49 Category 6 Limited Combustible Cable .... Our high performance copper riser and Plenum data cables for backbone and horizontal applications are produced by highly automated manufactur
Trang 1® S tr
Introduction 46
Augmented Category 6 Horizontal Cable 47
Category 6 Horizontal Cable 49
Category 6 Limited Combustible Cable 61
Category 5e Horizontal Cable 64
Category 5 Backbone Cable 76
Category 3 Horizontal and Backbone Cable 80
Category 1 Horizontal and Backbone Cable 84
Trang 2ADC offers a wide variety of copper cable for transmission of the most critical
Category 6 cable for the emerging 10 Gpbs Ethernet over UTP standard, as well as standards-compliant cable for Category 3, Category 5, Category 5e and Category 6 applications Our high performance copper riser and Plenum data cables for backbone and horizontal applications are produced by highly automated manufacturing processes that ensure consistent quality and dependability with superior electrical performance.
improves data thoughput, saves space, eases installation and reduces the danger of fire and smoke Through a unique design and advanced manufacturing techniques we are able to build AirES cable using air as a conductor insulator This groundbreaking process results in a cable that incorporates superior performance while reducing overall size up to 32 percent.
CopperTen™ Augmented Category 6 Cable with AirES® Technology
• The world’s first UTP structured cable to enable 10 gigabit Ethernet transmission over a full
• Unsurpassed electrical performance parameters – Increased signal to noise ratio (ACR) through performance increase in crosstalk and attenuation – Decreased crosstalk through reduced capacitive effects, with the introduction of air as
an insulator – Increased signal strength through less attenuation (Insertion Loss), a by-product of reduced
dielectric loss and twist rate
TrueNet® Category 6 and Category 5e Cables with AirES® Technology
• Improved physical and mechanical design attributes
• Increased signal speed and strength
• Unsurpassed electrical performance parameters – Increased signal to noise ratio (ACR) through performance increase in crosstalk and attenuation – Decreased crosstalk through reduced capacitive effects, with the introduction of air as
an insulator – Increased signal strength through less attenuation (Insertion Loss), a by-product of reduced
dielectric loss and twist rate
• Cross-sectional area reduction of 28 percent for TrueNet Category 5e and 32 percent for TrueNet Category 6 provide multiple benefits
– Increases fill rates by an average of 28 to 32 percent, decreasing installation costs
• Increases fill rates
• Decreases access-way space required – Improves safety in event of fire due to decrease of 32 percent in amount of fuel present – Provides four times greater crush resistance compared to UL 444 requirements
– Decreases installation time
• Reduces pulling tension by 32 percent
• Allows more cables to be pulled at the same time
• Promotes faster terminations
Trang 3• Unique oblique elliptical offset filler
for improved alien crosstalk
