Printing BRITISH STANDARD Specification for Conduit svstelTIS for ~ cable lTIanagelTIent Part 2 Particular requirements Section 2 3 Flexible conduit systerns The European Standard EN 50086 2 3 1995 wi[.]

Trang 1

BRITISH STANDARD

Specification for

cable lTIanagelTIent

Part 2: Particular requirements

Section 2.3: Flexible conduit systerns

The European Standard EN 50086-2-3:1995 with the incorporation of

amendmentAll:1998has the status ofa British Standard

This British Standard should be read in conjunction with

BSEN 50086-1: 1994

ICS 29.120.10

]\"{J COI'YL"G WITHOUT BSI PEIUllSSI0l\" EXCEPT AS PEIUllTTED BY COI'YIUGHT LAW

BSEN 50086-2-3: 1996

Jnc011Jorating Amendment No.1 and Currigendutn l'1u 1

-~~»~>:;~>-:;»-:;»-:;»», -'~»»»»»»»»>, :;»-:;»-:;>:

::~~::~~::::~'-'-"::::~::;:~::;:~: "":'~::~~::~~::~~::: ;::::~::::~::::

Trang 2

COllllnittees responsible for this British Standard

The preparation of this British Standard was entrusted to Technical Committee PELfI 13,Cable management, upon which the following bodies were represented:

ASTA Certification Services British Electrical Systems Association (BEAMA Ltd.) British Telecolll1IlUnicatiollS pIc

Electrical Installation Equipinent ~v1anufaeturers'Association Electricity Association

Gland Manufacturers' Technical Committee Institution of Electrical Engineers

Institution oflncorporated Executive Engineers

This British Standard, having

been prepared under the

direction of thl;;

Elcetroteehnieal Sector Board.

was pnhlished under the

aut110ri!yort11C Standards

Board and cornes into erlect on

i5 Aprii i996

Amcndmcnts issucd sincc public8.tion

The tl11lowing BSI references

standard:

CO!l1!l1 i!lee re leren ee PELIi i3

Uratllor C0!l1!l1en[lJ2/04071 IX'

Amd.No

10515

13549

Corrigendum No.

Date

Jan uary2000

26 February 2002

Comments

DeletionfrOlll i~->o.lllleX i~-".LA->o.of A-deviations for Finland

Correction to title of standard

Trang 3

Committees responsible National foreword Foreword

Text ofEN50086-2-3

BS EN 50086-2-3:1996

Page Inside front cover

11

2 3

Trang 4

l~ ational foreword

This British Standard has been prepared by Technical Committee PELII 13 and

is the English language version of EN 50086-2-3: 1995, Conduit systemsfor cable

fnunugefneni - Purl2-3:Purliculurl~eljuirefnenl.";J(}/~jle.,\ihlec(}tuluii,~:,.v,,,,'iefn ,·,

including amendment All: 1998 and corrigendum February 200 I, published by the European Committee for Electrotechnical Standardization (CENELEC) This British Standard is to be read in conjunction with BS EN 50086-1: 1994

Spec(!icationfor conduit systemsfor cable management - Palt J: General requirements The references to Part I should be read as references to

BSE1'"~50086-1: 1994 \vhich is the English language version ofE1'".J 50086-1: 1993.

A British Standard does not purport to include all the necessary prOVISIons ofa contract Users of British Standards are responsible for their correct application Compiiancc with a British Standard docs not ofitscif confer immunity

Summary of pages This docmnent comprises a front cover, an inside front cover, pages i and ii, theEN title page, pages2 to8,an inside back cover and a back cover

The BST copyright notice displayed in this document indicates when the

docurnent was last issued.

