AS/NZS 2293.31995/Amdt 11998 Emergency evacuation lighting for buildings
-Emergency luminaires and exit signs
Licensed to LUU MINH LUAN on 25 Feb 2002
Trang 2AS / NZS 2293.3/Amdt 1/1998-05-05
STANDARDS AUSTRALIA / STANDARDS NEW ZEALAND
Amendment No 1
to
AS / NZS 2293.3:1995 Emergency evacuation lighting for buildings Part 3: Emergency luminaires and exit signs
REVISED TEXT
The 1995 edition of AS / NZS 2293.3 is amended as follows; the amendments should be inserted in the appropriate places.
SUMMARY : This Amendment applies to Clauses 2.2, 2.3.1 and 4.3.1.
Published on 5 May 1998.
Approved for publication in New Zealand on behalf of the Standards Council of New Zealand on
27 February 1998.
AMDT
No 1
MAY
1998
Page 7 Clause 2.2
In the first line of the Note, delete ‘inspecting’ and replace with ‘regulatory’.
AMDT
No 1
MAY
1998
Page 7 Clause 2.3.1
Delete Items (a) and (b) and replace with the following:
(a) 10% of the reference value within 1 s of loss of the normal supply; and (b) 80% of the reference value within 15 s of loss of the normal supply
AMDT
No 1
MAY
1998
Page 13 Clause 4.3.1
Delete Item (ii) and replace with the following:
(ii) be arranged so that, immediately following disconnection, the drain imposed on the battery is not greater than that recommended by the cell manufacturer for the operating conditions, so that the battery will not be discharged to the extent that it
is incapable of recovery
ISBN 0 7337 1916 3