Publication 1756-IN574B-EN-P - May 2001

ControlLogix Redundant Power Supply

Chassis Adapter Module

Catalog Number 1756-PSCA

Use this publication as a guide when installing the ControlLogix™

1756-PSCA chassis adapter module

The 1756-PSCA power supply chassis adapter module is a passive device designed to funnel power from one or two ControlLogix redundant power supplies to the single power connector on the ControlLogix Series B chassis (Series B only) backplane

The redundant power supply system provides additional uptime protection for chassis used in critical applications The two

remotely-mounted supplies are designed to share the current required by the chassis and are available in AC and DC versions that can be mixed or matched when used in tandem

See an Overview of the Installation Process 2 See the European Communities (EC) Directive Compliance 3 Identify the Components of a Redundant Power Supply System 4 Recognize Chassis Adapter Module Physical Features 5

Connect the Chassis Adapter Module to the Redundant Power Supplies 9

See the Hazardous Location Information 13

Trang 2

In the event of a failure by one power supply, the remaining supply will accommodate the entire load of the chassis without disruption to chassis activity For more information on the 1756-PA75R/A or 1756-PB75R/A redundant power supplies, see publication

1756-IN573

Overview of the Installation Process

Follow these steps when installing and powering your redundant power supply chassis adapter module

1 Install the Chassis Adapter Module

2 Connect the Chassis Adapter Module to the Redundant Power

Supplies

The steps are described in detail, along with other important information, throughout this installation instructions

ATTENTION

!

Electrostatic discharge can damage integrated circuits or semiconductors if you touch backplane connector pins Follow these guidelines when you handle the 1756-PSCA

• Touch a grounded object to discharge static potential

• Do not touch the backplane connector or connector pins

• If available, use a static-safe work station

• When not in use, keep the power supply in its static-shield packaging

Trang 3

Publication 1756-IN574B-EN-P - May 2001

European Communities (EC) Directive Compliance

If this product has the CE mark it is approved for installation within the European Union and EEA regions It has been designed and tested to meet the following directives

EMC Directive

This product is tested to meet the Council Directive 89/336/EC Electromagnetic Compatibility (EMC) by applying the following standards, in whole or in part, documented in a technical

construction file:

• EN 50081-2 EMC — Generic Emission Standard, Part 2 — Industrial Environment

• EN 50082-2 EMC — Generic Immunity Standard, Part 2 — Industrial Environment

This product is intended for use in an industrial environment

Low Voltage Directive

This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2

Programmable Controllers, Part 2 - Equipment Requirements and Tests For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the Allen-Bradley publication Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Open style devices must be provided with environmental and safety protection by proper mounting in enclosures designed for specific application conditions See NEMA Standards publication 250 and IEC publication 529, as applicable, for explanations of the degrees of protection provided by different types of enclosure

Trang 4

Identify the Components of a Redundant Power Supply System

The components are shown below in a typical system configuration:

1756-PA75R and/or

1756-PB75R

Redundant power supply 2

supply cables (Length = 0.91m [3ft])

2

1756-PSCA Redundant power supply

chassis adapter module

1

User-supplied1 Annunciator wiring

(Maximum length = 10m [32.8ft])

2

1 Optional user-provided annunciator wiring can be connected to the solid state relay on the supplies for status and troubleshooting purposes For more information, see the Redundant Power Supply installation instructions, publication 1756-IN573.

1756-PA75R/A 1756-PA75R/A

1756-CPR

1756-PSCA

42655

Annunciator wiring

Trang 5

Publication 1756-IN574B-EN-P - May 2001

Recognize Chassis Adapter Module Physical Features

Your power supply chassis adapter module has multiple physical features as shown below

Physical Feature Description

Diagnostic status indicators There is a power indicator For more information on

the status indicators, see page 10.

Cable connector The cable connectors accommodates the female end

of the 1756-CPR cable For more information, see page 9.

Diagnostic status indicator

Cable

connectors

42683

Trang 6

Determine the Chassis Widths

The graphics below list the width of each ControlLogix chassis type with a redundant power supply chassis adapter module installed For more mounting information, see the ControlLogix Chassis installation instructions, publication 1756-IN080

18.54cm (7.3in)

1756-A4

1756-A7

29.04cm (11.44in) 42836

42835

7.0cm (2.76in)

17.5cm (6.89in)

15.8cm

(6.22in)

15.8cm

(6.22in)

Trang 7

Publication 1756-IN574B-EN-P - May 2001

1756-A10

40.54cm (15.96in)

1756-A13

51.04cm (20.1in)

1756-A17

66.04cm (26.0in)

42839 42838

42837

14.0cm (5.51in) 14.0cm

(5.51in)

14.0cm (5.51in)

14.0cm (5.51in) 10.5cm

(4.13in)

14.0cm

(5.51in)

13.3cm (5.24in)

14.0cm (5.51in)

13.3cm (5.24in)

