Longer wires, spliCed to these 2 wires, are connected 10 a remote PUSh-bulton switCh, Pressing the push-bu!lon switch energizes the solenoid and activates the plunger, The plunger awlie
Trang 1Honeywell sail switches (Fig T7) are used in flame A small metal sail, mounted on a pivOI, 9Klends inlolhe safeguard applications to prove combustion airflow before air stream Mechanical linkage transmits mol ion of the sail 1I1OJhloft ar.d while the burner is running They can also be to a switch The switch makes or breaks when the airflow used in air ducls to assure that a furnace is supplying reaches a speCified velocity The switch can be used in
Honeywell sail switches available for use in name safeguard systems are listed in Table VI al the end of the section Table VI includes switching action, operating air velocity and direction, sail size and malerial, and special applications For further Information, refer fa the Instruc
tion sheets tor the sail switches
54J7A,e; SU1A
FIG 77-HONEYWU~ SAIL SWITCHES
TABLE VI-SUMMARY OF HONEYWELL SAIL SWITCHES
S837A switch; one set
breaks
b Adjustable to aetlJale on upwarr:i airlDw (t:lr
" same a9 5437A axcept wiIhout case and
d AJso oparates lor upward air1k:lW, but operating air
Trang 2, ~.'
S43 SAIL SWITCHES S43 Sail Switches are especially suited for use with gas-firacl unit heaters and air conditioning systems All models have a steel sail which actuates an sps.I mercury
600,1000, or 12501eel per minute [3.05, 5.1, or 6.4 metres per second] Several sail sizes are available 10 accommo
date various sizes of air duels Models are available for usa in horizontal or va/lical duelS, and to actuate for any direction of airflow except downward
The.switCh iN !HE S43A or B modelS makes on increas·
lnQ air velocity; the switch in the S43D breales S43A med
els 3r~' dasigrted 10 operate in airflow !rom lett 10 right (lOOking allha face oflhe switch so the label can be read)
S43B and D models operate in airtlow from rl""llo left
One S43B model is adjustable 10 operate in upwaIdair110w
"E"cu,,~
lwPTCN
L :~~_r -CONOU" CONNECT'ON
SCREw TER"'NAL5 (2)
FIG 78- S43 SAIL SWITCH WITH COVER
REMOVEO
5437, S637 SAIL SWITCHES
5437 and 5637 sail Swilches are especially suited for use in larm crop dryers AU models have an aluminum sail whiCh actuates a MICRO SWITCH snap-acting switch
5437 models have an $pSI switch; 5637 models have ",n spdt switch Models with standard size sails (1 x 3 inches [25.4 x 76.2 mmjj actuate at an air velocity at '900 faet per
minute (9.6 metres per second) with the differential set at its minimum value They acluate at 2250 fee! per minute [11.4 metres per second] with the differential at its maximum value Other sail sizes result in different operating air velocllies (see Table VI) All models are designed to cper· ate In a horizontal airflow; lhey wIll also cperale in an u,r ward airflow, but the cperaling air velocity will change The 5437B is the same as the 5437A except that it does not have a case and caver In both models, lhe swilch makes on increasing air velocity (Fig 79) In the 5637A, one set of contacts makes (R to B) and the other set breaks (R 10 IN) on increasing air velocity (Fig 80) The normally cpen contact enerQizes the load when the air veloCity is great enough, and the normally closecl contact energizes an alarm when the air velocity drops off
tror vertical ducts)
The S43 Sail Switch may be used on several different types Of applicaticns; therefore, the location and Installa
tion will depend on the speCifiC jc:tl The case is usually mounled on the side ot a ducl or unil healer in a vertical
(upright) posilion The top of the case must be level lor pTq:lElr cperalion of the mercury swilch The sail should be
in the direct path of the airstream where the movement 01 the air will be unrestricted, and must be free to return to the -down" position under its own weight Wiring is routed lhrough the conduil oullel in the bottom of the case, and tnen connected to the 2 screw terminals on the terminal block inside the case (FiQ 78)
SoUJA OR B
"
& M""l<E5 01'1 'I'ICIlE""5'I'IG AlII VELOCITY
• A LOAO
FIG 79-S437A OR B INTERNAL SCHEMATIC
FIG 80-S637A INTERNAL SCHEMATIC
The 5437 or 5637 should be located so that the sail is in the direct path Of an unrestricted airstream It cperates basI in a horizontal duct In a vertical duct, the effect of gravity on the linkage changes lhe operatil"lQ painl Wiring
is rouled thrDLlQh the knockouts in each end of the case, ilJ"Id then connected to the screw terminals on the switch inside the case (Fig 81)
The differential on an S437A,B or 5637A sail Switch can be adjusted by lurning the differen.tial setting dial (Fig 81) The dial is marked with the lellers A, B, C, and 0 to indicate relative differentials from a minimum of 550 fpm (feet per minute) [2.8 metres per second, or m/s] to a maxi
25
Trang 3~:'<oc~ours (i)
DifFERENTIAl SETTING DIAl
""
FIG 81- S637A SAIL SWITCH WITH COVER
REMOVED (S437A OR B IS SIMILAR
EXCEPT FOR TERMINALS.)