• Features AirES® technology
• Manufactured with lead-free materials
Common Applications
• 4/16Mbps Token Ring (IEEE 802.5)
• 10Base-T (IEEE 802.3)
• 100Mbps TP-PMD
• Broadband and baseband video
• 100Base-T (Fast Ethernet)
• 100Base-T4 (Fast Ethernet)
• 100Base-TX (Fast Ethernet)
• 100VG-Any LAN (IEEE 802.12)
• 52/155Mbps ATM (ATM Forum)
• 622Mbps ATM (ATM Forum)
• 1000Base-T (Gigabit Ethernet)
• 1 Gigabit Networking System (WGNA)
• 1.2Gbps ATM (ATM Forum)
• 77 Channel broadband video
• 10GBase-T Ethernet (IEEE P802.1an)
• TIA/EIA 568-B.2-10 Draft Standards
• ISO/IEC 11801 Class Ed 2.1 Draft Horizontal
Nominal outer diameter:
Maximum average outer diameter:
(Useforconduitfillcalculations)
23 AWG solid bare copper All 4 pairs 100% FEP Fluoropolymer Non-lead, flame retardant PVC 0.295" (7.5mm)
0.295" (7.5mm) 0.275" x 0.330" (6.9mm x 8.4mm)
O r d e r i n g I n f o r m a t i o n
Description Catalog Number*
4-pair Plenum data cable
Trang 4• Broadband and baseband video
• 100Base-T (Fast Ethernet)
• 100Base-T4 (Fast Ethernet)
• 100Base-TX (Fast Ethernet)
• 100VG-Any LAN (IEEE 802.12)
• 52/155Mbps ATM (ATM Forum)
• 622Mbps ATM (ATM Forum)
• 1000Base-T (Gigabit Ethernet)
• 1 Gigabit Networking System (WGNA)
• 1.2Gbps ATM (ATM Forum)
• 77 Channel broadband video
• 10GBase-T Ethernet (IEEE P802.1an) proposed
• TIA/EIA 568-B.2-10 Draft Standards
• ISO/IEC 11801 Class Ed 2.1 Draft Horizontal Cable Requirements
Nominal outer diameter:
Maximum average outer diameter:
0.295" (7.5mm) 0.275" x 0.330" (6.9mm x 8.4mm)
Trang 5Category 6 Plenum Cable
TrueNet® Category 6 Plenum cable
® Category 6 Plenum cable
is also available in a side-by-side configuration
Common Applications
• 4/16Mbps Token Ring (IEEE 802.5)
• 10Base-T (IEEE 802.3)
• 100Mbps TP-PMD
• Broadband and baseband video
• 100Base-T (Fast Ethernet)
• 100Base-T4 (Fast Ethernet)
• 100Base-TX (Fast Ethernet)
• 100VG-AnyLAN (IEEE 802.12)
• 52/155Mbps ATM (ATM Forum)
• 622Mbps ATM (ATM Forum)
• 1000Base-T (Gigabit Ethernet)
• 1Gbps Networking System (WGNA)
• 1.2Gbps ATM (ATM Forum)
• 77 Channel broadband video
Trang 6Category 6 Plenum Cable
Ordering information follows on the next page
Specifications
ELECTRICAL CHARACTERISTICS Conductor DC resistance (maximum): 28.6Ω /1000 feet (9.38Ω/100 meters) @20°C
DC resistance unbalance (maximum): 2%
Mutual capacitance (maximum): 17 pF/foot (5.6nF/100 meters)
Operating temperature (maximum): 75°C
Operating voltage (maximum): 300VDC
Worst case cable skew: 25 nS/100 meters @100MHz
Nominal velocity of propagation: 73%
FITTED FREq IMPEDANCE INSERTION LOSS RETURN LOSS Pair-Pair NExT PSNExT (MHz) (Ohms) (dB/100m) (dB/100m) (dB/100m) (dB/100m)
SPEC Max TIA Spec Min TIA Spec Min TIA Spec Min TIA Spec
72.363.358.857.354.252.851.349.945.442.339.437.836.3
81.974.371.068.066.764.763.660.959.357.451.452.448.548.244.845.243.443.039.4
74.365.360.859.356.254.853.351.947.444.341.439.838.3
83.874.974.470.367.266.865.661.861.060.254.854.949.549.046.347.547.343.840.2
20.022.924.525.025.025.024.323.621.520.118.818.017.3
28.532.135.034.631.732.136.536.734.030.827.331.028.627.224.325.024.524.218.6
