Purpose of Short-Circuit Studies: A Short-Circuit Study can be used to determine any or all of the following: Verify protective device close and latch capability Verify protective d
Trang 1Engineering Calculation for Power
System Analysis
Trang 2CONTENTS
1 Load Flow Calculation 3-16
Case1-ANSI/IEEE Method
Case2-IEC Method
Case1-Single Machine System
Case2-Multi Machine System
9 Arc Flash Analysis 152-164
Trang 31 LOAD FLOW ANALYSIS
Trang 4INTRODUCTION:
Load flow solution analysis is essential for designing a new power system and planning of
the existing one for increased load demand, which determine the steady state operating
condition to calculate,
Voltage Profile - its magnitude in kV or % of nominal kV
Current flow throughout the System
MVA and /or MW plus Mvar power flows throughout each branch of the (i.e
transformer, cables, line or series reactor etc) electrical system
Voltage drop and Power factor
Branch Losses i.e MW & Mvar losses on each branch
Trang 5Input data required for LFA:
Sl.no Component Required input
2 Power Grid Voltage rating, MVA sc, X/R ratio
3 Syn Generator 1 Swing (slack) – %v and del
2 Voltage Control (PV) – MW, Mvar limits
3 Mvar Control (PQ) -MW, Mvar and Var limits
4 PF Control-MW and PF
4 Transformer Py kV, Sec kV, MVA, %Z Positive sequence Impedance,
%Tap, Tolerance and LTC settings
5 Motor 1 Status- Continuous , Intermittent or Spare
2 Rating-HP and kV
6 Syn Motor 1 Status- Continuous , Intermittent or Spare
2 Rating-HP and kV
7 Static Load 1 Status- Continuous , Intermittent or Spare
2 Rating-kV, MW, Mvar and PF
8 Lump Load 1 Status- Continuous , Intermittent or Spare
2 Ratings- kV, MW, Mvar and PF
3 Load Type-Motor Load or Static load
2 Cable Type- Size, Insulation, kV and #/Cable
3 Impedance/conductor-Positive sequence
8 Transmission Line 1 Length in ft/m/mile/km
2 Parameter-Phase conductor
3 Impedance per phase-positive sequence
10 Protective Devices 2 Circuit Breakers-Rated kV
3 Fuses-Rated kV
4 Switches-Rated kV and amps
5 Contactors- Rated kV and amps
11 Capacitor 1) Status- Continuous , Intermittent or Spare
2) Rating-kV, Max kV, Mvar Bank and No of Banks
2) Impedance- Positive sequence Z and X/R
Trang 6STEP by STEP Procedure for Load Flow Analysis
Trang 7Step 2 : Input Parameters/data for LFA
Load Type = 100% Motor Load & 0% Static Load
Trang 8Step 4 : ETAP WITH HAND CALCULATION
1 To find Voltage Drop(Vd)
Formula: %Voltage drop= Delta V*100 - eq1
To find Delta V:
Delta V= (√ (Vr+ (RP+XQ/Vr) ^2+ (XP-RQ/Vr) ^2))-Vr - eq2
Where:
Vr = Receiving end voltage
R = Resistance of the cable/transmission in p.u
P = Real Power in MW
Q = Reactive Power in Mvar
X = Reactance of the cable in p.u S= Apparent power in p.u
We know that,
Base MVA = 100 MVA Base kV = 11 kV Nominal kV = 11 kV Load PF = 0.8
R Ω/km = 0.0801 Ω
X Ω/km = 0.12736 Ω Length = 0.836 km Assume Vr = 1 p.u
To find Z base:
Zbase = BasekV^2/Base MVA
Trang 10To find % voltage drop:
Note Vs ≠Vr so we are finding the new Vr new
Vr new=Vr -Delta V -eq3
Trang 112 To find cable loss:
Formula:
MW =R*S^2*Base MVA*(Base kV/Nominal kV) ^2 - eq 4
Mvar = X*S^2*Base MVA*(Base kV/Nominal kV) ^2 - eq 5
Trang 123 To find Transformer Losses
Formula:
MW =R*S^2*Base MVA*(Base kV/Nominal kV) ^2 - eq 6
Mvar = X*S^2*Base MVA*(Base kV/Nominal kV) ^2 - eq 7
Trang 15Step 5 : Run Load Flow Analysis with ETAP software
Trang 16Step 6: Summary Report
Hand Calculation ETAP Result
