In the locked-rotor measurement, the current is measured at different supply voltage levels, and, based on that, the rated starting current is scaled to the rated voltage.. According to
Trang 1Scaling procedures for starting current measurements
B Y W A Q A S M A R S H A D ,
S A M I K A N E R V A ,
S I L V I A B O N O ,
M A S S I M O M E N E S C A R D I ,
& H O L G E R P E R S S O N
I N THIS ARTICLE, THE ACCURACYlevels of different scaling procedures for
starting current measurements are addressed through the statistical analysis of locked-rotor tests involving hundreds of medium–large induction
machines This is performed to ascertain the confidence level
of the predicted full-voltage starting currents from the reduced-voltage factory measurements, a necessity for motors with a strict tolerance to the starting current level It is shown that, for traditional scaling methods employing only measurements, this accuracy level is 88–90% for scaling step from 0.6 to 1.0 p.u voltage This figure could be raised to
Digital Object Identifier 10.1109/MIAS.2010.938385
© CREATAS
28
Trang 295–97% through a novel method that
also uses finite element method (FEM)
simulations for each individual test
volt-age The differences between FEM and
voltage measurements are documented
and used for correcting the full-voltage
FEM simulation Further, the use of
FEM is shown to help in the
understand-ing of the causes and locations of
measured voltage-dependent saturation
uncertainties The region (end-core,
over-hang, or main core) that contributes
the most to saturation uncertainties
is shown to be identifiable through
origin/parametric dependencies, leading
to a better product understanding and
more reliable scaling methods in future
Starting Currents in
Induction Machines
Starting current levels for a direct-online,
single-cage induction motor are typically specified to be four
to seven times the rated motor currents (4–7 p.u.) [1] These
figures are for medium–large induction motors, whereas these
values can be as high as 10–12 p.u for smaller motors
Start-ing currents of the delivered motors must usually follow one
of the following:
n the International Electrotechnical Commission (IEC)
60034-1 [2], allowing a 20% tolerance margin
n the National Electrical Manufacturers Association
(NEMA) MG1 standard [3], specifying tolerances
according to kilovoltampere per horsepower
n the customer specifications, defining individual
tolerance or absolute figures, e.g., in chemical oil
and gas sector:
nthe Shell Design and Engineering Practice (DEP)
33.66.05.31 [4] or American Petroleum Institute
(API) 541 standard [5] that requires a starting
current without tolerances, e.g., below 6.5 p.u
for medium-voltage motors
The Trend for Low-Inrush Current Motors
Recently, the demand for low-inrush current motors has been
slowly increasing because the starting current is typically less
than 5 p.u., and no tolerance margin is accepted between the
specification and delivered motor (referred below as
zero-tolerance designs) Marine, offshore petrochemical, and, in
general, all industry connected to a weak grid are
increas-ingly demanding such direct online solutions Costs, weight/
space requirements, and complexity are some of the factors
that rule out the use of alternative solutions, such as
soft-starters, transformer-starting, and converter-start [6] The
zero tolerances impose stringent demands upon exact
knowl-edge of all steps of the motor manufacturing process
Factors Affecting Starting Currents
The inductance of a machine and its variation during
startup roughly define the starting current for a given
applied voltage The inductance is generally divided into
three distinct regions: subtransient, transient, and steady
state The inductances are influenced by a number of motor
geometrical details as well as materials The starting currents
during the design stage can thus be influenced [6]–[12] by the following geometrical and physical parameters:
n Stator design: number of turns, end-windings layout, core length, and slot geometry
n Rotor design: slot dimensions, bar profile, and material
n Frame design: end-ring shield-ing, etc
The trade-offs between other per-formance parameters such as starting and breakdown torque, rated efficiency, and power factor also need to be con-sidered when limiting the inrush cur-rent during the design stage The mechanical and thermal limits of the structure also need to be taken into account [10]–[14]
Design Parameters Accuracy
Since all the manufactured motors need to be tested before delivery, in addition to the design effort, the emphasis is on (especially for zero-tolerance designs):
n design parameters accuracy
n measurements accuracy
n scaling accuracy
The accuracy level of the design parameters primarily depends upon the production site history that has been achieved through years of experience of machine modeling (reluctance networks, equivalent circuits, and FEM analysis), statistically calibrated against measurements on prototypes and delivered products Skin effect, iron saturation, and inductances modeling are some of the key parameters that define the true starting performance of an induction motor
