LIGHTING UNITS Lighting units as shown on the Drawings shall consist of lighting lantern, lamps, electrical control ballasts, and mounting accessories.. The components shall be in accord

Trang 1

LIGHTING AND POWER SUPPLY WORKS

Trang 2

TABLE OF CONTENTS

I REFERENCE STANDARDS

II MATERIALS

III LIGHTNING PROTECTION

IV WIRING FOR LIGHTING

V CABLE AND WIRE

VI GROUNDING

VII CONDUIT PIPE

VIII CABLE TRAY AND MOUNTING BRACKET FOR CABLE TRAY

IX ELECTRICAL SPLICE MATERIALS

X EXECUTION OF THE WORK

XI CONSTRUCTION REQUIREMENTS

XII CONSTRUCTION

Trang 3

I. REFERENCE STANDARDS

The work covered by this specification shall be carried out in accordance with the regulations issued by the local Electricity Authority and with the following applicable standards and codes as appropriate:

QCVN 07:2010/BXD: Building code - Urban Engineering

Infrastructure;

QCVN 20:2010/BGTVT: National technical regulation on aids to

navigation;

QCVN 39-2011/BGTVT National technical code on inland

waterway signaling;

QCVN 41:2012/BGTVT National Technical Regulation on Road

Signs and Signals;

TCVN 46:2007 Protection of Structures Against

Lightning - Guide for design, inspection and maintenance; TCVN 4756:1989 Specification on grounding for electrical

equipment;

TCVN 7447-5-51:2010: Installation system of low voltage – Part

5-51 Selection and installation of electric facilities – General rules;

TCVN 7447-5-52:2010: Installation system of low voltage –

Power line installation system;

TCXDVN 333:2005 Design standards of artificial outdoor

lighting for public buildings and urban infrastructure;

TCXDVN 259:2001 Design standards for artificial lighting

for urban roads, streets and squares;

TCXDVN 319:2004 Earthing system installation for industry

construction;

11 TCN 18-19-20-21:2006 Electrical installation regulations in Viet

Nam;

IALA International Association of Lighthouse

Authorities;

IEC 62305-1,2,3 International Standard for protection

against lightning;

Regulations and requirements pertaining to navigation signals for vessels shall be in accordance with international rules in accordance with the QCVN 20:2010/BGTVT, QCVN 39-2011/BGTVT and “IALA” requirements and recommendations

Trang 4

Regulations and requirements for lightning rods and associated grounding systems, using the rolling sphere method for lightning protection, shall be in accordance with all of the Regulations issued by the local Electricity Authority and reference:

 TCVN 9385:2012;

 IEC 62305-1;

II MATERIALS

1. LIGHTING UNITS

Lighting units as shown on the Drawings shall consist of lighting lantern, lamps, electrical control ballast(s), and mounting accessories Lamps for the bridge (BR), Main roads (MR), Access road to Toll plaza (AC), External Toll Plaza (TP), National Highway (NH), Province Road (PR) and Interchange (IC) shall be high-pressure sodium type The Contractor shall submit for approval, detailed light distribution diagrams for each type of lantern he proposes to install Furthermore, calculations shall be submitted showing the illuminance in candela per sq.m (cd/m2) at street level for carriageway, loop and ramp of interchange, and in lux at toll plaza areas

2 LIGHTING CONTROL PANELS

The lighting panels shall be included as feeders of the power source fed to the circuits of the street and bridge lighting and the guide signs The panels shall be

as shown on the Drawings or equivalent as approved by the Engineer

3 SUBSTATION

All power supply for lighting shall be as shown on the Drawings

The components shall be designed for 3-phase 4-wire, 50 Hz operation at 415/240 volts The components shall be in accordance with the Power Supply Company’s Standards and

Vietnam Standards:

a) Distribution Panel b) Lightning Arrestors c) Fuses Cut-out d) Transformers e) Low Voltage Power Cable from Transformer to Distribution Panel f) Concrete Poles and support fixtures

g) Overhead Medium Voltage Cables from existing distribution line including support and insulators

4 NAVIGATION LIGHT

General locations are indicated on the drawings The Contractor shall propose the exact location to the Engineer for his approval

(a)Lighting Units

Lighting units shall be flashing lights with swivel suspension They shall be provided complete with a battery box, rechargeable DC power storage batteries (having a minimum operating time of two hours without charging), a control box with necessary breakers, a terminal board and all accessories and cables needed to provide a complete operational system

