Not for use in ADC’s FDF 3.5-Inch Chassis – 4 Single Plug-In Modules The 3.5-inch VAM chassis fits into any 19-inch rack mounting environment.. Not for use in ADC’s FDF 1.75-Inch Chassi
Trang 14-Inch Chassis – 6 Single Plug-In Modules
The 4-inch VAM chassis fits into any 23-inch rack
mounting environment It accommodates a maximum of
six plug-in modules, six bulkhead plates, six blank panels
or any combination thereof.
Not for use in ADC’s FDF
3.5-Inch Chassis – 4 Single Plug-In Modules
The 3.5-inch VAM chassis fits into any 19-inch rack
mounting environment It accommodates a maximum of
four plug-in modules, four bulkhead plates, four blank
panels or any combination thereof Adjustable mounting
brackets are provided for 23-inch mounting environments.
Not for use in ADC’s FDF
1.75-Inch Chassis – 2 Single Plug-In Modules
The 1.75-inch VAM chassis fits into any 19-inch rack
mounting environment It accommodates a maximum of
two plug-in modules, two bulkhead plates, two blank
panels or any combination thereof Adjustable mounting
brackets are provided for 23-inch mounting environments.
Not for use in ADC’s FDF
FVM-19X175
Catalog Number*
FVM-19X350
Value-Added Module System
Chassis used in Non-ADC Optical Distribution Frame
Trang 2Features and Benefits
VAM chassis and modules available for all ADC fiber frames
One-stop shop for complete optical transport system requirements
Monitor testing
Enables providers to troubleshoot networks without forcing disruption of service
Enclosed plug-in modules
Optical components are protected from physical and environmental damage
Angled retainers
Maintains minimum bend radius of fiber patch cords
Horizontal mounted plug-in modules
Modules can be added or removed from the chassis without interfering with existing terminated
patch cords
Universal mounted plug-in modules
No need to order different part numbers for left side or right side mounted modules
Extensive product labeling
Customers have all the information required for installation and maintenance without referring
to the user manual or drawings
Flexible platform
Modules can be created for new applications quickly and easily to meet customer requirements
Module labeling system
Schematics are marked on peel-off labels that can be attached to the chassis designation
Trang 31x8 1x9 1x10 1x11 1x12 1x13 1x14 1x15 1x16 1x32
50/50 55/45 60/40 65/35 66.6/33.3 70/30 75/25 80/20 85/15 90/10 95/5 99/1 50/50 33/33/33 25/25/25/25 20/20/20/20/20 16.6/16.6/16.6/
16.6/16.6/16.6 14.3/14.3/14.3/
14.3/14.3/14.3/14.3 12.5/12.5/ 12.5 11.1/11.1/11.1/ 11.1 10/10/10/ 10 9.1/9.1/9.1/ 9.1 8.33/8.33/8.33/ 8.33 7.7/7.7/7.7/ 7.7 7.14/7.14/7.14/ 7.14 6.66/6.66/6.66/ 6.66 6.25/6.25/6.25/ 6.25 3.125/3.125/3.125/ 3.125
OR
2000 2100 2200 2300 2350 2400 2500 2600 2700 2800 2900 2950 2030 3900 4900 5300 6000
7000
8000 9000 A110 B111 C112 D113 E114 F115 G116 M132
Number of Splitters
Single splitter Dual splitter (2) Triple splitter (3)
A B C
Output Connector/Adapter Singlemode
2U 2A 4U 7U 7A 8A LA LU KU 00
Multimode**
2M 2N 5F 5U 9A 9B LM LN PM 00
non-ADC frames MiniVAM for Next Generation Frames*
For LGX-compatible frames
VLM-Input Pigtail Length
Example (In Meters):
01 = 1 m
10 = 10 m
00 = Adapters only on
input and output ports
Output Pigtail Length
*MiniVAMs are not available with split ratios above 1x8 nor can they be configured with three splitters They are not available with E-2000 connectors/adapters
Trang 4Mux Port Connector/Adapter
LC ultra polishBare fiber
Demux Port Pigtail Length
Configuration
VAM Style
Unidirectional multiplexerUnidirectional demultiplexerBidirectional λ1 Tx/λ2 RxBidirectional λ1 Rx/λ2 Tx
45 dB isolation, pass 1310
45 dB isolation, pass 1550(Dual only) unidirectional multiplexer, unidirectional demultiplexer**