Trang 5

EUROPEAN STANDARD

NORME E1JROPEENNE

EUROP AISCHE NORM

Ivlay 1995

+ All

December 1998

Incorporating corrigendum February 2001

l)cscriptors: Electric 1.viring SystClTI, flexible condl1it Incchanical characteristics electrical characteristics, test

English version

Conduit systems for cable management

Part 2-3: Particular requirements for flexible conduit

systems

(includes amendmentA II: 1998)

Systemes de conduits pour la gestion du

cfrblage

-Partie 2-3: Regles particulieres pour les

systemes de conduits souples

(inclut l' amendement A 11: 1998)

Installationsrohrsysteme zum FLihren von

Leitungen fiir elektrische Energie und fur Information

-Teil 2-3: Besondere Anforderungen fur flexible Elektroinstallationsrohrsysteme

(enthalt A.ndenmg All: 1998)

This European Standard "vas approvedbyCE1'-~ELEC0111994-12-06.CEl'~ELEC

members are bound to comply with the CEN/CENELEC Internal Regulations

which stipulate the conditions for giving this European Standard the status ofa

national standard without any alteration

Up-to-date lists and bibliographical references concerning such national

standards may be obtained on application to the Central Secretariat or to any

This European Standard exists in three official versions (English, French,

German) A version in any other language made by translation under the

responsibility of aCEI~ELEClllenlber into its own language and notified to the

Central Secretariat has the sanle status as the official versions

CENELEC members are the national e!ectrotec!mica! committees of Austria,

Belgium, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy,

Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and

United Kingdom

CENELEC EUiopean Committee[OiElectiotechnical Standaidization Comite Europeen de l'Jorlnalisation Electrotechnique Europaisches Komitee ftir Elektrotechnische Normullg

Ccntral Sccrctariat: ruc dc Stassart 35, B-l050 Brussels

© 1995Copyright reserved to CENELEC members

RefNo EN 50086-2-3:i995+Ali:i998 E

Trang 6

This European Standard has been prepared by

CENELEC Technical Committee TC 113, Cable

Management Systems

The text of the draft was submitted to the formal

vote and was approved by CENELEC as

E1'"~50086-2-3 on 1994-12-06.

This Part 2-3 specifies particular requirements for

A conduit systenl vvhich conlplles vvith this standard

is deemed safe for use

The following dates were fixed:

The following dates were fixed:

latest date by which the existence of the

a-rnenchnent has to be

announced at national level (doa) 1999-03-16 latest date by which the

amendment has to be implemented at national

level by publication of an

identical national standard or by endorsement (dop) 1999-06-16

Contents

latest date by which the

EN has to be

implemented at national

identical national

standard or by

endorsement ldop) 1995-12-01

latest date by which the

national standards

conflicting with the EN

have to be withdrawn (dow) 1996-12-0 I

For products which have complied with the relevant

national standard before 1996-12-01, as shown by

the manufactureror by a certification body, this

production until 2001-12-01

This Part 2-3 supplements or modifies the

corresponding clauses of EN 50086-1: 1993, Conduit

s:vstemsfor cable management - Part 1: General

requirement~.

Where a particular clause or sub-clause of Part 1is

not mentioned in this Part 2-3, that clause or

sub-clause applies as far as is reasonable Where

this Part 2~3states "addition", "lTIodification" or

"replacement", the relevant text of Part I is to be

adapted accordingly

Sub-elauses, tables and figures which are in

addition to those in Part 1are numbered starting

with 101 Annexes which are in addition to those in

Part ! are labelled AA, BB, etc

Foreword to amendment Ai i

At the request of the Finnish electrotechnical

committee, a draft for an amendment to

El'-~50086-2-3: 1995 vvas subtnitted to the

CENELEC members for acceptance in

October 1998

The text of the draft was accepted by CENELEC as

amendment A II to EN 50086-2-3: 1995

on 1998-12-16

Foreword

1 Scope

2 Normative references

3 Definitions

4 General requirements

5 General conditions for tests

6 Classification

7 Marking and docLUnentation

8 Dimensimls

9 Construction

10 Mechanical properties

11 Electrical properties

12 Thermal properties

13 Fire effects

14 External influences

15 Electromagnetic compati bility AnnexA

Annex AA (infortnati ve) A-deviations

Figure l02-Gauge for checking the

minimum inside diameter after resistance

to heat test Figure 103 -Assembly ofconduit and terminating fitting for bonding test

Page 2 3 3 3 3 3 3 3 3 3 4 4 5 5 5 5 8 8 6

7 7

Trang 7

EN 50086-2-3:1995

1 Scope

This clause of Part I is applicable, except as follows

i~ ddi tion:

This standard specifies theTequireUlents for flexible conduit systeuls

Conduit systems which are used as an integral part of other equipment also have to be tested according to the relevant standard for that equipnlent

2 Normative references

This clause of Part 1 is applicable

3 Definitions

This clause of Part 1 is applicable

This clause of Part 1is applicable

5 GeneraJ conditions for tests

This clause of Part I is applicable

6 Classification

This clause of Part 1 is applicable, except as follows 6.1.3.1, 6.1.3.2 and 6.1.3.3 are not applicable

71'v1arking and docunlentation

This clause of Part 1is applicable, except as follows

Addition:

7.1.101 The conduit shall be marked in accordance with 7.1 at regular intervals along its length of preferably 1 m but not longer than 3 m Where this is technically impractical, the mark shall be on a label attached to the product at each end

Compliance il· checked by inl]7ectio11.

7.1.102 The manufacturer shall document for the system the minimum inside diameter, the minimum bend radius and the classification in accordance with clause 6

COn1j7/ianceL)checked by' ins/JcctiOl1.

8 Dimensions

Rcplaccmcnt:

8.1 Threads shall comply with EN 60423

ClJn1}J!iance l:r;; checked h)/' mean.') qf the gauges slJcctfied in ElY 60423.

8.2 The IIlllllmum inside diameter of the conduit system shall be declared by the manufacturer

Compliance i, checked by measurement.

9 Construction

This clause of Part I is applicable

3

Trang 8

10 Mechanical properties

This clause of Part I is applicable, except as follows

10.1 Ivicchanical strength

10.1.1 Addition:

NOTE Very light ilexible conduits should not be considered as providing adequate mechanical protection and should not be used

\vithin the construction of buildings.

lOA Bending test

This sub-clause of Part 1is not applicable

10.5Flexing test

10 5.101 An assemhly of conduit with a terminating fitting, assemhled in accordance with the

manufacturer's instructions, shall be subjected to a flexing test by means of the apparatus shown in Figure 10I

10.5.102 The test shall be made on six samples of conduit of an appropriate length Three of the samples shall be tested at the declared transport, permanent application and installation temperature in

accordance with Table 1 with a tolerance of±2DC.The other three sarnples shall be tested at the declared permanent application and installation temperature in accordance with Table 2 with a tolerance of ±2°C

10.5.103The smnple shall be fixed to the oscillating member by means of the terminating fitting as shown

in Figure 101, sothat when the conduit is at the middle of its travel, the axis of the conduit is vertical and passes through the axis of the oscillation The apparatus with the sample shall be conditioned for2 h or until the sample has attained the declared temperature, whichever period is the longer

10.5.104 The oscillating member shall be moved backwards and forwards through a total angle of 180° divided equally about the vertical axis The assembly shall be subjected to 5 000 flexings at a rate of

40±5 fiexings per minute A flexing constitutes starting from the vertical position, one continuous cycle of lll0venlent of essentially sinusoidalfOlln.

10.5.105After the test, the sample shaH show no sign ofdisintegration, nor shaH there be any cracks visible

to nonnal or corrected vision 'vvithout Inagnificatioll

10.6 Coiiapsc test

This sub-clause of Part 1is not applicable

10.7 Terlsilestrength

This sub-clause of Part is applicable, except as foiiows

10.7.3Replacement:

For conduit systems where tensile strength is not declared, the tensile strength of the joint shall comply with classification Iin Table 6

11 Electrical properties

This clause of Part I is applicable, except as follows

1 1.5 Bonding lcsl

Rcplaccment:

A sample of conduit and terminating fitting shall be assembled in accordance with the manufacturer's Instructions and Figure 103 A current of25 A, having a ftequency of 50 Hz to 60 Hz, derived fronl an a.c source having a no-load voltage not exceeding 12 V, sha!! be passed through the assembly

for I min I~S,after which the voltage drop shall be measured between the points shown in Figure 103 and the resistal1ce calculated from the current and this voltage drop

The resistance shall not exceed 0,05 Q.

