Add reactor protection application scenario Update of technical data Add reactor current differential protection function 87R and inter-turn fault protection function 21IT Ad
Trang 3About This Document
About This Document
The manual describes the control, protection, measurement and supervision functions with the information of relevant hardware for PCS-978S Transformer Relay
Copyright © 2020 NR All rights reserved
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd No NR trademarks may be used without written permission NR products appearing in this document may be covered by P.R China and foreign patents NR Electric Co., Ltd reserves all rights and benefits afforded under P.R China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation NR Engineering Co., Ltd is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights
The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified Information in this document
is subject to change without prior notice
To the extent required the products described herein meet applicable IEC and IEEE standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly
Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency
to be met in connection with installation, operation, or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please
do not hesitate to contact us
Trang 4Document Revision History
Document Revision History
Update of switchgear control function
Modification of voltage selection diagram
Update of technical data
Add reactor protection application scenario
Update of technical data
Add reactor current differential protection function 87R and
inter-turn fault protection function 21IT
Add binary input and binary output module NR6661
Add mechanical relay input and output module NR6662
Replace the NET-DSP module NR6112B with NR6113
Deletion of the DC analogue input module NR6631B
Trang 5Overview
Overview
PCS-978S transformer relay has been designed specifically for the protection of various type power transformers, including two-winding transformers, three-winding transformers (up to 6 branches), auto-transformers, as well as shunt reactors PCS-978S is the main protection for the transformer and contains many other protections, control and monitoring functions With its modular structure, flexibility and the powerful PCS-Studio engineering tool, PCS-978S offers future-oriented system solutions with high investment security and low operating costs
The PCS-978S is applicable not only to conventional substations, but also to digital substations It supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network interfaces with high real-time performance The process level network supports peer-to-peer (P2P) mode and networking mode, including single network mode and dual network mode The station level network could also receive and send MMS messages (such as interlocking signals) or process level GOOSE messages (such as trip signals)
Trang 6 Various function modules can satisfy various situations according to the different requirements of users Flexible and universal logic programming, user-defined configuration of BI/BOs, buttons and LEDs and powerful analog programming are supported
Modularized hardware design makes the device be easily upgraded or repaired by a qualified service person It can be mixed with different I/O modules, with online self-check and monitoring function, and the device can be restored from abnormal operation only need to replace a single abnormal module
Support memory check and error correction function, ensure high reliability and safety
Support the internet communication protocol of native PRP/HSR and RSTP
Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351 communication service, GOOSE communication in station level & process level, SV communication with multi-sampling rate
Full comply with cyber security standards, including IEC62443, IEC62351, IEEE1686, NERC-CIP, support role based access control (RBAC), security audit, security encryption communication and security tool, improve the cyber security capability of devices
Powerful COMTRADE fault and disturbance recording function is supported The whole recording time is automatically configurable by the fault duration, which is convenient to fault analysis and replay The recording sample rate is up to 9.6kHz
Settable secondary rated current (1A/5A) and settable voltage threshold of binary input
Trang 7Highlights
PCS-Studio engineering tool is the application software on the user's PC for the interface with PCS S series devices providing all the related functionality It ranges from device configuration to full substation design of bay integration
Support IEEE1588, IRIG-B clock synchronization
Support actual system phase sequence, either ABC or ACB, incorrect connection of actual phase sequence can automatically be verified and relevant protection functions can be blocked
Equipped with high-speed large capacity output relay, its operation speed is less than 1ms and its break capacity is up to 10A The real-time supervision for output drive circuit can detect the abnormality in advance
Support setup up to 40 users and allow each user to own different password and access authority
Trang 8Features
Features
High degree of functional integration and flexible configuration modes, transformer main protection and back-up protection can be integrated in one device, or be separated in two devices
Up to 36 analog inputs can be provided and configured flexibly
The tripping output contacts can be configured by tripping matrix, which is flexible, convenient and suitable to any mode of tripping