(Dual only) bidirectional
λ1 Tx/λ2 Rx, bidirectional
λ2 Tx/λ1 Rx
ACEGJKL
Mux Port Pigtail Length
Example (In Meters):
01 = 1 m
10 = 10 m
00 = Adapters only on mux
and demux ports
**WDM Type “L” includes (1) unidirectionalmultiplexer (standard isolation) and(1) unidirectional demultiplexer (isolation specified by next character)
*MiniVAMs are not available with E-2000 connectors/adapters
Wavelength
1310 (λ1)/1550 (λ2)
1533 (λ1)/1557 (λ2)1310/1533/1557
1550 (λ1)/1625 (λ2)
1310 (λ1)/1625 (λ2)
ABCEF
For OMX™
600 frames For LGX-compatible frames
2U2A4U7U7A8ALALUKU00
LC ultra polishBare fiber
In the ordering charts, the abbreviation “mux” references the multiplexed
side of the WDM, the side where two optical signals co-exist on one fiber
The abbreviation “demux” references the demultiplexed side of the WDM,
the side where each signal appears on its own fiber Both unidirectional
and bidirectional WDMs are available as shown below
Trang 5Input pigtail length
Example (in meters):
90/1095/0550/5080/2075/2570/3060/4099/01
Module Style
Dual monitor cross-connectwith attenuator***
Customer premisesDual monitor cross-connectDual monitor cross-connect
1BDJ
Output Connector Type Singlemode
2U2A4U7U7A8A
2M2N5F5U9A9B
2U2A4U7U7A8ALALUKU00
LX.5® ultra polish
LC ultra polishBare fiber
OR
OR
2M2NSF5U9A9BLMLNPM00
LX.5® ultra polish
LC ultra polishBare fiber
Multimode**
123
1 circuit
2 circuits
3 circuits
Number of Circuits per VAM
*** This style cannot be used in
NGF-M modules
Standard VAM forFL2000 andnon-ADC framesWideVAM™ for FL2000WideVAM™ for non-ADC framesMiniVAM for NextGeneration Frames*
For OMX™ 600 frames For LGX-
Trang 6Adapter to attach patch cord or pigtail
to OSP port
Adapter to attachpatch cord toequipment
SPLITTER COMPONENTS
to equipment
or OSP fibers(2 mm jacketed)
2
IN OUT
FRONT REAR
OUTPUT
INPUT OUTPUT
Input Front, Output Front
1 x N
IN OUT
Input Rear, Output Front
5
2
FRONT REAR
Dual Monitor Cross-Connect
D
Tx Rx
Tx MON
Rx MON Tx Rx
SPLITTER 90%
10%
SPLITTER 90%
10%
Customer Premises Monitor Module
B
SRC Rx
CUST MON SRC MON CUST Rx SRC Tx CUST Tx
1 x 2 SPLITTER A
1 x 2 SPLITTER B
1 x 2
1 x 2
Rx
VAR ATTN
Dual Monitor Cross-Connect
J
Tx
Mon Tx Mon Rx Rx
Adapter port
Trang 7VAM-6PB5VAM-6PB9VAM-D6PB9
Trang 8Singlemode Wideband Optical Splitter Specifications
Other splitter configurations are available Please call ADC Technical Assistance Center.
50/5055/4560/4065/3566.6./33.370/3075/2580/2085/1590/1095/599/150/5033/33/3325/25/25/2520/20/20/20/2016.6/16.6/ 16.614.3/14.3/ /14.312.5/12.5/ 12.511.1/11.1/ /11.110/10/10 /109.1/9.1/ /9.18.3/8.3/ /8.37.7/7.7/ /7.77.14/7.14/ /7.146.66/6.66/ /6.666.25/6.25/ 6.253.13/3.13/ 3.13
3.7/3.73.2/4.12.7/4.72.3/5.32.2/5.52.0/6.01.6/6.81.3/7.81.0/9.2.8/11.2.5/14.40.3/22.53.7/3.75.9/5.9/5.97.4/7.4/7.4/7.48.6/8.6/8.6/8.6/8.69.8/9.8/9.8/ /9.810.6/10.6/ /10.611.3/11.3/ /11.311.5/11.5/ /11.512.1/12.1/ /12.113.1/13.1/ /13.113.3/13.3/ /13.313.8/13.8/ /13.813.8/13.8/ /13.814.5/14.5/ /14.514.9/14.9/ 14.918.5/18.5/ 18/5
3.1/3.12.7/3.62.3/4.12.0/4.71.9/5.01.7/5.41.4/6.21.1/7.1.8/8.4.6/10.2.4/13.2NA/NA3.1/3.15.0/5.0/5.06.2/6.2/6.2/6.27.3/7.3/7.3/7.3/7.38.1/8.1/8.1 /8.18.9/8.9/ /8.99.5/9.5/ /9.59.9/9.9/ /9.910.4/10.4/ /10.410.9/10.9/ /10.911.3/11.3/ /11.311.6/11.6/ /11.611.8/11.8/ /11.812.4/12.4/ /12.412.6/12.6/ 12.615.8/15.8/ 15.8
Splitter
Number
Splitter Type
Splitter Ratio
Maximum Insertion Loss*
Typical Insertion Loss*
* Does not include connector losses See table on the following page or contact the ADC Technical
Assistance Center
Maximum Insertion Loss
Maximum insertion loss is the upper limit of insertion loss for the coupler and applies over the entire wavelength range specified in the bandpass.