Where special devices are required for the coupling ofconduit and terminating fitting, it shall be sufficient

to remove the protective coating from the conduit, or the protective finish shall be removed in accordance with the manufacturer's instructions before the voltage is applied

Trang 9

EN 50086-2-3:1995

12 Thermal properties

This clause of Part I is applicable, except as follows

12.2.4 Rcplaccrncnt:

The load is then removed and immediately after its removal it shall be possible to pass the appropriate gauge, in accordance vvith Figure 102, through the conduit under itsOw'llweight and \vithout any initial speed, with the sample in the vertical position

13 Fire effects

This clause of Part I is applicable

This clause of Part 1 is applicable, except as follovvs

14.1.1.2 AddItIOn:

When tested for first numeral 5 or 6, the assembly shall be tested as a category 2 enclosure

14.1.2.2 Addition:

When tested for second numeral 3 or 4, the assembly shall be tested using the oscillating tube

15 Electromagnetic compatibility

This clause of Part I is applicable

5

Trang 10

_ -. - ~

/ A "

J ~ / / 1 ' \ _~-"I I :

I 1 1' I '" L / -'" -, I I , I

/ ' " I '\¥,/ I

LlL- rl I

Guide support block.~, - I I I - -S I

~~I I (/</j •

/\»11 I II/'::/'j ~ ,

rT' -L -' ' I rT' -L -' ' I lUi

I~~ I

View of guide support block +-il-f

1)-j-~

I ~ I

~

Key

i\. - conduit

D - tcnninating fitting

d"" - outside diameterofi\

Y - IllinirllUll1 bend radius dec1ared by Illanufaciurer

Figure 101 - Flexing test apparatus

Trang 11

EN 50086-2-3:1995

20

'-1 I

I ~ I _ I 'H '

,0f"\ J

"-J

I -r -TT- -r

1 r - I I ~

-I I~ 'IJ,'- LJ'

1

D-80 <?/~ of the 111<:Uud:'iClurer's declared IninlnUllTl inside dialueler ofconduit

o !11!11

Tolerance and axial dimensions:

Achnlssihle \\'ear:

:-0;2 mnl

/ /

3 mm steel plate

Terminating fitting secured

"-to platebytapped hole or '"

bylocknut on fitting thread

Figure 102-Gauge for checking the minimum inside diameter after resistance to heat test

fl

I L-,-ia I

J f -><: L ~ -,1' X 1 /Cood";'

" I I I I / /

Ell I /

//~II

I

Figure 103 - Assembly of conduit and terminating fitting for bonding test

7

Trang 12

This annex of Part I is applicable

Additional annex:

Annex A.A (infonnative)

A-deviations

A-dcviation: National deviation due to regulations, the alteration of which is for the time being outside the competence of the CEN/CENELEC member

This European Standard falls under Directive 73/23/EEC

NOTE (from CEN/CENELEC IR Part 2, 3.1.9) Where standards fall under EC Directives, it is the view ofthe Commission ofthe

1 ~ur()pcan C0i11t11unitics (().J No (~59; 1992-03-(9) 111 at the effect oCtIle decision of'thc Court or Just icc in case g15/79

Crct1l0tl in i/Vrankovich (European Courl Reports 19XO: p 35X3) is that cOl11pl iance with A-deviations is no longer mandatory and thal

provided for in the relevant Directive.

"A -deviations in an EFTl~ -country are vaJid lTIstca.d of the relevant provisions of the European Standard

in that country until they have been removed

6.1.1.2 and France (Departmental order of the Ministere de l'Eqllipement et dll Logement dated 22 6.1.2.2 October 1969 for low voltage electrical installations)

Classification not allowed

6.2.1

6.5.2

8

Austria [Austrian Electrotechnical Law (ETG) BGBL 106/1992 dated February 12, 1993 and Austrian E!eetrotechnica! Decree (ETV) BGB! 47 dated January 20, 1994]

France (Departmental order of the Ministere de l'Equipement et du Logement dated 22 October 1969 for low voltage electrical installations)

Classification IX according to Table 1 is not allowed

Austria [Austrian Electrotechnical Law (ETG) BGB! 10611992dated February 12, 1993 and Austrian Electrotechnical Decree (ETV) BOBl 47 dated january 20, 1994]

Classification is not allowed for installations in buildings