Now we wish to undertake a sequence of progressivelyharder problems of forced convection heat transfer in more complicatedflow configurations.Incompressible forced convection heat transfer
Trang 1[6.13] B S Petukhov Heat transfer and friction in turbulent pipe flow
with variable physical properties In T.F Irvine, Jr and J P
Hart-nett, editors, Advances in Heat Transfer, volume 6, pages 504–564.
Academic Press, Inc., New York, 1970
[6.14] A A Žukauskas and A B Ambrazyavichyus Heat transfer from
a plate in a liquid flow Int J Heat Mass Transfer, 3(4):305–309,
1961
[6.15] A Žukauskas and A Šlanciauskas Heat Transfer in Turbulent
Fluid Flows Hemisphere Publishing Corp., Washington, 1987.
[6.16] S Whitaker Forced convection heat transfer correlation for flow
in pipes past flat plates, single cylinders, single spheres, and for
flow in packed beds and tube bundles AIChE J., 18:361, 1972.
[6.17] S W Churchill A comprehensive correlating equation for forced
convection from flat plates AIChE J., 22:264–268, 1976.
[6.18] S B Pope Turbulent Flows Cambridge University Press,
Cam-bridge, 2000
[6.19] P A Libby Introduction to Turbulence Taylor & Francis,
Washing-ton D.C., 1996
Trang 3The bed was soft enough to suit me .But I soon found that there came such a draught of cold air over me from the sill of the window that this plan would never do at all, especially as another current from the rickety door met the one from the window and both together formed a series of small whirlwinds in the immediate vicinity of the spot where I had thought
to spend the night Moby Dick, H Melville, 1851
7.1 Introduction
Consider for a moment the fluid flow pattern within a shell-and-tube heat
exchanger, such as that shown in Fig.3.5 The shell-pass flow moves up
and down across the tube bundle from one baffle to the next The flow
around each pipe is determined by the complexities of the one before it,
and the direction of the mean flow relative to each pipe can vary Yet
the problem of determining the heat transfer in this situation, however
difficult it appears to be, is a task that must be undertaken
The flow within the tubes of the exchanger is somewhat more tractable,
but it, too, brings with it several problems that do not arise in the flow of
fluids over a flat surface Heat exchangers thus present a kind of
micro-cosm of internal and external forced convection problems Other such
problems arise everywhere that energy is delivered, controlled, utilized,
or produced They arise in the complex flow of water through nuclear
heating elements or in the liquid heating tubes of a solar collector—in
the flow of a cryogenic liquid coolant in certain digital computers or in
the circulation of refrigerant in the spacesuit of a lunar astronaut
We dealt with the simple configuration of flow over a flat surface in
341
Trang 4Chapter6 This situation has considerable importance in its own right,and it also reveals a number of analytical methods that apply to otherconfigurations Now we wish to undertake a sequence of progressivelyharder problems of forced convection heat transfer in more complicatedflow configurations.
Incompressible forced convection heat transfer problems normallyadmit an extremely important simplification: the fluid flow problem can
be solved without reference to the temperature distribution in the fluid.Thus, we can first find the velocity distribution and then put it in theenergy equation as known information and solve for the temperaturedistribution Two things can impede this procedure, however:
• If the fluid properties (especially µ and ρ) vary significantly with
temperature, we cannot predict the velocity without knowing thetemperature, and vice versa The problems of predicting velocityand temperature become intertwined and harder to solve We en-counter such a situation later in the study of natural convection,where the fluid is driven by thermally induced density changes
• Either the fluid flow solution or the temperature solution can, itself,
become prohibitively hard to find When that happens, we resort tothe correlation of experimental data with the help of dimensionalanalysis
Our aim in this chapter is to present the analysis of a few simpleproblems and to show the progression toward increasingly empirical so-lutions as the problems become progressively more unwieldy We beginthis undertaking with one of the simplest problems: that of predictinglaminar convection in a pipe
7.2 Heat transfer to and from laminar flows in pipes
Not many industrial pipe flows are laminar, but laminar heating and ing does occur in an increasing variety of modern instruments and equip-ment: micro-electro-mechanical systems (MEMS), laser coolant lines, andmany compact heat exchangers, for example As in any forced convectionproblem, we first describe the flow field This description will include anumber of ideas that apply to turbulent as well as laminar flow
Trang 5cool-Figure 7.1 The development of a laminar velocity profile in a pipe.