2.03.85.36.07.68.59.510.715.419.825.229.032.8
1.73.44.95.57.07.98.99.914.318.423.326.830.433.736.739.642.545.347.7
1481016202531.2562.5100155200250300350400450500550
72.661.856.254.249.848.246.544.439.435.933.230.628.925.521.822.527.324.024.7
67.855.849.747.843.741.839.837.931.927.824.021.819.8
73.662.757.255.251.149.347.445.540.136.833.631.729.126.221.322.128.323.625.7
70.359.553.451.346.744.341.839.230.022.514.38.83.5
84.271.266.462.861.557.457.751.347.941.629.926.922.216.614.710.28.44.80.7
72.361.555.453.348.746.343.841.232.024.516.310.85.5
86.871.769.865.164.859.460.252.549.342.733.230.326.719.416.812.010.48.81.7
1481016202531.2562.5100155200250300350400450500550
40.040.040.040.038.037.036.035.132.030.028.127.026.0
Trang 7TN6SP-XXYY TN6SP-XXRB TN6SPX2-XXYY
*To order cable sheath color, replace XX with:
Trang 8• Broadband and baseband video
• 100Base-T (Fast Ethernet)
• 100Base-T4 (Fast Ethernet)
• 100Base-TX (Fast Ethernet)
• 100VG-AnyLAN (IEEE 802.12)
• 52/155Mbps ATM (ATM Forum)
• 622Mbps ATM (ATM Forum)
• 1000Base-T (Gigabit Ethernet)
• 1Gbps Networking System (WGNA)
• 1.2Gbps ATM (ATM Forum)
• 77 Channel broadband video
Category 6 Riser Cable
Performance information follows on the next page
CONSTRUCTION
FeaturesAirES ® technology Conductors:
Trang 9Conductor DC resistance (maximum): 28.6Ω /1000 feet (9.38Ω/100 meters) @20°C
DC resistance unbalance (maximum): 2%
Mutual capacitance (maximum): 17 pF/foot (5.6nF/100 meters)
Operating temperature (maximum): 75°C
Operating voltage (maximum): 300VDC
Worst case cable skew: 25 nS/100 meters @100MHz
Nominal velocity of propagation: 69%
Ordering information follows on the next page
FITTED FREq IMPEDANCE INSERTION LOSS RETURN LOSS Pair-Pair NExT PSNExT
(MHz) (Ohms) (dB/100m) (dB/100m) (dB/100m) (dB/100m)
SPEC Max TIA Spec Min TIA Spec Min TIA Spec Min TIA Spec
72.363.358.857.354.252.851.349.945.442.339.437.836.3
81.073.764.065.763.861.159.958.553.152.350.547.647.742.645.241.942.540.038.8
74.365.360.859.356.254.853.351.947.444.341.439.838.3
83.476.965.667.265.962.260.160.654.054.452.249.950.144.145.944.845.841.641.1
20.022.924.525.025.025.024.323.621.520.118.818.017.3
27.232.234.233.833.930.633.132.933.529.423.527.127.923.321.522.120.418.518.3
2.03.85.36.07.68.59.510.715.419.825.229.032.8
1.83.65.15.87.48.39.310.414.919.024.027.430.833.936.639.442.344.847.1
14810
74.862.555.654.750.549.847.145.940.337.134.632.031.525.523.821.219.518.715.4
67.855.849.747.843.741.839.837.931.927.824.021.819.8
75.463.056.054.750.449.847.346.040.337.235.235.732.127.024.923.722.319.915.4
70.359.553.451.346.744.341.839.230.022.514.38.83.5
79.372.959.260.160.353.251.951.841.435.927.221.017.49.29.14.83.7
72.361.555.453.348.746.343.841.23224.516.310.85.5
81.874.460.661.663.554.353.452.042.237.029.023.319.810.89.85.96.7
14810
NOTE: The above listed discrete frequency electrical performance values are provided for engineering information only Actual compliance
testing is based on swept frequency measurements The spec values are based on TIA/EIA 568-B.2-1 specifications.
