1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Nuclear Power Part 5 potx

30 174 0
Tài liệu đã được kiểm tra trùng lặp

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề Nuclear Power Part 5
Trường học Unknown University
Chuyên ngành Nuclear Power
Thể loại Study document
Năm xuất bản Unknown
Thành phố Unknown City
Định dạng
Số trang 30
Dung lượng 903,62 KB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Nội dung

Operational data from a pressurized water reactor PWR and a coal-fired power plant are analyzed in this section to compare to the sensing line fault modelling.. Operational data from a p

Trang 2

significantly depending on where the void is located These differences in transfer functions

are physically attributable to the nonlinear system behaviour that results from

site-dependent sound speed differences due to the air position (Barbero et al., 2000) as well as

the concomitant changes in the standing wave frequencies (Schohl & Vigander, 1989)

4.3 Sensing Line Leakage

Leakage from a sensing line may be represented using the orifice equation of

p A C

where C f is a flow coefficient, and A is the flow area of the leak The linearized orifice

equation is

Q A C

Q p

where Q0 is the steady-state leakage flow rate The leak therefore becomes a parallel resistive

term in the sensing line model The equivalent resistance obtained from the linearized

version of the orifice equation relating steady-state flow, Q0, and pressure, p0, provides two

functional forms, specifically, ( )2 2 0 ( )

Q

coefficient, C f, ranges from 0.6 for sharp edges to 1.0 for rounded edges The former

expression for R is more useful for determining the leakage amount (Q0) from a PSD,

whereas the latter expression is appropriate for selecting R values to perform initial scoping

analyses based on the primary coolant system pressure (p0) Using the equivalent pi

representation, the leak may be placed at an arbitrary position along the sensing line, as

depicted in Fig 17

Using the model of Fig 17, a 50-m long, 2-cm diameter sensing line was simulated with a

1-mm diameter leak The leak position was varied, specifically, at 25%, 50% and 80% of the

tube length The transfer function results shown in Fig 18 demonstrate that although the

resonant peak frequencies do not change, the peak amplitude does In particular, the

magnitude of the peak at the fundamental frequency decreases as the leak position moves

from the inlet to the outlet, but other harmonics do not necessarily exhibit the same pattern

Such results are consistent with the theoretical and experimental observations by Lee et al

(2005; 2006) who found that the pattern of peak magnitude change can be utilized to

determine the position of a leak in a pipeline For large leaks, the fundamental resonant

peak location also shifts to higher frequencies, as shown in Fig 19

Fig 17 Sensing line with leak somewhere between the sensing line inlet and outlet

Fig 18 Effect on sensing line transfer function by the position (x) of a 1-mm diam leak within a 50-m long (L), 2-cm diam sensing line with water at 15 MPa and 300°C

Fig 19 Effect on sensing line transfer function by the position (x) of a 2.5-mm diam leak within a 50-m long (L), 2-cm diam sensing line with water at 15 MPa and 300°C

5 Operational Data Analysis

In the previous section, the modelling of sensing line anomalies using the equivalent pi circuit representation has been presented Operational data from a pressurized water reactor (PWR) and a coal-fired power plant are analyzed in this section to compare to the sensing line fault modelling

5.1 Sensing Line Blockage in a PWR

Steam pressure measurements were taken from four steam generators The four steam generators are identical so that the four pressure sensing systems are deemed similar to one another Twenty minutes of pressure noise data were acquired using a 200 Hz sampling frequency with a low-pass filter cut-off of 67 Hz Two different data sets were obtained

Trang 3

Pressure sensing line diagnostics in nuclear power plants 115

significantly depending on where the void is located These differences in transfer functions

are physically attributable to the nonlinear system behaviour that results from

site-dependent sound speed differences due to the air position (Barbero et al., 2000) as well as

the concomitant changes in the standing wave frequencies (Schohl & Vigander, 1989)

4.3 Sensing Line Leakage

Leakage from a sensing line may be represented using the orifice equation of

p A

C

Q p

where Q0 is the steady-state leakage flow rate The leak therefore becomes a parallel resistive

term in the sensing line model The equivalent resistance obtained from the linearized

version of the orifice equation relating steady-state flow, Q0, and pressure, p0, provides two

functional forms, specifically, ( )2 2 0 ( )

