Hệ thống kích từ số GEX 2000 dùng cho nhà máy nhiệt điện, loại kích từ không chổi than. Miêu tả về khối chức năng, giá trị cài đặt, hướng dẫn sử dụng trong vận hành và sửa chữa ................................................................................................................................................................................................................................
Trang 1GEX-2000 Generator Excitation Regulator
Technical documentation
Trang 21 INTRODUCTION 1
2 FUNCTION DESCRIPTION 1
2.1 MAJOR LOOP 2
2.2 SYSTEM CONFIGURATION 2
2.3 RECTIFIER BRIDGE 2
2.4 DE-EXCITATION AND OVER-VOLTAGE CIRCUIT 4
2.4.1 Calculation and choice of de-excitation resistance 5
2.4.2 Rotor over-voltage protection 6
2.5 FIELD FLASHING CIRCUIT 6
2.6 REGULATOR CONTROL UNIT 6
2.6.1 Collection of analog quantities 6
2.6.2 Switching value input and output 7
2.6.3 Communication 7
2.6.4 Human-computer interface 7
2.6.4.1 Keyboard 8
2.6.4.2 LED indicator light 8
2.6.4.3 Home screen display 9
2.6.4.4 Instructions of menu operation 10
2.6.4.5 Display measurement 10
2.6.4.6 Parameters menu 12
2.6.4.7 Protect switching menu 14
2.6.4.8 Input status menu 14
2.6.4.9 Transmission test menu 15
2.6.4.10 System test menu 16
2.6.4.11 Fault remember menu 16
2.6.4.12 Fault wave form menu 17
2.6.4.13 Event recording menu 18
2.6.4.14 Precision adjustment menu 18
2.6.4.15 Unit parameter menu 18
2.6.4.16 System setup menu 19
2.6.4.17 Test option menu 20
2.6.4.18 Other test menu 20
2.7 POWER SUPPLY 21
3 OPERATION 21
3.1 INTRODUCTION OF OPERATION PANEL 21
3.2 OPERATION METHOD 22
3.3 INCREASE/DECREASE MAGNET OPERATION 23
3.4 SOFT START 24
3.5 SYSTEM VOLTAGE TRACKING 24
3.4 NORMAL OPENING STEPS (LOCAL) 24
Trang 33.5 NORMAL CLOSING OPERATION 25
3.9 FAULT WARNING AND PROCESSING 25
4 MAINTENANCE OF EQUIPMENT 26
4.1 DAILY INSPECTION 26
4.2 MAINTENANCE 26
5 UPPER COMPUTER MONITORING 26
5.1 INSTALLATION AND STARTUP 27
5.2 CONNECTION TYPE 27
5.2.1 Single channel 27
5.2.2 Two-channel 27
5.3 SYSTEM SETTING 27
5.4 FUNCTIONS 28
6 CENTRAL CONTROL DESIGN GUIDELINE 33
7 TECHNICAL DESCRIPTION OF GEX-2000C/D MICROCOMPUTER EXCITATION REGULATOR 34
7.1 UNIT FEATURES 34
7.1.1 Main features 34
7.1.2 Operation environment 36
7.2 MAIN FUNCTIONS AND TECHNICAL CRITERIA 36
7.2.1 Main functions 36
7.2.1.1 Adjustment and control function 36
7.2.1.2 Limit and protection function 36
7.2.1.3 Other auxiliary functions 37
7.2.2 Main technical criteria 38
7.2.2.1 Analog-digit converter input parameter 38
7.2.2.2 Volume of switching value input/output 38
7.2.2.3 Output parameter 38
7.2.2.4 Network interface 38
7.2.2.5 Power supply parameter 38
7.2.2.6 Criteria parameter 39
7.3 PRINCIPAL INTRODUCTION 39
7.3.1 Main Principal 39
7.3.2 Single Board Principle 41
7.4 S I 44
Trang 41 Introduction
As a p r o d u c t o f G E X s e r i e s o f B e i j i n g K e D i a n Y i H e n g E l e c t r i c P o w e r T e c h n o l o g y C o , L t d ,
G E X - 2 0 0 0C / D m i c r o - c o m p u t e r e x c i t a t i o n u n i t i s a p p l i e d i n s y n c h r o n o u s g e n e r a t o r s e x c i t a t i o n s y s t e m
It is designed with single cabinet, featured with compact structure, easy installation and perfect function,
appl i es t o hydro- power ge nerat i ng uni t s and t her mal pow er gener ati ng unit s The general cabi net si ze i s
Trang 5De-Exc.Circuit Linear De-Excitation
Trang 6Ud is the DC output voltage,U2 is the AC input phase-to-phase voltage.αis the controlled angle.is the controlled angle.