The relay supports at most 6 branches differential protection The transformer angle can be adjusted flexibly, and any transformer angle compensation mode is supported and any side can be chosen as the reference side of differential protection
Reliable differential CT circuit failure supervision The relay can detect multi-phase CT wire-break, multi-side CT wire-break, short-circuit, and other complex situation The corresponding logic setting can be used to select blocking differential protection or not, in case of CT circuit failure
Multiple inrush current blocking options are provided Self-adaptive inrush current blocking criterion can ensure the relay fast operation for transformer energized on to a slight fault, meanwhile it will avoid the unwanted operation in the case of the energization inrush current caused by energizing transformer with no load, the recovery inrush current caused by cutting off the transformer external fault, and the sympathetic inrush current
Biased DPFC differential protection is regardless of load current and is sensitive to small internal fault current within the transformer Its anti CT saturation performance is also strong
Trang 951P Alm 87W 87T
Figure 1 Typical application of an auto-transformer
52 52
Figure 2 Typical application of a shunt reactor
Trang 10Functions Overview
Protection Functions
87T Transformer differential protection
Biased differential protection with three slopes
Biased DPFC differential protection
Unrestrained instantaneous differential protection
Optional inrush current distinguished principles: harmonic criterion or waveform distortion
Optional harmonic blocking modes: self-adaptive 1Pblk1P mode, 2PBlk3P mode, 1Pblk3P mode
Overexcitation detection: fifth harmonic or third harmonic criterion
Optional transfer methods: △→Y or Y→△
Independent CT saturation criterion
Differential CT circuit failure supervision
64REF Restricted earth-fault protection
Optional direction element
CT transient characteristic difference detection
CT saturation detection based on 2nd and 3rd harmonics
87W Winding differential protection CT transient characteristic difference detection
CT saturation detection based on 2nd and 3rd harmonics
87R Reactor differential protection
Biased DPFC differential protection
Biased current differential protection
Independent CT saturation criterion
Harmonic blocking criterion
Differential CT circuit failure supervision
21IT Inter-turn fault protection
Zero-sequence power directional element and zero-sequence impedance element
CT and VT circuit failure blocking
24 Overexcitation protection
Two stages definite-time overexcitation protection
Stage 1 of definite-time overexcitation protection for trip purpose
Stage 2 of definite-time overexcitation protection for alarm purpose
Trang 11Functions Overview
67G
50/51G
Earth fault protection
4 stages with independent logic by default
Optional direction element for each stage,
Optional measured zero-sequence current or calculated zero-sequence current
Optional definite-time characteristic and inverse-time characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
Harmonic control element for each stage
67Q
50/51Q
Negative-sequence overcurrent
protection
Up to 2 stages with independent logic
Optional direction element for each stage
Optional definite-time characteristic and inverse-time characteristic for each stage
49 Thermal overload protection Two stages thermal overload protection, and one stage for
alarm purpose and the other stage for trip purpose
50BF Breaker failure protection
Up to 6 circuit breakers are supported
Phase-segregated re-trip and three-phases re-trip
Optional current criterion (phase overcurrent element, zero-sequence overcurrent element, negative-sequence overcurrent element)
Optional circuit breaker position check
Two time delays
59P Overvoltage protection
Up to 2 stages with independent logic
Optional definite-time characteristic and inverse-time characteristic for each stage
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Selectable trip purpose or alarm purpose for each stage
27P Undervoltage protection
Up to 2 stages with independent logic
Optional definite-time characteristic and inverse-time characteristic for each stage
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Blocked by instantaneous VT circuit failure
Selectable trip purpose or alarm purpose for each stage
59G Residual overvoltage protection
Up to 2 stages with independent logic
Optional measured zero-sequence voltage or calculated zero-sequence voltage
Optional definite-time characteristic and inverse-time characteristic for each stage
Selectable trip purpose or alarm purpose for each stage
81O Overfrequency protection Up to 2 stages with independent logic
Voltage control element
Trang 12Functions Overview
81U Underfrequency protection Up to 4 stages with independent logic
Voltage control element
Control Functions
Switchgear control
Double point status synthesis
Remote/Local control mode switch
Interlocking logic for control
Direct control
Closing synchronism check with voltage selection
Switchgear trip counter
Tap position indicator and control
Measurement and Metering Functions
CT circuit failure Supervision (CTS)
VT circuit failure Supervision (VTS)
Self diagnostic
Powerful faults recording (max buffer for 10,000 sampled points at 4.8 or 9.6 kHz)
Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision events,
Trang 13Functions Overview
Modbus, DNP3.0, IEC 60870-5-103, IEC 61850 Ed.1 & Ed.2, IEC 61850 MMS Server, IEC 61850-8-1 GOOSE, IEC 61850-9-2LE SV, IEC 62439 Parallel Redundancy Protocol, IEC 62439 HSR Ring Redundancy Protocol