Q

coefficient, C f, ranges from 0.6 for sharp edges to 1.0 for rounded edges The former

expression for R is more useful for determining the leakage amount (Q0) from a PSD,

whereas the latter expression is appropriate for selecting R values to perform initial scoping

analyses based on the primary coolant system pressure (p0) Using the equivalent pi

representation, the leak may be placed at an arbitrary position along the sensing line, as

depicted in Fig 17

Using the model of Fig 17, a 50-m long, 2-cm diameter sensing line was simulated with a

1-mm diameter leak The leak position was varied, specifically, at 25%, 50% and 80% of the

tube length The transfer function results shown in Fig 18 demonstrate that although the

resonant peak frequencies do not change, the peak amplitude does In particular, the

magnitude of the peak at the fundamental frequency decreases as the leak position moves

from the inlet to the outlet, but other harmonics do not necessarily exhibit the same pattern

Such results are consistent with the theoretical and experimental observations by Lee et al

(2005; 2006) who found that the pattern of peak magnitude change can be utilized to

determine the position of a leak in a pipeline For large leaks, the fundamental resonant

peak location also shifts to higher frequencies, as shown in Fig 19

Fig 17 Sensing line with leak somewhere between the sensing line inlet and outlet

Fig 18 Effect on sensing line transfer function by the position (x) of a 1-mm diam leak within a 50-m long (L), 2-cm diam sensing line with water at 15 MPa and 300°C

Fig 19 Effect on sensing line transfer function by the position (x) of a 2.5-mm diam leak within a 50-m long (L), 2-cm diam sensing line with water at 15 MPa and 300°C

5 Operational Data Analysis

In the previous section, the modelling of sensing line anomalies using the equivalent pi circuit representation has been presented Operational data from a pressurized water reactor (PWR) and a coal-fired power plant are analyzed in this section to compare to the sensing line fault modelling

5.1 Sensing Line Blockage in a PWR

Steam pressure measurements were taken from four steam generators The four steam generators are identical so that the four pressure sensing systems are deemed similar to one another Twenty minutes of pressure noise data were acquired using a 200 Hz sampling frequency with a low-pass filter cut-off of 67 Hz Two different data sets were obtained

Trang 4

approximately three years apart under (1) normal (unblocked) conditions and (2) when the

pressure sensing line of one transducer was blocked

1 2 3 4

5 6

A

B C D E

Fig 20 PSDs of normal steam pressure noise data acquired at 200 Hz sampling frequency

from Channels 3 and 4 (Lin & Holbert, 2009b)

Fig 20 shows the PSDs of the noise signals obtained from Channels 3 and 4 before blockage

occurs There are a number of peaks in Fig 20 for each PSD; however, some of the peaks

originate from the other noise sources Therefore, it is essential to identify the resonant

peaks associated with the pressure sensing system From Eq (19) and simulation results for

complete pressure sensing systems, it is known that the peak intervals are roughly

equivalent Based on this pattern, the resonant peaks caused by the pressure sensing system

are enumerated as indicated in Fig 20 To verify the peak recognition, the PSD from

Channel 3 is compared to that from Channel 4 It can be seen in Fig 20 that the two PSDs are

almost identical up to the sixth peak while the higher frequency portion of the PSDs is not as

similar as it is in the lower frequency region The higher frequency data are corrupted by

other noise sources For example, peak C in Fig 20 is the 50 Hz electrical noise Because the

data from both channels were measured through two similar pressure sensing systems, the

shared resonant peaks are considered related to the pressure sensing system which agrees

with the peak recognition result based on the uniform peak interval

Fig 21 shows the PSDs of the noise signals acquired from the blocked (Channel 3) and the

normal (Channel 4) pressure sensing systems, respectively It can be seen in Fig 21 that the

first three resonant peaks of Channel 3 have vanished due to the blockage and the

magnitudes of the fourth and the sixth peaks are reduced significantly which is consistent

with the severe blockage simulation result shown in Fig 10 However, the PSD curve near

the fifth peak location rises abnormally which is not found from the simulation result This

could be the result of plant equipment or operational variation since the normal data and

abnormal data were taken three years apart It is possible that the 1% upgrade in power for

