Design procedure of power supply system Single line of lighting / socket Single line of A/C, pump, fan, comp., chiller, lift, other… Single line of production machine Single line of LV m
Trang 1PART I
ROUGH DESIGN
FOR FACTORY
Trang 2Page: 2/198
1 Design procedure
1.1 Design procedure of power supply system
Single line of lighting / socket
Single line of A/C, pump, fan, comp., chiller, lift, other…
Single line of production machine
Single line of LV main panel
Main CB capacity
Transformer number, capacity
S/S type
A: outdoor type B: Outdoor cubicle C: Kiosk
D: indoor panel
MV single line
(MV system specification)
(G) Cabling route / size
(F) Short circuit current
A: PC trans Capacity, %Z B: Distance from PC S/S
(E) Meter position CT/PT
A: MV on pole B: MV in elec Room C: LV in kiosk / outdoor cubicle
Trang 3(D) RMU
A: need
B: no need
(C) Wiring method A: U/G cabling
Trang 42.1.2 Procedure for lighting calculation
2.1.2.1 Make calculation from : refer to "example"
Example:
Make condition by you:
• Office -> FL40Wx2 Louver type / 500Lux
• Office area -> FL40Wx2 V type / 300Lux
Trang 52.1.2.2 Put in room name
2.1.2.3 Choose lighting type
- Incase have condition by Owner, follow requirement
- No requirement, choose VNKD standard
2.1.2.4 Illumination level E (Lux)
- Incase have condition by Owner, follow requirement
- No, requirement, choose VNKD standard
- Depend on lighting type
2.1.2.8 Measure room area
2.1.2.12 Calculate final illumination level
Trang 72.3 Illumination Factor (U)
Type Room (m2)
FL
V Type
FL Reflector
FL Louver
Mercury Metal halide Under 50 0,63 0,63 0,58
50 to 100 0,70 0,72 0,62
100 to 200 0,75 0,78 0,66
Over 200 0,80 0,82 0,68 0.75
2.4 Maintenance factor (M) : 70%
2.5 Illumination level and lighting fixture type
2.5.1 Follow Customer’s specification
2.5.2 If not requested, take under table
Trang 8V type Other office
area Reflector 250lux
Factory
FL Reflector
200lux
Entrance DL PLC 18W 2m pitch
Exit EXIT FL10W w/ battery - Near entrance
- Top of door to outdoor - -
EMG (office) 3W x 2 w/ battery
- Near car park
- 1nos/40m for road light - -
Trang 9Special room Estimated
Small fan (1PH) 1nos/1fan
4 Lighting / Socket distribution system
4.1 Make group
4.1.1 Separate to office and factory
4.1.2 Max Capacity / 1 group : 65kVA / 3PH(380-220)V
4.2 Circuit
15 nos FL40Wx2
6 nos HID (Mercury, Sodium, Metal halide) 150W
4 nos HID (Mercury, Sodium, Metal halide) 250W
3 nos HID (Mercury, Sodium, Metal halide) 400W
15 nos EXIT, EMG
1 nos Floor socket
5 nos wall socket
10 set small fan
Trang 114.4 Single line diagram
4.4.1 Typical drawing of distribution board
Trang 12Page: 12/198 4.4.2 Standard D/B
1 no MCB3P 100AF/60AT
30 nos MCB1P15AT
1 set N – Bar 30 Point
1 set G – Bar 30 Point
4.5 Main MCB trip current (A)
)(3803
)(
V
kVA Capacity Total
DB
×
≥ x 0.8 (DF)
DF: Demand factor (Lighting = 1, socket = 0.5)
4.6 Branch MCB: 1P15Ax3N, 3P20A
4.7 Neutral, grounding bar shall have termination point to be same number of circuit