Locked-Rotor and Run-Up Measurements
The starting current measurement is carried out by either locked-rotor or run-up methods The accuracy of the measure-ment is influenced by the test engineers’ experience and care, rotor position, and temperatures in the stator and rotor
In the locked-rotor measurement, the current is measured
at different supply voltage levels, and, based on that, the rated starting current is scaled to the rated voltage IEC 60034-1 [2] defines the locked-rotor current as the greatest steady-state, root-mean-square current taken from the supply with the motor held at rest, over all angular positions of its rotor,
at rated voltage and frequency According to IEEE 112-2004 [15], for this test, when possible, the measurements shall be taken at rated voltage and frequency since the current is not directly proportional to the voltage because of changes in reactance caused by saturation of the leakage paths
In the run-up measurement, the motor is started by reduced voltage, and the measured starting current is scaled to the rated voltage Usually, the motor is rotating slowly in a backward direction before startup (reverse-rota-tion start) to obtain the current at zero speed by the time the supplied electromagnetic transients have decayed
Scaling
When the full-voltage test is not possible on the factory test floors (e.g., for the largest induction machines) or when
THE DIFFERENCES BETWEEN FEM AND VOLTAGE MEASUREMENTS
ARE DOCUMENTED AND USED FOR CORRECTING THE FULL-VOLTAGE FEM SIMULATION.
29
Trang 3the maximum allowable stall-time limits full-voltage tests,
the reduced-voltage test is applied In this case, the
start-ing current is extrapolated from the reduced-voltage
measurements, a method commonly known as voltage
scal-ing In such cases, not only the measurements themselves
but also the accuracy of scaling methods (full-voltage
cur-rents prediction from reduced-voltage measurements)
attains vital importance For run-up tests, the same scaling
methods may be used as in the locked-rotor test
Accuracy of Scaled Measurement Results
As will be discussed later, the traditional scaling methods,
including those presented in [15] and [16], have a degree
of uncertainty Sometimes, factory acceptance tests (FATs)
provide scaled starting current levels that are not a true
representation of the motors’ actual starting behavior
Documented experience from many years reveals that even
though there may be occasional complaints for scaled results
predicted by FATs, seldom have such complaints been raised
during commissioning or the normal operation of the
motors This indicates that scaling would only cause the dif-ferences between measured results and design values Figure 1 shows the authors’ perception regarding uncertainties asso-ciated with the starting currents A careful benchmarking procedure by the authors on a few hundred machines has singled out scaling as the biggest factor associated with the full-voltage starting currents accurate prediction
Outline and Scope of the Study
This section presents the details of the work conducted by the authors regarding scaling The study covers a vast range of direct-online induction motors (taken from the list
in Table 1) Five to eight locked-rotor measurement results for each individual machine, all at different voltage levels, are used The following are the topics addressed:
n accuracy evaluation of the traditional scaling
n presentation of the novel combined FEM-measure-ments scaling method
n confidence-level evaluation of the aforementioned method based on statistical analysis
n insight into starting currents saturation physics by studying parametric dependencies
Issues such as repeatability, reliability, and test-conditions influence (e.g., ambient temperature and hot or cold motor) are addressed This is done through new measurements on 50 motors and the utilization of earlier documented measurement results of a few hundreds of randomly selected motors This vast amount of measured data allows the separation of measurement uncertainties from those of scaling procedures In this study it
is revealed that no significant differences exist between the measured values of locked current and run-up starting currents Hence, the analysis in the following sections is restricted to locked-rotor tests only Since the present study deals with vol-tages at machine terminals, the role the network impedance plays is not significant and is omitted from the study
The FEM approach is introduced as an alternative to traditional scaling methods that employ only measure-ments Thus, two new scaling methods that, in addition to measurements, employ FEM simulations are studied Since the FEM models use the true hysteresis (BH) iron curve for
Design (1–2)%
Measurements (1–3%)
Slip
0
Starting Currents Uncertainty
Scaling (1–15%)
1
Different accuracy bands for the full-voltage starting
currents The arrows show distinct regions corresponding to
the design and measurements uncertainty.
TABLE 1 MACHINE DATA.
IC516
Data might differ according to machine type.