mum of 900 tpm [4.6 m/s) For sail switches with the stan·
dard 1 x 3 inch [25.4 x 76.2 mm] sail, a minimum setting
(p:)sition A) resulls in an cperating air velocily of 1900 tpm
[9.6 m/sl (Fig 62) A maximum selting (positioo OJ results
in an cperaling air velocity ot 2250 tpm [ 71.4 rn/sJ The
switch breaks at 1350 tpm [6.9 rTVsl on decreasing air
velocity
The cperating air velocity and the differential are in
versely proportional lo the area of the sail Urger sails re
sult in operalion at lower air velocities and lhe dinerential
SPARK IGNITER
Q624A SOLID STATE SPARK GENERATOR
The Honeywell Q624A Solid State Spark Generator
(Fig 83) is used to ignite gas pilots with spark gaps up to
1/4 inch [6.6 millimelr8$] on commercial or irdustrial gas
burners It prevents detection of the ignition sPark when
prcperly applied in a flame deteclion system using a
C7027 C7035, or C7044 Minipeeper Ultraviolet Flame
Detector
The Q624A is rated for a 120 volt, 60 Hz power supply,
and prOVides 60 Sparks par'!ieCQr1(j with a peak voltage of
15,000 volls It is recommended for use with Ihe RA890G,
R4795, R4126, R4127, R4140, and R4150 Flame Safe
guard Controls II is a solid state device and weighs only 3
pounds [1.4 kilograms] versus 8-1/2 p:xJnds l3.9 kilo
grams} for standard Ignition transtonners
The sPark generator and the Mlnipeeper ullraviolet
flame deleclor are synChronized by the 60 Hz ac supply
voltage (Fig 84) They operate only during a small portion
at the cycle (shown by shaded areas) The spark occurs
during one-half of the cycle and the detector cperatBS dur
ing the opposite hait cycle Thus, the tlan-e detector is
never "IOOdng· when there is a spark
INSTALLING THE 0624A
MOUNTlNG
The Q624A mounts in Ihe same space used by a con·
ventional ignilion transformer The mounting plate permits
"•• "M+
~' VM C'''~~~''''''l,
Klimo 0 Itoo "M)M,"'''V''
FIG 82-ADJUSTABLE DIFFERENTIAL FOR AN
S437A,B OR S637A SAIL SWITCH (WITH STANDARD 1 X 3 INC'" (25.4 X 76.2 mm] SAIL SIZE)
decreases prc:portionately To Increase the cperaling air
velocity, the sail can be trimmed uSing a hea"Y shears If it
is cut to one·half its original size, the cperaling air velocity
and the differential will be dovtied
Follow the instructions of lhe system manufacturer, if available, or adjust the differential ar"d/or sail size 10 suit the requirernef1ts of your awlication
HIGH VOlTAGE El,.EC:TROOE
lhe use at the same mounllng holes without an adapter
plale, and it may be mounled in any posillon
Trang 4062.'" SP"'A~
GENERATOR
Ef:lERGIZEO
IFLA"E OlTiCTOIl OHI
FIG 84- SYNCHRONIZATION OF A Q624A
SOLIO STATE SPARK GENERATOR
FLAME DETECTOR
WIRING
The voltage and frequency of the power s~ly cen
netted to the Q624A must be 120 volts, 60 Hz The chaSSis
of the Q624A must be propfufy grounded at 9JI times, even
dUrlngbench testing; otherwise, the device may bum out
Loosen the cover screw (Fig 83) and remove the cover
Insert the 2leact.viras (NEC Class 1) through the knockout
in the boltom at the cese and connect them fa the screw
terminals on the terminal board, and to the terminal strip or
wirIng sl.Jbbase 01 the flame safeguard control (refer to Ta
bla VII and Fig 85 or 86) Terminals T1 and T2 on the
Q624A must be connected to the prc:per terminals of the
flame sa1ElQuard control, as given in Table Vll If the name
deteclof and the ignition transformer are nor properly Con
nected, the detector may sense ignition spark, which could
cause a hazardous condition
TABLE VII-WIRING CONNECTIONS FOR THE
0624A SOUD STATE SPARK GENERATOR
TER_ FLAME SAFEGUARD
Apprtlprlate ignition terminal
R4126 and R4127 T, lIS specified on ptDgrarrmel'
Instruction sheeL
l2 R4140 and R4150
T1 Appropriate Igntllon terminal
lIS speci1led on programmer Il'I9tnJction sheet
T2
I
necl the high voltage electrode (Fig, 83) to the ignition
eleCtrode on the gas pilot bomB! (The high voltaQEl eleC
trode may be a qulck-connect type, or it may have a
threaded lerminal nut, depending on the model of the
0624A.) Use Honeywell Spec No R1061012 Ignition ca
ble or eq.Jivalen1 (This wire is raled at 350 F [1T5 CJ for
~ .FEGu RO ,,.SIDE Qil
8 TER"" ITR" o~ ",R'NG ~VB8"'~[
& vS[ NH <l"'~l I "'Ill'"'' ,,,
FIG B5- 0624A CONNECTIONS TO AN
RAB90G, R4795, R4126, OR R4127 FLAME SAFEGUARD CONTROL
n l FEGVAIIO 'N~'O[ Q62
C"'''TRD'
_I",,.01l0N TEll"'"'''' O' F,A"E ~AF£"v"'''o
CONTROL SEE .O , TE ,,,STRun,o,, SHEET 'Oil HR"'I"A' OE~'G"AT'ON
& TERM'N"'L ITRIP DR ""RI ~uBB
& VSE Ie ." , ""RING "
FIG 86- Q624A CONNECTIONS TO AN R4140 OR
R4150 FLAME SAFEGUARD CONTROL