4.8 Cable:
0.6kV/PVC/PVC/3C-2.5mm2 or 0.6kV/PVC wire 2.5 mm2x3
- Light
- Socket 0.6kV/PVC/PVC/3C-4mm2 MH in factory
4.9 Outdoor and Factory HID lighting system
4.9.1 Select system
Operation HID
light
Number/1 -circuit
1P20A 1P20A 1P20A
4mm2 4mm2 4mm2
3P20A 3P20A 3P20A
4mm2 4mm2 4mm2
O
O
O 150W
>1.6AxN/3
>2.6AxN/3
>4AxN/3
Depend on Voltage drop
Trang 134.9.1.1 Operation system type 1
Magnetic contactor (MC) and push button (PB)
4.9.1.1.1 0 / 100% operation by manual cut and auto start
• Street light
• Outdoor HID
• Factory HID, garden light
• Remote PB system should be installed by owner’s requirement 4.9.1.1.2 0 / 33% / 66% / 100% operation
Trang 14Page: 14/198 4.9.1.2 Operation system type 2
Automatic operation 0 / 33% / 66% / 100%
• Road light
• Switch on by photocell
• Switch off by timer relay
• Grounding at each lighting position
• Cable shall be used for 0.6kV/XLPE/DSTA/PVC/4c- mm2
Trang 155 Power supply panel for Production machine
5.1.2 Rough calculate each total capacity (kW)
5.1.3 Check / compare with each max capacity
Capacity / 1 group:
Max: 100kW / 3PH380V Max: 50kW / 3PH200V Max: 30kW / 1PH100V
Note: If 1 set motor’s capacity is over 75kW/380V, 37kW/200V, 1 group shall be made
by 1 set motor
5.1.4 Check area / cable length, if some machine's position is far, separate group
5.1.5 Put in each machine's name and capacity to each typical dwg by Table 5.1.5.6~9
Trang 16Page: 16/198
5.1.5.1 Typical drawing of local power supply panel (3PH380V)
5.1.5.2 Typical drawing of local power supply panel (3PH380V/220V)
Trang 175.1.5.3 Typical drawing of Power Supply Panel (3PH-200V)
Trang 18THERMAL RELAY 1C
(mm2) 3C (mm2)
DIRECT START
STAR/DELTA STARTER kA
METER (A) GROUNDING WIRE (MM2)
Note: Motor capacity (kW) direct start on 600%
0.2 ~ 7.5 kW 10 sec 12 time 16 time
Trang 195.1.5.7 3PH400V MOTOR
CABLE & MCCB SELECTION FOR FEEDER (OVER 2 SETS OF MOTOR)
Trang 20THERMAL RELAY (A) 1C (mm2) 3C (mm2) DIRECT START STAR/DELTA STARTER (kA)
METER (A) GROUNDING WIRE (MM2)
Note: Motor capacity (kW) direct start on 600% x
Trang 215.1.5.9 3PH200V MOTOR
CABLE & MCCB SELECTION FOR FEEDER (OVER 2 SETS OF MOTOR)
Trang 22Page: 22/198 5.1.5.4 Typical drawing of Power Supply Panel (3PH-200V <50kW )
Trang 235.1.5.5 Typical drawing of power supply panel (3PH-173V/100V)
Trang 24Page: 24/198
5.1.6 Choose MCCB's rating / cable, grounding size for motor load by 5.1.5.6 / 5.1.5.8
5.1.7 Choose main MCCB rating, cable, grounding size by 5.1.5.7 / 5.1.5.9
5.2 Make 400V single line (local panel) for each group
5.2.1 MCCB rating for motor (pump, fan)
Branch / main MCCB’s trip current shall be selected by 5.1.5.6 / 5.1.5.7
Note: Be careful for MCCB’s kA
5.2.2 If load is heater, calculate as follow:
)(13803
)()
(
PF
Kw city HeaterCapa AT
MCCB
×
×
>
5.2.3 Cable/Grounding wire for motor shall be selected from 5.1.5.6 / 5.1.5.7
5.2.4 Grounding bar, if need neutral (3PH400V-230V) neutral bar shall be set