30
Trang 4modeling saturation, at least theoretically, it was believed
that the FEM should be able to provide a better picture of the
saturation at the full-voltage conditions in the machine than
through one of the traditional empirical extrapolation
meth-ods that are based only on measurements Unfortunately,
experience showed that even FEM simulations required some
sort of calibration/tuning to achieve the acceptable
confi-dence level in absolute terms Two such calibration
approaches are presented and discussed
Traditional Scaling Methods
Description of the Methods
Traditional scaling methods rely only on measurements
These include the methods presented in literature [17] as
well as those recommended by standards such as IEEE
112-2004 [15] and IEEE 115-1995 [16] The locked-rotor tests
are made for maximum available test room voltages The
onset of saturation and its dependency upon the test voltage
is captured through various curve-fitting techniques of the
three to six available measurement results The full-voltage
current is obtained through an extrapolation procedure The
accuracy of the result is based on the employed curve-fitting
technique, the maximum test voltage, and the number of
tests Usually, reference to any physical dependencies and
design factors is not explicitly made Some of these methods
that have been studied by the authors are listed below:
1) The current is calculated as varying directly with
voltage (1), with the exponent k¼ 1 (IEEE 112-2004
[15]) and then the full-voltage current is corrected
based on a certain rule of thumb (experience-based)
correction factor
Inom¼ Imeasured
Unom
Umeasured
k
, (1)
where Inom is the nominal current, Unom is the
nominal (rated) voltage, Imeasured is the measured
current, and Umeasured is the measured voltage
2) A more exact method (log–log) requires two
measure-ment points, and the exponent k in (1) is calculated
according to (2), IEEE 112-2004 [15]
k¼ log(Imeas1=Imeas2)= log(Emeas1=Emeas2), (2)
where E is the electromotive force that is
some-times approximated with the supply voltage U
3) IEEE 112-2004 [15] also states that, for better
accu-racy, a least-squares fit should be used when
deter-mining the scaling exponent k (2) This requires
multiple reduced-voltage test points
4) IEEE 115-1995 [16] instead suggests a semilog fit
Inom(Unom)¼ ef2(Unom), (3) where e is the base of natural logarithms (log) and
f2(Unom)¼ Unom Umeas1
Umeas2 Umeas1
3log Imeas2
Imeas1
þ log(Imeas1): (4)
5) A saturation factor approach is based on estimating the saturation factor (ksat) from tests and, conse-quently, predicting the full-voltage current from
Inom¼ Imeasksat(Unom=Umeas), (5)
ksat ¼ (Imeas2=Umeas2)=(Imeas1=Umeas1): (6)
6) An improved saturation factor approach uses a voltage dependence derived from the simple mag-netic circuit approach
NI¼ (Rairgapþ Riron)U, (7)
U / U; Riron/ 1=liron; liron/ 1=Uk: (8)
7) A second-degree polynomial fit of measured data is also considered
A complete onset of saturation is only possible at full voltages, which can be rather difficult to achieve in the tests rooms for many machines The accuracy of the tradi-tional scaling methods, i.e., those based only on measure-ments, is dependent upon the maximum test voltage that
is possible during the measurements (test room supply and motor stall time limitation), as well as on the num-ber of measurements (test room cost and test window limitation) In summary, the extrapolation accuracy of the employed curve-fitting technique is benchmarked in this study
Accuracy Evaluation Through Statistical Analysis
The accuracy of the different scaling methods is evaluated
by comparing the differences between the scaled results obtained from n 1 reduced-voltage measurements and the n:th measurement
1) The studied scaling method is applied on the
n 1 measurements (lowest test voltages), estimat-ing the startestimat-ing current value on the n:th measure-ment point (highest voltage)
2) The estimated value in n:th measurement point is compared with the actual measured value
This is followed by a detailed statistical analysis of these differences for certain sets of studied motors The analysis serves as the basis for defining the confidence level (error margin in terms of mean difference and standard deviation)
of the various studied scaling methods Classification of the motors based on different criteria such as power range, voltage level, and speed is also carried out
Comparative Analysis
The following methods are primarily investigated for benchmarking and also for improving their accuracy with the better curve-fitting techniques
Log–Log, Semilog, and Linear Scaling
The linear fit [the old practice, see 1) mentioned under the
“Description of the Methods” section], the semilog fit [see 4) above] and the log–log fit [see 2) and 3) above] are com-pared first It is found that, of these, the last is the most promising for predicting the full-voltage currents from the reduced-voltage tests Some of these results for synchro-nous motors have been provided in [17] 31