Trang 10Reel in a box—1000'
4-pair cable, CM flame rated
Nominal OD: 0.215" (5.46mm)Reel packaging
Reel in a box—1000'
2628
2628
TN6SR-XXYY TN6SR-XXRB
TN6SM-XXYY TN6SM-XXRB
*To order cable sheath color, replace XX with:
Trang 11• Broadband and baseband video
• 100Base-T (Fast Ethernet)
• 100Base-T4 (Fast Ethernet)
• 100Base-TX (Fast Ethernet)
• 100VG-AnyLAN (IEEE 802.12)
• 52/155Mbps ATM (ATM Forum)
• 622Mbps ATM (ATM Forum)
• 1000Base-T (Gigabit Ethernet)
• 1Gbps Networking System (WGNA)
• Individual 4-pair horizontal cables twisted and bound together with Kevlar® cord
• Patented impedance matching for zero-bit errors
• Manufactured with lead-free materials
Performance information follows on the next page
Specifications
Trang 12Category 6 Bundled Plenum Cable
Impedance Attenuation Return Loss Attenuation-To-NExT Ratio (Ohms) (dB/100m) (dB) Pair-To-Pair PowerSum Freq (dB/100m) (dB/100m) (MHz) Input Characteristic Typical Spec Typical Spec Typical Spec Typical Spec Typical Typical
DC resistance unbalance (maximum): 2%
Mutual capacitance (maximum): 17 pF/foot (5.6nF/100 meters)
Operating temperature (maximum): 75°C
Operating voltage (maximum): 300VDC
Worst case cable skew: 25 nS/100 meters @100MHz
Nominal velocity of propagation: 75% @100MHz
Ordering information follows on the next page
Trang 13ST = Standard bundled colors—white, blue, gray, orange, yellow, green
*To designate reel length, replace YY with:
Trang 14• Broadband and baseband video
• 100Base-T (Fast Ethernet)
• 100Base-T4 (Fast Ethernet)
• 100Base-TX (Fast Ethernet)
• 100VG-AnyLAN (IEEE 802.12)
• 52/155Mbps ATM (ATM Forum)
• 622Mbps ATM (ATM Forum)
• 1000Base-T (Gigabit Ethernet)
• 1Gbps Networking System (WGNA)
®
Features
• Individual 4-pair horizontal cables twisted and bound together with Kevlar® cord
• Patented impedance matching for zero-bit errors
• Manufactured with lead-free materials
Performance information follows on the next page
CONSTRUCTION
FeaturesAirES ® technology Conductors:
Specifications
Trang 15Category 6 Bundled Riser Cable
Impedance Attenuation Return Loss Attenuation-To-NExT Ratio
Freq (Ohms) (dB/100m) (dB) Pair-To-Pair PowerSum
NOTE: The above listed discrete frequency electrical performance values are provided for engineering information only Actual compliance
testing is based on swept frequency measurements The spec values are based on TIA/EIA 568-B.2-1 specifications.
Ordering information follows on the next page
Specifications
ELECTRICAL CHARACTERISTICS
Conductor DC resistance (maximum): 28.6Ω/1000 feet (9.38Ω/100 meters) @20°C
DC resistance unbalance (maximum): 2%
Mutual capacitance (maximum): 17 pF/foot (5.6nF/100 meters)
Operating temperature (maximum): 75°C
Operating voltage (maximum): 300VDC
Worst case cable skew: 45 nS/100 meters @100MHz
Nominal velocity of propagation: 77% @100MHz
Trang 16Category 6 Bundled Riser Cable
*To order cable sheath color, replace XX with:
ST = Standard bundled colors—white, blue, gray, orange, yellow, green
*To designate reel length, replace YY with:
Trang 17• Broadband and baseband video
• 100Base-T (Fast Ethernet)
• 100Base-T4 (Fast Ethernet)
• 100Base-TX (Fast Ethernet)
• 100VG-AnyLAN (IEEE 802.12)