continuous duty, and up to 500 F 1260 C] for intermittent use 11 has been tested t02S.ooo volts.) The ignition caDle should not exceed 15 reel [4.6 metres] in length,
CHECKOUT OF THE QS24A Aner Ihe Q624A installation has been compleled, the fol1owinQ checks should be made to ensure that the syslem is working pr~rly
IGNITION SPARK RESPONSE TEST The flame relay shOuld not respond lDull in) 10 ignition spark To determine flame detector sensitivity to ignition
spark per10rm the following steps:
1 Shut off lhe fuel suj:pJy to Ihe pilot and main fuel valve(s) manually
2 Slart the SYSlem f:7.j raising the controller set point or
3 Energize lhe Q624A Sofid State Spark Generator so
an ig1ition spark Is produCed between Ihe eleclrode and ground
4 Check to be sure that ignition has nol occurred rrttere should be no flame.) Repeal steps 1 through 3 until Ihere is no 1lame
5 Check the flams relay on Ihe flame saf~rd control 11 the relay has not pulled In the system is ~ralirlQ
prc:perly Continue the cheCkout with the Pilot Turndown Test
6 It the flame relay pUlis in, stop Ihe system, r~ace
the Q6.24A and repeat steps 2 through 5
260
Trang 5REMOTE RESET ASSEMBLIES - - -
11110Z11 (FOA AA.,o's A,NO A.7n·Sf
\187018
(FOA A.I'O·S)
11876011 (FOA A.l.0'S)
7 Ilihe flame relay pulls in after replacing the Q624A,
stop the system, replace the flame safeguard control, and
repeat steps 2 through 5
o - 8 If the flame relay pulls in after replacing the name
saf8QUard control, Contact the local Honeywell branch
office
Remole reset assemblies provide the capability of re
selting the lockout (safety) switch in flame saleguard con
trols from a remote location All example of this awlication
'IS where the flame safeg.Jard control is located on an inac
cessible roof or suspended from a ceiling with no catwalk
AIlother example is where the ftalT\El safeguard control is
mounted in an explosion-proot enClosure; the housing is
secured by many bolts In all of these awlications, it is dif
licult to gel allhe resel buttQ1 on the 11ame safeguard can·
lrol so the ability to remotely r9S9t lhe lockout switch is
highly desirable
Some insurance agencies and code bodies severely
restricllhe use 01 remale reset assemblies, If there is any
question, these aulhorities should be consulted prior to in
stallation of the reset assemblies,
REMOTE RESET COVERS
Remote reset covers are heavy dUty metal covers with
a remole reset assembly mounted 011 them The cover fits
over the flame safeguard control The remote reset as
semtJly consists of a 120 Vall, 60 Hz solenoid, with a plunger Ihat is direCtly ali ,-,ed with the (esel bullon Q11he ftalT\El safeguard control Connecled to the solenoid is a 17 inch [430 mm] length of 2-wire, flexible Conduit, plus 19 inches [480 mm] 01 exposed, insulated leadwires Longer wires, spliCed to these 2 wires, are connected 10 a remote PUSh-bulton switCh, Pressing the push-bu!lon switch energizes the solenoid and activates the plunger, The plunger awlies pressure to the reset bullon on the flame saleguard control to reset the lockout (safely) switch Flemote reset covers available are shown in Fig, 87, Honeywell part numbers are:
118701 a-for use on R4150 Flame Safeguard Programming Controls
118702B-1or use on RA890 and R4795 Flame sateguard Primary Controls
198365A-for use on R7795 Flame Safeguard Primary Controls,
118760B-for use on R4140 Flame safeg.Jard Programming Controls
PILOT TURNDOWN TEST Refer 10 the flame safeguard control )nslnJclion sheel tor the exact procedure to be used in performing the pilot lurndown test
FINAL CHECKOUT After other checks have been completed, restore the system to normal operation and ooserve at least one complete cycle fo be sure of satisfactory burner operation
FIG 87-REMOTE RESET COVE-FIS
Trang 6To Install a remote reset CO'll8r, loosen the screw(s) in
the old cover llf there Is one) and remove It Allgl the sola-
noid plunger In the new cover with the reset button on the
flame safeQ.JlHd control, and mounllhe cover Make sure
there !tiar leasl 1/4 Inch 16.5 mmj clearance 101" the
plunger Then tighten the cover screw(s)
AI the deSired remOle location mount a momentary
push-bullon swilch The switch must be rated to carry at
least 15 VA Ohe power qonsu~ion of the remote reset
solenoi9) Connecl the push.outton swilch 10 lhe solenoid
(Fig 88) Do notUS&8 toggleswiteh; if laft in the "on" posi·
tion II wguld cause the lockout switch to remain in the
"open" posilion The solenoid plunger of the remote resel
assembly must disengage from the reset bullon on the
flame safeguard conirol In order for the lockout sWitch to
