinforcement rings
Figure 19 — Pad reinforcement
Trang 26EN 50068:1991
5.7.5.3 Design and finish of openings
Openings are as far as possible to be arranged at a distance of at least x = 3t away from welded joints In
the case of openings in or adjacent to welded joints non-destructive testing of the welded joint in the area
of the opening shall be possible so that in case of doubt the soundness of the joint can be verified
Openings with sharp edges should be avoided
The throat thickness a) of a fillet weld of a pad reinforcement should be at least half of the pad
thickness (0,5h according to Figure 19) In the case of branch reinforcements the thickness of the
load bearing welded joint shall be at least equal to the thinner wall thickness of the connection
The materials of the shell to be reinforced and of the reinforcement itself shall be as far as possible of equal ductility When the design strength of the reinforcement is lower than the design strength of the shell this
shall be considered in the calculation according to 5.7.5.4 The inverse case shall not be applied in the
calculation
5.7.5.4 Weakenings
The weakening effect of openings is generally compensated for by the weakening factor (vA) For branches
perpendicular to the shell the factors vA given in Figure 27 and Figure 28 are adequately precise The wall
thickness tA in these figures is identical with the required wall thickness
NOTE The weakening factor presumes the ability of a structure to shake-down plastic deformations in the elastic range
Thin-walled shells with large openings do not match with this presumption due to their high membrane stress in relation to the bending stress.
If the nominal design strength (K) of the reinforcement is smaller than that of the shell to be reinforced
then for pad reinforcements the cross section of the reinforcement, and for nozzle reinforcements the
branch wall thickness, shall be reduced accordingly before determining the weakening factor vA
from Figure 27 and Figure 28
Figure 20 — Branch reinforcement
Figure 21 — Necked out opening
Trang 275.7.5.5 Calculation schemes
Openings may also be compensated according to the following relation:
which is based on the consideration of the equilibrium between the pressurized area and the load bearing cross section The wall thickness obtained from this relation shall be not less than that of the unpierced
shell For equation 16 the pressurized area Ap and the load bearing cross section AB shall be determined from Figure 22 to Figure 25 where
AB = AB0 + AB1 + AB2
The maximum length of the load bearing cross section to be considered in the calculation shall not exceed
b according to equation 18 for shells and ls according to equation 20 for branches The protrusion of a
branch may be considered in the calculation only up to a length of k 0,5 ls
The requirements specified for pad reinforcements and for reinforcements by increased wall thickness of the branch should be observed
If the nominal design strength K1 or K2 of the reinforcement is lower than the nominal design strength K
of the shell to be reinforced, then the dimensions shall comply with:
It should be pointed out that the required wall thickness tA is to be determined by iteration
(Equation 16)
(Equation 17)
Figure 22 — Calculation scheme for cylindrical shells
l´s
Trang 28EN 50068:1991
A Increased wall thickness of the shell
The weakening factor vA for openings according to Figure 16 and Figure 17 shall be taken from the
lower curve of the Figure 27 and Figure 28 (ts/tA = 0) depending on the ratio:
Figure 23 — Calculation scheme for spherical shells
Figure 24 — Calculation scheme for adjacent branches in
longitudinal direction of a cylinder
Trang 29B Pad reinforcement
If the wall thickness (t) of the cylinder or sphere is lower than the required wall thickness tA at the
opening, then the opening is adequately compensated, if the wall thickness tA is available round the opening over a width of:
In the calculation the wall thickness tA may be taken into account only up to twice the wall thickness (t)
of the shell The thickness (h) of the external pad reinforcement shall therefore not exceed the value t,
(except of set-in reinforcement rings) Internal pad reinforcement should be avoided as far as possible
The width (b) of the pad reinforcement (see Figure 19) may be reduced to b1 provided the thickness of
the pad (h) is increased to (h1) according to:
b1 · h1 U b · h
The limits laid down above should however be observed
C Increased wall thickness of the branch
For reinforcements according to Figure 20 and Figure 21 the weakening factor vA shall be taken
from Figure 27 and Figure 28 depending on the ratio of the wall thickness ts/tA and the related opening diameter:
The wall thickness of protruding branches according to Figure 20 (type c) may be reduced by 20 %
provided the protrusion is U ts (see Figure 26)
The ratio of the wall thicknesses should be
The required length ls of the branch is:
The length of the branch may be reduced to ls1 provided the wall thickness ts of the branch is increased
to ts1 according to:
but taking into account also equation 19
Figure 25 — Calculation scheme for adjacent branches in
a sphere or in circumferential direction of a cylinder
Trang 30EN 50068:1991
D Increased wall thickness of the shell and of the branch
Pad and branch reinforcements may be applied in combination for the compensation of openings (see Figure 26) For the calculation of this kind of reinforcement the requirements specified in B and C shall be applied together
Branches or sockets in series joined to the shell by fully penetrated welds with wall thicknesses calculated for internal pressure only may be designed in a simpler manner with a weakening factor determined by:
where:
L = centre distance of branches or sockets
For branches or sockets joined to the shell by partially penetrated welds di should be replaced by da in equation 23
5.7.6 Screws and bolts in circular flange joints
5.7.6.1 General
These rules apply for the design and manufacture of steel screws for such enclosure flange joints which are not subjected to significant extra forces due to connected piping This category contains screws and bolts for inspection hole covers, blind flanges, removable covers and flange joints
These rules do not apply to pipe flanges where the screws are subjected to higher loads; nor do they concern screws and bolts for manhole covers and the like where the principal sealing force is the pressure acting on the cover The general provisions are, however, applicable to such screws and bolts as well
5.7.6.2 Design rules for circular flanges
The loading of the sealed area with regard to internal pressure only shall be determined by:
Trang 31Figure 27 — Weakening factor vA for openings and branches
perpendicular to cylindrical and conical shells
Trang 32EN 50068:1991
Figure 28 — Weakening factor vA for openings and branches perpendicular to spherical shells
Trang 33The total screw clamping required for satisfactory sealing is determined by:
For flanges with O-ring seals m = 1,2 may be used.