15.8cm

(6.22in)

15.8cm

(6.22in)

15.8cm

(6.22in)

Trang 8

Install the Chassis Adapter Module

The chassis adapter module must be inserted on the leftmost side of a ControlLogix chassis Follow the steps below to install the module

1 Align the right side of the chassis adapter module with the left

edge of the chassis

2 Push the module on to the chassis until the locking tabs click.

42669

42670

Trang 9

Publication 1756-IN574B-EN-P - May 2001

Connect the Chassis Adapter Module to the Redundant

Power Supplies

Use the 1756-CPR cables to connect your chassis adapter module to your redundant power supplies

1 Leave a minimum of 4 in (10.2 cm) space between the left side

of the chassis adapter module and the cabinet housing your control system The 1756-CPR cable will not connect to the module in less than 4 in (10.2 cm) of space

2 Connect the cable to the chassis adapter module.

ATTENTION

!

Make sure the redundant power supply is turned off before connecting the 1756-CPR cables to the chassis adapter module or the power supply

31176-M

Trang 10

3 Connect the cable to the redundant power supply.

4 Tighten the screws to hold the cables in place Make sure you

completely tighten the cable screws to hold the cable in place for the life of the product

Troubleshoot the Chassis Adapter Module

Your chassis uses a green status indicator (LED) to display when power is applied to the chassis

• If the indicator is lit up, the chassis is receiving power from one or both of the redundant power supplies

• If the indicator is OFF, the chassis is not receiving power from the redundant power supplies In this case, check the power supplies for a reason

WARNING

!

EXPLOSION HAZARD

When used in hazardous area, do not attempt to connect or disconnect cables unless power has been removed, or the area is known to be nonhazardous

31174-M

Trang 11

Publication 1756-IN574B-EN-P - May 2001

Replace the Chassis Adapter Module

If you must replace a chassis adapter module, follow the steps below

1 Turn power off at the redundant power supplies.

2 Disconnect the redundant power supply cables from the

chassis adapter module

3 Push the top and bottom locking tabs on the chassis adapter

module to the side

4 Pull the module off the chassis.

5 Install a new chassis adapter module For more information,

return to page 8 of this document and follow the directions

42671

42672

Trang 12

1756-PSCA Specifications

Additional Information and Notes

The ControlLogix system must be mounted within a suitable enclosure to prevent personal injury resulting from accessibility to live parts The interior of this enclosure must be accessible only by the use of a tool

This industrial control equipment is intended to operate in a Pollution

Location ControlLogix chassis

Maximum Electrical Ratings 1.5A @ 1.2 V

4A @ 3.3 V 15A @ 5.1 V 2.8A @ 24 V Cable Assembly 1756-CPR (Length = 0.91m [3ft])

Dimensions (W x H x D) 3.4 x 15.1 x 14.4cm (1.34 x 5.95 x 5.67in)

Weight - approximate 0.45 kg (16 oz)

Environmental Conditions

Operating Temperature

Storage Temperature

Relative Humidity

0 to 60°C (32 to 140°F) -40 to 85°C (-40 to 185°F)

5 to 95% noncondensing Agency Certification

(when product or

packaging is marked)

Marked for all applicable directives Approved Class I, Division 2, Group A, B, C, D

Marked for all applicable acts N223

UL Listed Industrial Control Equipment for use in Class I, Div 2 Hazardous Locations

UL Listed Industrial Control Equipment For Use In Hazardous Locations, Certified For Canada

UL Listed Industrial Control Equipment Certified Process Control Equipment Certified Class I, Division 2, Group A, B, C, D

Trang 13

Publication 1756-IN574B-EN-P - May 2001

defined in IEC publication 664A, at altitudes up to 2000 meters without derating

Hazardous Location Information

The following information applies when operating this equipment in hazardous locations:

Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time

of installation.

WARNING

!

EXPLOSION HAZARD

• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

• Substitution of components may impair suitability for Class I, Division 2.

• If this product contains batteries, they must only be changed in an area known to be nonhazardous.

Trang 14

Informations sur l’utilisation de cet équipement en environnements dangereux :

Les produits marqués « CL I, DIV 2, GP A, B, C, D » ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux Lorsque plusieurs produits sont combinés dans

un système, le code de température le plus défavorable (code de température

le plus faible) peut être utilisé pour déterminer le code de température global

du système Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.

AVERTISSEMENT

!

RISQUE D’EXPLOSION

• Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l’équipement.

• Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs Fixer tous les connecteurs externes reliés à cet équipement à l’aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe 1, Division 2.

• S’assurer que l’environnement est classé non dangereux avant de changer les piles.

Trang 15

Publication 1756-IN574B-EN-P - May 2001

Ngày đăng: 05/06/2015, 17:18

TỪ KHÓA LIÊN QUAN

TÀI LIỆU CÙNG NGƯỜI DÙNG

TÀI LIỆU LIÊN QUAN

w