ee>rTWlete the circuli inside the control
& PRO.,O' 0"~ONN'C1 ",AN, ANOOV'R~OAOPRonc·~,,~ ""' I
A' RH ".O
In '0T< "Un 00"< 0'0" _TEO A ' " VA
In "0 ", A' O"'R<O ~, O "oLAno"
FIG 88- TYPICAL HOOKUP OF A REMOTE
RESET ASSEMBLY
If addilional wire is needed to reach the push'bullon
switch, splice it 10 the 2leadwires exlending from the flex
Ible conduit on the reset assembly (Fig B7) Moisture-ra-
siSlanl No '4 wire suilablefor atleasf 167 F [75 C) If used
with an RA8900r R4795 , or for all~1194 F 190 C] if used
with an R4140 or R4150, is recommended for normal
installations
The lockout switch can be reset right al the flame safe
guard control by pressing the end of the solenoid plunger,
or it CM be reselfrom lhe remole localion by presslnljlhe
remOle push-bullcn switch
REMOTE RESET ASSEMBLY (PART NO
118811A) FOR AN R4138C OR 0
This remote Jeset a.ssenbly Is very similar to the as
sembly used 011 Ihe ramote reset covers, except thai II
does not have a flexible conduit around its leadwlres and
It has asolenoid arm (Fig 90) which depresses lhe JoC~oul
swllch reset bUIlDl'l on the R4138when the solenoid Is en
ergiZed To mount the remole reset assembly on an
R4138C or D Induslrial Flame safeguard Control, insert
262
the nut and washer 00 the remote reset assembly Into lhe hole in the chassis just below the loc~out switch on the R4138 (Fig 89) Make sure the washer engages lhe Inside lip of the hole Slide the remote reset assembly upward (as shown by the arrow) as far as it will go Insert the mounllng screw and tIghten It securely (Fig 90) Make sure there is a minimum of 1/4 Inch [6.5 rTVTI] clearance between the solenoid arm and the lockout switch reset bullon when the lockout swilcn is reset Wiring and q:'lEIration 01 this assam· biy is the same as for the remote reset covers (Fig 68)
"ESU BUTTON
~O:~oJl
J';l! -SOLENOIO A
RESET ASSEMBLV
SOLENOID
' - - - W ' R E {2_(lLACKI
LFIG 90-A '18811A REMOTE RESET ASSEMBLY
INSTALLED
Trang 7INTRODUCTION - - -
A Flame safeguard System inclu~ all controls and
associated de~ces r8QJired far safe corrbustlon 01 the
lh(ee elements required for corroustion -fuel, air, and ig
nition-fuel is the easiest to control
The purpose 01 the valve train, then, is to control the
flow of fuel into a combustion chamber so Ihal it burns
evenly_ Even combustion conserves fuel, controls pollut
ant by-.producls, and provides the right amount of heal
needed for the process
In addition many ~roval bodies such as Underwriters L aOOrator(es Inc., Factory Mufual (FMj, and Factory insuranCe Association (EI.A.) issue co::ies for burning fuel safely
In this section, we will COYer the types of valves available and develop typical valva trains to be used in Flame safeguard Systems
TYPES OF V A L V E S - - -
There are four types of valves used with ffame safe
guard equipment They are the Manually Operated Valve
or the Automatic Solenoid Diaphragm, and Motorized
MANUALLY OPERATED VALVES
Although most valva trains reqJlra automatic opera
tion, the manual valve, Fig 2, still provides corwenianl fuel
shutoff for temporary maintenance or service
Manual shutoff valves are used in oolh the main and pi
lot fuel lines This valve is also called a plug cock because
263
it consists of a tapered plug with a horizontal opening As thEi manually operated handle turns thEi plug, gas llows through the opening
A V5050A FUElI Cock is anElIElclrically interlocking plug cock
The V5060A, Fig 3, has two internal1nterlock switches that are connEicted to the Flame safeguard Car'llrol and sa1ely Shutoff Valve These switches prEivent ignition of the pilot if thEi V5060A Valve is open AflEir thEi pilot is ignited, the V5D60A may be manually cpaned to light the main burner
ArlolhEir type of valvEi is the Manual Reset safety Shutoff Va)~e commonly called a Free-hardle Valve This valvEi closes automatically in response to Ihe Flame safeguard Controt, but must be opened by hand An electrical circuit holds the valve open but cannot open it by itself After thEi circuil is ElnEirgized, IhEi valve is ~by hand and remains open until tl"lEl circull is de-energized This
PLUG COCK MANUAL SHUTOFF VALVE
71-97558-1
Trang 8V5060A SUPERVISORY FUEL COCK
FIG 3-VS060A SUPERVISORY FUEL COCK
Free Handle Val e is used as the safety shutoff valve only
In manually ignited systems where the burner is seldom
shul down
AUTOMATIC VALVES
SOLENOiD VALVES
Of the three automatic valves the Solenoid is the sim
plest and generally lhe least 8lCpensiv8 A controller opens
the valve by running an electric current through a mag