• 52/155Mbps ATM (ATM Forum)
• 622Mbps ATM (ATM Forum)
• 1000Base-T (Gigabit Ethernet)
• 1Gigabit Networking System (WGNA)
• 1.2Gbps ATM (ATM Forum)
• 77 Channel broadband video
Specifications
Trang 18Category 6 Limited Combustible Cable
Impedance Attenuation Return Loss Attenuation-To-NExT Ratio Freq (Ohms) (dB/100m) (dB) Pair-To-Pair PowerSum (MHz) (dB/100m) (dB/100m) Input Characteristic Max EIA/TIA- Min EIA/TIA- Min EIA/TIA- Min EIA/TIA- Typical Typical 568 Cat 6 568 Cat 6 568 Cat 6 568 Cat 6
DC resistance unbalance (maximum): 2%
Mutual capacitance (maximum): 17 pF/foot (5.6nF/100 meters)
Operating temperature (maximum): 75°C
Operating voltage (maximum): 300VDC
Worst case cable skew: 30 nS/100 meters @100MHz
Nominal velocity of propagation: 77% @100MHz
Trang 19Description Weight (Lbs/kft) Catalog Number
4-pair cable, clear jacket
3133
TN6ESD-CL02TN6ESD-CLRB
TN6ESD-BL02TN6ESD-BLRB
Category 6 Limited Combustible Cable
Trang 20Category 5e Plenum Cable
TrueNet® Category 5e Plenum cable
® Category 5e Plenum cable
is also available in a side-by-side configuration
Common Applications
• 4/16Mbps Token Ring (IEEE 802.5)
• 10Base-T (IEEE 802.3)
• 100Mbps TP-PMD
• Broadband and baseband video
• 100Base-T (Fast Ethernet)
• 100Base-T4 (Fast Ethernet)
• 100Base-TX (Fast Ethernet)
• 100VG-AnyLAN (IEEE 802.12)
• 52/155Mbps ATM (ATM Forum)
• 622Mbps ATM (ATM Forum)
• 1000Base-T (Gigabit Ethernet)
• 1Gbps Networking System (WGNA)
Specifications
Trang 21Category 5e Plenum Cable
Ordering information follows on the next page
Specifications
ELECTRICAL CHARACTERISTICS
Conductor DC resistance (maximum): 28.6Ω/1000 feet (9.38Ω/100 meters) @20°C
DC resistance unbalance (maximum): 2%
Mutual capacitance (maximum): 17 pF/foot (5.6nF/100 meters)
Operating temperature (maximum): 75°C
Operating voltage (maximum): 300VDC
Worst case cable skew: 22 nS/100 meters @100MHz
Nominal velocity of propagation: 75%
NOTE: The above listed discrete frequency electrical performance values are provided for engineering information only
Actual compliance testing is based on swept frequency measurements The spec values are also based on the TIA/
70.058.752.550.847.144.942.641.135.231.728.627.325.423.822.1
63.851.845.743.839.737.835.833.927.923.8
70.258.952.851.147.445.043.041.435.232.028.727.425.824.422.8
60.349.243.040.836.033.530.928.218.410.3
76.364.258.156.452.049.447.344.134.827.422.816.68.65.20.3
63.352.246.043.839.036.533.931.221.413.3
78.068.659.157.853.851.249.047.936.929.426.218.710.17.71.8
14810
(MHz) (Ohms) (dB/100m) (dB/100m) (dB/100m) (dB/100m)
SPEC Max TIA Spec Min TIA Spec Min TIA Spec Min TIA Spec
14810
78.167.963.562.459.758.056.954.950.347.247.945.541.141.139.6
65.356.351.850.347.245.844.342.938.435.3
79.872.464.463.761.459.758.758.752.449.351.347.542.643.641.1
20.023.024.525.025.025.024.323.621.520.1
33.130.132.731.437.037.535.134.433.229.829.322.925.022.522.4
2.04.15.86.58.29.310.411.717.022.0
1.93.75.36.07.68.69.610.815.519.825.128.932.535.939.3
Trang 22Reel in a box–1000'Reelex–1000'
4-pair, side-by-side cable
Nominal OD: 0.19" x 0.40" (4.83mm x 10.16mm)
21232150
TN5ESP-XXYY TN5ESP-XXRB TN5ESP-XXII TN5ESPX2-XXYY
*To order cable sheath color, replace XX with: