Joint connection Sample dimension: Vertical standard: Φ48.58mm*3.22mm wall thickness Horizontal Ledger: Φ48.35mm*2.22mm wall thickness Ring dimension: Φ123.70mm*9.69mm wall thickness Ben
Trang 1CONSTRUCTION JOINT STOCK COMPANY NO.1
108 CAO THANG STREET, DISTRICT 3, HOCHIMINH CITY, VIETNAM
The following sample(s) was/ were submitted and identified on behalf of the client as:
Sample Name : RINGLOCK SYSTEM MATERIALS
Sample Number : SHCCM160100055
Test Required : Connection component test
Test method : SGS in house
Product or Lot No : CXJ2015-12-052
Material and Mark : Q235
Date of Receipt : Jan 05, 2016
Test Period : Jan 05, 2016 to Jan 11, 2016
Test result(s) : For further details, please refer to the following page(s)
******** To be continued********
Signed for SGS-CSTC Standards
Technical Services (Shanghai) Co., Ltd
Joyce Li
Authorized signatory
Trang 2Test method: SGS in house (See Annex A for sketches of the test methods)
Test result:
I Joint connection
Sample dimension:
Vertical standard: Φ48.58mm*3.22mm (wall thickness)
Horizontal Ledger: Φ48.35mm*2.22mm (wall thickness)
Ring dimension: Φ123.70mm*9.69mm (wall thickness)
Bending moment at junction
Allowable
moment
The sample should be in good condition when the bending moment was applied to 0.44kNm
The sample was in good condition when the bending moment was applied to 0.44kNm
Breaking
The connection component showed visible deformation when the maximum bending was applied to moment M=1.39kNm
Normal load (Tension) on junction
Allowable
load
The sample should be in good condition when the load was applied to 17kN
The sample was in good condition when the
load was applied to 17kN
Breaking
One of the wedge was broken when the load
was applied to 50.34kN
******** To be continued********
Trang 3Vertical load on ring
Allowable
load
The sample should be in good condition when the load was applied to 15kN
The sample was in good condition when the
load was applied to 15kN
Breaking
The connection component showed visible deformation when the load was applied to
34.19kN
Horizontal load on ring
Allowable
load
The sample should be in good condition when the load was applied to 7kN
The sample was in good condition when the
load was applied to 7kN
Breaking
The horizontal ledger and the wedge showed visible deformation when the load was applied
to 57.30kN
Note: the test span is 2000mm offered by the client
II Brace load (tensile force)
Sample dimension:
Diagonal brace: Φ48.22mm*2.21mm (wall thickness)
Vertical standard: Φ48.69mm*3.28mm (wall thickness)
Allowable
load
The sample should be in good condition when the load is from 5kN to 14kN
The sample was in good condition when the
load is from 5kN to 14kN
Breaking
The ring was broken and the wedge showed visible deformation when the load was applied
to 24.81kN Note: the test angle is 39° offered by the client
******** To be continued********
Trang 4III Vertical standard (post)
Sample dimension: Vertical standard: Φ48.71mm*3.26mm (wall thickness)
1) Free height 2.00m
Allowable
load
The sample should be in good condition when the load was applied to 39kN
The sample was in good condition when the
load was applied to 39kN
Breaking
The middle part of the standard was bent when the load was applied to 112.76kN
2) Free height 0.50m
Breaking
The middle part of the standard was bent when the load was applied to 161.73kN
Note:
1 All the requirements are offered by the client
2 Please see the annex A for sketches of the test methods and annex B for photos of test
******** To be continued********
Trang 5Annex A: Sketches of the test methods
Bending moment
Normal load Vertical load
******** To be continued********
Trang 6Horizontal load Brace load
Statement: Unless otherwise stated the results shown in this test report refer only to the sample(s) tested
Annex B: Test photos
Before bending moment test After bending moment test
******** To be continued********
Trang 7Before normal load test After normal load test
Before vertical load After vertical load
******** To be continued********
Trang 8Before horizontal load After horizontal load
Before brace load After brace load
******** To be continued********
Trang 9Before test (free height 2.00m) After test (free height 2.00m)
Before test (free height 0.50m) After test (free height 0.50m)
******** End of report ********