netic coil, Fig 4.lh6 coil, ac1lng as a magnet, pulls up the
valve disc and allows the gas or oil 10 flow Solenoid action
provides fasl CIp!:lning and closing limes, usually less than
one second in models wilhoul a thermistor delay
shutoff valves in gas pilollines The V8036 or V4Q36, Fig
S, is used in the main lines of smaJJ to maoum gas sys
lems Unlike Diaphragm or Motorized Valves, the Soler
noid is also used in ,:,il burning systems Use a V4046A,B
FIG S-V4Q36N8036 SOLENOID VALVES
for no heavier than No 2 oil; and use a V4021A for heavy
oil <lWlicallons ALL of lhese are Solanoid valves DIAPHRAGM VALVES
Diaphragm Valves, like the DrI8 Shown in Fig 6, are generally used on atmosph&ric typeo gas burners 10r smooth lightoN These valves have a slow opening and
last closing lime which deperdi on the amount of gas flowing over the diaphragTl
ThQ valve consists 0' a diachraam wifh a weiQ!l( over the valve seal A small inlernal solenoid valve blocks the gas flow 10 lhe bleed port
When the COn/roJlef is not camnglor heat, Fig 7, the Coil
is de energized The plunger in the three-way actuator is
In lhe DOWN position, 50 lhallhe bleed' port is closed and lhe supply port is opeM Gas 1l0'NS to the top 01 the dia· ohragm lhe gas pressure and the weight hold the valve closed
SLOW OPENING-FAST CL.OSING USED ON ATMOSPHERIC GAS BURNERS
V480R vsa
~v~ 113-7
FIG 6-V48/88 AND V4843/B843 DIAPHRAGM
71-97558-1
264
Trang 9PLUNGER WEIGHT DIAPHRAGM
VL~~~ :-::::: -~=~:::==r-live &3-1
FIG 7-S0LENOID VALVE - CLOSED
On a call lor heat, Fig 8 Ihe controller contacts close and the coil is energized This pulls the plunger to the UP p:>silion, opening the bleed port and closing the sl lWly port The Qas then bleeds off the lcp at the diaphragm, al
lowing Ihe Qas pressure 'Qeiow \0 lift the diaphragm and
open the val "'e
When aillhe Qas has bled off the lop of the diaphragn, Ihe valve is fully q::lEln, FIg 9, permitting gas flow to Ihe main burner
After 1M controllar is satisfied, the proceclJre is re
versed The controller contacts open so Ihal the coil is de
-,'
energiZed The plunger is released, moving \0 the DOWN p:>silion, FiQ 10 This closes lhebleed pan and q::lBns the sUJ)ply port so that gas at;tain flows to the lop at the dia·
PLUNGER WEIGHT OIAPHRAGM
FIG a-SOLENOIO VALVE - OPENING
snap acllon
Diaphragm 't/al't/85 are CJ,liet ard ha't/(1 a reasonably long life They are generally less expensi't/e than motor· ized 't/al't/85
Another ~ 01 diaphragm gas 't/al't/e is the COI'T"biM' tion 't/alve (Fig 11) The basic q::l9falion of this If8I't/e is the same as already dBscrlbed, except thai it adds (or corn
billB5) other f\.lnctlons into one 't/al'tle txxly The V484JIV6843B,C.L,N Valve Incorporales a single stage pt8S8U1'8 regJrator into the basic dlaphraQTi 't/al't/(1 desigl The V4844/V8844B.C,L, N models pro't/lde two stage pressure reg.rlation The one or two slages 0' pressure reg.rlation are used fa prO'ollde one or two staQ31iring rale control
to the burner system The V4843I\I8843P Val't/9 pro't/lde5
a intermittent pilol takeoff port
Trang 10FIG 11-V4843fV8843 AND V4844fV8844
COMBJNATION DIAPHRAGM VALVES
MOTORIZED VALVES
Motorized valves perform two runclions-satety shut
off and firinQ rale control We will discuss each 01 the fUnc
tions separately
SAFETY SHUTOFF 'vALVES
Safely shutoff valves are usad for large gas burners
Ihat require:
1 tighl closeoff
2 accurate control of large MlOUnls 01 fuel
The Honeywell family 01 Safety Shutoff Valves \s shown
The V4Q55 actuator contains only a dump valve for ONOFF cp9ralion The 1/4062 OFF-lO-HI actualor and V9055 mcd; dating actuator, FiQ 11" alse contain a bieed valve to control Ihe amount of gas flowing to the burner The bleed valve contrds the valve stem travel stanlng at the low fire position, and continuos 10 cperate only when lhe aclualor is driving the valve cpen
Valva actuatols have 2 cpenlng tirnes-13 and 26 seconds Models with 26 second limi"g have a small molar and Ol"lly 1 pIston in lhepu~ MOdels with 13 sec()(Xj liming have a large motor and 2 piston pumps
The different kinds of V5055 valves are shown in Rg
12 The VSQ55D,E are used for high pressure applica· tions, while V5055A·C are for low pressure appllca:ions Nole that the V4055 ON-OFF aCluator may be used with any varve The V4062 OFF·LO·HI and the V9055 modulating valves must be used only on the v5055B with a
Trang 11V40SSA WITH VSOSSA
INDICATION
VAlVE "SHUT"' INOICATION
••G" "
FIG f3-CUTAWAY VIEW OF AV4055A WITH A
V5055A
V4062 AND V9055 PUMP MOTOR ANO DUMP VAlVE ASSEMBlY
T f4E ON 0"" V40~5 HAS A DUMP VAlVE ONl V-NO BlEED VAlVE