5.2.5 Make single line diagram : write down capacity, MCCB rating, cable size, G size for
each circuit in 5.1.5.1 or 5.1.5.2
5.2.6 Demand factor for power supply panel (3PH200V, 3PH400V)
Voltage Max branch capacity Branch number Total DF
<10KW >10 sets 0.85
<10KW > 15 sets 0.8 3PH200V panel
<10KW >20 sets 0.7
<20KW >10 sets 0.85
<20KW > 15 sets 0.8 3PH400V panel
<20KW >20 sets 0.7
Trang 255.2.7 MCCB selection for big capacity production machine
5.2.7.1 If load capacity is over 20KW for 200V or 30KW for 380V shall request detail of load
to Owner Big capacity machine are almost following case
Case-1: combined by several motors
Case-2: including heater
In above case, MCCB selection shall be done by 5.2.7.2
5.2.7.2 MCCB selection for case-1 :
• Shall request detail motor capacity and operating condition for each motor to Owner and then decide DF
• MCCB rating and cable size shall be selected by5.1.5.7 for 380V or 5.1.5.9 for 200V
Trang 26by 5.1.5.7
5.2.7.3 MCCB selection for case-2:
• Shall request detail capacity and number for motor, heater
• Calculate full load current (AH) for heater
• Select MCCB AT (AM) for motor by motor selection table
• Selected MCCB for total load = AH + AM
Example:
(1) Condition:
Production machine : 3PH200V-60KW
Detail: Motor 5KW x 2 sets
Motor20KW x 1 set Heater 30KW x 1 set Operation : same time operation for 3 loads (2) Selection :
AH = 30.000W/(1.73 x 200Vx 1 (PF)) = 86.7A
AM = total 30KW, max 20KW -> 150A by 5.1.7.9
Selected MCCB (AT) = 86.7A + 150A = 237A -> 250AT
Trang 275.3 Make 3PH200V single line diagram
)(2
.1)(
PF
kW capacity grouptotal
kVA capacity
(safety factor x demand factor = 1.2 x 1.0)
→ Main CB rating for transformer secondary:
- Calculated trip current Ac = Trans (KVA) x 1000 / (1.73 x 200V)
- Selected trip current As by 5.1.5.9
- Shall compare Ac with As, if Ac < As size up trans capacity up to Ac > As
)(75
.0
PF
kW ity totalcapac
×
≥
(safety factor x demand factor = 1.0 x 0.75)
→ Voltage 3PH- 400V/210V (Delta/Star) or 3PH-22kV/210V (delta/ delta)
→ Install at electrical room with 200V LV main panel
5.3.1.3 3PH200V total load (kW) > 400kW
→ Oil transformer
→ Trans capacity (kVA)
8.0)(
)(7
.0
PF
kW ity totalcapac
Trang 28Page: 28/198
5.3.2 3PH200V single line (local panel) for each group
5.3.2.1 MCCB rating for motor shall be selected from 5.1.5.8 / 5.1.5.9
5.3.2.2 If load is heater, calculate as follow
MCCB (AT) >
)(12003
)(
PF V
kW city Heatercapa
×
×
5.3.2.3 Cable / Grounding wire for motor shall be selected from 5.1.5.8 / 5.1.5.9
5.3.2.4 Grounding bar only
5.3.3 Make single line diagram : write down capacity, MCCB rating, cable size, G size for
each circuit in 5.1.5.3 or 5.1.5.4
5.3.4 3PH200V LV Main panel : refer to item 7
5.4 Make 1PH100V single line (local panel)
5.4.1 Select transformer
5.4.1.1 One set dry transformer shall be selected for each group
5.4.1.2 Transformer Capacity (kVA)
8.0)(
)(
PF
kW capacity Grouptotal