Typical Insertion Loss
Typical insertion loss is the expected insertion loss value for the coupler measured at the specified center wavelength (i.e 1310 nm and/or 1550 nm).
Trang 91260/1360 nm1430/1580 nm
55 dB minimum
< -55 dB.5 dB maximum
.45 kg (1.0 lb.) maximum for 25 mm and 900 mm fiber,
1 kg (2.2 lbs.) maximum for cabled fiber assemblies
300 cycles; 45 kg (1.0 lb.) maximum load (fiber cable only)
100 cycles; 45 kg (1.0 lb.) maximum load (fiber cable only)10-55 Hz per FOTP II condition I
8 drops from 1.5 metersAll materials used in fabrication of coupler housing meet
UL 94, Level V-I requirements
336 hours, 60°C at 95% relative humidity
336 hours, 85°C
336 hours, -40°C to 85°C
Singlemode Optical Splitter Specifications
Value-Added Module System
Singlemode Optical Connector Specifications
Ultra Polish PC Connectors
Angled Polish Connectors
INSERTION LOSS(dB)
0.3 dB maximum0.1 dB typical0.5 dB maximum0.1 dB typical
RETURN LOSS(dB)
57 dB minimum
65 dB minimum
Trang 10Uniformity: 1.0 Log2N (where N = number of channels)
Polarization Stability: 0.5 dB maximum
Bandpass: (see table below)
Insertion Loss: (see table below)
Flex: 45 kg (1.0 lb.) maximum for 250 mm and 900 mm fiber;
Twist: 1.0 kg (2.2 lbs.) maximum for cabled fiber assemblies
Vibration: 10-55 Hz per FOTP II condition I
Impact: 100 cycles; 8 drops from 1.5 meters
Flammability: All materials used in fabrication of the coupler housing meet
UL 94, Level V-I requirements
ENVIRONMENTAL
Humidity Resistance: 336 hours, 60°C at 95% relative humidity
Thermal Aging: 336 hours, 85°C
Temperature Cycling: 336 hours, -40°C to 85°C
Multiplexer/Demultiplexer:
High Isolation Demultiplexer:
Very High Isolation
MINIMUM ISOLATION (dB)1530
45 15
PASSBAND(nm)
MINIMUM ISOLATION (dB)N/A
20
351313
PASSBAND(nm)
Trang 11All-Front Access Design
Sliding radius limiters provide ultimate fibermanagement by addressing one of the most criticalelements of fiber cable management: bend radiusprotection As fibers leave the tray, a speciallydesigned bell-shaped exit point provides maximumedge protection
By controlling the movement of fibers within thetray, error-proof slack loop management ismaintained, ensuring 30 mm bend radius protectionwithin the tray This is crucial in ensuring no fiberbreaks, which cause service failures and increasenetwork operations costs
Sliding adapter packs allow easy access forconnecting jumpers and cleaning connectors,ensuring that any fiber can be installed or removedwithout inducing a macrobend on an adjacent fiber.That can mean the difference between a networkreconfiguration time of 20 minutes per fiber and one
of over 90 minutes per fiber
These trays are lockable, further ensuring theintegrity of the fibers by greatly reducing the chancefor accidents
Modular Design
The value of a single interface for performingmultiple tasks in your network cannot be denied Byemploying a one-rack-unit modular tray, networktechnicians have ready access to terminating,splicing, and storing fiber This one-stopmanagement approach means time saved and value added
Trang 12Drawer Configuration
Connector/Adapter Style
Lock Type
2432
The termination-only fiber management tray provides termination for 24 or 32 fibers in an all-front-access design This tray mounts in 19-inch, 23-inch, or ETSI racks Sliding radius limiters provide cable
management for incoming and outgoing fibers.
