pressure may cause simultaneous adjustment of fan speed and 'damper opening to change the airflow, and pu~ speed and valve opening to control the flow of fu&: all.. a change in steam pre
Trang 1FIG 8- PRESSURE DROP VS CAPACI'N FOR A 'NPICAl BUlTERFlY VALVE MAXIMUM OPENING
ANGLES SHOWN 'ARE USEO AS TRIAL SETTINGS WHEN AOJUSTING VALVES FOR HtGH FIRE
sure regul!'llor oullel pre,ssure by O~ in \Of<: to allow for the
additional pressure drcp across the 2 inch SSQVs
This requires estimating a new pressure dfcp for the
pressure regulator SSOVs and Firing Rate Control, plus
repealing the sizing procedure
SIZING CHART FOR FIRING RATE
CONTROL VALVE
Butterfly Valves are otlen used for Firing Rale Control
Valves SinCe a Butterfly Valve ctleS no! provide light clo
sure, a safely shutoff can!rol valve (SSOV) must be used
l4)slream
Inaddilion 101M buUerlly control valve size, we neeO 10
know lhe mallimum QQenino angle (in degrees) U'OOd as a
trial selting when adjusting a BUllerfly Valve to hi~ fire
In our ellample the eslimaleO pressure drq:J across the
liring rate control is 6.5 inches wC wilh a capaCity of 10,500
cfh at standard conditions
a If SSOV estimaled <md actual pressure drop are lha
~ Mark the intersection oflhe estimated Butterfly Valve pressure drq:J and capacity, X on Fig 8 Use Ihe valve size and opening angle indicaled IYy
lhe nearest slanted line below X In this case, ar;ply· ing the estimated pressure drq:J results 'n a 2 inch valve wHh a mallimum opening angle at 45 degrees
b If SSOV aclual pressure droo is less than lbe esli· malad pressure droo
Add lhe pressure drq:J difference (0.8 inch we) to the pressure Orq:J available for the Bullerlly Valve
0.8 + 6.5 '" 7.3 in we
Mark the intersection 017.3 in wc and lhe capacity
y, Use the valve size and opening angle indicated by lhe nearest slanteO line below In lhis case, we have a 2 inch valve with a 40 degree opening
Trang 2V5055 VALVE SIZING NOMOGRAPH
Non, II ",,",.1 ' "1'0.,10< " " 0."1 ,,~ o J Dr I G) ''0'" ··C~" ~ '0
,k'Q , , _ on• •nd , ' " "t ,~ .1'r " D'QQ·· c -" _, I,.," ,.<h "" '0
0 ',n 0 ',,,,,,.I,, _ ··S «'« <;",,' II_ )-l"
r:o, ',Qn" '0 ' ""'d "Clh G_ fh :· Dr I;., ~ ''0"' "B.,n", Clh," 'h,,,,,"
D.,.,,,,,, 'J) ,.Q ·" .<,(OO.~.,,'"'··O' '"_ , "oeM 01 101 " d I,,,, @ , 1
So ,'· _ _ "",n' "II, bo,_.n , , .>0 ,i,,,.
, _ '~"""'''Q_ aI t,"" (!)
·· C",·· ,.t ,'h' t" ,
The correct size V505 5 Industrial Gas Valve can be quiCkly selected usinog this nomograph The nomograph is available in pads at 25 under form number 70-86.27
Tha 1oll0winog 8)(amples show how to use the VS055 Valve Sizing Char1
2 Valves Piped in Series
Regulator Outlet Pressure - Piping Pressure Drcp
= V5055 Inlet Pressure 27.6 in we - 1 In we = 26.6 in WC
2 Determine tile oullel pressure for V5055 The outlet pressure equals lhe inlel pressure minus the pressure drcp across the valve
71·97558-1
Trang 3NOTE: Since we calculated the corrected capacity
under standard conditions, 10,370 cfh we can skip
lines 1 and 2 In lhe 1,'5055 Valve Sizif'l;l Chart
direcllol"6
3 Draw line 3 from 14.6 inches we on the Outlet Pressure
scale 10 12.0 Inches we on the Pressure Prep scale
Since Qutlet Pressure scale is In psi un/Is, multiple 14.6
inches we by (he conversion 1aclor1rom IheAPPENPIX
10 gel the correct psi unl!
