scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution scada for power distribution
Trang 1Dr NDR Sarma
SCADA and Distribution Automation
IEEE Hyderabad Section Joint Chapter of PES/IAS Societies
Trang 2Generating Plant
Step-up transformers Circuit breakers Transmission System
Transformers in Bulk power substations
Solar or Wind Sources (100KW to 1MW)
Distribution Transformer
Dispersed Storage and generation (DSG)
Voltage Regulator
Capacitor bank
Sub-transmission system
Distribution substation
phase Primary feeders
Three-Battery or Fuel cells,
Trang 3Sub-Station Transformer
Trang 4Incoming feeders
Trang 6Distribution Transformer Location
Trang 7Distribution Transformer (1-Ph) Location
Trang 8Switch at a DT
Trang 9Switch on a 11kV feeder
Trang 10Power System connectivity
33 kV lines
220kV Lines
EHV substations
Distribution substations
17.6/220 kV
Sub-station
220/33 kV Sub-station
33/11 kV Sub-station
Industry at 33 kV
11 kV lines (feeders)
Distribution Transformer
11/ 0.4 kV
Industry at 11 kV (Domestic, Commercial, Agricultural)Customers
Trang 11Power System in a typical city
EHV Sub-stations
Distribution s/s
Trang 12Power System in a typical city
Distribution s/s
Trang 13IT Applications to Power
• Power System Operation and Control
- Power Plant Automation
- Energy Management Systems
Trang 15Primary circuits
Generating Plant
Step-up transformers Circuit breakers Transmission System
Transformers in Bulk power substations
Solar or Wind Sources (100KW to 1MW)
One-phase lateral feeder
Distribution Transformer
Dispersed Storage and generation (DSG)
Voltage Regulator
Capacitor bank
Sub-transmission system
Distribution substation
phase Primary feeders
Three-Battery or Fuel cells,
Trang 16Primary circuits
Generating Plant
Step-up transformers Circuit breakers Transmission System
Transformers in Bulk power substations
Solar or Wind Sources (100KW to 1MW)
One-phase lateral feeder
Distribution Transformer
Dispersed Storage and generation (DSG)
Voltage Regulator
Capacitor bank
Sub-transmission system
Distribution substation
phase Primary feeders
Three-Battery or Fuel cells,
( Decision supportTools )
219 kV
248 MW
SCADA and Application Functions
Trang 17Levels of Automation
Substation Level Automation
Feeder Level Automation
Customer Level Automation
Voltage Regulator
Solar or Wind Sources (100KW to 1MW)
One-phase lateral feeder
Distribution Transformer
Dispersed Storage and generation (DSG)
Capacitor bank
Sub-transmission system
Distribution substation
phase Primary feeders
Three-Battery or Fuel cells,
Trang 18Function of Distribution Automation System
Remotely monitors the distribution system,
facilitates supervisory control of devices and provides decision support tools to improve the system performance
• SCADA
(Supervisory Control And Data Acquisition)
• Application Functions
Trang 20SCADA
How ?
Trang 21SCADA Features
Hardware Components
Software Components
Trang 22SCADA – Hardware Components
(Voltage : 10 V DC)
Transducer output (011011110011)
A/D Converter output
(Voltage : 10 kV) Field Values
Trang 23Remote Terminal Unit (RTU)
Trang 24Pole Top RTU
Trang 25Remote Terminal Unit (RTU)
Trang 26Communication Options
• Wired
• Wireless
Trang 27Communication Options - Wired
• Twisted pair cables
• Co-axial cables
• Fiber Optic cables
• PLCC
Trang 28Communication Options - Wireless
Trang 29Communication Systems - MARS
• Multiple Address Radio System
• Primarily for Data Communication
• Voice Communication possible using a hand set
• Polling interrupted during voice call
• Voice restricted to emergency situations
Trang 30Communication Systems - MARS
• Frequency of operation : 800-900/400-512 MHz
• Range : 20-30 Kms
• Half duplex
• Offers data rates up to 9600 Bps
• Very popular for DA application
Trang 31Typical Multiple Access Radio Network
Trang 33Control Center Architecture
SCADA Host Systems
LAN
MMI 1
MMI 6
Video Projector
Printer Sharer PERIPHERAL
SERVER -2
Time Center
Trang 34SCADA – Software Components
• Graphical User Interface
• Logging and Reporting
Trang 35SCADA – Software Components(Contd.)