the NPP in the interim affected the later data

1 2 3

5.2 Sensing Line Voids in a Fossil Unit

Field tests for void detection were conducted at the Kingston steam plant (Schohl, 1987a; Schohl, 1987b; Schohl et al., 1987; Schohl and Vigander, 1989) where nine coal-fired generating units are operating A depiction of the sensing line for pressure measurement at the discharge of the Unit 1 raw water service pump is shown in Fig 22 The 1.02-cm diam copper line has a total length of approximately 80.5 m including an elevation gain of about 13.7 m from the pump, located in the power plant basement, to the control room pressure gauge There are three tees along the line Two of them were installed near the pump and the condenser respectively to provide locations for air injection The third tee was placed under the control room (807) for attachment of a hydrophone

Trang 5

Pressure sensing line diagnostics in nuclear power plants 117

approximately three years apart under (1) normal (unblocked) conditions and (2) when the

pressure sensing line of one transducer was blocked

1 2

3 4

5 6

A

B C D

E

Fig 20 PSDs of normal steam pressure noise data acquired at 200 Hz sampling frequency

from Channels 3 and 4 (Lin & Holbert, 2009b)

Fig 20 shows the PSDs of the noise signals obtained from Channels 3 and 4 before blockage

occurs There are a number of peaks in Fig 20 for each PSD; however, some of the peaks

originate from the other noise sources Therefore, it is essential to identify the resonant

peaks associated with the pressure sensing system From Eq (19) and simulation results for

complete pressure sensing systems, it is known that the peak intervals are roughly

equivalent Based on this pattern, the resonant peaks caused by the pressure sensing system

are enumerated as indicated in Fig 20 To verify the peak recognition, the PSD from

Channel 3 is compared to that from Channel 4 It can be seen in Fig 20 that the two PSDs are

almost identical up to the sixth peak while the higher frequency portion of the PSDs is not as

similar as it is in the lower frequency region The higher frequency data are corrupted by

other noise sources For example, peak C in Fig 20 is the 50 Hz electrical noise Because the

data from both channels were measured through two similar pressure sensing systems, the

shared resonant peaks are considered related to the pressure sensing system which agrees

with the peak recognition result based on the uniform peak interval

Fig 21 shows the PSDs of the noise signals acquired from the blocked (Channel 3) and the

normal (Channel 4) pressure sensing systems, respectively It can be seen in Fig 21 that the

first three resonant peaks of Channel 3 have vanished due to the blockage and the

magnitudes of the fourth and the sixth peaks are reduced significantly which is consistent

with the severe blockage simulation result shown in Fig 10 However, the PSD curve near

the fifth peak location rises abnormally which is not found from the simulation result This

could be the result of plant equipment or operational variation since the normal data and

abnormal data were taken three years apart It is possible that the 1% upgrade in power for

the NPP in the interim affected the later data

1 2 3

5.2 Sensing Line Voids in a Fossil Unit

Field tests for void detection were conducted at the Kingston steam plant (Schohl, 1987a; Schohl, 1987b; Schohl et al., 1987; Schohl and Vigander, 1989) where nine coal-fired generating units are operating A depiction of the sensing line for pressure measurement at the discharge of the Unit 1 raw water service pump is shown in Fig 22 The 1.02-cm diam copper line has a total length of approximately 80.5 m including an elevation gain of about 13.7 m from the pump, located in the power plant basement, to the control room pressure gauge There are three tees along the line Two of them were installed near the pump and the condenser respectively to provide locations for air injection The third tee was placed under the control room (807) for attachment of a hydrophone

Trang 6

811 814

Pump

Unit 1 Condenser

Fig 22 Schematic of Kingston Unit 1 raw water service pump pressure impulse line,

adapted from (Schohl, 1987a)

For the tests, the effects of the control room pressure gauge were removed by closing the

in-line isolation valve (814) below the gauge Then, measurements (termed “pseudo no-air” for

reasons which will be explained later) taken after attempting to purge the line of air were

compared with measurements recorded after air was inserted either close to the pump or

near the condenser The background flow noise was measured using the hydrophone at 815

To remove the random signal content, leaving the periodic components, spectra obtained

from 40 consecutive time records, each 8 seconds long, were averaged together (Schohl,

