CONFIDENTIAL: PUBLICATION AND REPRODUCTION ONLY WITH OUR WRITTEN CONSENT QA198/8/99 DATA PROGRAM LABORATORY PRUFBERICHT AUTHOR/Verfasser: Bob Hibberd SIGNED AUTHOR: George George

Trang 1

CONFIDENTIAL: PUBLICATION AND REPRODUCTION ONLY WITH OUR WRITTEN CONSENT QA198/8/99

DATA PROGRAM LABORATORY

PRUFBERICHT

AUTHOR/Verfasser: Bob Hibberd SIGNED AUTHOR: George Georgevits

SIGNED RELEASE: Mill 4

FOR INFORMATION: KRA, R & D MANAGER;

zur Kenntnis:

4._ TASK (Aufgabenstellung)

Category 5 Testing of HIGHBAND 10 Module

2 SUMMARY (Zusammenfassung)

3._ TEST EQUIPMENT (Prifmitte!

4 TEST RESULTS (Prifungen und Ergebnisse)

Trang 2

POWER AND DIGITAL PDI INSTRUMENTS PTY LID

Electronies and Communications Consulting Engineers

ace utr

ROSEVILLE NSW 2069 ROSEVILLE NSW AUSTRALIA FAX: +61 2 9412 1920

ABN 21 002 065 769

TEST REPORT

No.0080

TRANSMISSION TESTING ON KRONE

HIGHBAND 10 MODULE

for

KRONE (AUST) TECHNIQUE PTY LTD

DATE: 1st November, 2000 PREPARED BY: G GEORGEVITS (B E Hons)

REPORT CONSISTS OF 10 PAGES

Trang 3

PDi LABORATORY TEST REPORT No 0080

TITLE: Krone - Highband 10 Module Transmission Testing

TABLE OF CONTENTS

1 Background

2 Aims of Testing

Attenuation Return Loss NEXT

4 Test Results and Conclusions

5 Additional Background Information

6 Tables of Test Results

7 Graphs of Test Results

APPENDIX 1 - Test Setup Details

APPROVED: 3 8

Trang 4

PDI LABORATORY TEST REPORT No 0080

TITLE: Krone - Highband 10 Module Transmission Testing

1 BACKGROUND

PDI was requested by Krone (Aust) Technique Pty Ltd to carry out transmission tests on a sample Highband 10 module to

determine whether or not the sample was compliant with

Standard ANSI/TIA/BIAS68A ("the Standard") Category 5

transmission performance requirements

2 AIMS OF TESTING

1 Carry out the transmission testing 1 - 100MHz for

attenuation, return loss and near-end crosstalk in accordance with the procedures set out in the

Standard

2 Based on test results, provide advice as to whether

the product was compliant with the Standard requirements for Category 5 transmission performance

3.1 Test Setups

Refer to APPENDIX 1 for schematic diagrams of the applicable test setups Refer also to Section 5 below for details of the

test equipment used to perform the testing

3.2 Range of Tests Performed

The following tests were performed at 1O0OMHz on the first port

of the patch panel module sample provided:

Attenuation on all four pairs Near-end crosstalk on all six pair combinations Return loss on all four pairs

3.3 Test Leads

Connection to sample was via UTP category 5 solid twisted pair conductors Where applicable, attenuation due to the test

leads was factored out of the measurements by the network

analyser calibration procedure

APPROVED: 3 8

Trang 5

PDI LABORATORY TEST REPORT No 0080

TITLE: Krone - Highband 10 Module Transmission Testing

For the attenuation measurements, a 14dB attenuator was

inserted in series with the twisted pair send lead to the

device under test (DUT} in order to prevent inaccuracies

caused by line reflections

Where the readings were thought to exceed the noise floor or limit of dynamic range of the network analyser, the reading was recorded as greater than this limit, rather than recording the actual reading This was done to avoid showing misleading results

In all cases, such readings were a long way past the required passmark for the respective parameter being measured

4.1 Summary of Test Results

The following provides a summary of product performance for the ports tested

Where a "fail" is indicated, the number of instances of

failure to comply with the Standard requirements is also

indicated in brackets, followed by the total instances that test was performed

4.2 Conciusions

From the test results, the following conclusions may be drawn:

1 The product sample exceeds Cat 5 transmission performance

requirements, by a large margin in all instances for all the required transmission parameters