Field Equipment Connectivity
Transducer output (011011110011)
A/D Converter output
Protocols
Trang 36SCADA – Software Components(Contd.)
(011011110011)
A/D Converter output
( Voltage : 11kV) Field Values
Trang 37SCADA – Software Components(Contd.)
Trang 38SCADA – Software Components(Contd.)
Voltage Regulator
Solar or Wind Sources (100KW to 1MW)
One-phase lateral feeder
Distribution Transformer
Dispersed Storage and generation (DSG)
Capacitor bank
Sub-transmission system
Distribution substation
phase Primary feeders
Three-Battery or Fuel cells,
Interlocks based on Attributes, values/status
Single, Group, Sequential and Closed Loop Control
Select-Check-Execute, Immediate Execute
Control
Trang 39SCADA – Software Components(Contd.)
Voltage Regulator
Solar or Wind Sources (100KW to 1MW)
One-phase lateral feeder
Distribution Transformer
Dispersed Storage and generation (DSG)
Capacitor bank
Sub-transmission system
Distribution substation
phase Primary feeders
Three-Battery or Fuel cells,
Interlocks based on Attributes, values/status
Single, Group, Sequential and Closed Loop Control
Select-Check-Execute, Immediate Execute
Control
Trang 40SCADA – Software Components(Contd.)
Alarms & Events
Configurable Event Types
Current Alarms Configurable
Trang 41Graphical User Interface
SCADA – Software Components(Contd.)
Real Time display
Single Line Diagrams,Graphics,Maps
Trends; Real-time and Historic
Alarms; current and Historic
Interface to control field devices
Trang 42Automated Mapping and Facilities Management (AM/FM)
• Display of geographical Maps
• Dynamic info on Maps
• Layering, Zooming, Scrolling and Panning
• Historical data on Devices
(From T&D World, Oct 2001)
(From T&D World, Oct 2001)
Trang 43Distribution Automation :
- Application Functions
Trang 44Operational problems and Potential Applications of DAS
• Fault location, isolation and Service Restoration
• Maintaining good voltage profile
Trang 45Application Functions
• Network Reconfiguration
a) Fault localization b) Service Restoration c) Load Balancing
• Integrated Volt-Var Control
• Remote Metering
• Automatic Load Shedding
• Load Management
• Automated Mapping and Facilities Management (AM/FM)
• Trouble Call Management System (TCMS)
• Load Survey and Energy Accounting
1.Ch Narasimha Murthy, KV Raju, A Ramakoteswara Rao, N Balakrishna Reddy, NDR Sarma, P Vani, Sanjay J
Mali, Jhuma Nath, KJ Babu Narayanan, "Gachibowli Distribution Automation", Proceedings, DA/DSM Asia
'96, New Delhi, India, 17-19 Sept 1996, Vol 5, pp 31-40
2 NDR Sarma, "Rapid Growth Leads to System Automation Efforts", Transmission and Distribution World,
Sept, 1997
Trang 46Network Reconfiguration - Fault Localization
• Locates faulty section in a radial distribution feeder by operating “Load Break Switches” on a feeder
Remotely controllable Switch
Trang 47Remotely controllable Switch on a 11kV feeder
Trang 48Remotely controllable Switch on a 11kV feeder
Trang 49Distribution s/s
Network Reconfiguration - Fault Localization
• Localization is faster compared to
manual determination of
faulty section Fault
Trang 50• Restores service to non-faulty feeder sections by reconfiguration
Trang 52Network Reconfiguration - Service Restoration
Trang 53• Fault Identification
Network Reconfiguration - Service Restoration
• Determination of affected load points
- After isolating the faulted component(s), system would be divided ingroup of connected components
- Loads in the groups with no source points are affected load points
Trang 54Network Reconfiguration – Service Restoration
Trang 55Network Reconfiguration –
Service Restoration