PUMP MOTOR
Bl E, 0 VA.lVE
OU"'P VAlVE
OUMP VAlVE SOlENOIO
FIG 14-INTERNAL VIEW OF V4062 OR V9055
A Characterized Guide (or skirted gJidel Ag 15 has notches or V's cut into lhe gJide to determine the valve flow characteristics II provides a predictable relationship between stem travel and gas flow
As the valve varies the fuel, a c:lalTp3r linked to the valve actuator varies the corrbJstlon air In this way the valve ar1d actuator control both the fuel and air noodecl to vary the burner firing rate The V4062N50SSB and the V9055,iV5055B seNe a dual purpose as safely Shutoff Valve and Firing Rate Control
These combinations may only be used on alm0scherlc burners where codes allow a dual fUr1ction 't'2tlve For other applications a Bullerfly Valve IS used whiCh will be dis
cussed laler
CHARACTERIZED GUIDE
FIG 15-A CHARACTERIZED GUIDE The V5055C,E valves reQlJire a valve seal overtravel in
terlock (Fig 16) 10 make sure the main fuel valve is closac! before allowir1g lhe ignition sequence to start To accomplish this, the V5055C,E valve with two seals is used with a valve-closed indication switch on tne valve actuator The
~ switch can be wired to either make or break a circuit when the valve is in the closed position,
VSOSSC, E
VALVE SEAL OVERTRAVEL INTERLOCK
"SHUT"" Ols.::
JUST PP.lOA TO STANDARD SEAl ClOSING
Io':",,~ ElOTH VALVE SEALS ARE CLOSED
sPECIAL VALVE SEAL
ON VS05SC AND EONLY _~ SWITCH IN ACTUATES
FIG 16-V5055C,E VALVE SEAL OVER
TRAVEL INTERLOCK
As lhe valve closes, the ~r seal CID8eS fi",t, step
ping the gas flow The valve stem musl ·overtraveJ-pas! this point before lhe switch closes Fir1ally the lower seal Is closed
The switch Is normally wired ir1to Ihe • Preignition Interlock· circuit at the Flame sa~rd Control to prevent ignilion unless the valve is ·proved- to be closed
FIRING RATE (BUTIEAFLY) VALVES (FIGS 17 AND 161
By controlling the amount of fuel entering the bJrnaC this valve determines the rale of combustion, or fIrlng rata
71-9755&1
Trang 12VALVE
_ _ _ CRANK ARM
:; -DFlIVE PIN
STRAI'l RELEASE SPRI'lGS 121
ACTUATING ARM
AI the same time, the valve actuator controls a damper
which, in turn, controls the flow of combustion air 10 the
burner
FIRING RATE
VALVE
COtlTROLS CO"8USTION
PLATE
Oyo " ""
FIG 18-V51E BUTTERFLY VALVE
Other names for the cord)inalion firing rate valve and
actualor are: Burner-ll'l)Ut Control Valve, Combustion
Control Valve, MeterillQ Valve, Modulating Valve, Operat
illQ Valve, and ThrotWIlQ Valve
As mentioned be1ore, the V9055/V5055 Modulating
Safely Shutoff Valve may be used fOf Ihis p,Jrpose, but be
C8Ll!ie mosl applications rBqJire single function valves,
lhe V51E Butterfly Valve (Fig HI) is mosl ofIen used The
V51E is combined with an M941 actuator and 0100 link·
age Since the V51 E Butter1ly Valve 00es not closetlghUy,
a separate safely shutoff valve must be provided
The BL/tler1Jy Valve is named aner Its rOlaling hinged
plata that reserrbles the opened wings 01 a butter1ly This
valve has a hiQh flow capaCity and relatively constant rela
liDnShip between fuel110w and the angle of alve ~illQ
(Flg 19) This feature IS useful for close modulation of air
and fuel gases '0 large furnaces An M941 Modulrol Actuator (Fig 20) controls the valve While simultaneously 0p
erating a corrbuslion air damper Together, the valve and actuator provide a stable mixture of air and fuel
As the controller energiZes the M941 actuator, the increased resistance unbalances the molor bridge circuil
To correct the unbalance, the motor drives the linkage to rotale the hinged plate on the V51 E and open the Butter1ly Valve The actuator continues to drive open until its feedback potentiometer moves to rebalance the circuit and stop Ihe motor
VALVE OPENING ANGLE DIRECTLY RELATED TO GAS FLOW
oyO" "
FIG 19-VAlVE OPENING ANGLE IS DIRECTLY
RElATED TO GAS FLOW
FIRINGRATf
FIG 20-M941 MODUTROl MOTOR
71·97558-1
268
Trang 13VALVE T R A I N S - - -
In this $eclion, we '1'111 davelcp a typical gas and oil
valve lrain used in a Flame SafElQU3rd System For spe
cific information on valv9 trains approved by various ap
proval bodias, see the Recommet'ldad Valve Trains
setticn
GAS' VALVE TRAINS
BAsIC COMPONENTS
~ shown in Fig 21, the first and most Ilasic cDlT'PO
nenl Is the pipe, or gas line used to carry gas to the com
bustion chamber
The gas .111 nol be Mowing continuously throu'tt!lhe
pipe, 50 we need a manual plug cock to !urn the gas on or
off t:If hand Tl'1is plug cock is called thE! Manual Shutoff
Valve (MSQVj
In a basic manual 1i{j110tf system lhe operator ius!