MW Mvar MW Mvar Cable Losses
Trang 172 SHORT CIRCUIT ANALYSIS
(IEEE / ANSI AND IEC METHOD)
Trang 18CASE 1:-ANSI / IEEE METHOD INTRODUCTION:
The ETAP Short-Circuit Analysis program analyzes the effect of 3-phase, line-to-ground,
line-to-line, and line-to-line-to-ground faults on electrical distribution systems The program
calculates the total short circuit currents as well as the contributions of individual motors,
generators, and utility ties in the system Fault duties are in compliance with the latest
editions of the ANSI/IEEE Standards (C37 series)
Purpose of Short-Circuit Studies:
A Short-Circuit Study can be used to determine any or all of the following:
Verify protective device close and latch capability
Verify protective device Interrupting capability
Protect equipment from large mechanical forces (maximum fault kA)
I2t protection for equipment (thermal stress)
Selecting ratings or settings for relay coordination
Elements that Contribute Current to a Short-Circuit:
Inverters
I0 from Yg-Delta Connected Transformer
Elements that do Not Contribute Current in PowerStation:
Static Loads
Trang 19 All Shunt Y Connected Branches
Short-Circuit Phenomenon:
Trang 20Copyright 2003 Operation Technology, Inc – Workshop Notes: Short-Circuit ANSI Slide 9
Steady
t )
sin(
-Z
Vm )
t sin(
-Z
Vm i(t)
(1) )
t Sin(
Vm dt
di L Ri v(t)
L
R -
theyields1equation Solving
i(t)
v(t)
Symmetrical Faults:
The ETAP Short-Circuit Analysis program analyzes the effect of 3-phase
Symmetrical faults on electrical distribution systems The program calculates the total short
circuit currents as well as the contributions of individual motors, generators, and utility ties in
the system Fault duties are in compliance with the latest editions of the C37 series which
calculates
Momentary symmetrical fault current in kA
Interrupting symmetrical fault current in kA
Unsymmetrical Faults:
The ETAP Short-Circuit Analysis program also analyzes the effect of 3-phase
unsymmetrical Faults like
Line to Ground fault
Double line fault
Double line to ground fault
Trang 21½ Cycle Network
This is the network used to calculate momentary short-circuit current and protective device
duties at the ½ cycle after the fault
1 ½ to 4 Cycle Network
This network is used to calculate the interrupting short-circuits current and protective device
duties 1.5-4 cycles after the fault
30-Cycle Network
This is the network used to calculate the steady-state short-circuit current and settings for
over current relays after 30 cycles of the fault
Device Duty and Usage of Fault Currents from Different Networks:
½ Cycle Currents (Sub transient Network)
1 ½ to 4 Cycle Currents (Transient Network)
HV Circuit Breaker Closing and Latching
Capability
Interrupting Capability
LV Circuit Breaker Interrupting Capability -
Trang 22ANSI Calculation Standard Compliance:
ETAP short circuit calculation per ANSI/IEEE Standards fully complies with the latest
ANSI/IEEE and UL Standards, as listed below:
IEEE C37.13 1990 Standard for Low-Voltage AC Power Circuit Breakers
Used in Enclosures IEEE C37.013 1997 Standard for AC High-Voltage Generator Circuit
Breakers Rated on a Symmetrical Current Basis IEEE C37.20.1 1993 2002 Standard for Metal Enclosed Low-Voltage Power
Circuit Breaker Switchgear IEEE Std 399 1990 & 1997 Power System Analysis – the Brown Book
IEEE Std 141 1986, 1993, 2002 Electric Power Distribution for Industrial Plants – the