Up to four 10Base-T/100Base-TX copper Ethernet ports
Up to fourteen 100Base-FX optical Ethernet ports
Up to four 1000Base-SX optical Ethernet ports
Two RS-485 serial ports for communication or printer
One RS-485/TTL serial port for clock synchronization
Two RJ45 debugging ports (front and rear)
4 Programmable operator pushbuttons with user-configurable labels
Up to 18 programmable target LEDs with user-configurable labels
1 RS-485 rear ports for printer
Language switchover—English+ selected language
Configuration tool—PCS-Studio
Additional Functions
User programmable logic
Switching system phase sequences function (ABC or ACB)
Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE 1588: Clock message based on IEEE 1588 via optical fibre interface
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
SNTP (BC): Broadcast SNTP mode via Ethernet network
Trang 15Typical Application
Typical Application
PCS-978S can be applied for a two-winding transformer, three-winding transformer or auto-transformer
in any voltage level, or a shunt reactor PCS-978S provides full transformer protections which are configurable by user Ancillary functions of fault diagnostic, disturbance records, event records and communication function are integrated in the device
PCS-978S is adaptive to the following 2/3-windings transformers or autotransformer
Trang 17Protection Functions
Protection Functions
Transformer Current Differential Protection (87T)
In power system, the power transformer is one of most valuable and expensive equipment If a fault occurs in the protection zone of a transformer, current differential protection operates quickly to clear the fault to avoid the transformer from damages or reduce the maintenance cost as low as possible
Transformer differential protection supports up to 6 group CT inputs, and can be used for 2-windings, 3-windings transformer and auto-transformer There are 24 vector groups available for two-winding transformer and 288 vector groups available for 3-winding transformer
Transformer differential protection includes biased differential element, instantaneous differential element, DPFC biased differential element Biased differential element is biased characteristic with three slopes Instantaneous differential element is without biased characteristic and blocking logic and can accelerate to operate for transformer's severe internal faults DPFC biased differential element calculated by current variation has high sensitivity to inter-turn faults and high-impedance fault under heavy load Three differential elements mentioned above work coordinately to form the high-speed current differential protection with high sensitivity
Restricted Earth Fault Protection (64REF)
Restricted earth fault protection (REF) is meant to protect a single winding of a power transformer, and the protected winding must be earthed In the case of delta windings, the winding must be earthed by an earthing transformer, which must be electrically placed between the winding and the current transformers REF can be applied to protection of two-winding transformer, three-winding transformer or auto-transformer
REF is a kind of differential protection, so it calculates differential current and restrained current The differential current is a vector difference of the neutral current (i.e., current flowing in the neutral conductor) and the residual current from the lines For internal faults, this difference is equal to the total earth fault current REF operates on the fault current only, and is not dependent on eventual load currents This makes REF a very sensitive protection
The difference between current differential protection and REF is that the first one is based on adjusted phase current balance and the latter is based on balance of calculated residual current and residual current from neutral CT
Three groups of REF are for each side of a three-winding transformer at most REF is not affected by inrush current and the tap of transformer CT Transient detection function based on the ratio of residual current to positive current is adopted to eliminate the influence of difference of transient characteristic to REF
Trang 18compensation 3I0Cal'_H2
Magnitude compensation
Figure 8 Application for two-winding transformer with two CBs at one side
Trang 19REF at HV side
Magnitude compensation
Figure 9 Application for auto-transformer
Maximum 4 group of CTs and 1 neutral point CT inputs for REF, and the maximum current inputs applied for an auto-transformer with two circuit breakers at HV and MV sides respectively
Winding Differential Protection (87W)
When each side and common winding of auto-transformer are installed with three phase CTs, winding differential protection can be equipped Winding differential protection is based on Kirchhoff's law, so inrush current has no effect on it Winding differential protection consists of phase winding differential protection and residual winding differential protection Residual winding differential protection adopts the calculated residual current of each side and common winding for the protection calculation and three-phase CT polarity is easy to be checked The operation principle of which is similar to that of REF, but compared to REF, winding differential protection can operate not only during internal earth faults but also during phase-to-phase faults