Trang 5The log–log curve fitted
extrap-olation provides the lowest error
to the actual current at
maxi-mum tests voltage This error is
roughly two to ten times better
than the other two approaches
In this comparison, the highest
test-room voltage is treated as
the rated voltage
n A difference of up to 30% in
scaled values is observed when
comparing the log–log approach
[see 3) above] against the linear
approach [see 1) above]
n For the log–log approach, a
spread in scaled results of up to
20% is observed when k (2) is
derived from only two test
points [see 2) above]
correspond-ing to different test voltages
n There is also spread in log–log
estimations when successive highest voltages are
removed from the curve-fitting algorithm The
spread among scaled results is as high as around 5%
in certain cases when at least three test points are
used for the estimation Results with only two test
points have a much greater spread
Log–Log, Saturation Factor, and Second-Degree Fit Scaling
The best of the earlier discussed scaling methods, the log–log
method [see 3) discussed earlier] is consequently compared for
accuracy against a suggested second-degree polynomial fit
[see 7) above] as well as the traditional saturation factor
tech-niques [see 5) and 6) stated earlier] For the studied cases, it is
found that:
n All methods are equally good if the maximum test
voltage is above 0.95 p.u
n For scaled results using 0.6 p.u maximum test
voltage, the differences to actual measured values
are roughly of the same order for all the three
methods The saturation factor method exhibits
the lowest differences band, i.e., 5.5% The
sec-ond-degree fit has a difference band of 6%,
which is slightly below that of the log–log
method of 6.5%
n The differences for the second-degree fit are
ran-dom, whereas for the other two methods, they are
always in the same direction Thus, the log–log fit
is always predicting lower than the measured
values, whereas the saturation factor method always predicts higher than the measured values
Accuracy Levels
To provide generalized accuracy figures for the investigated scaling methods, a more detailed study was carried out for the log–log, the saturation factor, and the second-degree fit scaling methods Results are provided in Table 2 for a scaling step of 0.4 p.u., i.e., when the maximum test voltage used for scaling
of the results is 0.4 p.u below the maximum available test voltage The scaled results in Table 2 are compared against the maximum available test voltage, which may be lower than 1 p.u For example, when the maximum available test voltage is 0.6 p.u., the estimation at this voltage is made from tests that use a maximum test voltage of 0.2 p.u
The results in Table 2 show that this set of scaling meth-ods have an uncertainty margin of roughly 10% The simpler methods always provide an underestimation, whereas the more advanced ones can provide an overestimation as well
It is found that the error margin of the saturation factor approach (2) decreases more than that of the other ap-proaches, as the scaling voltage step is decreased Still, all these curve-fitting methods depend primarily on the quality
of information embedded in the test data (saturation), the full-voltage scaled results becoming poorer with a decreasing highest test voltage Hence, it can be concluded that the scal-ing methods that are based only on measurements are unac-ceptable for zero-tolerance inrush current design motors FEM Approach 1: Tuning of FEM Models
In the first variant, a two-dimensional (2-D) FEM simulation
is tuned against a reduced-voltage measurement with an expectation that the full-voltage simulation could provide correct results A common understanding is that the uncer-tainties/errors in 2-D FEM simulations are due to the wrong input data fed, such as the end-windings inductances and material properties, to 2-D-FEM models It was believed that such differences could be neutralized by a single calibration against the measurements, achieved through tuning of the input data, such as the end-windings inductances
One such example is provided in Figure 2 Here, the FEM model of a certain machine is tuned against a
reduced-voltage locked-rotor mea-surement through variation of end-winding inductances and material properties However, this approach did not yield the correct full-voltage starting current For a scaling step of 0.45 p.u., an underestimation
by 7% can be observed This error is believed to be due to the influence of three-dimensional (3-D) effects upon saturation (frame region and end-winding
TABLE 2 SCALING THROUGH MEASUREMENTS:
ACCURACY LEVELS FOR A SCALING STEP OF AT LEAST 0.4 PER UNIT.
Scaling Method
Error to
THE FEM APPROACH IS INTRODUCED AS
AN ALTERNATIVE
TO THE TRADITIONAL SCALING METHODS THAT EMPLOY ONLY MEASUREMENTS.