Trang 5

Lighting units shall be securely fixed to the edge beam or soffit of the bridge The navigation light shall have 6 volts 9 watts with 32 high LED in accordance with the Vietnamese Standards

The lighting unit shall be a bracket-mounted or ceiling mounted type The minimum class protection shall be IP 54 for the entire optical unit which shall

be suitable for a humid tropical environment

Lens of lighting units shall be organic optical and UV resistance with D140mm diameter The body of luminaire shall be polycarbonate and solar panel, battery built-in one

Description Specification Visible distance 8km

Source of light 32 high LED, depend oncolour Effective intensity & Colour

light

Green; 55Cd; White, red, yellow: 38Cd

Horizontal out put 3600 Vertical divergence 6.50 at 50% intensity

200 mode according to code Flashing mode QCVN20:2010/BGTVT,

standard 22 TCN 269-2000 and IALA

Exact flashing mode +/-1%

On/ off level 70/150lux Time of automotive Steady on: 7 days Flashing (Fl5s ):33days Sealed battery (6V-10Ah)x2

Working life of battery 3 years Solar battery 9W, single crystal solar panel Flashing circuit BH998 P3

Pulse charging circuit T=0.25s Temperature range

operation -400 -:- 600 C

(b)Flashing Lights

Lighting units shall be flashing type, white, and green or white, green and red (as indicated on the Drawings) that flash on and off at regular intervals at the same intensity with an on-of time of more than two seconds Effective intensity shall not be less than 38 candela

(c)Stand-By Battery

Battery (ies) shall be rechargeable, fully sealed, lead-acid, maintenance free with a 6 volt 10Ah capacity with 2 sets for each lighting unit

5 LIGHTING POLES

Lighting poles shall be galvanised steel, in accordance with the details shown on the Drawings, as outlined herein and in accordance with the requirements of Specification section 08800

Trang 6

All materials shall be in natural colour and shall not be painted or coated with any other material All pole items shall be galvanised steel and all hardware shall be galvanised steel Scratches, marks, dents or other damages to poles and fittings shall be cause for rejection Any marks or stains resulting from wrapping materials shall be removed

All poles shall be individually spiral wrapped and in addition, shall be packed for shipping in groups with suitable form fitting wood dunnage between all poles and completely around each group at a minimum of 4 locations, and held with suitable metal strapping Packing not in conformance with this provision shall

be cause for rejection of poles All loading and unloading of poles shall be under the supervision of the manufacturer and/or Contractor All miscellaneous pole line hardware required to complete the project shall be standard material manufactured for pole line construction All poles supplied shall be of the anchor base type, and shall have a cast steel anchor base fitted over the shaft and secured with two circumferential welds

All metal parts shall be hot-dip galvanized as stipulated under Specification section 08800 The hand hole and servicer door for the terminal connection shall be 1.0 meters above

ground level This door shall be attached to each lighting pole by

hinge strap

6 HIGH MASTS

The masts shall be made of steel folded in conical sections, automatically welded in one longitudinal seam The sections shall be telescopic jointed or by means of bolts If bolted joints are used, flanges shall not disturb the aesthetics of the silhouette of the mast and should preferably be positioned inside the mast

The steel parts of the mast shall be hot dip galvanised over their entire surface

in accordance with the requirements of Specification section 08800 After installation of the mast, all exposed anchor bolts and securing nuts on the foundation shall be given one coat of an approved bituminous paint All scratches and other damage of the finish occurring during transport or installation works shall be thoroughly cleaned and touched up

The masts shall be bolted on a reinforced concrete foundation by means of steel bolts and nuts of adequate diameter and quantity The foundation shall be made of concrete and rolled steel bars in accordance with the applicable requirements of this Specification

For the maintenance purpose of lanterns and exchange of lamp, the position

of lanterns bracket shall be operated by motor and/or hand from top to bottom The masts shall have a lockable access door at ground

level

The lamp accessories such as fuses, ballasts, ignitors and capacitors shall be mounted on a suitable frame and installed inside the mast at ground level Provisions shall be made that no moisture, either from condensation or from entering rain water will drip on the lamp accessories Rising cables from the accessories to the lamps shall be bunched and fixed in the mast Near the accessory frame inside the mast an earth terminal of at least M10 diameter shall be provided, directly welded to the mast At the top of the mast a head frame shall be provided suitable to receive the lightning fittings in quantities and directions as shown on the drawings