Development of a laminar flow
Figure7.1shows the evolution of a laminar velocity profile from the
en-trance of a pipe Throughout the length of the pipe, the mass flow rate,
where A c is the cross-sectional area of the pipe The velocity profile, on
the other hand, changes greatly near the inlet to the pipe A b.l builds
up from the front, generally accelerating the otherwise undisturbed core
The b.l eventually occupies the entire flow area and defines a velocity
pro-file that changes very little thereafter We call such a flow fully developed.
A flow is fully developed from the hydrodynamic standpoint when
∂u
at each radial location in the cross section An attribute of a dynamically
fully developed flow is that the streamlines are all parallel to one another
The concept of a fully developed flow, from the thermal standpoint,
is a little more complicated We must first understand the notion of the
mixing-cup, or bulk, enthalpy and temperature, ˆ h b and T b The enthalpy
is of interest because we use it in writing the First Law of
Thermodynam-ics when calculating the inflow of thermal energy and flow work to open
control volumes The bulk enthalpy is an average enthalpy for the fluid
Trang 6flowing through a cross section of the pipe:
T b ≡ rate of flow of enthalpy through a cross section
rate of flow of heat capacity through a cross section
Thus, if the pipe were broken at any x-station and allowed to discharge
into a mixing cup, the enthalpy of the mixed fluid in the cup would equalthe average enthalpy of the fluid flowing through the cross section, and
the temperature of the fluid in the cup would be T b This definition of T b
is perfectly general and applies to either laminar or turbulent flow For
a circular pipe, with dA c = 2πr dr , eqn (7.5) becomes
A fully developed flow, from the thermal standpoint, is one for which
the relative shape of the temperature profile does not change with x We
state this mathematically as
where T generally depends on x and r This means that the profile can
be scaled up or down with T w − T b Of course, a flow must be namically developed if it is to be thermally developed
Trang 7hydrody-Figure 7.2 The thermal development of flows in tubes with
a uniform wall heat flux and with a uniform wall temperature
(the entrance region).
Figures7.2and7.3show the development of two flows and their
sub-sequent behavior The two flows are subjected to either a uniform wall
heat flux or a uniform wall temperature In Fig.7.2we see each flow
de-velop until its temperature profile achieves a shape which, except for a
linear stretching, it will retain thereafter If we consider a small length of
pipe, dx long with perimeter P , then its surface area is P dx (e.g., 2π R dx
for a circular pipe) and an energy balance on it is1
Trang 8Figure 7.3 The thermal behavior of flows in tubes with a
uni-form wall heat flux and with a uniuni-form temperature (the
ther-mally developed region).