32
Trang 6inductances), which are missed in a reduced-voltage 2-D
tuning endeavor
By considering the starting current (saturation) levels
for other machines, an error figure of 10% was
estab-lished for this method The error margin in this case is
still comparable with the traditional scaling methods
Further, the amount of effort required in the iterative
tuning procedure for each machine in this method makes
it unsuitable for daily factory scaling usage and is not
dis-cussed further
FEM Approach 2: Trends-Based Scaling
In an alternative investigated FEM, for a machine under
consideration, the FEM simulations are carried out
corre-sponding to each of the conducted tests It is found that,
for any given machine, the differences between
measure-ments and FEM simulations have a defined slope when
plotted against the test voltages even when no tuning is
performed Thus, it is possible to predict the full-voltage
starting currents using these differences predicting trends
The full-voltage FEM simulations are run and the
corre-sponding corrections made
Figure 3 shows the differences of FEM simulations to
measurements against test voltage for a certain set of
studied motors Results from both harmonic and
time-stepping FEM simulations are provided It can be seen that
the difference between the FEM simulations and
measure-ments in most cases is not constant but can still be
repre-sented through a straight line having a certain slope This
observation points to the possibility of using the
differen-ces between the FEM simulations and measurements at
reduced voltages to yield linear correction factors (slopes),
which in turn can be used to correct the full-voltage FEM
simulations to provide fairly accurate scaled results
The Analysis Method
The analysis method is investigated for accuracy on 205
different machines Table 3 provides a listing of the
machine types and frame sizes that have been used in the
analysis (full details are provided in Table 1) In the
presented analysis:
The FEM simulations are compared against three reduced-voltage measurements The maximum of these reduced test voltages is around 0.6 p.u
n The slope for the differences between the FEM simulations and measurements is obtained
n The full-voltage FEM simulation results are adjusted based on the slope of the differences and the scaling (voltage) step
n The scaled results are compared against the actual measurements at the highest test voltages
n The results are statistically analyzed according to the mean error and its standard deviation
Accuracy
Results for the differences are summarized in Figure 4 It can be seen that the mean difference is 1.4% and the
Starting Current: FEM to Measured (%)
–20 –15 –10 –5 0 5
0 0.2 0.4 0.6 0.8 1 1.2
Test Voltage (p.u.)
O, Solid Line: Harmonic [], Dashed Line: Time Stepping
Motor 4 Motor 3Motor 2 Motor 1
3
Motor 5 and 6
Starting currents: differences between the FEM and measurements.
TABLE 3 DESCRIPTION OF MACHINES USED IN THE TRENDS-BASED FEM STUDY.
Voltage
Current
0
1
2
3
4
5
6
7
Voltage (kV)
FEM Tuned Measured FEM Original
2
Tuning of the FEM results against the reduced-voltage
measurements.
0.96 0.97 0.98 0.99 1 1.01 1.02 1.03 1.04 1.05 1.06
Starting Current: Difference (p.u.) 0
20 40 60
Measured to Trends-Based FEM Predicted Starting Current Voltage Scaling Step for FEM: 0.4 p u (Mean: 1.01396, Standard Deviation: 0.0123)
4
Statistical summary of differences in starting currents between the highest-voltage measurements and
Trang 7standard deviation is only 1.23% Hence, a 95%
confi-dence level is within the 5% error margin Figure 5 shows
these differences against the maximum available test
volt-age For a test voltage higher than 0.5 p.u., the differences
are within 3% Further, some of the cases could be clearly
identified to be outliers due to special test conditions, FEM
input data error, measurements errors, etc Hence, for all
practical cases, the 95% confidence level for the discussed
method is within a 3% error margin This error in scaling
is realistic even for zero-tolerance designs with a certain
built-in acceptable design margin
In the discussion earlier, the trends (slopes) used to
cor-rect the FEM simulations used only three test results To
benchmark an improvement in accuracy possible with
further tests, the aforementioned results are compared
against a case in which the trends (slopes) are determined
with five test points (Figure 6) From Figure 6, it can be seen
that the results for the three test-point cases are
underesti-mated, and a significant deviation exists between the
three-test-point and five-three-test-point cases Hence, it can be seen
that even this method is sensitive to the number of test
points, and a recommendation is to use as many test results
as possible From Figure 6, it is found that most results
belonging to the cases that are left and right of the center
column had either test points that were too close or some of
the results for the lowest test voltages were questionable
Hence, other recommendations are that the test should be as