Trang 7

The mast shall have a harmonious silhouette and the Contractor shall submit for approval, full information on the shape and detailed dimensions of the proposed masts

Before manufacturing the masts, the Contractor shall provide calculations and obtain the Engineer's approval for detailed construction drawings of the mast The calculations shall cover the complete structure, including head frame and lanterns, and shall show that:

 No parts of the assembly are submitted to stresses above acceptable limits,

 The deflection caused by dynamic forces does not exceed acceptable limits; and

III LIGHTNING PROTECTION

(a)General

This section gives requirements and procedures applicable for the furnishing and installing all materials, and equipment necessary to complete installation

of lightning rods, with arresting system in accordance with the drawings

All lighting rods and arresting systems, including materials and accessories shall be in accordance with the following, which are incorporated as an integral part of this Specification:

 TCVN 46:2007 Protection of Structures Against Lightning - Guide for design, inspection and maintenance;

 IEC 62305-1,2,3 International Standard for protection against lightning;

The location of each facilities and appurtenances shown on the Drawings are approximate and the Contractor shall propose the exact location to the Engineer for approval

(b)Lightning Rods

Lightning rods shall consist of metallic body made of stainless steel alloy used for receiving a lightning stroke directly and be connected to earth electrode by lightning conductors

(c)Lightning conductor

The lightning conductor that connects the lightning receiving parts with earth electrodes, to pass the lightning current shall be annealed flat copper bar 25mmx3mm, copper stranded wire of D10mm or strip or tubes which conform

to requirements

The down conductor shall be copper 25mmx3mm and be protected on the surface of the reinforced concrete pier

The combined value of earthing resistance of foundation of the object to be protected and that of earth electrode shall be not more than 5 

(d)Earth Electrode for Lightning

The earth electrode shall be a copper plate of 5mm thick, 1.0m x 1.0m with a 1.5m length of annealed flat copper bar 25mmx3mm

IV WIRING FOR LIGHTING

All cables to be used for roadway lighting shall be of the type and size shown on the Drawings

Trang 8

Cables shall be pulled into a pole through pipes prepared in the foundation of the pole, and shall be connected to the terminals in the terminal box installed

in the pole

All poles shall include an approved miniature circuit breaker rated at 2P 6 amperes, 240 volts, installed in the base of each pole and accessible through the service door of the pole The circuit breaker shall protect both the pole cables and the electrical control ballast

Cables installed in the pole shall have three conductors of minimum cross section of 2.5mm2 as prescribed in "Cable and Wire" herein

Cables shall be adequately attached to the lantern so that lantern terminals shall

be free from carrying their weights

Roadway lighting cables shall be two (2) core through to the

last pole

Roadway lighting control cables for reduce capacity of lamp shall be four (2) core through to the last pole, with conductors of minimum cross section of 6mm2

V CABLE AND WIRE

All cables shall be suitable for operation at the specified voltage in open, duct

or conduit, under the condition that the maximum conductor operating temperature at rated current shall be less than 70C

Cable colours shall comply with Vietnam Standards or other approved colour code standards

Cables shall be delivered to the Site on substantial non-returnable wooden drums, each bearing a securely fixed label stating gross weight, serial number, length of cable and other description

Covers shall be provided around the periphery of the drum in order to protect the cable in transit and the inner cable end shall be adequately protected by

a metal guard or other approved means Both ends of the cable shall be sealed

by a suitable method to prevent the entrance of moisture

All cables inside of the lighting pole from electric panel to lantern shall have three conductors per lantern Cables shall be 600 volts, grade "Polyvinyl Chloride Insulated and Sheathed Cable (CVV)” or shall be of the type approved

by the Engineer

All cables for the roadway lighting system to be installed underground shall

be XLPE insulated, Double Steel Tape Armouring (DSTA) and PVC sheeting type Cu-XLPE/PVC/DSTA/PVC (CXV-DSTA) or equal approved by the Engineer

Conductors shall have a minimum cross-sectional area of 6mm2 for use in underground installations

All cables shall be delivered with an appropriate test certificate and approved by the Engineer before installation

VI GROUNDING

Metal conduit, steel poles and cabinets shall be made mechanically and electrically secured to form a continuous system and shall be effectively grounded Bonding and grounding jumpers shall be copper wire of the same cross-sectional area for all systems

Bonding jumpers shall be used in all non-metallic boxes Metallic boxes shall employ hubs of double lock-nuts and bushes The bonding of all conduits, lighting poles and panels to form a continuous ground system shall be in