Ud=1.35U2Cosαis the controlled angle
Excitation regulator adjust controlled angle αis the controlled angle continuously according to generator and busbar conditions
Three-phase fully-controlled rectifier bridge should be work under three operation conditions,according to
the different controlled ange αis the controlled angle
W h e n 0°<αis the controlled angle.< 9 0°,Ud is positive value ,the bridge is under rectifier operation U d i s p o s i t i v e v a l u e ,Ud is positive value ,the bridge is under rectifier operation t h e b r i d g e i s u n d e r r e c t i fi e r o p e r a t i o nconditions,Ud is positive value ,the bridge is under rectifier operationand t energy s uppliedthe g o c eneratorf t i s omeo r rom he nput ides f ectifierbridge
W h e n 9 0°<αis the controlled angle.< 1 8 0°,Ud is positive value ,the bridge is under rectifier operation U d i s n e g a t i v e v a l u e ,Ud is positive value ,the bridge is under rectifier operation t h e b r i d g e i s u n d e r i n v e r t i o n o p e r a t i o n
conditions.the energy of generator field winding discharge gradually
When αis the controlled angle.=90°,Ud is zero,there are no energy exchange between input and output sides of rectifier bridge
The following figure is the wave form with inductive load
Trang 7用 FinePrint 打印 - 可在 www.fineprint.cn 订购 打印 - 可在 www.fineprint.cn 订购 可在 www.fineprint.cn 订购 订购
2.4 De-Excitation and Over-Voltage circuit
T h e D e - e x c t i a t i o n c i r c u i t i s c o m p o s e d o f f i e l d c u r r e n t b r e a k a n d l i n e a r - r e s i s t a n c e Inverse de-excitation is used for normal stop operation If there are some emergency accident, field-current
breaker trip immediately and the residue energy of rotor winding will be released by linear-resistance
The function of field-current breaker is breaking the rotor excitation current circuit and makeing sure that
residue energy of rotor winding transfer to de-excitation resistance
Trang 82.4.1 Calculation and choice of de-excitation resistance
The choice for de-excitation resistance value which refer to rotor winding reverse voltage generated duringthe course of de-excitation and the speed of de-excitation is very importance
The rotor winding voltage during the course of de-excitation calculated according to the following equation
I is the generator excitation current
The calculation equation for time constant of de-excitation:
De-excitation resistance value usually calculate as 2.5R , in consideration of the insulation of rotor f
winding when field-current breaker trip under 2 times force excitation In this case,the rotor windingvoltage is smaller than 60 percent of winding withstand voltage.the rated current of de-excitationresistance usually greater than 20 percent of rated excitation current
Trang 92.4.2 Rotor over-voltage protection
T h e n o n - l i n e a r r e s i s t a n c e c o n n e c t e d t o D C s i d e o f r e c t i f i e r b r i d g e i n p a r a l l e l i s u s e d f o r a b s o r b i n g t h e
excessive voltage produced by the following reasons:
Over voltage in DC side of rectifier bridge caused by rapid de-excitation
Over voltage caused by thunderstrike
Over voltage caused by closing or opening generator circuit breaker asynchronously
Over voltage caused by generator short-circuit、under excitation and so on
Setting rule for the action value of rotor over-voltage protection:
Less than 75 percent of rotor winding test voltage
Less than the most permit voltage of rectifier bridge
Greater than 2.5 times peak voltage value of excitation transformer secondary side
2.5 Field flashing circuit
The field flashing power come from DC or AC plant power supply
Field flashing function have two operation mode, automation and manul
A b i n a r y o u t p u t s i n g a l w i l l b e s e n t o u t a u t o m a t i c a l l y a n d f i e l d f l a s h i n g c o n t r a c t c l o s e duntil s tatorv roltageu t 2 p ise o rp go 0 t ercentv wf eated r eneratorw erminal oltage hen xcitation egulator ork