14.6 )( 0.0361 = .527 pst Draw line 3 from 527 psi on QVllel Pressure scale \0
12.0 Pressure Droo scale
4 Draw line 4 trom 10,370 cfh on the Burner CFH Gas
Flow caoacity scale through intersection of Ml and line
3, fa the valve site scale 12 inches)
EXAMPLE 2
Determine the 1,'5055 Valve sizQ from lhis job's
5j:lElciflcat ions:
Heat Conlent of Gas 2,500 Btu/cu ft Inlel Pressure Available at 1,'5055 13 Inches wC
Eslimated Pressure Drop
OJtlet Pressure al 1,'5055 6 Inches wc
Trang 4••
SOLUTION
calculate cfh required
7,500,000 Btuh - 2,500 Btu/cu ft '" 3,000 cfh
1 Draw line 11rom 0.64 on "SpecifiC Gravity Correclioo~
'scale 10 3000 on "CFH Gas Flow· scale
2 Draw line 2 tram 1.53 on -SpecifiC Gravity SCare,~
through interseclion of line 1 and M2, 10 • Bl,rrner CFH
Gas Flow." This is the adjuslecl gas 110w
3 Draw line 31rom I) inches we on Outlet Pressure scale
107 inches we on the Pressure Droo scale Since the Outlet Pressure scale is in psi units, mulliply 6 inches
we by Ihe conversion taclor In (he APPENDIX to get psi units
Trang 5CONVERSION TO STAHDARD CONDITIONS
STANDARD CONDITIONS
-"'061 valve sizing charts provide coordinates under a
sal of slandard conditions This allows systematic selec
tion of gas valves for various applications These standard
corditlons are:
1 Capacity - cubiC; feel per hour lcfh) ConverSion 10r
mula on page 14
2 Specific Gravity - 0.64 sp gr
3 AWtude ~~sea level
CONVERT CAPACITY TO 0.64 SPECIFIC GRAVITY
4 Pressure Drop - , inch walEir column (lin we) across valve
These condilionsare seldom fOUnd on an actual job To use the valve sizing charts, we must convert the jd:l condi· lions in this BKample to the equivalent cfh gas rating under the standard conditions
CONVERT CAPACITY IN BTUH TO CFH
CftJ =
Btu/cu
CONVERT CAPACITY TO 0.64 SPECIFIC GRAVITY
HOW TO USE CHART
Listed valve·capaciTy ratino;:; ~re based on O.6'llp gr 9U W})en the required cfh ""pa";I~ is kncwn (or 911 of other
specific <:IfavitY it can be convened to the 0.64 'p g< tQw~al~nt by use of correcl multiplying faclor Obtained from
this charI Example; A nfve capacity of 2670 cfh blwd on 0.72 lp <:If gax is ~C1ui~d_ Whit valve capacity based on
0.64 sP \IT ","S will be nlCluved? Solution: On wrtSul sc.&Ie of chart find 0.72 sp gr From that point, move horitonlillly
10 ri'ilhl 10 intenecl the cUJVe; lhen move Itn.ighl down 10 bottom seale and !ud lhe conversion factor, 1.06
Mwtiply the 2670 cfh by the conve";"n factor: 2670 dh" 1.06 = 2830 d'h
When the raled capaeity of ill ulve ror 0.64 'P \IT gas is 'b1own ilS equivalent Cap'C)ty for 'l"" of other <peeific
gravity may be determined by dlvidinq the raled capacitY by Ihe conversion faclor ElIa~ The rated capacifY
of II cenain valve is 3500 cFh What is ill; equivalent capacity lor 0.72 lp \IT gas? Soluticnc 3500 cfh
~'" 3301 cFh
I
i ,
To find cFh itt 64 op gr, mwtiply cfh at "x" ,p, qt,
iD find "Fh at "J<" sp qt, divide cFh at 64 "p gr by conversi\ln faclor
Trang 6CONVERT CAPACITY TO SEA LEVEL AL TITUOE
CONVERT CAPACITY TO SEA LEVEL ALTITUDE
HOW TO USE CHART
When required valve capacity in cfh at sea levrl is known lilt equivaltnl rtquinod capacity at hiqher elevationJ r.1ay
be dele,mined by use of correct multiplyinq factor obt.tintd from litil chari
Example: A valve capaaty or:sooo dh ill required It 5 ltvel Whll would be the required capacity at an elultion
~t above sea lewl?
Solution: On vertical scale of chart, find 4550 ft From lhat point, move horizontally to riqhl to intersect lile curve;
lilen move straiqht down to bottom scale and read lile conV'trslon flctOt, 1.087 Multiply Ihe 3000 cfh by lil factor;
3000 cfh ill: L087 = 3261 cfh
NOTE: To find the capacity at sea level when the capacity at I hiqhet eltvation is known, ~ the known capacity
by the conve,.,.jon factor 3261 cfh = 00
Trang 7PRESSURE DROP CONVERSION
REOUIRED PRESSURE UNIT POUNDS
Absolute Pressure = Gauge Pressure + 14.74 psi
tf lhe available pressure drop across the valve was 1/4 25 psi x 27.7 (conversion factor for inches wc) =
psi, the equivalent pressure in inches wc would be: apprOXimately 7 in wc
'.
Trang 8I N T R O D U C T I O N - - -
DEFINITIONS
1119 firing Crate is Jhe combustion rate II is the rate at
which air, fuel, or snair-fuel mixture Is supplied loaburner
or furnace It may be expressed in volume (cubic feel of
gas or gallons of oil), weight (tons of coal), or heal units
(Btu's) sul=9lied par unit lime (usually per h::lur) FirinrJ rate
control (or combustion control) is simply a means of regu
launQfUel supply, air supply, and the ratioofairto1uelsup
ply according to load dernard
PURPOSES
Automatic Mng rate conlrols are offen used 10 $illl'Jify
operatioo and to relieve operators from tedious monitoring
dUlies However, their primary purpose is lor economy
To proouca Ihe mosl economical ep8ralion, lh&cOIltrol
system must mainlaln the air-fuel ratio at an optimum
value over the entire load range Usually, The system must
also control other imp::msnl facfOfs such as steam pras
sure, furnace draft, waler level and steam lemperature It
is virtually impoSSible for an operafor to maintain the pre
cise control necessary to achieve the gteatest econany
FACTORS AFFECTING THE FIRING RATE
Although the actual neaullQ load pfaceQ on the plant is
the primary consideration other faclors also affect the fir
ing ral& Since ducts, pipes, and flue passages absorb
much of the lotaf heal produced, opening and closing
lhem in ditf~rent palterns varies the heat loss immensely
The pickup demand or the furnace or boiler also con
sumas part of the heat output When a bJrr.er syslem is
started, the mass of metal that comprises me furnace or
bOiler absorbs a great amount 01 heat before all)' enters
the system, and it also radiales a portion of the heal 10 lhe
surrounding surfaces Finally, lhe efficiency of the fUrnace
or boiler ilself has a bearing on the amOl.n1 at fuel that is
burned The efficiency depends to a great exlent on the
he-at transfer qualities of the boiler or furnace
LIMITATIONS ON THE FIRING RATE
Turndown is lhe ralio or tna maximum firing rate (high
fire) 10 Ihe minimum /iring rate (Jaw fire) al which a burner
