Licensee Conditions of use This is a licensed electronic copy of a document where copyright is owned or managed by Standards Australia International.. Your licence is a single user lic

Trang 1

Licensee

Conditions of use

This is a licensed electronic copy of a document where copyright is owned or managed by

Standards Australia International Your licence is a single user licence and the document may not

be stored, transferred or otherwise distributed on a network You may also make one paper copy

of this document if required

Web Check-up

AS/NZS 2293.21995/Amdt 11998 Emergency evacuation lighting for buildings

-Inspection and maintenance

Licensed to LUU MINH LUAN on 25 Feb 2002

Trang 2

AS / NZS 2293.2/Amdt 1/1998-05-05

STANDARDS AUSTRALIA / STANDARDS NEW ZEALAND

Amendment No 1

to

AS / NZS 2293.2:1995 Emergency evacuation lighting for buildings Part 2: Inspection and maintenance

REVISED TEXT

The 1995 edition of AS / NZS 2293.2 is amended as follows; the amendments should be inserted in the appropriate places.

SUMMARY : This Amendment applies to Clauses 1.4.2, 3.1 and 3.4.

Published on 5 May 1998.

Approved for publication in New Zealand on behalf of the Standards Council of New Zealand on

27 February 1998.

AMDT

No 1

MAY

1998

Page 5 Clause 1.4.2

In the last line, delete ‘inspecting’ and replace with ‘regulatory’.

AMDT

No 1

MAY

1998

Page 10 Clause 3.1

Add a new sentence at the end of the second paragraph, as follows:

Details of any corrective actions taken shall be recorded in accordance with Clause 1.4.2

AMDT

No 1

MAY

1998

Page 11 Clause 3.4

Delete the existing Clause and replace with the following:

3.4 BATTERY REPLACEMENT Whenever the batteries of emergency luminaires and exit signs are replaced for any reason, such replacements shall be made in accordance with the following:

(a) Where more than one cell is utilized, the complete battery pack shall be replaced (b) Replacement batteries shall be of the same type and ampere-hour capacity

(c) A discharge test shall be conducted in accordance with Clause 3.2.2 except that the test shall be continued for 1.33 times the required in-service duration

ISBN 0 7337 1915 5