Winding differential protection is based on Kirchhoff's first law and calculates differential currents of electrical connection circuits including phase A, phase B phase C and residual differential currents Inrush current and tap change of the transformer have no effect on winding differential protection Winding differential protection has high sensitivity to internal earth faults because there is no load current
in the restraint current Normally, winding differential protection is applied in following two situations
Trang 20REF at HV side
Magnitude compensation
Figure 10 Winding differential protection applied to auto-transformer
Magnitude
protection Magnitude
Trang 21to accelerate the operating speed for reactor's severe internal faults without biased characteristic and blocking elements DPFC biased differential element calculated by current variation has high sensitivity
to earth faults at ground end of reactor Zero-sequence differential element based on calculated residual current of two sides of reactor has high sensitivity to asymmetric fault Above four differential protection elements work coordinately to form the high-speed current differential protection with high sensitivity
Inter-turn Fault Protection (21IT)
Shunt reactors as the key equipment are widely applied in extra-high voltage and ultra-high voltage level power system, which has a dominate effect on safe operation of the power system The inter-turn fault is
a common internal fault occurred in reactor, but current differential protection cannot operate during inter-turn faults Considering earth fault protection cannot be taken as the fast protection for inter-turn faults, a dedicated protection for inter-turn protection of reactor is needed to be equipped
Inter-turn faults in reactors present a formidable challenge to the protection engineer The current and voltage changes encountered during an inter-turn fault can be of similar magnitude as load variation, and therefore, sensitive, reliable protection schemes should be considered
Inter-turn fault protection consists of zero-sequence power direction element and zero-sequence impedance element They can improve sensitivity and ensure the device against maloperation during external faults, transient process (such as series compensated lines, LC resonance, power swing etc.)
or abnormal conditions (such as pole disagreement, CT secondary circuit failure, etc.)
Inter-turn fault protection adopts the current from CT at line side of reactor The amplitude of residual voltage is compensated to ensure zero-sequence power direction element can distinguish direction correctly when system impedance is too low Inter-turn fault protection will be blocked during CT and VT circuit failure
Overexcitation Protection (24)
Overexcitation results from excessive applied voltage, possibly in combination with below-normal frequency Such condition may occur when a unit is on load, but are more likely to arise when it is on open circuit, or at a loss of load occurrence Transformers directly connected to generators are in particular danger to experience overexcitation condition
During overexcitation, field current of transformer rises greatly to cause excessive heating and severe damage The transformer, working magnetic flux density near the knee point, is subject to overexcitation Frequency range for normal operation is 45~55Hz for 50Hz working frequency of power system and 55~65Hz for 60Hz working frequency of power system
Overexcitation protection can be configured at any side of transformer through PCS-Studio, and it is
Trang 22Protection Functions
recommended to be equipped at the side without OLTC
Overexcitation protection consists of two stages definite-time overexcitation protection and one stage inverse-time overexcitation protection for trip purpose or alarm purpose The voltage for protection calculation is RMS of three phase voltages and not affected by frequency fluctuation Overexcitation inverse-time curve is sectional linear curve, which has high adaptability
Phase Overcurrent Protection (50/51P, 67P)
The device can provide 6 stages of phase overcurrent protection with independent logic Each stage can
be independently set as definite-time characteristics or inverse-time characteristics The dropout characteristics can be set as instantaneous dropout, definite-time dropout or inverse-time dropout Users can choose whether it is blocked by the voltage control element, direction control element, or harmonic control element The direction control element can be set as no direction, forward direction and reverse direction The phase overcurrent protection picks up when the current exceeds the current threshold value, and operates after a certain time delay, once the fault disappears, the phase overcurrent protection will dropout
Earth Fault Overcurrent Protection (50/51G, 67G)
The device can provide 4 stages of earth fault overcurrent protection with independent logic Each stage can be independently set as definite-time characteristics or inverse-time characteristics The dropout characteristics can be set as immediate dropout, definite-time dropout or inverse-time dropout Users can choose whether it is blocked by the direction control element or the harmonic control element The direction control element can be set as no direction, forward direction and reverse direction The zero-sequence current used by earth fault overcurrent protection can be calculated zero-sequence current or the measured zero-sequence current, it can operate to trip or alarm, it can be enabled or blocked by the external binary input
Negative-sequence Overcurrent Protection (50/51Q, 67Q)