as automation mode In case the stator voltage can not maintain at the point of 20 percent of rated terminal
voltage, a field flashing failure singnal will be sent
It is necessary that Pressing the button SB3 when the field flashing mode is manual.In this case, excitation
regulaor operate by manual mode
Notice:
A.Th e r e a r e n o a u t o m a t i c f i e l d f l a s h i n g s i n g a l , w h e n e x c i t a t i o n r e g u l a t o r o p e r a t e u n d e r m a n u a l m o d e
FCR.In this case, the button SB3 must be press
B.Excitation current set value is 5 percent of rated no-load excitation current under manual mode.In this
case,if the stator voltage can not hold, it is a suggestion that increasing the excitation current setting
value IFR to 15 percent of rated no-load excitation current
C.There is a risk that generator voltage and excitation current oscillate in a greater range after changing
excitation current setting value to 15 percent of rated no-load excitation current.At worst, generator
stator voltage could exceed allowable values
D.It is a suggestion that the manual field-flashing operation pressing the button SB3 is in service as a
backup choice for the above reasons B&C
2.6 Regulator Control Unit
G E X - 2 0 0 0C e x c i t a t i o n r e g u l a t o r i s l o c a t e d i n s i d e r e g u l a t i n g c a b i n e t , i s d i v i d e d i n t o s i g n a l p r o c e s s i n g ,
c o n t r o l c o m p u t e r , s i g n a l o u t p u t , c o m m u n i c a t i o n a n d h u m a n - c o m p u t e r i n t e r f a c e By c o l l e c t i n g v a r i o u s
a n a l o g q u a n t i t i e s a n d s w i t c h i n g v a l u e i n f o r m a t i o n o f g e n e r a t o r u n i t , t h r o u g h C P U c o m p u t i n g a n d
processing, control silicon controlled rectifier bridge output, reach the purpose of excitation system control
2.6.1 Collection of analog quantities
Trang 10Stator current 5A (1A) 803:1,803:2,803:3 803:6,803:7,803,8
Synchronizing
Rotor voltage Actual value 807: 1, 807: 2
Rotor current Collect form current divider 807: 3, 807: 6
2.6.2 Switching value input and output
Remote central controlled operating excitation unit signal input (common terminal 901: 9)
E x c i t i n g u n i t w o r k i n g c o n d i t i o n a n d a l e r t i n g s i g n a l o u t p u t ( c o m m o n t e r m i n a l 8 0 5 :1)
Channel A automatic
operation
805: 3 Constant reactive operation 805: 13
Channel A manual operation 805: 5 Constant Power Factor 805: 11
Alerting signal output(公共端公共端805:23)
Trang 11driven negative supply inside and backlight and chip power-supply control circuit outside.
L C D i s f u n c t i o n e d m a i n l y o f h u m a n - c o m p u t e r i n t e r a c t i o n i n t e r f a c e , i n c l u d i n g m e a s u r e m e n t s h o w i n g ,
parameter adjusting, fault display, system setting, combination with keyboard and completion of the above
features There are 6 LED indicator lights and 10 keys
“ ”(enter)
Make s turec heo urrenta g t t perationn m e ndt o o he ext enu, nsuring heparameter modification In the initial interface, press “ ” and go
to the next main menu interface
“Q”(back) Exit the current operation and back to the previous menu, cancel the
parameter modification
Trang 12“+”, “-” increasing and decreasing They can also be used for parameter modifying, correspond to figure
2.6.4.2 LED indicator light
Automatic operation
indicator light Light on in automatic operation status
Manual operation indicator
light Light on in manual operation status
PSS operation indicator
Constant reactive operation
indicator light Light on in constant reactive operation status
Constant power factor
operation indicator light Light on in constant power factor operation status
Channel fault indicator
light
(Channel alerting indicator
light)
Light on and keep by itself in unit internal fault or protection movement
limitation status, light off after signal return2.6.4.3 Home screen display
After s tarting,t unit a heutomaticallye i ntoh somenterst d creent s o o isplay s ahem ystem peration tatus nd ainmeasured data The corresponding measurement displaying is as follows, all variables are shown as actual