turns on the MSOV to start the gas r10Wlng into the com
bustion charrber Then, he throws in a lighted match, rag
or piece of paper and stands back as the gas bursts Into
Ilames
However, most applica(ions Icday reqUire a smoother,
safer lightaff So, we will acid a smaller pipe, the pilot line
(FiQ 22) An MSOV is required in the pilot iine, too
When ttIe puot flame is going, the main MSOV Is cpened The pllolflame lights the main gas as SOClf1 as It Erlters the ccmbuStion char'nl:ler
This manLli'lllightolf syslem works well as long as a person constantly watct'es the name If the flame lJ)9S out
ciJe 10 a pil (;03d gas line or some other undasirabJa occur
rence, he can close the valves and shul eXIwn the t;)Jrner HO'l¥ever, it he does nol notice a name out siluatlon immediately, the cOl'TbJ:stion chan1:ler wilf nlf wilh urbJrned gas lhe urbJrned gas, of course, creates a very dangerous situation when the burner is rei(1lited
So, to walch over the flame, we need an automatic flame safeguard system wilhin the valve train Our firsl corrpanent is a Safety Shuloff Valve (SSOV), FiQ 23, 10
II~
•
SAFETY SHUTOFF VALVE
FIG 23-SAFETY SHUTOFF VALVE (SSOV.)
automatically lurn the gas on and off
Notice tNt the syrrtJol used in Fig 24 has a mile block above it This block represenls the actuator
We will also wanl a SSOV in the pilolline
Something musllell the Safety Shutoff Valve when to open and close the gas line This is a logiC panel which Inetudes the Flame SatE9JSJd Control Tnis conlrol is the heart Of the Flame Safeguard System, Fig 25 Usually,
Trang 14the panel is located on the wall, a few feet from the valve Iraln and the corrtlusllon charrber It could also be mounted ri~t on the boiler
We also need a Flame Deleclor (FIg 26) 10 walCtl for a flame in !he corrt:lustion charrber
Now, to start the burner with our automatic valve train
we first open both the Manual Shutoff Valves Then, when
we need heat, the Flame Safeguard Control q:e1S the Safety Shutoff Valve iJ"lthe Plio! Une At the same lime, it turns on an ignitioJ"l sci-uce for the pilot, Fig Zl
Wh8l'1 the flame detector sees the pilot flame, 1\ tells (he Flame Safeguard" Contralto ~n lhe Safely Shutoff Valve
In the lllain burner line The pilol then 1i~IS the main burner, Fig 28
Once the main burner Is lit, we can Jeavethe pilot on or lurn il off If (he pilot remains burning while the main burn
system, the Flame Safeguard Control Signals (he pllol SSOV to close the gas line once the flame detector has proved the main burner name
If bolh the pilot and main flame go out (Fig 29), the
ttame delector will break ils clrcuillo the Flame safeguard Control The Flame Sa1eglJafd Control, in tum, will signal
FIG 25-THE FSG CONTROL IS THE HEART OF
THE FlAME SAFEGUARO SYSTEM
FIG 26-THE FLAME DETECTOR WATCHES
FOR A FLAME
both pilot and main SSOV's to stq:l gas now This is the Safety Shutoff Circuit
UI"BU~"O~ C~"·",.
CIRCUIT
AvO " , SSOV PILOT LINE
COM8USTION CHAMBER
FIG 29-SAFETY SHUTOFF
Trang 15Another point we must consider is providing gas to the
burner at [he right pressure, Fig 30 Gas enters Ihe valve
train at a pressure as hio;j1 as 10 pounds per sqJare inch
Unfor1unately, gas at this pressure cannol mix properly
with air and p:JOr combustion results For proper combus
tion, a typical pressure is 4 inches we or only 0.15
psI-This means thatlhe valve train must deCrease the pres
sure considerably So we will aoo a Pressure Regulating
Valve (PRVl as shown in Fig 31 The ut=P€!r pan 01 the
'RV
SYMBOL
FIG 31-A PRESSURE REGULATOR VALVE
PRY symbol is an oval, representing the diaphragm in the
PRY
Since we want 1:1e PRY to cuI down the pressure, we
will locate it upstream of the SSOV in both the main and
pilot tinas, Fig 32 The raduced pressure Increases the ef
ficiency and life 01 the SSOV
Iryou compare the 110w orgas 10 the flow of a river, VOU
can see why this location is called upstream If we located
the PRV on the other side 01 the SSOV, It would be cbYvn
Now we have an autOlT'l8l1c 5VS18m for lighllng the pilot and main burner
SAFETY SHUTOFF REQUIREMENTS Under normal conditions, our automatic system should safelV light the plio! ana main burners, prOViding tha,tthe SSOV Cbes not leak Unfortunately any valve can leak Slio;j1tly if the seat does not closs perfectly So i1 we shut down our automatlc valve train ror the weekend, a sli~
amount 01 gas may leak through the SSOV and continue past the open MSOV into the burner Remember, since this is an automatic system the MSQV will be left open
When we start the burner up on Monday morning, we may have an explosion due to a combustion charrber fiJI! of un
To eliminate any gas leakage proolem, we need a
blower (Fig 33) 10 get rid of any accumulated urburned
MSOV "'v S$OV
FIG 33-A BLOWER GETS RIO OF
ACCUMULATED, UNBURNEO GAS
gas before we light the burner The motor which drives the blower is usually called a burner motor Now Iilring slarh p, the flame safeg.lard control Si\T.als the blower to blow air Ihrouo;j1the cOl'Tt1uStion charrber ana clear oul the gas This is called purging
To purge the con1JustlOl charrber 01 all urtx.nned gas,
we should use about 4 changes of air That is, we should blow through about 4 limes the volume of air that the can
71-97558-1
Trang 16ouslion charTbar holds 1lle tIame safEQJard control limes
the purging procass to provide 4 changes of air