The device can provide two stages of negative-sequence overcurrent protection with independent logic Each stage can be independently set as definite-time characteristics or inverse-time characteristics The dropout characteristics can be set as immediate dropout, definite-time dropout or inverse-time dropout For a double-circuit or a ring network line, the negative-sequence fault current may have different flow direction Considering the protection selectivity, the negative-sequence overcurrent protection can be blocked by the direction control element Negative-sequence overcurrent current can operate to trip or
Trang 23Protection Functions
estimation is made based on the measured currents and the built thermal model of the transformer with two time constants
Breaker Failure Protection (50BF)
According to the tripping information from the device and the auxiliary information (the current and the position) of target circuit breaker, breaker failure protection constitutes the criterion to discriminate whether the target circuit fails to open If the criterion is confirmed, breaker failure protection will operate
to trip the target circuit breaker with the re-tripping time delay, trip it again with the first time delay and trip the adjacent circuit breakers with the second time delay As a special backup protection, breaker failure protection can quickly isolate the fault, reduce the affected range by the fault, keep system stability and prevent generators, transformers and other primary equipments from seriously damaged For breaker failure protection, phase-segregated re-trip, three-phases re-trip and two time delays are available
Phase Overvoltage Protection (59P)
The device can provide two stages of phase overvoltage protection with independent logic When a high voltage occurs in the system, it is greater than the voltage threshold, phase overvoltage protection will operate to remove the device from the system after a time delay In addition, the overvoltage protection also provides the alarm function, prompting the overvoltage of the system, it allows users to find the cause timely, and preventing further deterioration of the fault Each stage of phase overvoltage protection can be independently set as definite-time characteristics or inverse-time characteristics The dropout characteristics can be set as immediate dropout and definite-time dropout
Users can select phase voltage or phase-to-phase voltage for the protection calculation
“1-out-of-3” or “3-out-of-3” logic can be selected for the protection criterion (1-out-of-3 means any of three phase voltages, 3-out-of-3 means all three phase voltages)
Phase Undervoltage Protection (27P)
The device can provide two stages of phase undervoltage protection with independent logic When the voltage drops in the system and it is lower than the voltage threshold, phase undervoltage protection will operate
Taking into account that the role of undervoltage protection is to remove the running device from the system, but in order to prevent undervoltage protection is always operating when it is not charged, the breaker closed position check criterion is added, users can choose to detect the breaker position, current
or no-check as the releasing condition for the protection
In addition, the undervoltage protection also provides the alarm function, prompting the undervoltage of the system, it allows users to find the cause timely, and preventing further deterioration of the fault Each stage of phase undervoltage protection can be independently set as definite-time characteristics or inverse-time characteristics The dropout characteristics can be set as immediate dropout and definite-time dropout
Users can select phase voltage or phase-to-phase voltage for the protection calculation
Trang 24Protection Functions
“1-out-of-3” or “3-out-of-3” logic can be selected for the protection criterion (1-out-of-3 means any of three phase voltages, 3-out-of-3 means all three phase voltages)
Residual Overvoltage Protection (59G)
The device can provide two stages of residual overvoltage protection with independent logic When the residual voltage is greater than the voltage threshold, the residual overvoltage protection will operate to remove the device from the system after a time delay In addition, the residual overvoltage protection also provides the alarm function, it prompt that there is an earth fault leading to residual voltage generation, it allows users to find the cause timely, and preventing further deterioration of the fault The dropout characteristics of residual overvoltage protection can be set as immediate dropout and definite-time dropout
Overfrequency Protection (81O)
The device can provide two stages of overfrequency protection If the system frequency is greater than the setting, overfrequency protection will operate to remove some part of active power supplies from the system Overfrequency protection is with independent definite-time characteristics and with instantaneous dropout characteristics
Underfrequency Protection (81U)
The device can provide four stages of underfrequency protection If the system frequency is less than the setting, underfrequency protection will operate to shedding some part of loads from the system Underfrequency protection is with independent definite-time characteristics and with instantaneous dropout characteristics
Trang 25a local control The switchgear control function is closely related to interlocking, double point status (DPS), remote/local control mode switching and trip counter
A control command can realize various control signals such as the CB/DS/ES opening/closing In order