value (See chart)
Status display area:
Trang 13Name Definition Name Definition
UG1 Three-phase average value of terminal voltage (line
IG1 Stator three-phase current average value Q Reactive power
angleIFD Exciting current of exciter COSΦ Power factor
UGR In automatic operation, terminal voltage PID adjust
current-sharingoperation status
Fi e l d s u p p r e s s i o n s w i t c h : w i t h o n s p e c i f i c d e s c r i p t i o n , f i e l d s u p p r e s s i o n s w i t c h i s c o n n e c t e d w i t h
normal close auxiliary contact; the status is shown as open or closed
Channel status: the operation status of regulator in the channel Three cases: operation, track and quit
Main switch: display the generator is parallel operation or no-load operation The main switch status
can be distinguished in accordance with parallel breaker open contact
Trang 14submenus In menu operation, use “ ”, “ ”“ ”, “ ” to move cursor, press “ ” and go to the
corresponding sub-menu, press “Q” and exit home screen The main menu is as follows
2.6.4.5 Display measurement
The menu displays the measured data and computed value on screen Displayed value as follows:
Measurement UG1: KV I LA: A UAB1: KV I LB: A UBC1: KV P: MW UCA1: KV Q: Mvar
I G: KA Cos
I A: KA F0: Hz
I B: KA F1: Hz
I C: KA ARF UG2: KV URAN: V UAB2: KV UPSS: V UBC2: KV U5V: V UCA2: KV U12V: V UFD: V H0: %
I FD: A US: KV
UG1 Measured PT three-phase line voltage average valueUAB1, UBC1, UCA1 Measured PT three-phase line voltage
IG Stator three-phase current average value
IA, IB, IC Three-phase stator current
Trang 15Name Definition UG2 Instrument PT three-phase line voltage average valueUAB2, UBC2, UCA2 Instrument PT three-phase line voltage
UFD Exciting voltage of exciter (output voltage of
COSΦ Power factor, displayed three decimal places
F0 Generator terminal voltage frequency
impact when the signal is zero
H0 Rotor equivalent heat productivity percentage
2.6.4.6 Parameters menu
In t hem main m enu,t c t pove phe “ ursor”, p opuppo arameter,assword,i p nressnputi assword umber n
cursor place by pressing “ ”, “ ”, press “ ”, “ ” to move the cursor
Trang 16Password * * * *
After inputting the correct password, press “ ” and go to submenu of parameter
Move the cursor and select submenu by “ ”, “ ”“ ”, “ ”, press “ ” and go to submenu of
parameter, p “ ” a gainwress mhen t p odify v che iarameterf s p alue, n ursor s lashing, elect arameter umberplace needed modifying through “ ”, “ ”, modify parameter value using “ ”, “ ” (Circulatory
change from 0 to 9), then press “ ” and save modification, press “Q” back to the previous menu, and
give u m p odification,t d v i theo isplayedv The p arameteralues and m odificationss he etupriginal alue.creen
is as follow
Automatic PID parameter setup screen:
Trang 18U E L Li miter
A: (0 ,Ud is positive value ,the bridge is under rectifier operation - 18Mvar ) B: ( 30MW ,Ud is positive value ,the bridge is under rectifier operation 0 )
2.6.4.7 Protect switching menu
The menu will display and set switching status of function switches
Use “ ”, “ ”“ ”, “ ” t os electm iodifyingPress “ ” t oetems.nteri m nto s odifyingp tatus, ress
“ ”, “ ” t oc hanges switchingt p “ tatus,” a gaint cheno completeress i m urrenta tem odification, tthe s amet t cime g bhe t tursorp mo Press “Q” t ogack o heo t acktreviousp o mhe aenu.reviousg enu nd ive
up modification
2.6.4.8 Input status menu
It mainly display on-off of inputting quantities real-time status Pressing “ ”, “ ” can turn page
Pressing “Q” and go back to main menu
Trang 192.6.4.9 Transmission test menu
In t hem main s enu,transmission t estielect tem,p “ ress”, p opups ubmenu,s o c electN b utput hannel o y
“ ”, “ ”“ ”, “ ”, press “ ”, move the cursor to “on/off”, press “ ”, “ ” and select
transmission s tatus,t p hen“ ” t osress tartt a est,t c ftertransmission s tatustest, hange“off” Press “Q”o
and go back to main menu See chart
Trang 202.6.4.10 System test menu