separated as possible in terms of test voltages, and extreme
care is needed when making the lowest voltage tests
Comparison to the Traditional Methods
One of the aims of this work had been to determine the full-voltage starting current values when actual tests could only be possible with reduced voltages Figure 7 compares the differences in the full-voltage estimated results between the trends-based FEM and various traditional methods The newly suggested method has a maximum spread of 17% to traditional methods The overestimation, underestimation, or mixed behavior of the traditional scal-ing methods can also be witnessed
Origins of Uncertainty
In this section, the differences between the measurements and FEM are discussed in relation to the saturation behav-ior of the machines
Possible Reasons for Differences
The differences between FEM simulations and measure-ments are generally believed to be due to the following:
n the inaccuracies in the input data to FEM, e.g., end-windings inductances and material properties (BH curves and resistances)
n manufacturing tolerances and related deviations
n 3-D-effects approximations in the 2-D-FEM models
Of these, issues such as manufacturing tolerances are in general not voltage dependent, whereas others such as the saturation are known to be dependent upon voltages The iron saturation affects mainly the inductance related to the active length of the machine but does impact the end region/end-winding inductances as well (based on machine design, e.g., aspect ratio) Other parameters, such as the end-winding inductances and rotor resistances, that are sometimes treated as constants in the 2-D-FEM tools have also been found to vary with the voltage For example, the authors have found that the end-windings inductance dur-ing the start has been found to be considerably dependent upon the saturation of the end-core region
During a direct online start, the inrush current is limited by the stator leakage inductance An increasing applied voltage means a higher flux in the machine This
0.3 0.4 0.5 0.6 0.7 0.8 0.9
Maximum Test Voltage –10
–5 0 5 10
Method A Method B Method C Method D Method E Method F
Method G
7
Difference in scaled full-voltage currents: trends-based FEM against various traditional scaling methods (marked as different patterns).
0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65
Maximum Test Voltage –10
–5
0
5
10
5
Differences in starting currents between the highest-voltage
measurements and trends-based scaling against the
scaling (voltage) step.
–8 –6 –4 –2 0 2 4 6 8 10 Starting Currents Differences: Three Tests
Against Five Tests 0
50
100
6
Distribution of the difference between full-voltage starting
currents (in p.u.) derived from compensating slopes with three
and five tests (mean: 0.839, standard deviation: 1.312).
34
Trang 8will cause certain iron regions in the
machine to saturate and will cause the
inductance to decrease Thus, the stator
current in the machine will increase more
than what would have been expected
through a linear correlation to maintain
the corresponding flux in the machine
Investigations show that the FEM
results are almost always lower than the
measured values, as illustrated in Figure 3
The following are the possible reasons
for lower currents in the FEM
simula-tions than those in measurements
n The lamination materials used
in the machines are found to
have generally lower losses than
those provided in the specification
and, hence, originally assumed
for calculations [18] Reduced
iron losses usually mean also poorer BH curve due
to more silicon and less iron
n The end-winding inductance that is input to the
FEM simulations usually represents the operating
conditions at rated slip At locked-rotor conditions,
high starting currents occur, which are known to
decrease the windings inductances due to
end-core saturation and, hence, higher than expected
currents result during measurements
Interpretation of Different Slopes
Figure 3 also shows that trends (slopes) for differences
between the FEM and measurements vary
A positive slope shows that the saturation model in the
FEM is tuned to fit the rated conditions and is
underesti-mated at lower voltages The input parameters to design
tools are generally calibrated for the full-voltage rated
con-ditions In case of the FEM, the modeled BH curves (for
this particular study) had been calibrated after the knee,
and hence, less saturation in the FEM simulations than in
reality is witnessed at lower voltages (operation in the
region below the knee) In such a case, the end-winding
inductance can be believed as independent of voltage, and
the change in the offset can be primarily due to the
satura-tion of the main core, the 2-D phenomena
A negative slope shows that the difference in the
cur-rents increases as test voltages are increased This means
that the measurements are showing a higher saturation of
the core than that modeled in the FEM with an increasing
voltage This is either because of the onset of saturation in
the end core region, which decreases the end-winding