This result is also valid for the bulk temperature in a turbulent flow
In Fig 7.3 we see the fully developed variation of the temperatureprofile If the flow is fully developed, the boundary layers are no longer
growing thicker, and we expect that h will become constant When q w is
constant, then T w − T b will be constant in fully developed flow, so thatthe temperature profile will retain the same shape while the temperature
rises at a constant rate at all values of r Thus, at any radial position,
In the uniform wall temperature case, the temperature profile keeps
the same shape, but its amplitude decreases with x, as does q w Thelower right-hand corner of Fig.7.3has been drawn to conform with thisrequirement, as expressed in eqn (7.7)
Trang 9The velocity profile in laminar tube flows
The Buckingham pi-theorem tells us that if the hydrodynamic entry length,
x e, required to establish a fully developed velocity profile depends on
uav, µ, ρ, and D in three dimensions (kg, m, and s), then we expect to
find two pi-groups:
x e
D = fn (Re D )
where ReD ≡ uavD/ν The matter of entry length is discussed by White
[7.1, Chap 4], who quotes
x e
The constant, 0.03, guarantees that the laminar shear stress on the pipe
wall will be within 5% of the value for fully developed flow when x >
x e The number 0.05 can be used, instead, if a deviation of just 1.4% is
desired The thermal entry length, x e t , turns out to be different from x e
We deal with it shortly
The hydrodynamic entry length for a pipe carrying fluid at speeds
near the transitional Reynolds number (2100) will extend beyond 100
di-ameters Since heat transfer in pipes shorter than this is very often
im-portant, we will eventually have to deal with the entry region
The velocity profile for a fully developed laminar incompressible pipe
flow can be derived from the momentum equation for an axisymmetric
flow It turns out that the b.l assumptions all happen to be valid for a
fully developed pipe flow:
• The pressure is constant across any section.
• ∂2u ∂x2is exactly zero
• The radial velocity is not just small, but it is zero.
• The term ∂u ∂x is not just small, but it is zero.
The boundary layer equation for cylindrically symmetrical flows is quite
similar to that for a flat surface, eqn (6.13):
Trang 10For fully developed flows, we go beyond the b.l assumptions and set
v and ∂u/∂x equal to zero as well, so eqn (7.13) becomes
1
r
d dr
r du dr
= 1µ
dp dx
We integrate this twice and get
u =
1
4µ
dp dx
This is the familiar Hagen-Poiseuille2 parabolic velocity profile We can
identify the lead constant ( −dp/dx)R2 4µ as the maximum centerline velocity, umax In accordance with the conservation of mass (see Prob-lem7.1), 2uav= umax, so
Thermal behavior of a flow with a uniform heat flux at the wall
The b.l energy equation for a fully developed laminar incompressibleflow, eqn (6.40), takes the following simple form in a pipe flow wherethe radial velocity is equal to zero:
2The German scientist G Hagen showed experimentally how u varied with r , dp/dx,
µ, and R, in 1839 J Poiseuille (pronounced Pwa-zói or, more precisely, Pwä-z´¯e e) did the same thing, almost simultaneously (1840), in France Poiseuille was a physician interested in blood flow, and we find today that if medical students know nothing else about fluid flow, they know “Poiseuille’s law.”
Trang 11For a fully developed flow with q w = constant, T w and T bincrease linearly
with x In particular, by integrating eqn (7.10), we find
d dr
r dT dr
The first b.c on this equation is the symmetry condition, ∂T /∂r = 0
at r = 0, and it gives C1 = 0 The second b.c is the definition of the
mixing-cup temperature, eqn (7.6) Substituting eqn (7.19) with C1 = 0
into eqn (7.6) and carrying out the indicated integrations, we get
C2= T b − 7
24
q w R k
Trang 12Equation (7.22) is surprisingly simple Indeed, the fact that there isonly one dimensionless group in it is predictable by dimensional analysis.
In this case the dimensional functional equation is merely
h = fn (D, k)
We exclude∆T , because h should be independent of ∆T in forced tion; µ, because the flow is parallel regardless of the viscosity; and ρu2
convec-av,because there is no influence of momentum in a laminar incompressibleflow that never changes direction This gives three variables, effectively
in only two dimensions, W/K and m, resulting in just one dimensionlessgroup, NuD, which must therefore be a constant
Example 7.1
Water at 20◦C flows through a small-bore tube 1 mm in diameter at
a uniform speed of 0.2 m/s The flow is fully developed at a point
beyond which a constant heat flux of 6000 W/m2 is imposed Howmuch farther down the tube will the water reach 74◦C at its hottestpoint?