In this interface, you can carry out step response test and display the chosen variable oscillogram Allshould be displayed as unit value in graphic Step value can be changed in range of ±20% The second itemneeded to be set is the keeping time of step signal, setting range can be from 0 to 15 seconds, the minimumresolution is 0.1 second, after choosing start menu, press “ ” and step value starts to output, now themenu shows finished and will start again until 20 seconds recording time If abnormal situations appear inthe test process, press “ ” immediately and step value will be cancelled, the menu shows start again.After test, select WAVE and press “ ”, then it will display recording value, keys “ ” and “ ” canchange the current recording value UG1, UG2, IG, UFD, IFD, ILA, ILB, P, Q, , UGREF and IFREF,totally 12 oscillograms Press “ ” again then will appear a cursor, corresponding point time and currentamplitude in the top right corner (unit value display) Press “ ”, “ ” and move left/right slowly, press
“ ” and move right quickly, press “ ” and move left quickly Press “Q” and exit menu step by step.This interface needs password for entry
2.6.4.11 Fault remember menu
In fault remember menu, press “ ” and go to fault remember submenu The displayed parameter is asshown in the graphic, press “ ” and “ ” to change issue items, maximum 20 items, numbered from 1,
circularly display Press “Q” to go back to the main menu
Trang 21FAULT WAVE WAVE:
Trang 222.6.4.13 Event recording menu
2.6.4.14 Precision adjustment menu
In the main menu, select precision adjustment item, press “ ”, password authentication, after inputting
f u n c t i o n, m o d i f i e s t h e d i f f e r e n c e b e t w e e n a c t u a l m e a s u r e d v a l u e a n d d i s p l a y e d v a l u e
Its window is as the chart showing Modify the reference constant value of Keyboard operation
UAB1: 0 998 UFD: 1 000 UBC1: 0 899 I FD: 1 030 UCA1: 0 995 URAN: 1 000
I A : 0 998 AD16: 1 000
I B : 0 968 I LB : 1 000
I C : 0 992 I LA : 1 000 UAB2: 0 998 U12V: 0 988 UBC2: 0 868 U5V : 0 976 UCA2: 0 908 P1 : 0 978 USA : 1 000 Q1 : 0 948 USB : 1 000 U1 : 1 000 USC : 1 000 U2 : 1 000
Adj ust Accuracy
2.6.4.15 Unit parameter menu
In t hem main s enu,u p electi p nit“ ”, a fterparameter assingp tem,a asswordress s uthentication, ubmenu
is popup Operate in accordance with parameter setup
Trang 23
-Unit Rated Ug: 10.5 KVRated Ig: 1.24 KARated Ufd: 153 ARated Ifd: 5.57 ANo-load Ufd0: 50 VRated Ild: 5 AF_PWR Supply: 400 Hz2.6.4.16 System setup menu
Data -In t h e m a i n m e n u , s e l e c t s y s t e m s e t u p m e n u , a f t e r p a s s i n g p a s s w o r d a u t h e n t i c a t i o n , s u b m e n u i s p o p u p
showing some important information of current unit See chart below:
Password setting Set users’ password, which has four digits, when change password, enter the new
one and press “enter”, then password is changed successfully
Mailing address
Us e d f o r 4 8 5 m a i l i n g a d d r e s s s e t t i n g , t h r e e d i g i t a l i n t e g e r , r a n g e i s 0 255; ensure the two channels of which one i s odd, the other one is even for t wo-
-channel system
Baud rate 1 Corresponding baud rate of RS232 communication
Optional value: 9600, 19200, 38400; unit: bpsBaud rate 2 Corresponding baud rate of CAN communication (no need of change, already set in
procedure inside)
Trang 24Fault clear Clear fault record, select “Yes” in this menu, press “enter” and then the fault record
t o t h e p r e v i o u s m e n u , i f y o u w a n t t o g i v e u p d a t e c h a n g i n g , p r e s s
“Q” and the current system date will be shown
2.6.4.17 Test option menu
In the main menu, select test option menu, press “ ”, after passing password authentication, enter
into submenu There are totally 6 submenus
Test Test Enable: Enable/ForbidTest Signal NUM: 0
Option -Test Type: With CMP/Without CMP/EndPSS Limitation Value: 5%
Test signal summing
point
Set place of test signal summing point
0 voltage set point1-8 spare
9-27 PSS transfer function summing point