will operate satisfactorily It is also expressed as the range
of firing rales over which satisfactory combuslion can be
obtained For ax~le, lhe firillQ rale 01 a burner with a 4
to 1 turndown range can be varied from ils maximum (100
pl3rcent) clown to 1{4 at ils maximum (25 percenl), A high turndown ralio Is particularly desirable for batCh-type fur· naces or others lhat are shut down periodically A high fir· ing rale can be usecs to Mal lhe furnace rapidly after il is started up again After the flIrnal:e is heated up, the firing rale can be turned down 10 normal
Flame t::Jow-off limilS the maximum firing rate A Ilame moves away from a burner when the velocity at lheair-tuel mixture is greater than the velOCity Of the Ilame front (flame propagation rate) Blow-cff often resuHs in the flame being
Drat!: is lhe movement of air into and through a CON'Ous
{ion cflamber, brEl8ctling stack, and chimney
Natural draft results from the difference in density of the heated air rising through the slack or chimney and the
COOler displacinQ air Mechanical draft is crealad try mao chinery, such as a fan or blower Types of mechanical draft are forced and indUCed draft
Forced draft is produced by a fan or blower located at lhe inlel air passage 10 the combustion charrt:lel' Induced
draft is produced by a partial vacuum within the corrous
tion chaiTtler, created by a fan al the outlet at the
cMlTtler
Natural draft depoflds on ma", variables $Uch as 1hE! temperature of the atmosphere, height Of the stack, direc· tion and force Oflhe wind, and other environmenlal conditioos Blowers or fans supply a conslanl draft lhat is
independent 01 these conditions Therefor'll, mechanical
draft is used as the main source of air
Every tiring rale and type 01 fuaJ fequirss lhe prcper
amount 01 draft for best results 1he draft that is needed
also depends a lot on Ihevolume ofth'll cO'T'Ouslion cham
ber Da"l)f¥s in tl"l& air passages are use::llo control the
draft Darrpar p::lSilions are varied as tne firing rale is varied
FIRING RATE CONTROL METHODS - - -
In large plants, mothodl; of regulating the firing rate are
(1) fland, (2) base load and (3) automatic In hand regula
tion, a fireman allends \0 a ballery of boilers and/or fur
naces He adjusts lhe valves and da,rrp.:lrS manually to
301
keep the pressure ancVor temperature constant In base
load regulation, most Of a gr~ of boilers and/or furnaces are cperated at a ste&'t, hil1l firing rare but one or fTIOfe are operated at a variable rate \0 handle peak loads In
71-97558-1
Trang 9automatic regulation, an automatic firing rale control sys
tem ts used to provide smoother reQ.Jlatlon and beUet
cOl'l'b.Jsl:lon Some of the automatic systems used will be
discussecUn this section
AUTOMATIC FIRING RATE CONTROL
SYSTEMS
Different arranoemeF'lts of elements are used 10 pro
vide firing rate control Initially, the syStem is Iriggered by a
disturbaAce In the'CCintrolled variable, Such as steam pres
sure in,aooiler or wall temperature In a furnace The initial
disturbanca then causes a sequence of adjl lStJTlentS, In
parallel or in cascade (series), to control the various parts
of the syslem
pressure may cause simultaneous adjustment of fan
speed and 'damper opening to change the airflow, and
pu~ speed and valve opening to control the flow of fu&:
(all) In a cascade system a change in steam pressure
might lnlllate a change In cCllTbuSlion airflow, and the
dlange in airflow might lhen adjust the rate of fuel flow
Funher cascading might occur it the airflow is changed by
an adjus1manl of Ihe induced draft, and lhe resulting
ct\aIlgEl in furnace pressure is then corrected by a change
in the forced draft
A firing rate control system usually falls inlo 1 of 4 gen
eral classes-paranat, serieas·fuel, sories-air, or calorime
ter syStem Each System may not fall exactly Into 1 of the
classes, but l1'I8y be modified to be a combination of 2
classes Usually, one particular syslem (or combination)
will be the best lor a panicular plant based on economy,
type 01 fuel safety required, or lhe type of cperallon
In each system, a Change in the controlled variable
(such as sleam pressure in a boiier plant or temperature in
a healing furnace) generates an error signal The error Sig
nails then senT 10 adjust the fuel flow and air flow To c0m
pensate for varial.ions in fuel condlion or lor tube foUling in
boilers a ralio regulator (see belOW) is included lO-make
adjustmenls in the air-fuel ratio The ralio regulator maybe
as Sirl1Jte as the linkage between 2 valves, it may be a
valve-type device, or it may be a complex eleclrooic
device
PARAl.l.El CONTROl SYSTEM (FIG 1)
In the parallel control system, the error signal is sent si·
multaneously to adjust both fuetflow and airllow The ratio
regulator may ~ in either circuil It is generally in the cir
cuit having the greater capacity, so the capaciTy of theboil·
er or furnace will not be reduced if the ratio of fuel 10 air is
decreased Thus, ilthe blower or fans have greater capac
ily than tha fuel feeding equipment, the ratio regulator is
pul in the airflow circuit
The parallel syStem is the simplest and requires the
least hardWare II is nol dependent on signals indicative of
the actual flOW of fuel or air Therefore, it is most used in
plants where the fuel buming rate would be difficult to
measure directry, such as a plant using grate firing of coal
SEAlES-FUEl CONTROL SYSTEM (FIG 2)
In the series-fuel control system, lhe error signal conImls only the fuel flOW Measurement of the fuel flow then prcdJcBS a Signal that controls the airflow The fuel flow must be readily measurable, which Is true for most gases
liq,Jid fuels, and even pulverized coal A series sysIem is generally considered to be very effective in controlling the air-fuel ratio because the flow of one is used 10 determine the flow requirement of the other
Because airflow Is the dependenl variable, air will not Increase if fuel is not available, wen t~ the SyStem may be calling for more heal This Is advantageous 00