APPROVED: 43 Q

Trang 6

PDI LABORATORY TEST REPORT No 0080

TITLE: Krone - Highband 10 Module Transmission Testing

5 ADDITIONAL BACKGROUND INFORMATION:

FILE:

CLIENT:

DATE OF TESTING:

PRODUCT DESCRIPTION:

PART TYPES/NOs:

APPLICABLE STANDARD:

TEST EQUIPMENT:

0080REP DỌC Krone (Aust) Technique Pty Ltd

30.10.00

Highband 10 Module

6468 5 061-00

ANSI/TIA/EITA-568A, AS/NZS 3080:1996

HP8754A, Serial No.2516U02068

Hewlett Packard Storage Normaliser, Model

8501A, Serial No.2404A01641

Hewlett Packard Vector Voltmeter, Model

HP85081B Input Module Hewlett Packard Accessory Kit, Type 11570A Rohde & Schwartz Synthesised Signal

Generator, Type SMS, Model 302.4012.25, Serial No.0180

PDI reference attenuator, 40.2daB, 100 ohm, balanced, Serial No.94239, traceable

0322BF

Trang 7

PDI LABORATORY TEST REPORT No 0080

TITLE: Krone - Highband 10 Module Transmission Testing

Freq (MHz) Pair #1

1.0

4.0

10

16

20

31

62

100.0

5

<0.1

<0.1

<0.,1

<0.1

<0.1

<0.1

3; 1

10

Pair #2

<0.1

<0.1

<0.1

<0.1

<0.1

<0.1

<0.1 0.11

6.2 Near-end Crosstalk (NEXT)

Freq (MHz)

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

Pair Combination:

#1-#2

>75

>75

68

64

62

59

53

49, GŒ

6.3 Return Loss

#1-#3

>75

>75

>75

>75

>75 73.1 68.3 63.7

Freq (MHz) Pair #1

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

>35

>35

>35

>35

>35

33.9 28.5 26.1

#1-#4

>75

>75

>75

>75

>75

>75

>75 73.5

Pair #2

>35

>35

>35

>35

>35

>35 31.3

28.5

Cat 5 Standard

<0.1 <8.1 0.2

<0.1 <0.1 0.2

Cat 5

#2-#3 #2-#4 #3-#4 std

>75 >75 >75 >65

67.9 >75 68.3 >60 64.2 >75 64.7 >56

Cat 5

Standard

Pair #3 Pair #4 Limit

>35 >35 23

>35 >35 23

>35 >35 23

APPROVED: #9 Š

Trang 8

PDI LABORATORY TEST REPORT No 0080

TITLE: Krone - Highband 10 Module Transmission Testing

7.1 NEXT

-30

—— CATS LIMIT

—— NEXT 1-2

—— NEXT 24 L7

-50 "—————.- -e-zanl DU] BA

7

7

Lt

80

1.00 FREQUENCY (MHz) 10.00 100.00

D

mo

NA a

N

10.00 HEOEAOYAMQ 10003

APPROVED: #9 Q

Trang 9

PDI LABORATORY TEST REPORT No 0080

TITLE: Krone - Highband 10 Module Transmission Testing

7.3 RETURN LOSS

—— CATS LIMIT

——PRH

—PR#2

—— PRB

cB

Li

Z7)

L2

40

APPROVED: #9 Š

Trang 10

TEST SETUP

Spot Frequency Attenuation and NEXT Measurement

SLNINENSYAW

YAISATYUNY

LWZUTANS

amiss

HUISATYUNY

HNHOH.LSN

UT@S8dH

YUPSGZEdH

TITLE: Krone - Highband 10 Module Transmission Testing

PDI LABORATORY TEST REPORT No 0080

APPENDIX 1 -

FIG.1

"T21đÄL

LWANAURS

MOLLUNNELLY

TVD1EAL

9/10

wate

W311114$

HAISATYUNY

HXOMLIN

UTBS8dH

UES¿8đdH

REPORT COPYRIGHT PDI

Trang 11

PDI LABORATORY TEST REPORT No 0080

TITLE: Krone - Highband 10 Module Transmission Testing

FIG.2 Spot Frequency Return Loss Measurement

N01¿0Mi1MH31

10/10

asec

APPROVED: #9 8

REPORT COPYRIGHT PDI