Note: t fhis iunctionu o i P st sedt t snly e n mSS b sest,a he est ignal nabling ust e et sdisabled status in normal operation
Test type
Set test mode having compensation test, uncompensated test and finished status;
When test type is uncompensated, PSS output is zero, test PID characteristics;
When test type is compensation test, P of PSS output is zero, test signal join, testPSS+PID characteristics;
When test type is finished status, PSS works normally;
Note: i c n hangingt t f e estP oype, t mirst xitd SS,U bserve he easured isplaying PSSoutput, input PSS until UPSS stable output is close to zero
Trang 25PSS limiting value Set the proportion of PSS output corresponding PID output, generally not more
than 10%
PSS input Set t hel imitingv o P i aluea w af w SSg nput,a r s rell s hen enerator ctive eaches ated
active proportion, input PSS
PSS exit Set the limiting value of PSS exit, as well as when generator active reaches rated
active proportion, quit PSS2.6.4.18 Other test menu
The following screen appears after entering into the menu
Other
Test -COST CTR Angle Enable: Enable/ForbidCOST CTR Angle Set: 150
Constant controlled
angle output enable
In unloaded status of generator, change it to permit, controller output is constantcontrolled angle output This function is only used for test
Constant controlled
angle output
Se t c o n t r o l l e d a n g l e o f c o n s t a n t o u t p u t , r a n g e d f r o m t h e m a x i m u m c o n t r o l l e dangle to the minimum controlled angle
3 Operation
Trang 26Functions of each part from top to bottom, from left to right is as follows:
1PV Terminal voltage
meter Indicate the generator terminal voltage (stator voltage)2PV Field voltage meter Indicate generator rotor voltage
1PA Field current meter Indicate generator rotor current
H1 Alerting Excitation fault singal
HA/H2 FCB Close Close the field current breaker and Indicate closed position
TA/H3 FCB Open Break the field current breaker and Indicate opening position
SB1 EXC ON Excitation regulator start running after pressing the button
SB2 EXC OFF Excitation regulator stop running after pressing the button
QLA Field flashing The b uttonu f msed f orf wanuale rield olash hen xcitation egulator perate
by manual mode1QK Channel Select Select one of the two regulatrol as the master unit
In u nloadedo i peration, m ncrease/decreasec t i agnet orrespond o ncrease/
d e c r e a s e t e r m i n a l v o l t a g e ; i n p a r a l l e l o p e r a t i o n , i n c r e a s e / d e c r e a s emagnet correspond to increase/decrease reactive power
3QK Auto/Man M a k e t h e r e g u l a t o r w o r k i n m a n u a l ( c o n s t a n t c u r r e n t ) , a u t o m a t i c
(constant voltage)
Trang 27No Name Function
4QK Mode Slect Make the regulator work in constant power factor or constant reactive
power through switchover
5QK Rem/Loc Select local operation or remote master control operation
Constant power factor operation is the additional adjustment method of automatic operation,
change the set voltage value under automatic operation method in accordance with certain
step size and frequency, and then adjust terminal voltage of generator, thus make sure the
g e n e r a t o r p o w e r f a c t o r u n c h a n g e d In c o n s t a n t p o w e r f a c t o r o p e r a t i o n , i n d i c a t o r l i g h t o f
automatic o aperationc p fnd o onstanto c owerp i o actora t s peration n ontroller anel s n t he ametime
Constant power operation must meet the following three conditions:
1 The generator operates in parallel, and active power and reactive power is 2% more than
rated value
Trang 28as the adjustment target value
a u t o m a t i c o p e r a t i o n m e t h o d i n a c c o r d a n c e w i t h c e r t a i n s t e p s i z e a n d f r e q u e n c y , a n d t h e n
adjust t erminalv o g oltaget m sf tenerator,g r husp u ake ure he enerator eactive ower nchanged
In r e a c t i v e p o w e r o p e r a t i o n , i n d i c a t o r l i g h t o f a u t o m a t i c o p e r a t i o n a n d c o n s t a n t r e a c t i v e
power factor operation on controller panel is on at the same time
