n The time taken completing a site survey of cable routes will expedite the installation.. n Be aware of all electrical cable runs and inductive lighting.. label each cable before instal
Trang 1
Installation Tips
Do’s and don'ts for installation
This advice applies equally to copper and
fibre-optic cable
Trang 2
4 General Public Safety Rules
r
n KRONE is obliged by European Law to make course attendees
aware of Health and Safety rules and correct working practices
Trang 3n Protective shoes must be worn at all times
n Protective gloves should be worn when pulling in cables
n Goggles must be worn when removing ceiling tiles or when drilling and chopping into walls
n Itis advisable to wear protective overalls to stop loose clothing
getting caught
Trang 4
— Right ladder for right job
— Bad weather use
— Slippery surfaces
n Before using ladders and stepladders, make sure the correct Safety Procedures are followed for:
Trang 5— Stop and inform your supervisor
— Always ask your Supervisor if you have to work in the proximity of unknown substances
n Always observe your national Health and Safety at Work
regulations
Trang 6
4 Possible Routes
PP
n A careful survey of cabling and wiring routes should be made to
select the best alternatives
n The time taken completing a site survey of cable routes will
expedite the installation
n Look for possible routes:
— Suspended floors
— Suspended ceilings
— Building risers
n Concealed cable systems should be used wherever possible
n Be aware of all electrical cable runs and inductive lighting
n Be aware of anything that could cause interference to the cable
Trang 7
— 2meters at frame (for terminating)
n For short runs pace out length
n For suspended ceilings, remember to include length to ceiling and drop to floor
n Do not exceed the cable lengths specified in the Standards
n Consideration should be given to the use of fire retardant cable with low smoke emission properties such as LSZHFR (Low Smoke Zero Halogen Flame Retardant)
Trang 8
Cables should follow well defined routes
Tray work can be used when available, but must be segregated
from other cables
Where tray work is not available fixing to the top ceiling must be
made every 300mm max
Route round walls or under the floor using trunking, if this is not
possible, use cable tray in the ceiling space
Trang 9n When cables are concealed, they must be labelled at all points
where they enter and emerge
n Fire walls and barriers must be reinstated to the original standard of
Trang 10
yg Site Plans and Building Plans -
n Site plans will be available for a new construction; consult with
customer and construction company for running cables
n Occupied building: Ask customer for a plan with socket
requirements marked on it
n Aroom or closet should be chosen for the central distribution
n There should be adequate room to work freely around the frame
Trang 11n Universal Stripping Tool for
removing insulation without
damaging the conduciors
n Side (Diagonal) Cutters (10 to
12mm) for cutting the cable off the
reel and to trim the cable ends
Trang 12
_y Box Labelling
r
n Label the ends of cable and the corresponding box This will help for
identification purposes at the central distribution frame and socket
Trang 14
4 Precautions for Sub-floor and Ducting Access
E
n Floor access traps should not be left open and unguarded
n When working in a floor access use proper guard rails round tile
Trang 15gy Suspended Computer Floor
Trang 16gy Suspended Computer Floor
P
n When running under raised tile floor, lift as many panels as possible to get from Ato B
n Cables must be labelled at all points where they enter and submerge
n Cables must follow well defined routes via floor access
Trang 17
gj Suspended Computer Floor
P
n Communication cables should be separated from electrical cable by either
an electrical screen or a minimum distance of 50 mm to reduce
Trang 18use the correct categorised 4-Pair Cable
label each cable before installation, mark it at both ends - more
than once - using a waterproof marker
make the longest run first, so that you can take advantage of the pull string on the shorter runs
fun cables straight and free of kinks with gentle bends for any
change of direction
run cables point to point in one continuous length without any
joints in the run
Trang 19
4 Do
n make a schematic diagram showing where the cable runs are
and numbers of the rooms they go to
— later, when you wire the patch panel, this plan will tell you what order to position the cables
n protect cables where they pass through or over sharp edges,
holes etc
Trang 20
cut unlabelled cable; label cable before routing it or you'll lose
track of which cables go to which rooms
label cable "Ms Scholl’s room." Instead, use a label that will be
understandable to someone years later, such as "Room 103"
plan runs longer than 90 metres
tun UTP/FTP/STP cabling outside!
fill trunking to more than 40% capacity
Trang 21n bend cables to less than 8x the diameter of the cable during
installation and 4x when installed
n Stretch cables (max pulling force should not exceed 110
Trang 22tie cable ties too tight - they should be able to slide a little
Install or lay cable too close to fluorescent lights or power lines This may result in interference and reduce network quality and/or
speed
fun cables near or parallel to power cables
fun cables near devices which can introduce noise (i.e heaters, printers, monitors, lights, copiers, microwaves, etc.)