Red Book IEEE Std 242 1986 & 2001 IEEE Recommended Practice for Protection and
Coordination of Industrial and Commercial Power Systems – the Buff Book
UL 489_9 1996, 2000, 2002 Standard for Safety for Molded-Case Circuit Breakers,
Molded-Case Switches, and Circuit-Breaker Enclosures
Trang 23Input data required for SCA:
Sl.no Component Required input
1 Bus Nominal kv
2 Power Grid Voltage rating, MVA sc, X/R ratio
3 Syn Generator 1 Swing – %v and del
2 Voltage Control – MW, Mvar limits
3 Mvar Control-MW, Mvar and Var limits
4 PF Control-MW and PF
5 Imp/Model-Impedance(Xd’’,Xd’, Xd, Xo, X2 and X/R)
4 Transformer 1 Rating-Py kV, Sec kV, MVA
2 Impedance-%Z (+Ve & -Ve sequence Impedance)
3 Tolerance
4 Tap-Fixed Tap and LTC settings
5 Grounding-Py and Sec
5 Motor 1 Status- Continuous , Intermittent or Spare
2 Rating-HP and kV and select MFR details
3 Model-%LRC, %PF
4 Model-Parameters-X0, X/R
6 Syn Motor 1 Status- Continuous , Intermittent or Spare
2 Rating-HP and kV and select MFR details
3 Model-Impedance(Xd’’,Xo,Xd’,X2, X/R)
7 Static Load 1 Status- Continuous , Intermittent or Spare
2 Rating-kV, MW, Mvar and PF
8 Lump Load 1 Status- Continuous , Intermittent or Spare
2 Ratings- kV, MW, Mvar and PF
3 Load Type-Motor Load or Static load
9 Cable 1 Length in ft/m/mile/km
2 Cable Type- Size, Insulation, kV and #/Cable
3 Impedance/conductor-Positive sequence
8 Transmission Line 1 Length in ft/m/mile/km
2 Parameter-Phase conductor
3 Impedance per phase-positive sequence
9 MOV 1 Rating-HP, kV and rated Torque
10 Protective Devices 1 Circuit Breakers-Rated kV, Amps, Interrupting kA
2 Fuses-Rated kV, Size, Amps, Interrupting kA
3 Switches-Rated kV , BIL ratings and amps
4 Contactors- Rated kV, Interrupting kA and amps
11 Capacitor 1 Status- Continuous , Intermittent or Spare
2 Rating-kV, Max kV, Mvar Bank and No of Banks
12 Impedance 1 Rating-Amps and kV
2 Impedance- Positive sequence Z and X/R
Trang 24Step 1: Build the single line diagram using ANSI / IEEE method
Trang 25Step 2 : Input Parameters/data for short circuit Analysis
Trang 26Step 3 : Apply Fault
Apply fault at the bus 4 by opening the short circuit study case editor and open the
motor side circuit breaker, because the Calculation 1 was done without motor contribution
First step to find Grid, Cable and Transformer reactance Sum of this will get the
Total reactance, using this we can find out the symmetrical fault current at the faulted bus
Calculation 1: Without motor contribution
Formulae:
I symm =MVAsc/√3*kV -eq 1 MVAsc=symm fault level *1.6 -eq 2 Symm fault level=1/ X TOTAL - eq 3
To find XTOTAL
X TOTAL = Xgrid+ Xcable+ X TFR - eq 4
i.e total reactance of all components in the system
Xgrid =Base MVA/MVAsc
Trang 27Total reactance
X TOTAL = Xgrid+ Xcable+ X TFR
=0.0013+0.00485+0.009587
X TOTAL =0.011485 -eq 5
To find Symmetrical fault level substitute 5 in eq 3
Symm fault level =1/ X TOTAL
=1/ XTOTAL =1/0.011485 =87.68MVA -eq 6
Then find MVAsc at the faulted bus
For this substitute eq 6 in eq 2
MVAsc=symm fault level *1.6
Trang 28Step 5 : Run Short Circuit Analysis without motor contribution
Trang 29
Step 6: Build the single line diagram using ANSI / IEEE method
Trang 30Step 7: Compare hand calculation with ETAP software
Calculation 2: With motor contribution
Formulae:
Isymm=MVAsc/√3*kV -eq 8MVAsc=Base MVA/ XM -eq 9
XM = Xd1'' / rated input MVA -eq 10 Xd''=1/LRC p.u -eq12Where
