I ntroduction: Feeder Protective Relaying Feeder Protection Relays are act as a Primary & Backup Protection Primary Protection act with in 50-100ms Backup Protection act when
Trang 1PRESENTED BY
JAY B THAKAR SAGAR J KOTHARI
E valuating P rotective R elay P erformance
T hrough R elay T esting
Trang 2I ntroduction: What is Protective
Relaying???
“ Voltage & Current Amplitude, Phase Angle, Frequency
continuously in electrical
networks to detect Faults in
networks & isolate faulty
section ” before any serious
Damage.
2
Trang 3 Transmission Line Protection
Electrical Machine Protection
Relays
Generator Unit Protection
Transformer Unit Protection
Motor Unit Protection
3
Trang 4I ntroduction: Feeder Protective
Relaying
Feeder Protection Relays are act
as a Primary & Backup Protection
Primary Protection act
with in 50-100ms
Backup Protection act when
Primary protection fails Operation
of Backup Protection is Time
4
Trang 5I ntroduction: Electrical Machine
Protection Relay
Electrical Machine Protection
Relays: Unit Protection
Unit Protection relays are Act for
time of unit Protection relays are
30 to 80ms
5
Trang 6R
Trang 7I ntroduction: Dynamic Power
What are the harmonic content & Relay operating
time during an internal fault followed by CT
saturation?????????
How I can see the performance of Distance
Protection relays on CCVT transient????
7
Trang 8O utline
W hat is the existing relay test practice?
W hat is the advance relay test practice?
S ummary
Trang 9W hat is the Existing Relay Test Practice?
Trang 1010
Constant Current Method:
phase angle and Ramps Voltage from normal voltage to
threshold value until the relay operates
is varying at time
P hasor Testing: S teady State Testing
Voltage Ramp starts to decrease from Normal Voltage to until relay Trips
Trang 1111
Dynamic State Testing means
true fault simulated Power
Trang 1212
D ynamic State Testing: T est P rocedure
Power System Model
Trang 1313
P hasor Testing: D ynamic State Testing
Pole Slipping Detected &
Issued Trip command
Trang 14 Transformer Inrush current, Over
Excitation phenomenon & It’s Effect
on relay operation
T ransient Testing:
Trang 15W hat is the Advance Relay Test Practice?
Product Design Application Test
Simultaneously Apply Fundamental Freq & Harmonic Freq components (Including DC OFFSET) of Voltages and Currents Phasor
Trang 1616
Simulation Programs like
Trang 17Test Software (TransWin) Testing Kit (F6150)
Relay
TRIP
V & I Sources
Trang 1818
T ransient Testing: P reventive Study
Dynamic State Testing
Trang 19R esults: S ensitivity
Test Cases Description Results
Test Case-1 Initial CT
Operating Time
86.5ms
Test Case-3 CT Saturation for
4-5 Cycles after one cycle
Operating Time
150ms
Test Case-4 Dynamic State
Testing Fault, Fault, Post-Fault)
(Pre-Operating Time
33.4ms
Trang 20S ummary
Existing Test Practices serves a limited purpose
to check setting calibration but Not to Evaluate
t h e r e l a y a p p l i c a t i o n p e r f o r m a n c e
Dynamic State Testing is easy to conduct & more meaningful testing than steady state testing but, still it is on fundamental frequency so it is difficult to known the transient behavior of relays
Relay performance on transient behavior needs to
be evaluated to assure the best decision
regarding;
Investment
Application Practice
Relay Performance under critical conditions
Resolve problem for relay design issues
Trang 21T hank Y ou