Loads at nodes 15, 44 and 56 (L7&, L4 and L3) are affected loads for this case
Trang 56• Fault Identification
Network Reconfiguration - Service Restoration
• Determination of affected load points
- After isolating the faulted component (s), system would be divided ingroup of connected components
- Loads in the groups with no source points are affected load points
• Determination of non-restorable affected load points
- No alternate path for an affected load point
- Service restorable to such non-restorable affected load points only after repairing the faults
- Consider the network with all components (except faulted components)
- Check the connectivity
- If connected, service restorable to all components
Trang 57Network Reconfiguration - Service Restoration
• Determination of non-restorable affected load points
- No alternate path for an affected load point
- Service restorable to such non-restorable affected load points only after repairing the faults
- Consider the network with all components (except faulted components)
- Check the connectivity
- If connected, service restorable to all components
- If not connected, network will be divided into different groups
* Type 0 : Does not have affected load points and source points
* Type 1 : Have source points
* Type 2 : Has affected load points but no source points
Loads in Group of Type 2 are non-restorable affected load points !
Network obtained after deleting groups of type 0 and 2
is considered for further analysis
Trang 58Network Reconfiguration - Service Restoration
• Determination of all possible service restoration strategies
- The complete network is reduced to a smaller network by merging
all the connected (except those corresponding to switches in interlocking sequence) together
Network obtained after deleting groups of type 0 and 2
is considered for further analysis
- All ’interesting trees’ of this reduced network correspond to a possible restoration strategy
- Restoration is based on
- satisfaction of current and voltage constraints
- minimum switches
- minimum losses
Trang 59Network Reconfiguration - Service Restoration
Trang 60Network Reconfiguration – Service Restoration
Trang 61Network Reconfiguration –
Service Restoration
Loads at nodes 15, 44 and 56 (L&, L4 and L3) are affected loads for this case
Trang 62Network Reconfiguration – Service Restoration
Trang 63Network Reconfiguration – Service Restoration
Trang 64Network Reconfiguration – Service Restoration
Trang 65Network Reconfiguration – Service Restoration
Trang 66Network Reconfiguration - Loss Minimization
• Composition and hence consumption patterns of loads on
different feeders are different
• Thus, a particular configuration of the distribution system which is set for minimum loss at a certain instant of time will no longer be a minimum loss configuration at a different instant of time
• This is an important function in Distribution Automation
• Therefore, there is a need to reconfigure the system for loss
minimization when ever there is a change in the loading pattern
on the system
Trang 67Network Reconfiguration – Loss Minimization
Distribution s/s
• Considerations
* Presence of alternate paths
* Operation of LB switches
* Need to have remotely controllable switches
* Reconfiguration for minimum losses
Trang 68* Need to have remotely controllable switches
* Reconfiguration for minimum losses
NDR Sarma, KS Prakasa Rao, " A New 0-1 integer Programming Method of Feeder
Reconfiguration for Loss minimization in Distribution Systems", International Journal on
Electric Power Systems Research, Vol 33, 1995, pp 125-131
Trang 69How to reconfigure for Loss Minimization ?
