The key component to remember is that the square wave of an Ethernet signal is made of many different sine waves, each important to creating the shape of the square wave.. Ethernet signa
Trang 1of the most commonly asked questions with the introduction of the TrueNet ™ Structured Cabling System is,
“Why do you only offer patch cords in certain lengths?”
Specifically, those lengths are 4, 7, 10 and 15 feet
And the simple answer is: certain patch cord lengths
cause unacceptable signal reflection and distortion to
Ethernet signals, leading to errors and poor network
throughput Factory-terminated 4, 7, 10 and 15 foot
TrueNet cords prevent this distortion, preserving the
integrity of 10/100Base-T Ethernet signals
What is an Ethernet signal?
The explanation of what an Ethernet signal is, is rather
complex In fact, in order to begin, it is first important to
understand the composition of an Ethernet signal
An Ethernet signal is designed to mimic the binary language
of computers (ones and zeros), by creating a signal which
can be sent over a distance One of the binary signaling
methods that is easiest to understand is Morse code, where
a quick “dot” is one and a long “dash” is zero Ethernet
uses electrical impulses to create a signaling method which
also can be interpreted as zeros or ones The basic idea is to
create a square wave, seen below (Figure 1), where the
instantaneous changes up and down are used in indicate the
one or zero Using electrons to create a signal that looks like
a square wave is somewhat tricky, but here is the basic idea:
An electrical impulse takes the shape of a sine wave A wave has two components: the amplitude and the frequency (frequency can also be called wavelength) The amplitude is the “height” of the wave The frequency, or wavelength, is the number of peaks in a given timeframe (see Figure 2)
The illustration below (Figure 3) shows four different sine waves, each with the same amplitude, but having varying frequencies
In order to create a signal that looks like a square wave, you need to create a signal which combines many frequencies together (see Figure 4)
The key component to remember is that the square wave
of an Ethernet signal is made of many different sine waves, each important to creating the shape of the square wave
Ethernet Signal Preservation
In Factory-Terminated Patch Cords for Local Area Networks.
O
Wavelength
Figure 2: Sine wave.
Figure 1: The square wave of an Ethernet signal.
Figure 3: Sine waves of varying frequencies.
Trang 2The next important thing to understand is that Ethernet expects the size and shape of the square wave to fall within
a set of defined boundaries, so that the signal can be properly interpreted One example of these boundaries is the rise and fall time, or the time that it takes to indicate a change in state (see Figure 5) If either of these parameters don’t fall within the prescribed limits, a “one”might be misinterpreted as a“zero” (which would cause an error)
Now, “What does any of this have to do with patch cord lengths?” To get to the answer, we have to go back
to the sine wave
Ethernet signals and patch cords
We pointed out that an Ethernet square wave is made up of the sum of many sine waves If anything should happen to the energy in one or more of those sine waves as they travel down the wire, the shape of the square wave can change
To look at it another way, if you remove any one sine wave from the square wave, the shape changes Therefore, it is critical to ensure that signal energy is preserved as a signal travels along a wire, so the shape of the wave stays consistent
As a sine wave is generated, the greatest amount of energy
is released at peaks of the cycle (since a sine wave oscillates around a zero line, peak energy occurs at the “peak” and
“valley” of each cycle) (see Figure 6) If anything happens to disrupt the wave at these points, the signal strength of that wave is severely compromised As it turns out, the most disruptive elements to signal strength in a network node are the connection points Remember that any node in a network consists of a number of connections between the signal-generating ends (the NIC and the hub/switch) Patch cords are plugged into the station outlet, patch panels, etc The reason that connection points are disruptive is two-fold First, it represents a transition of physical materials and geometry which occurs in the path of the signal This disruption is further exacerbated when the connected
Rise Time
Nanoseconds
Fall Time
Figure 5: Rise and fall time is the length of time, in nanoseconds, that it takes for a signal to rise or fall from one state to another, signaling a “one.”
Add sine waves of different frequencies together
Add even more frequencies
And it starts to look like a square wave!
Figure 4: The square wave of an Ethernet signal is made of many different sine waves combined together.
The key component
to remember is that
the square wave of
an Ethernet signal
is made of many
different sine waves,
each important
to creating the shape
of the square wave.
Trang 3elements are not electrically matched well The second
reason is that the connection points are usually very close to
one of the active sending elements of the network (NIC or
hub), where signal strength is the strongest, and has the
most energy The first connection point is obviously the
patch cord Therefore, the integrity of patch cords is critical
(see Figure 7)
When the sine waves hit the connection point, if any
wave is at its point of maximum energy, one of two
things can happen:
1 The energy can be reflected back toward the source
2 The energy can be dissipated and lost
In either case, the shape of the sine wave is distorted,
which then can distort the square wave
Since the wavelength of a sine wave actually corresponds to
a physical length in meters, it is possible to determine the
physical distances where the peaks and valleys of the wave occur It is therefore possible to determine the optimal length of a patch cord so as to position the first connection point at a physical distance where minimum energy
is occurring (see Figure 8)
The most important thing to do is to minimize the energy reflection at the sine wave frequencies that are most critical
to the shape of the square wave For 10/100Base-T Ethernet, the frequencies of greatest concern are the approximate window between 10 MHz and 31 MHz
Patch cord lengths which do not take this distortion effect into account can allow maximum energy at the critical frequencies to be present at the connection point, which has the effect of distorting the square wave, and causing bit errors in Ethernet
The technique of using specific patch cord lengths to reduce errors has been confirmed with active network analysis of bit error generation in otherwise identical patch cords plugged into the same channel Patch cords of the proper length generated no errors, while patch cords of the incorrect length returned error after error De-embedded electrical testing also confirms this result, in the form of excessive return loss on the resonance producing lengths
Consequently, the decision was made with the launch of the TrueNet patch cord line to only include lengths which are
“safe” for use in Ethernet systems These lengths are 4, 7, 10 and 15 feet, respectively Other lengths from 1 to 20 feet can produce unacceptable error generation under normal use
All TrueNet cords are 100% performance tested and factory terminated to the proper lengths to ensure optimum performance
NIC
Patch Cord Connector Connector
Horizontal Cable
Patch Cord
HUB
Figure 7: The patch cord represents the first, and most critical, connection point in the network.
Zero Energy
Maximum
Energy
Maximum Energy
Wavelength
Figure 6: As a sine wave is generated, the greatest amount of
energy is released at peaks of the cycle.
Trang 4The philosophy of the TrueNet system is to eliminate the root causes of poor throughput in structured cabling systems Fortunately, the benefits of patch cords that do not have error-causing lengths is demonstrable in any cabling system, even if no other TrueNet components are used
Bottom line — certain lengths of patch cords generate errors, others do not KRONE is committed to providing only the best possible data transmission solutions to the marketplace KRONE’s TrueNet patch cords have been designed from the ground up to preserve the integrity of Ethernet signals
KRONE, Inc.
North America Headquarters
6950 South Tucson Way
Englewood, CO 80112-3922
Telephone: (303) 790.2619
Toll-Free: (800) 775.KRONE
Facsimile: (303) 790.2117
www.kroneamericas.com
www.truenet-system.com
Zero
Energy
Maximum Energy
Resonance Producing Length
Non-Resonance Producing Length
Zero Energy
NIC NIC
Figure 8: TrueNet patch cords are available only in lengths “safe” for Ethernet systems.
All TrueNet cords are 100% performance tested and factory terminated to the proper lengths to ensure optimum performance.