INSTRUCTION MANUAL

SUDDEN OIL PRESSURE RELAY TYPE PVOA­Y2 ­ 2

(2 contact )

HYODA INSTRUMENTS CORPORATION

Trang 4

reactors shall be provided with safety device that is securely protect an equipment from potential damage caused by internal faults

1 Features

(1) If an accident occurs in a equipment, this relay quickly responds

to fluctuations in the internal pressure and works even if a pressure difference is slight

Therefore the time between the occurrence of an accident and

shutdown can be extremely shortened

(2) Since this relay is mainly to be installed the tank side of a

transformer

(3) This relay uses microswitch for the electric contact, which ensures switching and high reliability

2 Structure

The structure of this relay is shown in Fig 1 As shown in the figure,

The body is made of aluminum alloy casting which provides high air­

tightness The internal section is composed of a movement bellows,

pressure­receiving bellows, orifie(equalizer) and micrositch The switch terminal is to be taken out of the upper terminal box

3 Operation

When the internal pressure of the transformer tank rises rapidly due to

an accident in the transformer, the hydraulic pressure compresses the pressure­receiving bellows, which pushes UP the movement bellows

The motion of the top of the movement bellows pushes in the microswitch lever activating the contact

If hydraulic pressure fluctuation in the transformer are negligible, the microswitch will not be activated regardless of the numerical value of the pressure

Due to the capacity limit in the bellows, if the normal pressure at the Installation position exceed 0.027MPa (about 3m of oil head), this Relay may not operate properly

Trang 5

2

Fig.1 SUDDEN OIL PRESSURE RELAY

1 Cover

2 Equalizer

3 Movement bellows

4 Case

5 Operation check shaft

6 Operation check cap

7 Pressure­receiving bellows

8 Microswitch

9 Name plate

10 Rellef plug

Trang 6

represents the value of pressure increase in the transformer tank: the x­ axis represents the time between the occurrence of pressure increase and the activation of the microswitch The diagonal broken line in the figure indicates the rate of pressure increase in the transformer The intersection of the broken line and the curve thick line indicates the corresponding operation time

Minimum operating pressure difference: 0.025+30% (MPa)

Minimum operating pressure increase rate: 0.005+40% (MPa/ sec)

As this evident from the operating characteristics shown in Fig.2, this

Relay instantly responds to such a rapid pressure increase as expected

in the case of an accident in a transformer: the higher the rate of

pressure increase is, the quicker the operating time becomes

Fig.2 Operating characteristic curve of Impact Hydraulc Relay

Type: PVOA­Y2­2

Trang 7

4

5 Contact operation check

(1) Keep a value open it a valve is provided in between the Relay and the transformer tank

(2) Disconnect an auxiliary Relay circuit from the Relay Connect a test

light circuit

(3) Dismount the cap of the inspection shaft that is attached under the

Relay housing

(4) Quick push the inspection shaft brim by hand

So that the pressure­receiving bellows is pushed up and actuate a

switch

(5) After the test is carried out, the cap of inspection shaft should be

screwed original oosition

6 Handling caution

(1) If the Relay is given a shock during transportation, its function could

be deteriorated For the transportation, remove the Relay from the

transformer and transport it separately

(2) This Relay is mounted on the transformer tank side wall in between

0.5~3meter below an oil top level, using a butterfly valve, etc

whose opening area should be as large as possible

(3) After the Relay is properly mounted the air vent (fig,1­ number 10)

should be opened to allow a little of an oil to flow out Then, close the

air vent