Purging gets rid of the gas leakage danger at li~toff,
but doeS nothing 10 prevent the accumulation of urtlumec:I
gas If.we add a second SSOV (Fig 34), 2 valves would
."" uiO
have 10 leak al lhe same lime to create a problem
For more protection, we can add anolher pipe (Fig 35)
between the 2 SSOV's leading to the outside air An auto
matic vent valve is then aQjed (0 vent any leaking gas
while the SSOV's are closed While the SSOV's are q;>en
and gas is nowin.g to the Dlrner, the vent valve is closed
This valve arrangement Is called Doutie·Block-and·
Bleed (Fig 36) While the burrler IS shul oown, any gas that
leaks pasl the first Safety Shutoff Valve will escape, or
"tieed Off, w to the oulside atmosphere through the Vent
FIG 36-DOUBLE·BLOCK·AND-BLEED,
Valve The second Safety Shutoff Valve, Just cbwnstream
from IheVent Valve will bloCk atT'fgas which is not vented With lhe combusllon chamber also vented to the al· mosphere through its exhaust sy.stem, there will be no pressure cJi1terence across the second SSOV Fig 37 So
and is recp Jired tly some approval bodies
GAS PRESSURE CONTROL Our system is still not cOll'flletelysate What if our Pressure Regulating Valve falls? Gas at pressures up 10 10 psi could enter the combustiOn chamber, There will be 100 much gas tor the combustion air available, and the flame will go out
71-97558·'
Trang 17We will be left with a fuel-rich mixture (Fig 38) in the
combustion chamber, a &ituaflon thai 1& alway& very dan
gerous But, as condltions sland, the milliure cannot be ig
nited because thera Is 100 much gas for the air available
But air does come Inlo the cart:lu:stlcn charrt:Jer natu
rally (due fo atmospheric pressure) Of mechanIcally ~1t"Q
forced In through purglng)_ Finally when enough air en
fers to create a mixture that can be i(7lited by a very low
ener.m' source, the concentrated fuel-air mixture ex·
plooes, (Fig: ~)
, lOPS''''
FIG 38-FAILED PRV = FUEL-RICH MIXTURE
To stop this situation, we need a High Pr855ure Switch
to notify lhe Flame safeguard Control to shut down the
system The High Pressure Switch samples the gas pres·
sure and open& an eleclrical circuit iflhe pressure rises
past some preset level This swilch never blocks the gas
flow, it just taps into the line to sample the pressure
We should locale this switch near the burner (Fig 40)
since we want to keep the gas pressure at the burner
within the limits for proper corrt:ostion For this reason,
the High Pressure Switch is often callecl a High Uml!
The High Pr86SUre Switch should be installed just up
stream of the Manual Shutoff Valve In most valve trains,
the Manual Shutoff Valve should CornEl last, so we can
shut off the burner but still have gas available for checking
lhe olher ~alves and switches
We can let the burner restart automatically when the
pressure returns to normal Or we can r8CJllre someone to
push a button on the High Pressure Switch before the
burner can be started again This is called Manual Reset
With Manual Reset someone is going 10 notice that
something Is wrong Usually the q)ElratOf will correct the
So we need a Low Pressure Switch or low Limit to signal the Flame safeguard Control when the pressure falls
to a preset level The best pressure sampling locatioo is with the High Pressure Switch right next to the burner (Fig 41) However, with our low Pressure Switch downstream
of the Safety Shutoff Valves, the switch will be sensing zero pressure when the burner is not running and the Safety Shuloff Valves are closed With this location on a manual reset system we will have to push the button every time we want to start the burner
So, our Low Pr855ure Switch should be moved upstream at both safely Shutoff Valves (Fig 42) Now we have 2 pressure switches 10 keep us within our limits tor
sale burner c:peration
As we mentioned before the Manual Shutoff Valve is the last controt in the main gas tine, so we can lahul off the gas SlJR)ly to the burner, but still have gas available tor checking lhe olher valves and switches But, if we need to replace a valve, how do we shu! off the gas? We need an
Trang 18FIRING RATE VALVE
CONTROL OF GAS FLOW
The Firing Rate Valve (Fig 4.lI) is no! really necessary to
the safety of lhe valve train, but it provides a convenient
methOO of controllit'lg the flow of fuel
The valve should be placed close to the burner to get
lhe best oontrol In sorr'Ie valve trains, you will see lhe Fir
ing Rate Valve located just atter fhe second SSOV and
ahead 01 the Hi'lt1 Pressure Switch In other trains, the
valve will be downstream or lhe PRV and upstream of the
Low Pressure Switch The preferred location is near the
burner (Fig 45)
Thai completes the schematic or our valve train Now
this is what an actual gas valve train looks like (Fig 46)
Here is the end 01 the combustion chamber, showing
Ihe complete valve train Notice how much smaller lhe
pipes are in the Pilot Une than in lhe Main Burner Une The
straight through the whole combustion chamber This
photo also ShOws lhe location of the Flame Deteclor This
deteclor is a Honeywell C7012E Purple Peeper Ultraviolet
Flame Detector The C7012E Is colored violet to indicate it
is an ultraviolet detector
274
CO BUSTIOIIi CHAMBER
FIG 46-THE COMPLETED VALVE TRAtN Fig 47 shows the logic panel, which includes a Flame
Safeguard Conlrol -Ihe hear1 ollhe system Nolice the in dicating lamps which show the status of the system
71-97558"