Solution. As a fairly rough approximation, we evaluate properties
at (74 + 20)/2 = 47 ◦ C: k = 0.6367 W/m·K, α = 1.541 × 10 −7, and
ν = 0.556×10 −6m2/s Therefore, Re D = (0.001 m)(0.2 m/s)/0.556×
10−6 m2/s = 360, and the flow is laminar Then, noting that T is
greatest at the wall and setting x = L at the point where Twall= 74 ◦C,
0.2(0.6367) 4(6000)1.541(10) −7 = 1785
Trang 13so the wall temperature reaches the limiting temperature of 74◦C at
L = 1785(0.001 m) = 1.785 m
While we did not evaluate the thermal entry length here, it may be
shown to be much, much less than 1785 diameters
In the preceding example, the heat transfer coefficient is actually
The high h is a direct result of the small tube diameter, which limits the
thermal boundary layer to a small thickness and keeps the thermal
resis-tance low This trend leads directly to the notion of a microchannel heat
exchanger Using small scale fabrication technologies, such as have been
developed in the semiconductor industry, it is possible to create
chan-nels whose characteristic diameter is in the range of 100 µm, resulting in
heat transfer coefficients in the range of 104 W/m2K for water [7.2] If,
instead, liquid sodium (k ≈ 80 W/m·K) is used as the working fluid, the
laminar flow heat transfer coefficient is on the order of 106 W/m2K — a
range that is usually associated with boiling processes!
Thermal behavior of the flow in an isothermal pipe
The dimensional analysis that showed NuD = constant for flow with a
uniform heat flux at the wall is unchanged when the pipe wall is
isother-mal Thus, NuD should still be constant But this time (see, e.g., [7.3,
Chap 8]) the constant changes to
NuD = 3.657, T w = constant (7.23)for fully developed flow The behavior of the bulk temperature is dis-
cussed in Sect.7.4
The thermal entrance region
The thermal entrance region is of great importance in laminar flow
be-cause the thermally undeveloped region becomes extremely long for
higher-Pr fluids The entry-length equation (7.12) takes the following form for
Trang 14the thermal entry region3, where the velocity profile is assumed to be
fully developed before heat transfer starts at x = 0:
x e t
Thus, the thermal entry length for the flow of cold water (Pr 10) can be
over 600 diameters in length near the transitional Reynolds number, andoil flows (Pr on the order of 104) practically never achieve fully developedtemperature profiles
A complete analysis of the heat transfer rate in the thermal entry gion becomes quite complicated The reader interested in details shouldlook at [7.3, Chap 8] Dimensional analysis of the entry problem shows
re-that the local value of h depends on uav, µ, ρ, D, c p , k, and x—eight
variables in m, s, kg, and J K This means that we should anticipate fourpi-groups:
NuD = fn (Re D , Pr, x/D) (7.25)
In other words, to the already familiar NuD, ReD, and Pr, we add a new
length parameter, x/D The solution of the constant wall temperature
problem, originally formulated by Graetz in 1885 [7.6] and solved in venient form by Sellars, Tribus, and Klein in 1956 [7.7], includes an ar-rangement of these dimensionless groups, called the Graetz number:
con-Graetz number, Gz≡ ReD Pr D
Figure 7.4 shows values of NuD ≡ hD/k for both the uniform wall
temperature and uniform wall heat flux cases The independent variable
in the figure is a dimensionless length equal to 2/Gz The figure also
presents an average Nusselt number, NuDfor the isothermal wall case:
NuD ≡ hD
k = D k
1
L
3The Nusselt number will be within 5% of the fully developed value if x e t
0.034 Re D PrD for T w= constant The error decreases to 1.4% if the coefficient is raised from 0.034 to 0.05 [Compare this with eqn (7.12) and its context.] For other situations,
the coefficient changes With q w = constant, it is 0.043 at a 5% error level; when the
ve-locity and temperature profiles develop simultaneously, the coefficient ranges between about 0.028 and 0.053 depending upon the Prandtl number and the wall boundary con- dition [7.4, 7.5].