equlJ:YT19nt fired wllh a by-prcdJct fuel that may be in short supply at limes When lhere is a fuel shortage, the system prevenls the InlrcducUoo of large quantities of air, which would deCrease the effectlve heat El\l'9n further
However, if the air SlWly fails or airflOW' Is reduced excessively by a fan failure, there is a danger of filling the furnace with unburned fuel sinCe the error signal can still cause the system to continue fuel flow, Airflow failure will decrease the heat release in the furnace, further aggravat
.I,!lg the situation by causing a demand for even mora heat and fuel Electronic circuits may be used to overcome this problem by prOViding fuel cutback If eirflow ~g; fuel flow
by a predelermined amounl Also, a flame safeguard control can be used 10 Shut clown the burner; the flame will go
OU! when the air supply drops too low to su~n
combus-RATIO REGULATOR
FUEL FLOW
ERROR SIGNAL
_.J_-,
I ALTERNATE I
'LOCATION •
OF RATIO • : REGULATOR
Trang 10lion Many burners also have airflow interlocks 10 shut
them down if airllow decreases to a predelermined value
SERIES-AIR CONTROL SYSTEM (FIG 3)
"the Series·alr control system overcomes thQ disadvan
taQ3 of the series-fuel system; cutback of fuel is lDb8rEl!J(
upon a decrease In airflow The error signal controls only
IhQ airflow Measuremenl of thQ ail1low then produces a
the fuel flow will be decreased accordingly preventing the
furnace 1rom bEIIng filled with unburned fuel This system
is vel)' :satisfactory and IXlPUlar when fhe ail1low can be
readlly measured
CALORIMETER CONTROL SYSTEM (FIG 4)
In lhe calorimeter control system, the error signal CCll'l
trolsoOnly lhe fuel flow, and measurement of the steam now
produces a signal thai is used 10 control ail1low, The
amount 01 steam produced is proportional to the firing rale
(or fuel flow) so fuel flow is measured indirectly by meas
uring steam flow Because stearn flow is substituting for
fuel flow, the ratio regulator is in the steam flow clrcuil
It lakes a definite amount ot air to burn a quantity of a
given fuel that will release a certain amount 01 heal If the
rate of heat release is known, the amount of air required
can be determined The amount of steam prodJced is pro
p::>rtionalto the rate of heal release, so a measurement of
steam flow can be used to control the airflow Since a
measur<lment at steam flow is indirectly a measurement at
heat, the system derives its name from lhe calorimeter, an
apparatus for mensurfng amounts of heat
Steam leaVing the SuPerheater is usually held wilhin
close limits of pressure and temperature so its enerlJll
content per p::>und will not vary appreCiably Therefore,
each p::>und of steam carries the same amount of heat
energy, so steam flow is proportional to the firing rate It steam pressure or temperature vary el'lOUl;1l 10 causa appreciable error, compensating devices can be added to the system to correct the steam flow for standard conditions
As with the series-fuel system there is the danger of accumulating unburned fuel In the furnace if the air sowly fails A decrease in airllow will decrease the heat release, which will deCrease lhe steam !low, causing a further reduction in airflow Meantime, the system is calUng for more heat and more and more fuel is being &4JPlled As in thQ series-fuel system eleclronic circuits may be used to OYElrcome this problem by prOViding fuel cutback; but in this case, steam flow instead of fuel flow is CClI'1l)3.red with airflow
AIR-FUEL RATIO REGULATORS
Besides complex electronic systems (whiCh are be
yond the scC9'3 of this reference), there are 3 basic types
at air-fuet ratio regulators - Pl area control (2) pressure control, and (3) flow control All 3 actually keep the flow rates at the air and fuel proponlonal They differ In the basic prq:'l8rty that is controlled direCtly to achieve a cO"lStanl air-fuel ratio
AREA CONTROL (FIG 5)
A simple mechanism is used to cause the opening area
of 2 valves, one controlling airflow anclone controlling ruel flow, to vary in proponion fa each other For 2 varves with identical characteristics, a mechanical connection between them will produce directly proponional rT'lO\IeITl9Ot
If one valve rolates through a 45 degree angle, the other will also rolate through a45 degree angle: and If this movement causes a 25 percent chaf1Q8 in the flow rate of ona fluid it will cause a 25 percent change in the flow rate of
AIJ'lfLOW
ERROR SIGNAL
FUt:L FLOW
RATIO REGULATOR
AIRfLOW
I
RATIO REGULATOR
"
FIG 3-SERIES-AIR CONTROL SYSTEM
71-97558·1
Trang 11ERROR STEAM
I
RATIO REGULATOR
MfQ Co., Qeveland, Ohio.)
1M other If the vatve characleristics are not the same, the
now rales of the air and fuel will match only aI one lXlinl,
resulling In a lean mixture aI some firing rates and a rich
mixture at others
Two·rotary valves on a common shaft may be used, but
a ~de arrangement with a parallel ann or Hype
lInkage Is preferred because the linkage can sometimes
be adjl.lSted to correct tor different characleristics In lhe 2
valves one or, preferably, both valves should have man
ual means of adji"lSling their cpenings for setting the air·
tueI ratio Inilially
The L.9Cilream pressurfil!S 01 both air and fuel must be
constant, reqJlring an air blower with a constant pressure
characteristic and a fuel pressure regulalQ{ ahead of Ihe
fuel control valve For all, ils temperalure must be con
stanl fa avoid changaS in Its flow rate 0Je 10 viscosity
variali~
PRESSURE CONTROL (FIGS 6 AND 7)
The resistance to flow downsTream trom the clYltrol
valves Is a constant in boIh the fuel and air lines of any
bum&l' system The flow through a constant resistance is
prc:portlonaJ (0 the &q.Jare root 01 fhe pressure ditterentlat
across lhal resistance By keeping the air and fuel pres
sures equal (or proportional), their flow rates are kept pro
IXlrtional thrOU\1lOUI lhe entire turndown range of the
burner This type of ratio regulator works with constant ar·
eas and variable pr8SSUres, which is lTlOre accurate and
usually less expensive lhan the area control msthod
Wl1EIn this type of ratio regulator is in the fuel line, il is
cross-conneclad 10 the air Ii.ne by a small impul6B line, and
vice versa It c.onsi&ts 01 a globe-type valve in which Ihe