Strip off too much sheathing or untwist the pairs more than 13mm
Trang 23
4 Leave enough spare cable
r
n Don't cut corners with cable - leave ample slack A metre or so of
cable costs a lot less than the time it takes to redo a cable run
because of cable lengths being too short or the cable being
stretched
n When you wire the jacks and patch panel you should have enough
Slack to reach the floor and extend another metre at both ends of
the cable
— In addition, it’s standard practice to leave a service coil - a few extra
feet of cable coiled up inside the ceiling or other out-of-the-way place However, do not exceed the 90m rule
Trang 24
4 Common cabling installation faults
r
n Excessive untwisting of the pairs prior to insertion into the IDC
contacts The maximum allowed is 13mm;
Trang 25n The most common problem associated with large impedance
variations is excessive return loss
n Disturbing the pair geometry and removing too much cable sheath can adversely affect FEXT and Attenuation performance
n There are no standard requirements on the maximum amount of
cable sheath to remove, but we recommend that no more that 75
mm (3.0”) of the sheath be removed
Trang 26
— October 1995: “The amount of untwisting in a pair as the result of termination to connecting hardware shall be no greater than 13mm (0.5”) for Cat 5 cables and no greater than 25mm (1.0”) for Cat 3 cables”
n No more than 13mm (0.5") of pair untwist should be made for Cat
5e and Cat 6 cables
Trang 27
— Care should be taken to — Do not exceed 13mm of untwist minimise cable sheath for Cat 5e and Cat 6 cabling
disturbance and/or removal Do not exceed 75mm
Trang 28
Floor Distributor Layout
Information on laying out a cabinet for use as
a floor distributor
Trang 29n The detailed layout of distributors will vary naturally from
installation to installation depending on the equipment fitted, but
there is an overall scheme that is becoming generally accepted
n The scheme allows for the expansion of the wiring network and
maintains a consistent arrangement of equipment without the need for constant reorganisation when additions or alterations are made
Trang 301 UTP/STP cabling to users’ outlets
Normally RJ45 patch panels
2 Twisted-pair connections to voice circuits from the PBX via the
4 Electrical mains distribution
A bank of unswitched mains sockets.
Trang 314.Optical fibre terminations to the campus data network
Normally a ‘fibre tray’ or Patch panel
Occasionally the connection to the campus data network may be achieved by means other than optical fibres (e.g coax or twisted pair cables)
5.Cable management components
A 1U unit with open loops to hold cabling neatly in place below patch panels and active components
NOTE: The use of nylon cable ties is now not recommended Cable bundles should be formed/secured using fabric Velcro ties This form of cable tie allows additions and changes to be made easily, does not
distort cables and will not tear the insulation If nylon cable ties are used, mechanical tie-wrap guns should never be used
Trang 32
yj Recommended cabinet layout =
n Locate the Horizontal Wiring patch panels at the top of the rack,
expansion is downwards towards the active equipment
n Locate Active Communications equipment in middle of the rack and expand either towards the voice patching fields at the bottom of the rack or towards the horizontal wiring patching fields at the top as
Space permits
n Optical fibre trays/patch panels are located at the bottom of the
rack, below the voice patching field and may expand downwards
n Voice circuits, either patch panels or magazine mounted modules
are located above the fibre trays and expands upwards towards the active components in the middle of the rack
Trang 33
4 Cabinet layout: Example
-
Horizontal Wiring to
OO OO OO OOD OOD OND OVD OOD OO OVD OD OO
Trang 34
4 Notes
P
1 Mains distribution for the rack is located at the back of the cabinet
and is fed from an unswitched fused spur which is in turn derived
from an independent feed on the mains distribution board within the
Cable management for permanent wiring is located at the back of the
Trang 35n Cable shielding must be connected to earth in each Distributor
n Electrical continuity of shielding must be maintained along the
whole run of the cable
n The earthing scheme must guarantee a minimum of 192 anda
maximum of 1V r.m.s between the earth potential of any two points
Trang 364 Mounting SC and ST Fibre connectors
Trang 38g Fibre cabling cross-connection
Trang 40_y Laying cables (1)
n Properly supported ladder rack
Allowing cable transition between
floors
Trang 41
4 Laying cables (2)
n Cables going through risers
between floors must be properly
supported for their weight
Trang 42
„# Laying cables (3)
n Proper use of waterfall (rounded
transition) fittings for cable changing from a horizontal path to
a vertical one This maintains the
minimum bend radius for Cat 5e and Cat 6 cable
42
Trang 43‘Finished section going into s7 -; All |
conduits that has been properly = ae]
bundle to Ladder Tray with ual | |
The conduit bushings on the
end of the conduits are fitted to prevent the cable being nicked
on rough conduit edges during
Trang 444 How not to install cables!
44
Trang 45n 2: The cable bundle is practically
laying in the fluorescent light just
Trang 46
_y Laying cables - Installation errors (2)
n This is not acceptable The cable
should have branched out at the
support
Trang 47
_4 Laying cables - Installation errors (3)
n Never run parallel with electrical
conduits or strap to them
Trang 48
aes
y Laying cables - Installation errors (5)
force
A cable that has been crushed
Another example of a cable loop that that has been forced straight
Trang 49
n The pairs are correctly untwisted
to within 13mm of the IDC
termination
n Don't “re-twist’ the wires, the twist
rate is designed for optimum
performance - re-twisting can alter
Trang 50gy Sheath removal r
n Too much sheathing has been
removed from the cable
n Only enough sheath has been
removed to make up the
connector
Trang 51
_y Cable tie wraps
r
n The tie wrap is too tight, the cable
geometry has been altered Never
cinch plastic cable ties overly tight
lf it deforms the outer cable jacket
it is too tight
m The cable tie is holding the cable
but not changing the geometry
m@ The use of mechanical or powered
cable tightening devices is strictly
prohibited
Trang 52
4 Wall fixings
P
n The cable geometry has been
altered by stapling the cable too
tightly x
n The cable geometry has been
maintained, the cables are
supported but not compressed v ==
Trang 534 Bend radius
F
n Excessive bending tends to open
wire twists making the cable more
susceptible to noise
n The cable are laid within the 4x
outside diameter limits
n When installing cable do not
exceed 8x the outside diameter
Trang 54
_y Wall-mounted cable supports
Trang 55gy What is wrong here?
Trang 56And what is wrong here?
r
n Unacceptable wiring practice 2
56