MVAsc =Short Circuit MVA at the faulted bus
kV =Nominal kV at the faulted bus
Xm = Motor reactance
Xd'' = Dynamic reactance of the motor
LRC =Locked Rotor Current
Then find the reactance of the motor 1
X M1 = Xd 1 '' / rated input MVA
= 0.25/5.676
X M1 =0.0440
Trang 31Then find the MVA at the faulted bus
MVAsc = Base MVA/ X M1
= 1/0.0440
MVAsc=22.70
Substitute the above values in eq 8
Then to find the short circuit current by motor 1 contribution
Then find the reactance of the motor 2
X M2 = Xd2'' / rated input MVA
= 0.1818/1.282
X M2 =0.1418
Substitute the above values in eq 9
Then find the MVA at the faulted bus
MVAsc = Base MVA/ X M2
= 1/0.1418
Trang 32MVAsc=7.051
Substitute the above values in eq 8
Then to find the short circuit current by motor 2 contributions
KA m2 =MVAsc/ (√ (3)*kV)
=7.051 / (√ (3)*6)
KA m2 =0.678 kA, short circuit current due to motor2 contribution
Note:-Sum of all the short circuit current without motor contribution and with motor
contribution gives the total fault current in the faulted bus
From the above results w.k.t
Symmetrical fault current = 13.49 kA without motor contribution - eq 13
Short circuit current by motors = 2.858 kA ( KA m1 + KA m2) - eq 14
Sum of above two equations 13 & 14
We get the total Symmetrical fault current
KAsc Total =13.49+2.858
=16.45 kA
Symmetrical fault current (I symm ) =16.45 kA (with motor contribution)
Trang 33Step 8: Run short circuit Analysis with motor contribution
Trang 34Step 9: Comparison Table
With Contribution
Without contribution
With contribution
Without contribution
ANSI/IEEE
Method
Trang 35CASE 2:- IEC METHOD
INTRODUCTION:
The ETAP Short-Circuit Analysis program analyzes the effect of 3-phase, line-to-ground,
line-to-line, and line-to-line-to-ground faults on electrical distribution systems The program
calculates the total short circuit currents as well as the contributions of individual motors,
generators, and utility ties in the system Fault duties are in compliance with the latest
editions of the IEC Standards (IEC 60909 and others)
Purpose of Short-Circuit Studies:
A Short-Circuit Study can be used to determine any or all of the following:
Verify protective device close and latch capability
Verify protective device Interrupting capability
Protect equipment from large mechanical forces (maximum fault kA)
I2t protection for equipment (thermal stress)
Selecting ratings or settings for relay coordination
Elements that Contribute Current to a Short-Circuit:
Inverters
I0 from Yg-Delta Connected Transformer
Trang 36Elements that do Not Contribute Current in PowerStation:
Static Loads
Motor Operated Valves
All Shunt Y Connected Branches
IEC Short-Circuit Calculation (IEC 909):
Initial Symmetrical Short-Circuit Current (I"k)
Peak Short-Circuit Current (ip)
Symmetrical Short-Circuit Breaking Current (Ib)
Steady-State Short-Circuit Current (Ik) ETAP checks the protective device rated making and breaking capacities against the fault
currents and flags inadequate devices
Types of SC Faults
Three-Phase Ungrounded Fault
Three-Phase Grounded Fault
Phase to Phase Ungrounded Fault
Phase to Phase Grounded Fault
Phase to Ground Fault
Trang 37Types of Short-Circuits
Near-To-Generator Short-Circuit
This is a short-circuit condition to which at least one synchronous machine
contributes a prospective initial short-circuit current which is more than twice the
generator’s rated current, or a short-circuit condition to which synchronous and