Trang 9

accordance with applicable code standards Lighting poles in embankment sections shall be individually grounded by a grounding rod

Size of grounding wire shall be minimum 10mm2 Bare Copper Conductor (BCC) or equivalent subject to approval by the Engineer

Ground rods shall be copper 16 dia x 2,400 millimeter minimum, depth 0.7 meter below finished grade and thermo-welded or connected using connection hardware to the 10mm2 grounding wire

The Contractor shall investigate each site and measure the grounding resistance

of the sites After taking the data, the Contractor shall provide the data to the Engineer and obtain his approval before installation

The grounding resistance shall be 10 ohms or less, or as approved by the Engineer Details of all grounding points shall be submitted to the Engineer for approval

VII CONDUIT PIPE

Conduit to be installed below ground, above ground, in the concrete or on the surface of structures shall be flexible conduit pipe type HDPE (High Density Polyethylene) Cable pipes installed below ground are termed as ducts and are dealt with in Conduit Pipe

Conduit to be embedded in concrete shall be HDPE in accordance with the requirements of TCXDVN 7997:2009

VIII CABLE TRAY AND MOUNTING BRACKET FOR CABLE TRAY

All details regarding requirements, material and installation of cable trays shall

be as shown on the Drawings

The Contractor shall design and provide necessary cable trays for the locations indicated on the drawings The trays shall be securely fixed so that distance between the supports is less than 2 meters The cable trays shall be made of hot dip galvanized steel For cable tray installed in exposed locations, the cable tray, and all mounting bracket fittings shall be of the highest quality for durability

IX ELECTRICAL SPLICE MATERIALS

Splices and taps shall be made with pressure type solderless connectors to securely joint the wares both mechanically and electrically

An epoxy resin, cast type insulation shall be formed in clear plastic moulds The material used shall be compatible with the insulation specified in the Contract Drawings or this Specification Materials to be used for the work shall conform

to the requirements of JIS C2804, C2805 and C2806, or shall have the quality approved by the Engineer

Insulating tape when specified for use in splice formation shall conform to JIS C2336 Unfused quick disconnect connectors such as In-line connectors or Tee connectors shall be

of quality approved by the Engineer

X EXECUTION OF THE WORK

The actual fabrication, installation, and testing of the work described in this Specification section shall be carried out by trained and experienced personnel

Trang 10

who are familiar with the requirements for this work and with the manufacturer’s recommendations for installation of the specified items

All work shall comply with the Drawings, this Specification section and the codes, regulations and requirements stipulated in this Specification section or

by the relevant Vietnamese Authorities

1 LIGHTING UNITS

Lighting units as shown on the Drawings shall consist of lamps, canopy, body, electrical control ballasts, and mounting accessories

The Contractor shall submit for approval light distribution diagrams for each type

of lantern he proposes to install Unless specifically shown on the drawings

or instructed by the Engineer, all lanterns should be of the semi-cut off or fully cut off type

Permitted spill light levels shall be controlled on both the front and rear of the lighting unit as follows: At the right of way limit on the opposite side of the road – maximum 5 Lx, and at the right of way limit to the rear of the lighting unit – zero The Contractor shall submit factory test data to demonstrate conformance with these spill light levels

2 LIGHTING CONTROL PANELS

The lighting control panels shall be included as feeders of the power source fed to the circuits of the street lighting The panels shall be as shown on the Drawings or equivalent subject to approval by the Engineer

The panels shall be substantial, free-standing structures on a concrete foundation a minimum of 40 cm above ground level

Panel roofs shall be in conformance with the Drawings or equivalent subject to approval by the Engineer

The panel and door shall be made from stainless steel sheet not less than 2.3 millimetres in thickness with the necessary steel frames The welding for all outside joints shall be smooth finished

The panel shall have a bottom design that will permit tack welding to channels that shall be set on the raised concrete foundation

The panel shall be fully assembled and wired at the

factory

Main and small wiring shall be easily accessible for maintenance and inspection Small wiring shall be effectively isolated from the main wiring

Each panel shall have one or more nameplates for identification Nameplates shall be made of laminated plastic with white characters to show through a black top layer when cut or engraved

Panel housings shall be fitted with a substantial lock with a master key if appropriate

3 LIGHTING POLES

All poles supplied shall be of the anchor base type, and shall have a cast steel anchor base fitted over the shaft

The service door and cover plate for the terminal connection shall be 1.0 meter above ground level

Identification plates shall be attached to each lighting

pole