Constant reactive power operation must meet the following three conditions:
1 The generator operates in parallel
2 The generator operates in automatic operation method
3 Method selecting switch is located in constant reactive power factor input place
The above four operation methods can be interruptedly switched in operation, it’s notable that procedure
control manual tracking has 30 seconds delay, so when switch to manual operation from any methods, pay
attention that switch 30 seconds after operation parameter changing No need of delay when switch from
manual operation to other methods
Channel switchover
The t a lternateswo c tandbye hannelsd t CAN-BUS, t husrxchange ealizemata t hroughutuali o racking, n rder
to prevent faul t tracking delay, so the tracking of standby channel for operation channel has 30 seconds
delay, and there is 30 seconds delay before channel switchover
3.3 Increase/decrease magnet operation
Excitation o mperationm c odelv o ainly f r ompletev U ariouss a i perations or eference oltage GR, uch s ncrease
and decrease excitation, increase and decrease antiseize processing of excitation relay point, the maximum
and minimum limited location of reference voltage, and increase and decrease excitation automatically or
shut a utomaticallyi p a l n rotectingm s t ndr imitingv f z ovement,a f tep est, aising oltage rom ero, utomatic ield
s u p p r e s s i o n a n d o t h e r f u n c t i o n s e t c c a n b e r e a l i z e d b y d i r e c t l y c h a n g i n g r e f e r e n c e v o l t a g e v a l u e
Because microcomputer excitation is generally digital set, reference voltage is only a variable of internal
s t o r ag e, t h e o pe r a t or ca n c h an ge i t ex t er n al l y, i n ad di t i on, t h e co m pu t er i ns i d e ca n a l s o ch an ge U G R a s
needed, t t rhus heo e ealizationo f f ixcitationq simple a ndr perationeliable,w i o ounctionshicht s nes uitef he
advantages of microcomputer excitation
Th e a d j u s t m e n t o f v o l t a g e s e t v a l u e U G R i s c a r r i e d o u t t h r o u g h r e a d i n g c l o s i n g c o n d i t i o n s o f
i ncr ease/ decre ase exci tat i on node by comput er , t he longer node cl osi ng t ime i s, the mor e UGR adjus ted
measure is Excitation operation can be realized by operating “increase”, ”decrease” button of GEX-2000
control panel-respectively increase/decrease corresponding UGR, and so on
3.3.1 Anti-adhesive function of increase/decrease excitation node
Trang 29Th e f u n c t i o n i s o n l y e f f e c t i v e u n d e r a u t o m a t i o n m o d e a n d c o u l d e n a b l e o r c a n c e l i n t h e m e n u
"Function on"
Notice:
The f unction“system v toltage ” i sp rackingriort “soft so ”,so dtart isable“system v toltage ” f irstlyirackingn
menu before using “soft start”
3.5 system voltage tracking
“system voltage tracking ” make the terminal voltage rapidly rise closed to system voltage after making
enabled and measuring system side voltage
Notice:
D i s a b l e t h i s f u n c t i o n , i f s y s t e m v o l t a g e d o n’t p i c k u p b y e x c i t a t i o n r e g u l a t o r , i f n o t s o ,g e n e r a t o r v o l t a g e
couldn’t build up
3.4 Normal opening steps (local)
Check the following components are in proper place:
AC breaker 1QF is in open position,field-current breaker MK is in open position and green lamp
Switch 3QK“Auto/Man”is in auto position;
Select “local” of “local/master” switch 5QK;
The generator reaches rated speed 3000 r/min; having raising voltage condition, start to raise voltage:
1) Close AC breaker 1QF;
2) Press button HA, the red indicator light is on at the same time;
3) Press button SB1,regulator is running and generator terminal voltage rise up
4) When the terminal voltage is stabilized in setting voltage by soft start, increase voltage to
rated terminal voltage nearby through “increase/decrease” switch 2QK;
“inc reas e/decr ease” butt on 2QK if the vol t age c an not mai ntai n, incr ease manua l set val ue by
increase button 2QK then press “field flashing” button SB3;