SC connector on back of bulkhead)
SC connector on back of bulkhead)
Trang 13Fiber Management Tray
1 Rack Unit – Termination and Splice
12-Termination/Splice (right splice entry)
24-Termination/Splice (right splice entry)
24-Termination/Splice (right splice entry)
24-Termination/Splice (left splice entry)
Catalog Number FMT - D 0 0 -
Configuration
(left splice entry)
(right splice entry)
Lock Type
Chip Style (mini splice tray)
SC connector on back of bulkhead)
SC connector on back of bulkhead)
The termination and splice tray terminates and
splices 12, 16, or 24 fibers in an all-front-access
design This tray mounts in 19-inch, 23-inch, or
ETSI racks Sliding radius limiters provide cable
management for incoming and outgoing fibers.
Panels loaded with pigtails come with color-coded
900 micron pigtails.
Trang 1416-Termination/Storage (universal storage)
24-Termination/Storage (left storage)
24-Termination/Storage (right storage)
Catalog Number FMT-D 0 0 0 -
Configuration
Lock Type
connector on back of bulkhead)
connector on back of bulkhead)
1 All 19" mounting brackets are reversible and can
mount in EIA and WECO racks
2 40 mm recess FMTs are equipped with a special
trumpet sliding radius limiter Other mounting styles
cannot be used in 40 mm recess applications.
The termination and storage tray terminates and stores 12, 16,
or 24 fibers in an all-front-access design This tray mounts in
19-inch, 23-inch, or ETSI racks, while sliding radius limiters
provide cable management for incoming and outgoing fibers.
Trang 15Fiber Management Tray
1 Rack Unit – Slack Storage Panels
Catalog Number FMT - D 0 0 0 00 - 00
The slack storage tray offer bulk storage for up to 60 fibers, and discrete slack storage for up to 16 fibers This all-front-access tray mounts in 19-inch, 23-inch, or ETSI racks Sliding radius limiters provide cable management for incoming and outgoing fibers.
Trang 16Catalog Number FMT - DAS0000 -
1 All 19" mounting brackets arereversible and can mount in EIAand WECO racks
2 40 mm recess FMTs are equippedwith a special trumpet slidingradius limiter Other mounting
styles cannot be used in 40 mm
recess applications
Trang 17Fiber Management Tray
1 Rack Unit – Termination and Splice Fixed Bulkhead
This configuration features fixed bulkhead style adapter plates and accommodates singlemode SC (ultra polish and angled), E-2000, LC and LX.5®, as well as multimode SC, LC, and LX.5 adapters The tray can be ordered with adapters only, or with pigtails.
Catalog Number FMT-D 0 0 -
Configuration
TW Termination/splice with bulkhead
plate (right splice entry)
plate (left splice entry)
Lock Type
Number of Ports with Adapters 1
(right splice entry)
Trang 18plate (right storage entry)
plate (left storage entry)
Lock Type
1 All 19" mounting brackets are reversible and can
mount in EIA and WECO racks
2 40 mm recess FMTs are equipped with a special
trumpet sliding radius limiter Other mounting styles
cannot be used in 40 mm recess applications.
Termination/Storage Fixed Bulkhead
Trang 19Fiber Management Tray
1 Rack Unit – Accessories
Sliding Adapter Packs
FC hybrid (FC connector on front;
SC connector on back of bulkhead)
FC ultra polish
ST®hybrid (ST®connector on front;
SC connector on back of bulkhead)
ST®ultra polish
SC ultra polish
FC angled polish
SC angled polish
E-2000 angled polish
FC with zirconia adapter
SC with zirconia adapter
ST®with zirconia adapter
Catalog Number
FMT-2SAP05FMT-2SAP09FMT-2SAP01FMT-2SAP02FMT-2SAP03FMT-2SAP04FMT-2SAP07FMT-2SAP0FFMT-2SAP0JFMT-2SAP0KFMT-2SAP0LFMT-2SAP0NFMT-2SAP0P
Description
Wall mount kit
Cable clamp kits
.25" offset from frame
1.25" offset from frame
Vertical cable guides
Black
Putty
O r d e r i n g I n f o r m a t i o n
Trang 203 mm outer diameter cable: 32 cables, length 2.5 m each
2 mm outer diameter cable: 48 cables, length 2.5 m each1.7 mm outer diameter cable: 60 cables, length 4 m eachDiscrete storage
3 mm outer diameter cable: 16 cables, length 1.7 m each
2 mm outer diameter cable: 16 cables, length 2 m each1.7 mm outer diameter cable: 16 cables, length 2.5 m eachTermination/splicing (12, 16, or 24 splices)
A