plug is-aitached to and movecl by a diaphragm 1'he pres
sure on one side of the diaphragn is proportional to that 01
the air line, and the prassure on the other side is prC4'O'
tional to lhat Of the fuel line If the pressures are not the
same, the urCialance causes the diaphragm to move The
diaphragn mc:wes the valve plug, adjusllng the flow 01 fuel
(01' air if the regulalor Is In Ihe air nne) until the pressures are the same
The air gas rallo regulator shown In Fig, 6 is connecled
In the gas line An air I~lse line (usually atxlul '/4 InCh pipe) Is conneclecl 10 the CClfTPartment below ttlE! diaphragm The air pressure In the i~16B line Is adjl.lSteclto achieve the desired alr gas ratio If the maximum air pres
$Ute Is more than the maximum available gas pressure, a
tieed"f is used to permit a cenain amount of leakage1rom
the 1l"rpU16B Une 10 ensure tM correci ratio at hiQh firing rates If the i~lse line were left open to the almosphere,
111El reguJalor would prOduce zero gas, used In ~ng
(zero governor) types 01 premixing burners The spring is used for counlerba.lancing the weights of lhe shaft, plug and diaphragn assElITbly so that the diaphragm 1Joals freely The balancIng diaphragn prevents t.pStream gas
pressure acling on the underside 01 the valve plug from lifting the plug
When b.Jrning all In low-pressure air atomizing burners,
it is desirable 10 maintain an oil pressure several times
greater than lhe COrTtx.lslion air pressure The air-oil ralio
regulator shown in Fig 7 prOduces a oownslream oil pressure proportional to Ihe pressure elrertecl on the tc:p side of 1M air diaphragm The j~lseair pressure p lShes down
on the air diaphragn, lending 10 move the valvs shaft asserTt:lly downward The downstream oil prassure pushes
up on the oil diapnragn, tending 10 raise the valve shaft assembly The space between the diaphraQ'Tls is ventoo
to the atmosphere If the area of 111EI air diaphragm is 12 limes [he area oflhe oil diaphragm, the oil pressure has to'
be 12 limes the air pressure in order to balanc9 it The oil valve opens wider untillhe 12:1 pressure ralio is attained
An adjustable lension spring balanCes the weight of the diap,ragms, shaft and valve plug
FLOW CONTROL (FIG 8)
A llow control system actually measures Iheair1/aw and
fuei flaw and conlrols the flow 01 one of them accordingly
Trang 12A conslriction, such as an orifice, is plaCed in both the air
and fuel lines The pressure differential across the con,
striction measures the flow thtough that line Both pres'
~re differentials are Iransmitled to some controliing
d9vJce that adjusts Ihe 'low 0' either the air or fuel to main
tain the desired air-fuel ratio
The alr-gas rallo re(JJtalor shown in Fig 8 conltols the
flow of air An Input coolrol valve controls the flow at gas
upstream and downstream Il'Jl=Iulses from an orifice in the
gas line act on qJpOSite sides oflhe gas diaphragm Simi
larly', impulseS from the air line act on the air diaphragm so
as'to oppose the action on lhe gas diaphragm lhe result
ing movement of the shaft between the 2 diaphragms is
amplified and transmitted hyc!raulically (by the hydraulic
,"
L'''(
+OAS a"L"""""'"
O, 9>tR "
'"'".:O"'-~:=:?:::§~SPR, ",
Q.R''''''
FIG 6-iYPICAL AIR-GAS RATIO REGULATOR
USING PRESSURE CONTROL, (From
Combustion Handbook try North American
Mfg Co., Cleveland, Ohio.)
relay and crank type cylinder} to the butterfly valve in the air line The butterfly valve moves untillhe now (pressure dif1erenlLal) across the air orifice balances out the flow across the gas orifice The orifices are usually sized so that equal pressure drops correspond to the correct ratio
01 flow rates The ratio regulator also has a manual adjust·
ment tor selecting the desired air-fuel ratio
,
FIG 7-iYPICAL AIR-OIL RATIO REGULATOR
USING PRESSURE CONTROL (From
Combustion Handbook by North American
Co., GJevs(and, Ohio.)
"R ORIFICE BUTTERFLY VALVE
FIG a-TYPICAL AIR·GAS RATIO REGULATOR USING FLOW CONTROL (From Combustion
Handbook try North Amen'can Mfg Co., Oeveland, Ohio.)
Trang 13FIRING RATE
TIle size and aw1icalion 01 a burner determines how II
iG fired Ditlerent rnel!nds 01 flrino result In various
prepurge configurations An a,wrovall:lOC¥ may require a
specifiC prepurge COnfiq.Jtalion for a given awlica1ion
The swilching required fa achieve a certain prepurge corr flq.Jralion is providedby the proper model 01 a flame sale
guard pr~ammlng conlrol programmer)
METHOD OF FIRING
CONnNUOUS FIRING sinal1~t burners, such as dtyQrs are usuarty let! on continuously There afe also continuous InciJslrial fur
naces Ih~ which the work loads are conveyed al a constanl speed
ON-OFF FIRING TIle most economical method of firing is sirrq::lly to turn the burner on when heal is required and oft when there is
er"lCJl 91 heat This is the most efficient method because
the air-fuel ratio can be sel exactly at its optimum value, an::! it remains constant while the burner is on Fewer con
trols ars requlrec:l, so It is also less expansive initially Orr 01'1' filing is used mostly on warm air turnaces in residential and corrmerclal buildings, and also for residential awn
aness such as hot waler healers
HIGH-LOW FIRING
Hig-.-Iow firing provid9s 2 firing rates, high fire and low fite, according to "eat demand The high fire rale is 00
tained by simultaneously PJs!tioning lhe dampers 10 aO'nil more combustion air and the fuel valve to admit more fuel
(In a 2·slage bur~r, a secord fuell/alva is cpened 10 aO'nit more fuel.l High·low firing is used on large, commerCial and industrial burners to provide a safe Ii~t-off A higher firing rare is r8QUired than Is safe for on-off firing, so the burner must light off at low fire to al/Oid a possible eKp1o
sion High temperalure blast turnaces, such as brick kilns
use this melhod of firing They are f~ed as high as possible for a short time, and then turned down to low fire for a wnile This melhQj has been found 10 save 10 to 15 per·
Cent of the fuel required 101 modulalac:l firing
MODULATED FIRING Modulaled firing provides a gradually varying firing rate belween high fire and low fire, according to heal de