≥
5.4.1.3 Rating: 3PH400V/182-105 V (Delta/Star)
5.4.1.4 Install at local with panel
5.4.2 1PH 100V single line (local panel) for each group
5.4.2.1 Primary trans MCCB trip current <
V
kVA Trans
3803
).(
9.0
1733
)(9
.0
×
×
Trang 295.4.2.3 Branch: MCB 1P(15A~20A)
Max load / 1 circuit : ≤ 1.5kVA
if bigger than 1.5kVA, MCB trip ampere ≥ 1.2 x load(VA)/100V
5.4.2.4 Cable size: 0.6kV/PVC/PVC/3Cx2.5mm 2
5.4.2.5 Grounding bar
5.4.2.6 Socket outlet shall be estimated for each load
5.4.3 Make single line diagram : write down capacity, MCCB rating, cable size, G size for
each circuit in 5.1.5.5
Trang 306.3.1 MCCB rating: same as 5.2.1 with note
6.3.2 Heater: same as 5.2.2 tem
6.3.3 Make single line diagram : put main/branch MCCB's trip current, cable size,
grounding size by 5.1.5.6 / 5.1.5.7 in 5.1.5.1 / 5.1.5.2
6.3.4 Neutral :
• Use for control circuit or small load
• If use for big load with small N-load, shall consider which system is better ( 4 core cable or small transformer with fuse)
• If choose 4 core cable system, N-phase cable size shall not be used for smaller than 50% of phase cable
• 1-N-cable shall be used for per 1 circuit
6.3.5 Demand factor for power supply panel (3PH380V) : Same as 5.2.6
6.3.6 MCB, cable selection / calculation for 1PH220V load
6.3.6.1 System
for mixed with 3PH380V and 1PH220V load, shall select one of following 2 system
3PH4W system (4 core cable + G) 3PH3W + small trans
1PH220V total capacity (KW) > panel total (KW) x 5% < panel total (KW) x 5% Branch MCB MCB + fuse MCB
MCB for over current, fuse for short circuit
Trang 316.3.6.2 Calculation for single 1PH220V load
• Full load current Af = KW x 1.5 / (220V x 0.8 (PF))
(1.5 is starting current factor)
Load : 1PH220V Air-con 1.5kW and 3.5 kW
• 1.5kW AC MCB trip A = 1.5kWx10000x1.5 / (220Vx0.8PF) = 12.7A -> 15AT
• Cable size = 2.5mm2
• 3.5kW AC MCB trip A = 3.5kWx1000x1.5 / (220Vx0.8PF) = 29.8A -> 30AT
• Cable size = 6mm2
6.4 Control
6.4.1 One set magnetic contactor (MC) with thermal relay shall be set per 1-circuit,
MC’s capacity (kW) = motor capacity
6.4.2 One set relay / 1 circuit
6.4.3 Two set push button / 1 circuit
6.4.4 Three set pilot lamp / 1 circuit
6.4.5 One set select switch / 1 circuit
6.4.6 If request remote switch, control cable and push button shall be indicated on dwg 6.1.4.7 Neutral and grounding bar
Trang 32Page: 32/198
7 LV main panel
7.1 Single line diagram
7.1.1 Put each panel capacity, cable size and MCCB rating in typical drawing
(3PH4W-400/230V)
Trang 337.1.2 Put each panel capacity, cable size and MCCB rating in typical drawing
(3PH-200V, < 400KVA)
Trang 34Page: 34/198
7.1.3 Put each panel capacity, cable size and MCCB rating in typical drawing
(3PH-200V, > 400KVA)
Trang 35kVA Trans
2103
)(
×
≤
V
kVA Trans
4003
)(
×
≤
7.1.4 Trip current: same as local main MCCB or MCB
Note: never use MCB
7.1.5 Interrupting current: refer to (12.1.1)
7.2 Capacitor with MCCB, MC, PF controller, PB, PL