asynchronous motors contribute more than 5% of the initial symmetrical
short-circuit current ( I"k) without motors
Far-From-Generator Short-Circuit
Trang 38 This is a short-circuit condition during which the magnitude of the symmetrical ac
component of available short-circuit current remains essentially constant
Trang 39IEC Calculation Standard Compliance:
Standard Pub Year Title
IEC 62271-100 2003 voltage switchgear and control gear – Part 100:
High-voltage alternating-current circuit breakers IEC 62271-200 2003 High-voltage switchgear and control gear – Part 200: AC
metal-enclosed switchgear and control gear for rated voltages above 1 kV and up to and including 52 kV
IEC 62271-203 2003 High-voltage switchgear and control gear – Part 203:
Gas-insulated metal-enclosed switchgear for rated voltages above
52 kV IEC 60282-2 1997 High-voltage fuses – Part2: Expulsion fuses
IEC 61363-1 1998 Electrical installations of ships and mobile and fixed offshore
units – Part 1: Procedures for calculating short-circuit currents
in three-phase a.c
IEC 60909-0 2001 Short-Circuit Currents in Three-phase a.c systems - Part 0:
Calculation of Currents (including 2002 corrigendum 1) IEC 60909-1 2002 Short-circuit currents in three-phase a.c systems - Part 1:
Factors for the calculation of short-circuit currents according
to IEC-60909-0 IEC 60909-2 1992 Electrical equipment - Data for short-circuit current
calculations in accordance with IEC 909 (1988) IEC 60909-4 2000 Short-circuit currents in three-phase a.c systems Part 4:
Examples for the calculation of short-circuit currents IEC 60947-1 2004 Low voltage switchgear and control gear, Part 1: General
rules IEC 60947-2 2003 Low voltage switchgear and control gear, Part 2: Circuit
breaker
Trang 40Input data required for SCA:
Sl.no Component Required input
1 Bus Nominal kv
2 Power Grid Voltage rating, MVA sc, X/R ratio
3 Syn Generator 1 Swing – %v and del
2 Voltage Control – MW, Mvar limits
3 Mvar Control-MW, Mvar and Var limits
4 PF Control-MW and PF
5 Imp/Model-Impedance(Xd’’,Xd’,Xd,Xo,X2 and X/R)
4 Transformer 1 Rating-Py kV, Sec kV, MVA
2 Impedance-%Z (+Ve & -Ve sequence Impedance)
3 Tolerance
4 Tap-Fixed Tap and LTC settings
5 Grounding-Py and Sec
5 Motor 1 Status- Continuous , Intermittent or Spare
2 Rating-HP and kV and select MFR details
3 Model-%LRC, %PF
4 Model-Parameters-X0, X/R
6 Syn Motor 1 Status- Continuous , Intermittent or Spare
2 Rating-HP and kV and select MFR details
3 Model-Impedance(Xd’’,Xo,Xd,X2,X/R)
7 Static Load 1 Status- Continuous , Intermittent or Spare
2 Rating-kV, MW, Mvar and PF
8 Lump Load 1 Status- Continuous , Intermittent or Spare
2 Ratings- kV, MW, Mvar and PF
3 Load Type-Motor Load or Static load
9 Cable 1 Length in ft/m/mile/km
2 Cable Type- Size, Insulation, kV and #/Cable
3 Impedance/conductor-Positive sequence
8 Transmission Line 1 Length in ft/m/mile/km
2 Parameter-Phase conductor
3 Impedance per phase-positive sequence
9 MOV 1 Rating-HP, kV and rated Torque
10 Protective Devices 1 Circuit Breakers-Rated kV, Amps, Interrupting kA
2 Fuses-Rated kV, Size, Amps, Interrupting kA
3 Switches-Rated kV , BIL ratings and amps
4 Contactors- Rated kV, Interrupting kA and amps
11 Capacitor 1 Status- Continuous , Intermittent or Spare
2 Rating-kV, Max kV, Mvar Bank and No of Banks
12 Impedance 1 Rating-Amps and kV
2 Impedance- Positive sequence Z and X/R