marlCt The burner lights off at low tire 1l1en a controller varies ll\EI firing rate as necessary to k~ the conI rolled variable (usually prBSSUre or temperalurel at the controllEi"
sel PJlnt Modulaled firing provides precise coolrol, but it
is the least efficienl because it is ditficull 10 keep the air
fuel ratio conSlanl over the entire mlX1Jlating range It is used on industrial furnaces or bOilers 'or applicatlOflS re
quiring close pressure or temperature tolerances, such as chamical process heaters used tor tleal-trQ8ling metals
PREPURGE CONFIGURATIONS
AJ:proval bodies require a pr~rge period, prior 10 oorner Iighl-otl, to remove any fuel or fuel vapors that may have accumulated In th$ butner or stacks By incrQ8sing lhe amounl of air lTlOYed through the combustion chafT', ber, the possitillly of a rough IiQtll-cN or explosion clJa 10 accumulated fuel Is decreased This is why a ~hlgh fire" prepurge Is usually required tor hi~-Iow or mcx)Jlalec! methOOS at tiring The ~high fire" Is really a l!!i~().I!I.!§Ir
since lhere is ro fire during prElPJrge What it really means
Is that the darrper controUing corrbustion air is c:penac:lto
lis maximum ~ition to move> as much air as possIble
same as the high lire position of the damper during the run period when the burner Is firing
It would seem Ihal the longer lhe prepurge period the beller However a burnar system starts ~ when there is a call for heat Be10re the burner can be igniled to provide heat, the prepurge period aclually COOls the system OOwn ev81'l more Therefore, [he beSt pr~rQ8 coofiguratioo for
a gi"'en system is one that provides sufficierll airflow in the shortesllime, taking into consideration ~roval 00Cl'f requirements, I~ 01 equipmenl, and cost 01 conlrOls Prepurge types and firing rate sWi~Chjng necessary 10 meet awroval 00Cl'f req Jlrements for vaiiOU'S methods of flrinQ are summarized in Table I Insurance comp9.r'1ies insure bolh prcperty loss due to explosions and dowr'1time causing loss of productior'1 It they requIre safely controls thal causa urnecessary down lime they pay, Since they reqUire cerlain firing rate contrOls, you can see the imper·
tance of IheS4 controls to the safety of the Ourner system
STANDARD ON-OFF PREPURGE
No firing rate SwilCtling is rElQJired The amount 01 air admiUed during the prepurge pariod is Itle same as the amount of combuslion air provided during the run period witr the burner firing
OPEN DAMPER PREPURGE Firing rale swilChlne in fhe programmer drives a 2-posilion damper molar open 10 its hi~ fire p.:lsiliOn near the beginning of the prepurge periOd, aUOW's it 10 close to lis
low fire p.:lSihon before ignition trials, and drives il back
open 10 high fire for the run period
LOW FIRE PREPURGE This Is !in outdated type 01 prepurge that is seldom used anymore in flame safeguard awlicalions Firing rate switching in lhe programmer keEpS a proportioning damp
er motor at ils low fire position until after i'7lillOn trials, when switching releases the motor 10 modJlate UI"lCeT the control of a series 90 pressure or temperature conlroller
Trang 14TABLE I-PAEPURGE CONFIGURAnONS
1-wireb
UL Modulating
(2-stage firing)
or 4-wire Fire Fire
R4181A1042,-A1059
& UL - Underwriters l at:x:lratories Inc requirements
<&"-Factory Mutual requirements
IAI-Industrial Risk Insurers (formerly F.I.A.) requirements
b Firing rate motor mUSI close by itselt (spring-return) when power is removed
C Outdated type; seldom used anymore
d Low fire switch stops sequence before ignition trials until low fire position is proven
ill Same as LQw·High-Low except additional high fire switch stops sequence near begiMing of prepurge until hi1tl tire p:lSil'ion is proven '
I Switching returns firing rale motor to its low tire position when the run period is OVer
LOW-HIGH-LOW PREPURGE
Firing rate swllchlng in the programmer drives a pro
p:lrtioning damper molar o~n to its high fire position near
the beginning of the prepurge perioo, closed to its low fire
position before Ignilion trials, ard releases it to modulate
under the control at a series 90 pressure or t9ITperature
controller lor the run period The programmer has provi
sions for a proved 10w-firl;l-5tart interlock Oow fire switch),
which stops the sequence before ignition trials until the
damper motor has closed to its low fire position
LOW-HIGH-LOW PROVEN PREPURGE
This is the same as lOw-high-low prepurge, excepl that
Ihe programmer also has provisions for a proved high fire
interlock (high fIre switch), which slops the sequence near
the beginning of the prepurge perioo until the clarrper m0
tor has opened to Its hit;jl fire posillon
PROVED LOW-FIRE-START INTERLOCK
A proved low-fire-start interlock Is r9QJired for hl~-klw
Of modulated burners (except those with low fire prepurge, which is outdated and seldom used anymore) This inl9ftock must ensure that allliring rale controls are In the low fire position (a firing rate no! eXCeeding 33 percenl of the
maximum) betote the burner can be iglited This is usually accompllshed by means at an auxiliary switch {low fire SWitCh) mounted on the drive Shaft or the firing rale motor The auxiliary switCh is wired inlo the safety conlrol (programmer) circuit
PROVED HIGH FIRE INTERLOCK
In addition 10 a proved low-flrl;l-5tart interlock, Factory Mutual and In:iJstrlal Risk Insurers (formerly F.l.A.) also reQUire a hit;jl fire swilch 10 prove thai the ~r is tully cpen wring prepurge fo ensure that 9I"lCll.Q1 air Is moved
!hrOU<tl the combustion charrber The hit;1'l tire swllch Is usually also an auxll1ary switch on the firing ratelOOlOf'
Trang 15FIRING RATE SWITCHING IN PROGRAMMERS -
By means of simpllfiod schematic dlagrams and timer
seq Jente charts, we wlU show how fhe PfOlJfammers ae
CCllT'9liSh firing rate switching For simpliCity, only the cir·
cuits and conlaCts nec~ry 10 de6Cribe the basic
operation are shown For a complete description ollhe 0p
eration cif ~ actual programmer, Jefer 10 the Detailed Orr STaling ~nce 01 an A4140G1007 (1orm 6D-0443) or an
R4140L"'-4"7 (form 60-{)4.44)
TImer contacts are oesicnaled M1B, M3A, etc Termi·
nals L1 and l2 are the -hoi- and ~common· terminals 01 ttle power SLWly External oevices are shown in 001(95