• There are several methods in the literature
Trang 700-1 Integer Programming Method
• Elements 12, 23 and 16 are initially open
• Node 6 can be switched to Ckt 2 or node 14 can be switched to ckt 1
• Node 9 can be switched to Ckt 3 or node 23 can be switched to ckt 1
Trang 710-1 Integer Programming Method
• Nodes 6,9,14 and 23 can be associated with variables X6, X9, X14, and X23
• These variables are 0-1 integer variables
• X6= 1 implies that node 6 is connected to ckt 1 and X6= 0 implies that
node 6 is NOT connected to ckt 1 but connected to ckt 2
• Thus the values of X6 and X14 will decide whether node 6 is to be
switched on to ckt 2 or node 14 is to be switched on to ckt 1
• It is important to see that each node is connected to any one circuit,
i.e., both cannot be zero simultaneously
X6 + X14 ≥ 1
Trang 72• Current in element 1 can be written as
0-1 Integer Programming Method
• Power loss in element 1 can be written as
Trang 73• Power loss in element 1 can be written as
0-1 Integer Programming Method
Trang 74General Form for loss in element 1
General Form for loss in element i
Trang 750-1 Integer Programming Method
Loss Function for Circuit 1 is obtained by taking summation over all elements in the circuit
Trang 760-1 Integer Programming Method
Trang 77Power loss functions
Trang 780-1 Integer Programming Method
Total loss function for the entire system
This function has to be minimized subject to
Trang 790-1 Integer Programming Method
Trang 81Network Reconfiguration - Load Balancing
• Composition and hence consumption patterns of loads on different feeders are different
• To distribute loads among transformers/feeders
• Remote control of switches for reconfiguration
Trang 82Distribution s/s
Load Balancing - Illustration
* To distribute loads among transformers/feeders
* Remote control of switches for reconfiguration
• Considerations
NDR Sarma, P.S Nagendra Rao, V.C Prasad and KS Prakasa Rao, "A New and Efficient Method of
Feeder Reconfiguration for Load Balancing in Distribution Systems", Proceedings of 59th American
Power Conference, Chicago, USA, April, 1997
Trang 83Why Distribution Automation ?
Benefits
- Tangible
- Intangible
Trang 84Tangible Benefits
Substation Automation
Feeder Automation
Customer interface Automation
Reduction in O&M Costs of LTC
• Deferment of additional feeders
• Effective utilization of existing feeders
Reduction in O&M Costs of:
• Regular Meter Reading
• Reprogramming of Meters
• Service Connect/Disconnect
• Processing of Customer Claims
Reduction in O&M Costs for:
• Routine Relay Testing
• Relay Setting
Reduction in O&M Costs of:
• Routine Data Collection
• Non-Routine Data Collection
• Data Analysis
• Testing of Data Logging Devices
• Repair of Data Logging Devices
Increased Revenue Due to:
• Loss Reduction due to Feeder Reconfiguration
• Loss Reduction due to Capacitor Banks Automation
• Faster Service Restoration
Reduction in Capital Expenditure
Increased Revenue Due to:
• Reduction of System Peak Load
• Tamper Detection to Reduce Electricity Theft
• Reduced Payments for Customer Claims
Reduction in O&M Costs of:
• Fault Location and Isolation
Trang 85Summary of cost/benefit Analysis Results (done in 1991)
based on tangible benefits
Substation Automation
Feeder Automation
Customer interface Automation
Details of the area : 32,000 customers with electric and gas meters with a mix of 53 % residential,
8 % commercial 37% industrial and 2% agricultural.
Peak demand : 124 MW Area served by three major substations (230/21 kV, 115/12 kV, 60/12 kV) with 13 primary feeders circuits (eleven 12kV and two 21kV) in the area David L Brown, et al., “Prospects For Distribution Automation at Pacific Gas & Electric
Company”, IEEE Transactions on Power Delivery, Vol 6, No 4, October 1991, pp 1946-1954.
Trang 86Feeder Automation
Customer interface Automation
Trang 87• Technology Development Project supported by
DoE, Govt of India
• Involves all aspects of DA
Specifications, Design and Development, Implementation
1.Ch Narasimha Murthy, KV Raju, A Ramakoteswara Rao, N Balakrishna Reddy, NDR Sarma, P Vani, Sanjay J
Mali, Jhuma Nath, KJ Babu Narayanan, "Gachibowli Distribution Automation", Proceedings, DA/DSM Asia
'96, New Delhi, India, 17-19 Sept 1996, Vol 5, pp 31-40
2 NDR Sarma, "Rapid Growth Leads to System Automation Efforts", Transmission and Distribution World,
Sept, 1997