inductance, or an increased saturation of the 2-D geometry,
which decreases the slot and differential leakage
inductan-ces The end result is an increase in the measured current
when compared with FEM
A zero slope indicates that the saturation model in the
FEM is acceptable, and the difference is due to a wrong
input parameter in the FEM In this case, the
end-wind-ings inductance can be said to be constant
2-D (Tooth-Tip/Airgap) or 3-D (End-Region) Saturation
As stated earlier, a higher saturation in reality than that
modeled by the FEM is believed to be the reason for the
negative slopes in Figure 3 This can
be either because of the saturation of the end core that affects the end-wind-ings inductance (3-D phenomena) or a higher than expected saturation of the teeth tips (due to flux paths in the air gap and surroundings) and effecting slot/differential leakage (2-D phenom-ena) It can also be the case that both phenomena are present with one being more dominant than the other It is found that this dominance can be observed by
n the slopes’ dependencies upon the pole number
n the slopes’ dependencies upon the aspect ratio (core length/air gap diameter)
End-Region Saturation
End-region saturation is due to 3-D effects, which would be dominant for machines having a low aspect ratio (short machines with a high shaft height) and/or for machines having a low pole number (greater end-windings overhang)
Tooth-Tip Saturation
Tooth-tip saturation is due to 2-D effects, which would be dominant for machines having a high aspect ratio (long machines with a low shaft height) and/or for machines hav-ing a high pole number The 2-D leakage increases with the pole number
Findings
The following are the saturation uncertainties findings
n For all the studied groups of machines, the slope magnitudes always decreased with the pole num-ber This showed that the end-winding overhang is directly proportional to the saturation of the end region (frame, end-core, shaft, etc.) and, hence, the uncertainty in the 2-D FEM models
n The trend against the aspect ratio varies when the machines with only negative slopes are considered For the smaller machines, the end-core saturation (3-D leakage) is found to be predominant, whereas for the bigger machines, it is the main core satura-tion (2-D leakage) that is found to have the big-gest influence
Figure 8 shows the slopes of discussed differences against the aspect ratio (core length/air gap diameter) and pole number for certain particular groups of machines In Figure 8, (a) shows a group for which the core-end saturation is dominant (3-D/end-winding-leak-age), (b) shows another group for which the main core saturation is dominant (2-D/tooth tip, zigzag leakage) instead, and (c) shows a group for which the end-region (frame/end-plate) saturation is dominant (3-D/end-wind-ing leakage) In Figure 8(c), the decrease in slopes with the pole numbers reflect the fact that the end-windings overhang decreases with the pole number This group may also simultaneously exhibit the behavior of either Figure 8(a) or (b) as well
THE LOG–LOG CURVE FITTED EXTRAPOLATION PROVIDES THE LOWEST ERROR
TO THE ACTUAL CURRENT AT MAXIMUM TESTS VOLTAGE.
35
Trang 9Uncertainties associated with the scaling of starting
cur-rents have been studied through a detailed statistical
analy-sis of hundreds of medium–large induction machines The
various traditional scaling methods using only
measure-ments are evaluated for their accuracy This figure is found
to be 88–90% for the individual studied methods Thus, it
can be stated that FATs that employ scaling to predict the
rated-voltage starting currents are not always accurate and
merely provide an indication of the starting current level
The introduced FEM and measurements-based novel
scaling method is shown to fulfill an accuracy level of up to
97% for a voltage scaling step of 0.35 p.u The value
decreases to 95% for a scaling step of 0.45 p.u The
differ-ences between the FEM simulations and the measurements
are found to be increasing, decreasing, or remaining
unchanged with an increasing test voltage The differences,
which are almost always negative, are due to the incorrect
prediction of saturation levels by the FEM By observing certain parametric dependencies, it is shown that it is pos-sible to locate the region that contributes the most to this saturation modeling uncertainty, i.e., tooth/air-gap region, end-region (frame/end-shield), and end-core region References
[1] C Sadarangani, Electrical Machines Stockholm, Sweden: Royal Insti-tute of Technology, 2000.
[2] Rotating Electrical Machines—Part 4: Methods for Determining Synchronous Machine Quantities from Tests, IEC Standard 60034-4, 2008.
[3] Motors and Generators, ANSI/NEMA MG Standard 1-2003.
[4] Electrical Machine—Cage Induction Types (amendments/supplements to IEC 60034-1 Rotating Electrical Machines, Part 1: Rating and Performances 2010), Shell DEP Standard 33.66.05.3-Gen, 1999.
[5] Form-Wound Squirrel-Cage Induction motor—250 Horsepower and Larger, API Standard 541, 1995.