Operation 01 the firing rale motor Is deScribed in detail In the seedndpar1 of this section covering Honeywell Control
A 2-posJl!on, spting·t~um llcluator is used to control the dar'rper When p:rNer is removed, a spring en the ac
hator Shaft m~chanicaJJy returns lhe aclualor to its closed
position
Prepurge starts on a cal! for heal As saonas proper air
"flow is e!tab\ished, Ihe airtlow switch close's, er'oergili~
',' the damper actuator on terminal 10 (through the airflow
switch, jurrper, and M108) TIle actuator drives the darrq>
er open ~o high lire ~ition)
At 30 seconds, M10B opens The darrper actualor is d8-energiz.ed an::! the sprinQ-relurn drives Ihe darrper clQSEld Al ~ ~, lnlern.al programmer switching s:ops the timer until the low fire swilCh closes, proving thai the daf1lJ9r is in ils low fire position before ignition trials
Ignition lrlals begin at 42 seconds Tl1e darrper stays closed during most of this period Near lhe end of ignition trials, al ti9.5 seconds, M108 closes The damp€lf actuator
Is -.ergi.!:ed anddrives Ihe damper open (10 high fire PJSi
& ~T""To AM , ,~ 5"' v ""''' lOON IUAC S.CC"""
& , -A , T ,.UA"lICI.""ffN U 'NAU" .O
A IN CA""~ ACTUATM ,S"IlC,
11A'·I'O:I'''''''._'''~·.I'''''N AUU.HOII " D rocoorr"OL tNE
FIG '0- TYPICAL TIMER SEQUENCE CHART
FOR '-WIRE (OPEN DAMPER) FIRING RATE SWITCHING
tion) for the run period The timer steps for !he run periOd, and I'" damper stays open during the run period When the tun period ands, the limer starts The caU for
heat ends and power is remoVEldfrom terminal 10, deener·
gillng the acll.la~or The spring-return drives tM damper
closed
3-WIRE FIRING RATE SWITCHING
Figs '1 and 12 show the firing rate sWitchi~ at old
fire and lOW fire proving circuits is nOI shown because it is similar to the opera.tion for 4-Wire switching, whiCh follows Notice lhat the prQgramrner SwiTching (Fig 111 doeS not
awly power to lhe motor, but cnly shorts between molar and c()l"(roller terminals, or opens them
A proportioning, sptfng-return or spring·biased motor
must be used to control the damper When the red ·R~
(comrrn:n) lag of the circuli fa a spring·rerum motor is
FIG 9- TYPICAL 1-WIRE (OPEN DAMPER)
SWITCHING
FIRING RATE SWITCHING,
Trang 16FIG 12-TYPICAl TIMER SEQUENCE CHART
FOR 3-WIRE FIRING RATE SWITCHING
opened, a spring on the molor shaff mechanically returns
the molor 10 its closed position The spring·tiased molDl'
has a spring allached\o ilsbalancing relay When the "R"
leg is coened, the spring pulls the balancing rela.y to its
closed position, and the molor is than electrically returned
to ils closed posilion
As usual, prepurge starts on a call for heat At 2 sec
Or'lOs, M98 closes, shorting between terminals 10 and' 1
on lheprogrammer and between terminals Rand B on the
firing rate molor The motor dlives the damper cpen 10 its
high fire posi\ion At 7 seconds internal prCJgrammer
switching stops lhe timer unlillhe high fire switch closes,
prOVing that the damper is open 10 provide maximum air·
flow during prepurge
At 42 secondS, M9B opens, opening Ihe • R· leg of the
motor circuit The spring (or spring-bias) drives the motor
and darnpel' closed At 60 seconds, internal prCJgrammer
switching stops the timer until the lOW fire switch closes,
proving that the damper is in its low fire position before ig
nition trials
Ignition trials begin at 72 seConds, and the damper
stays closed during mas! of this period Near Ihe end 01 ig
nition trials, at 101 seconds, M9A closes, shorting be-
t een terminals 11 ard 12 on Ihe programmer, and
connecting the A terminals of the molar ar.d controller
The firing rate motor is released to mcx:::Iulate under conlrol
of the series 90 coni roller The limer slops for Ihe run
period
The firing rale motor modulates according 10 heat de
mand during lhe run period When the run period endS,
the timer slarts Al 118 seconds, M9A opens, cpening the
• A· leg 01 the malar circuit The spring (or spring-bias)
drives the molar and damper closed
4-WIRE FIRING RATE SWITCHING
The 3-wire firing rale switching Circuit restricts users ~o
a firing rate molar .ith a spring-return or spring-biasecl
balanCing relay Therefore newer A4150G ard Lmcdels,
and all A4140G and L models, have 4-wire firing rate
switching circuits These models also allow Ihe use of m0tors thai are electrica.11y driven in both directions
FiQS 13, 14, and 15 show the firing rale switching 01 a typical R4140L Programmer Operation 01 both the higl fire and low fire proving circuits Is shown (Fig 14) R4140G I'T'ICX1els have provisions only for the low 11re switch Prepurge starts normally on a call 10r heal lhe timer motDl" (Fig 14) Is energiZed IhroU(1l MJA Al 3 seconds, M10B opens ard Ml0A closes (Fig 13), shorting between terminals 10 and 11 on the programmer, and between ler·
minals Rand B on lhe 1iring rate motor The motor drives lhe oamper open to its high tire position At 10 secondS,
M3A opens (Fig 14), stc:«>ing the timer molar When the high tire switch closes, prOVing thallh8 damper Is cpen 10
provide maximum airtlow during prepurge, the timer motor
is energiZed thrOUQh tha high fire $Wilch ard M5B; prspurga continues
At 20 secondS, M3B closes (Fig 14), bypassing the high fire switch At 26 seconds, M10A opens (Fig 13) cpening the A leg 01 Ihe motor circuit If a spring-return or
spring-biased molar is used, it starts to drive the damper
FIG 14- T'(PICAL OPERATION OF HIGH FIRE
AND LOW FIRE PROVING CiRCUITS
Trang 17FIG 15- TYPICAL TIMER SEQUENCE CHART FOR
4.WIRE FIRING RATE SWITCHING
closed At 30 seconds, M10S closes, shorting between
(ermlnals l ' and 14 on the programmer ~hrough M10S
and MBS) and between terminals Rand W on lhe firing
rate motor If an electrically driven motor is used il drives
the damper closed Al 5' seCOl'lds M5B opens (Fig 14),
st,,",lng the timer motor MSA closes When the low fire
swllch closes proving (hat the damper Is in its low fire IX>"
slim before Ignition Irials, lhe limer molor is energized
Of the low fire switch is connecled in the alternate Iocallon the limer molar 16 energizecJ through M3B, the low tire switch and M5A.)