to ensure the reliability of the control output, a locking circuit is added to each control object The operation is strictly in accordance with the selection, check and execution steps, to ensure that the control operation can be safely and reliably implemented In addition, the device has a hardware self-checking and blocking function to prevent hardware damage from maloperation output
The switchgear control function can cooperate with functions such as synchronism check and interlocking criteria calculation to complete the output of the corresponding operation command It can realize the normal control output in one bay and the interlocking and programmable logic configuration between bays
This device supports the following functional control module:
CSWI Control of circuit breaker (CB), disconnector switch (DS) or earthing switch (ES)
RMTLOC Remote or local control mode
XCBR Synthesis of CB position, three-phase or phase separated
XSWI Synthesis of DS/ES position
SXCBR/SCSWI Trip counter of CB/DS/ES
RSYN Synchronism check for CB closing
CILO Interlocking logic for CB/DS/ES control
MCSWI Manual control of CB/DS/ES
CHKPOS Position verification for switchgear control
Remote/Local Control Mode Switch
Since the source of a control command may be SAS or NCC, or may be triggered by the device LCD or terminal contact, it is necessary to provide a remote/local control mode switch function
The remote/local control mode switch function determines whether the device is in the remote or the local control permission state through the configuration of terminal contact, function key, or binary signal Each control object provides a remote/local input, and the control module determines the current control authority to be remote or local according to the input value By default, if the input is not configured, any control operation is blocked
Trang 26Control Functions
Double Point Status
A double point status (DPS), which usually indicates switchgear status, can be derived from 2 ordinary binary inputs The unit also supports the DPS synthesis through switchgear opening and closing positions after jittering processing The synthetic DPS contains original SOE timestamp The CB control function supports phase-separated position inputs and can synthesize these inputs into general position
Trip Counter
The trip counter function takes the DPS of switchgear position as input count the trip times For CB, this device supports phase-segregated and general trip counter The trip counter function is triggered by DPS change The counting result is stored in non-volatile memory for power-off holding
Interlocking
The interlocking function will influence the control operation output When the function is enabled, the device determines whether the control operation is permitted based on the interlocking logic result Each control object is equipped with an independent interlocking logic which supports unlocking operation through a binary signal
The interlocking function is very important for the control operation of switchgears During the operation
of primary equipment, the positions of the relevant equipment must be correct for operation permission For remote control, i.e command from SAS or NCC, this device could judge the interlocking logic depending on the message within the command; for local control through device LCD or terminal contact, please use the corresponding logic setting to enable/disable the interlocking function
Trang 27Control Functions
Voltage Selection
The voltage selection function can be used to switch the reference and synchronization v oltages for the synchronism check function in double busbars and one-and-half circuit breakers scenarios, or to switch three-phase voltages among double busbars used by protection calculations or measurements The
"Near priority" principle is adopted by default, and the user interface for programmable switching logic is also reserved
The voltage selection module is used in the following scenarios:
For single circuit breaker with double busbars, the selection of appropriate voltage from both busbars for synchronism check is required Line VT input is taken as reference
Ua Ub Uc
Bus2 Bus1
DS1.DPS
DS2.DPS
UB1 UB2
Trang 28Control Functions
For single circuit breaker with double busbars, the selection of three-phase voltage from both busbars is used as reference voltage of synchronism check Single-phase voltage from line VT is the synchronization voltage
Ua Ub Uc
Bus2 Bus1
DS1.DPS
DS2.DPS UB2
DS1 DS2
CB
Line UL1
Ua Ub Uc UB1
Figure 13 Voltage connection for double busbars 2
Trang 29Control Functions
For one-and-half breakers arrangement in the application scenario of double circuit breakers, the selection of voltage from Line1 VT, Line2 VT and Bus 2 VT is the reference voltage to check synchronism with Bus1 voltage for the closing operation of Bus1 side circuit breaker
Ua Ub Uc UB1
UL2 UL1
Figure 14 Voltage connection for one-and-half breakers arrangement
Tap Position Indicator
A tap changer is a connection point selection mechanism along a power transformer winding that allows
a variable number of turns to be selected in discrete steps A transformer with a variable turn's ratio is produced, enabling stepped voltage regulation of the output The tap selection may be made via an automatic or manual tap changer mechanism
The Tap Position Indicator (TPI) input could be 6-bit Binary-Coded Decimal (BCD), independent contacts, carry inputs or DC analog input The indicator supports phase-separated inputs and discordance alarm