[6] T A Gallant and P J Tavner, “Low starting current cage induction motors for the offshore petrochemical industry,” in Proc IEE Power Electronics Machines and Drives Conf., Bath, U.K., Apr 2002, pp 387–391 [7] J Bredtthauer and N Struck, “Starting of large medium voltage motors: Design, protection and safety,” IEEE Trans Ind Applicat., vol 31, no 5, pp 1167–1176, Sept./Oct 1995.
[8] M R Khan, I Husain, and M F Momen, “Lightly ferromagnetic rotor bars for three-phase squirrel-cage induction machines,” IEEE Trans Ind Applicat., vol 40, no 6, pp 1536–1540, Nov./Dec 2004 [9] O Weingartner, “Asynchronous rotor,” Patent DE3 502 697, June 5, 1986.
[10] D J T Siyambalapitiya, P G McLaren, and P J Tavner, “Transient thermal characteristics of induction machine rotor cage,” IEEE Trans Energy Conversion, vol 3, no 4, pp 849–854, Dec 1998.
[11] T A Gallant and J P Pestle, “The modern design of reliable squirrel cage rotors,” in Proc IEE Electrical Machines and Drives Conf., 1987,
pp 140–144.
[12] G E Parry and J J Middlemiss, “Design and construction to achieve low starting currents on hazardous area motors,” in IEE Colloquium Machines in Hazardous Areas (Dig No 1997/057), Feb 18, 1997,
pp 5/1–5/4.
[13] M R Feyzi and A M Parker, “Heating in deep-bar rotor cages,” IEE Proc Electr Power Applicat., vol 144, no 4, pp 271–276, July 1997 [14] M F Cabanas, J L Ruiz Gonzalez, J L B Sampayo, M G Melero,
C H Rojas, F Pedrayes, A Arguelles, and J Vina, “Analysis of the fatigue causes on the rotor bars of squirrel cage asynchronous motors: Experimental analysis and modeling of medium voltage motors,” in Proc 4th IEEE Int Symp Diagnostics for Electric Machines, Power Electron-ics and Drives (SDEMPED’03), Aug 24–26, 2003, pp 247–252 [15] IEEE Standard Test Procedure for Polyphase Induction Motors and Genera-tors, IEEE Standard 112-2004.
[16] IEEE Guide: Test Procedures for Synchronous Machines, IEEE Standard 115-1995.
[17] W Arshad, C Danielsson, H Persson, H Lendenmann, and J Ha¨gg,
“Rated starting performance of solid-pole salient synchronous motors from reduced voltage factory tests,” in Proc IEEE Industry Applications Society Petroleum and Chemical Industry Committee (PCIC’07), Calgary, Alta, 2007, pp 1–10.
[18] W Arshad, T Ryckebush, F Magnussen, H Lendenmann, and A Boddeflack, “Incorporating laminations processing and electrical machines manufacturing steps in design tools,” in Proc IEEE Industry Applications Society Annual Meeting, New Orleans, LA, Sept 2007,
pp 94–102.
Waqas M Arshad (waqas.arshad@se.abb.com) is with the ABB Corporate Research in Raleigh, North Carolina, and Va¨stera˚s, Sweden Sami Kanerva is with ABB Oy, Electrical Machines in Helsinki, Finland Silvia Bono and Massimo Menescardi are with the ABB SACE in Vittuone (Milan) Italy Holger Persson is with ABB Automation Products/ Machines in Va¨stera˚s, Sweden Arshad and Kanerva are Mem-bers of the IEEE This article first appeared as “Medium–Large Induction Machines Starting Currents: Scaling Accuracy & Sat-uration Uncertainties” at the 2007 IAS Annual Meeting
Aspect Ratio: Core Length/Airgap Diameter (Arbitrary Values)
Aspect Ratio: Core Length/Airgap Diameter (Arbitrary Values)
Pole Number (Arbitrary Values)
(a)
(b)
(c)
8
Finding saturation uncertainties origin from parametric
dependencies (x, y, and z are arbitrary numbers) Various
grouping of machines: (a) unexpected saturation dominant
in the core-end region (3-D/end-winding leakage); (b)
unexpected saturation is dominant in the main core region
(2-D/tooth tip and zigzag-leakage); (c) unexpected
saturation is dominant in the end (frame/end-plate) region
(another contributor to the 3-D/end winding-leakage).
36