7.2.1 - Total capacitor’s capacity (kVAR) = 3PH motor load (kW) (exclude heater,
lighting) x 0.7(DF) x 0.4 / 0.8(PF) ≈ trans.(kVA) x (0.25< ….<0.3) for LV main panel
- Trans (kVA) x 0.3 for 3PH200V main panel
7.2.2 Standard: 100kVAR/set, 50kVAR/set, 25kVAR/set
7.2.3 Number of 50(kVAR) capacitor =
)(50
)('
kVAR
kVAR sCapacity itor
TotalCapac
7.2.4 Reactor : 6% (kVA) with each capacitor (kVAR)
7.2.5 Power factor controller : 6-step, 12-step
7.2.6 Branch MCCB, MC
Capacitor
(kVAR)
MCCB 3P (AT)
MC 3P (A)
Reactor
(kVA) 400V 210V 400V 210V
Trang 36Page: 36/198
7.3.2 Switch
Trip current ≤ 800(A) MCCB
Trip current > 800(A) ACB (max 4000A)
7.4 Interrupting current : refer to 12.1.1
7.5 Meter
7.5.1 Ampere, Volt meter with select switch
7.5.2 kW meter
7.5.3 PF controller: meter and controller
7.5.4 Current trans (CT) for above
7.5.5 Other meter if request by Owner
7.6 Protection relay
7.6.1 Over current relay (OCR): MCCB, ACB has internally
7.6.2 Ground fault relay (GFR): ACB has internally, MCCB don’t has internally
3PH3W 3 sets 1 set 3PH4W
w/ shunt trip coil
4 sets 1 set
Setting under 100A
Trang 377.6.3 Earth leakage relay (ELR)
• Should be used only by Owner’s request
MCCB - 3PH3W ZCT+ELR
MCCB w/ shunt strip ELCB ELCB
MCCB - Feeder
MCCB - 3PH4W
ZCT ELR
MCCB w/ shunt strip Main
Trang 38Page: 38/198 System:
7.7 Secondary (feeder) cable / grounding wire :
7.7.1 For power supply panel (production, AC, pump) shall be selected from (CAL-)
7.7.2 For light DB, for heater: shall be selected as cable’s allowable current (A) x 0.8 > main
MCCB’s trip current
7.7.3 0.6kV/XLPE/PVC cable shall be used
7.8 Branch cable from feeder cable
• The joining directly from main feeder to branch cable, MCCB shall be installed by following condition:
Trang 39
MTL<1000kVA 0.8 ≥ MTL
x0.8kVA
I(A) = T/√3x400V
I(A) = T/√3x22000V
MTL>1000kVA 0.75 ≥ MTL
x0.75kVA
I(A) = T/√3x400V
I(A) = T/√3x22000V
I(A) = T/√3x22000V
MTL<400kVA 0.75 ≥ MTL
x0.75kVA
I(A) = T/√3x210V
I(A) = T/√3x220003PH
210V
MTL>400kVA 0.7 ≥ MTL
x0.7kVA
I(A) = T/√3x210V
I(A) = T/√3x22000V
Note:
Max capacity of trans : - Depend on secondary CB capacity
- 2500kVA (3600A secondary current) at 400V
- 1300kVA (3600A secondary current) at 210V
8.2 Secondary cable
• Main CB trip current ≤ selected cable allowance current (A)x1.0
• 0.6kV/XLPE/PVC/1C for over 240mm2 shall be used
9 Voltage drop
9.1 Calculation
Max Vd (total 5%) Voltage drop (V)
Main feeder Branch 1PH2W Vd = 35.6xL(m)xI(A) / S(mm2) x 1000 ≤ 2%
3PH3W
3PH4W
Vd = 30.8xL(m)xI(A) / S(mm2) x 1000 ≤ 3%
If direct to load = 5%
≤ 2%
L: cable length (m), I: rated current, S: Cable size
Trang 40Page: 40/198 9.2 I(A) rated current
3PH 380V, 3PH 200V 1PH 220V
Feeder for motor panel I = panel(kW) x 0.8 / √3 x 400V x 0.8 -
Feeder for lighting panel I = panel (kVA) x 0.8 / √3 x 400V -
Each motor I = Motor(kW) / √3 x 380V x 0.8 -
10.1 Grounding for substation
10.1.1 Resistance max = 4 ohm
10.1.2 Mesh connection system