Ignilion trials begin al 60 seCO'ldS and the damper slays closed during most of this period Al 66 seconds M3B opens and M3A closes (Fig 14), bypassing oolh Ihe high fire and low fire swilCheS The timer motor keeps runnil1Q and Ignilion trials continue, Near the and of ignition trials, al95 seconds, M8Bopens and M8A closes (Fig 13),
shortinQ belween lerminall!l" and 120n the programmer (through M1 OB and MBA), and conneCllng the R terminals
of the motor and controller The firing rale molar Is re
leased to l1"lCllislale under control at the sefles 90 controller The limer st~ for Ihe run period
The firing rale molar modulates according 10 heal de
mand during lhe run period, When Ihe run period ends,
the limer statts AI '12 seconds, MaA opens (Fig 13), openll1Q lhe R leg o1lhe malar circuil 11 a sprinQ'relurn or sprinQ"biased molar is used, Il starts 10 drive the damper closed At '16 seconds, MBS closes, shorting be/ween terminals l ' and 14 on Ihe programmer (through "-1108 and MBSl and between lerminals Rand W 01 lhe firing rale motor If an electrically driven molar is usecI il drives the damper closed
Trang 18HONEYWELL CONTROL S E R I E S - - -
The electrical series of a control-20, 40, SO, 60, 70, 80,
SO-identifies the vqllage leve! on which a conlrol ~r
ales and Ihe switching or modQ of operation it provideS
Cqnlrollers provide spst or SIXft swilching, and switch
eilher line or low v01laga (For further information on con
trolla'rs, refer 10 Ihe Flame safeguard Reference on Auxil·
lary Equipment, form 70-8120.) We can see that by
combining Ihese 2 factors, we can identify 4 dil1erent S&
rias -spsf line, spst low, SIX1I fine, stXfI [ow These 4 series
and their characteristic controller switching actions Bfa
Series 20 (low voltage, spjI) is not USEId in flame safeguard applications series 50 (mechanical) is represented
by V50S5 and V51 E gas valves, which have separa:e actuators, and by the VS060A Supervisory Fuel Cock Series
70 (electronic) Is represented by name detectors and
flame signal amplifiers Series 80 ~ow voltage SPSI) is represented by a few flame sa1eQ.Jard primary Controls
(RA890'S) indicaling simply thai they have a low voltage contro circuit and by a tew SQlenoid-opllrated gas valves Series 40 and 60 (line voltage), used in on-otf or hiQ1·low Systems, will be discussed briefly Series 90 (mociJ~ting\
is the hearl at mosl firing rale control systems, so it will be
described in detail Table II summarizes Honeywell control series
SERIES 40 (LINE VOLTAGE, SPST) CONTROLS
Series 40 controllers ard limits used in flame saf9QJS.rd
awlications are commonly temperature or pressure sens
Ing devices They provide ::.pst (singla-pole, single-throw)
swaching In olher words, they make a set at contacts to
start SyStem operption, and break the sel of contacts 10
stop' SyStem operation
Se(ies 40 controll(Jrs and limits are rated for direct
switching of line voltage loads They commonly use either
mercury switch or open contact switChing mechanisms
Open contact mechanisms must be snap-acling 10 pre
vent arcing across the contacts
FINAL CONTROL ELEMENTS
series 40 final conlrol elements - solenoid valves, re
lays, contactors, and motors- have only 2 positionS They
remain In the normally de-energized position until pow·
ered; at which time, they g) 10 Ihe energized position,
When pOwer is Interrupted, they return autanallcally 10
the de-energized position A normally closed series 4()
solenOid valve, ror e)llample, opens when powered, re
mains open as long as power Is aw1ied ard closes as
soon as power is cut off
311
Fig, 17 shows a series 4() relay CC{11roJ!ed by a series
40 cootroller with a series 40 limit TIle relay shown pro
vides spst switching; it could provide more COf1'l>lex switching control, The S91les desiglalioo, series 40 re1ets
10 the control circuit voltage ard control Circuit switching
action If the sWitching action 01 the relay shown were
spdt, the relay would no! be desiQr1aled serles &l eYen
tl10uQh it provides line VOltage spdt: swilching, It wwld remain series 40 after the Coil circuit TIlere are, in fact, no series 60 relays and no series 60 soJ9I"lOld valves since
lhese devices are, by nature, on-off (spst) controls
de-energized Fig 18 shOws a series 4() motor under cen
Irol 01 a series 40 controller
The limit switch cuts off power to the motOl' windirv;>
When the motor reaches ils full open po:sillon The braJlfI
'rVinding holds the armature agaInst a brake shoe 10 hold
71·97558-1