The force on each screw or bolt is:
where:
n = number of screws per flange joint
In determining the screw forces differences in the coefficients of thermal expansion and differences in temperature between flange and screws or bolts shall be taken into account
5.7.6.3 Calculation of screws and bolts
The design area (Ab) of the screw thread is determined by:
With the safety factor S = 1,5 against yielding of bolt material this equation becomes:
If the screw or bolt temperature can be established mathematically or empirically, this temperature shall
be the design temperature However, the minimum design temperature shall be 20 °C even if the
calculation gives a lower value
Figure 29 — Circular flange joint
(Equation 25)
(Equation 26)
(Equation 27)
(Equation 28)or
Trang 34EN 50068:1991
5.8 Calculation of integral flanges and flat circuit covers
For the purpose of calculation of integral flanges and flat circuit covers the following specific symbols are used:
c
D3 diameter of the section through the flange where the radial bending stress is
M1 bending moment per unit length of the mean circumference at junction between
M2 radial bending moment per unit length in flanges N·mmtotal radial bending moment in flanges N·mm
M3 bending moment per unit length of the mean circumference at junction between
Pa total axial force by internal pressure acting on shells or hubs N
Pp total force by internal pressure acting on the annual area inside the gasket N
r fillet radius at junction between flange and shell or hub mm
Trang 355.8.1 General
These rules deal with circular flanges permanently attached to cylindrical shells The flange is assumed to
be made in one piece with the shell or joined to it by welding The flange may be joined directly to the shell
or via a hub which may be tapered or have constant wall thickness
Figure 30 shows without sealing details examples of some different flange types which shall not be considered to be standard
Thus the flange in Figure 30 a) may have a hub of the same wall thickness as the shell and be welded to the shell In Figure 30 d) the flange itself may be welded to the hub
The following rules may also be used to design flange joints to dished ends
5.8.2 Flanges with flat sealing surface and O-ring seal (Figure 31)
The total bending moment (M) of the external forces on the flange shall be calculated according to:
where Pa and Pp are obtained from the equations 31 and 32
NOTE This calculation is based on the assumption that the cross section of the O-ring is smaller than that of the groove.
Figure 30 — Examples of different flange types
t3 maximum wall thickness of tapered hubs mm
Ba axial stress by internal pressure acting on shells or hubs N/mm2
Bb bending stress in shells, hubs or flanges N/mm2
B1 total maximum stress in shells or hubs at junction with flanges N/mm2
B3 total maximum stress in shells at junction with hubs N/mm2
Trang 36EN 50068:1991
(Equation 31)(Equation 32)
Figure 31 — Forces and moment arms for flanges with O-ring seal
Figure 32 — Hubless flange sections for stress calculation
Trang 375.8.3 Flanges with long untapered hub (Figure 33)
These rules also deal with hubless flanges joined to cylindrical shells as shown in Figure 32
The term “long untapered hub” refers to a hub where:
with
and
A Stress in section I-I
The bending moment M1 in section I-I per unit length of the circumference at diameter Dm1 for hubless
flanges of Dm2 respectively for flanges with long untapered hub is calculated according to:
with
where Ù is to be replaced by the corresponding subscript (1 or 2)
The factor A is to be taken as a function of K1 and K2 from Table 3 or from Figure 34 The values of K1and K2 are calculated according to:
The logarithm ln of the numeral m is to be taken from Table 4 or from Figure 35 as a function
Trang 38EN 50068:1991
When m = Dy/Di k 1,5 then the value of ln m can be calculated with great accuracy by means of:
NOTE The equation 40 is also to be used for values of m = Dy/Di approaching 2,5 without great error in the bending moment M1.
The factor A is always less than 1 The figures in Table 3 are therefore decimals; 95 means 0,95
and 096 means 0,096
NOTE The values of the factor A in Table 3 and in Figure 34 apply provided that the flanges have screw holes; an average weakening factor of 0,8 has been inserted If exceptionally there are no screw holes (e.g clamp rings), K2 determined by
equation 39 is to be multiplied with 1,25 to compensate for the weakening factor.
The total maximum stress B1 in section I-I as the sum of the bending stress through the moment M1
and the axial tensile stress through the internal pressure (p) is obtained as follows:
with
and
where:
tE = wall thickness in section I-I of the shell or hub
5.8.4 Flanges with short untapered hub ( Figure 33)
The term “short untapered hub” refers to a hub where:
with ¶2 according to equation 34
A Stress in section I-I
The bending moment M1 is calculated according to equation 36 for a hubless flange, i.e one joined
directly to the shell having the wall thickness t1 This value of M1 is signified by M11
Then bending moment M1 is calculated according to equation 36 for flange with long untapered
hub having the wall thickness t2 This value of M1 is signified by M12
The bending moment M1 in section I-I per unit length of the circumference is calculated
with M11and M12 according to:
The total maximum stress B1 in section I-I is given by equation 41 with the wall thickness t2
æ ö = ln 1 c( + ) = c
1 c/2+ -
Bb1=6 M1/t2E