1987a) Fig 23 shows the effects of air added into the sensing line on power spectra of the

flow noise with respect to air near the pump According to Schohl (1987a), electrical noise

appears in the PSD at 60 Hz, and pump first and second order harmonics occur at 29 Hz and

58 Hz, respectively From Fig 23, it can be recognized that added air manifests itself as an

additional peak at 24.2 Hz, as noted by Schohl (1987a) This peak corresponds to surge

oscillation of the column between the process line and the inserted air Besides, except for

the peak near 44 Hz, the resonant frequencies greater than 24 Hz are all moved slightly

toward higher frequencies because of the added air

In order to verify the developed pressure sensing system model, the raw water sensing line

system (see Fig 22) is represented using a five-segment impulse line equivalent pi circuit, as

shown in Fig 24, with the hydrophone and air realized by a single diaphragm capacitor,

C d = ΔV d / p o, and acoustic capacitors, via Eq (35), respectively According to the Kingston

test report (Schohl, 1987a), this sensing line was not equipped with air bleed lines so that

there was no way to confidently purge all air from the line Furthermore, the trapped air in

the sensing line was distributed among several locations, with each location holding a small

air pocket, rather than centralized at one location as a single large void Therefore, in the

network of Fig 24, two small air pockets realized by two acoustic capacitors are inserted,

respectively, at locations 809 and 814 which are two higher positions (see Fig 22) considered

more likely to trap air Hence, we refer to these results as the “pseudo no-air” cases because

of the two trapped air pockets which are included in the model

Pseudo no-air Air near the pump

Fig 23 The power spectra of the flow noise; data are from (Schohl, 1987a)

Z5 Y5

Y5

P i

P o

Hydrophone (815)

Trapped and Inserted Air (809)

Z1 Y1 Y1

Trapped Air (814) Pump

Trang 7

Pressure sensing line diagnostics in nuclear power plants 119

809 811

814

Pump

Unit 1 Condenser

Fig 22 Schematic of Kingston Unit 1 raw water service pump pressure impulse line,

adapted from (Schohl, 1987a)

For the tests, the effects of the control room pressure gauge were removed by closing the

in-line isolation valve (814) below the gauge Then, measurements (termed “pseudo no-air” for

reasons which will be explained later) taken after attempting to purge the line of air were

compared with measurements recorded after air was inserted either close to the pump or

near the condenser The background flow noise was measured using the hydrophone at 815

To remove the random signal content, leaving the periodic components, spectra obtained

from 40 consecutive time records, each 8 seconds long, were averaged together (Schohl,

1987a) Fig 23 shows the effects of air added into the sensing line on power spectra of the

flow noise with respect to air near the pump According to Schohl (1987a), electrical noise

appears in the PSD at 60 Hz, and pump first and second order harmonics occur at 29 Hz and

58 Hz, respectively From Fig 23, it can be recognized that added air manifests itself as an

additional peak at 24.2 Hz, as noted by Schohl (1987a) This peak corresponds to surge

oscillation of the column between the process line and the inserted air Besides, except for

the peak near 44 Hz, the resonant frequencies greater than 24 Hz are all moved slightly

toward higher frequencies because of the added air

In order to verify the developed pressure sensing system model, the raw water sensing line

system (see Fig 22) is represented using a five-segment impulse line equivalent pi circuit, as

shown in Fig 24, with the hydrophone and air realized by a single diaphragm capacitor,

C d = ΔV d / p o, and acoustic capacitors, via Eq (35), respectively According to the Kingston

test report (Schohl, 1987a), this sensing line was not equipped with air bleed lines so that

there was no way to confidently purge all air from the line Furthermore, the trapped air in

the sensing line was distributed among several locations, with each location holding a small

air pocket, rather than centralized at one location as a single large void Therefore, in the

network of Fig 24, two small air pockets realized by two acoustic capacitors are inserted,

respectively, at locations 809 and 814 which are two higher positions (see Fig 22) considered

more likely to trap air Hence, we refer to these results as the “pseudo no-air” cases because

of the two trapped air pockets which are included in the model

Pseudo no-air Air near the pump

Fig 23 The power spectra of the flow noise; data are from (Schohl, 1987a)

Z5 Y5

Y5

P i

P o

Hydrophone (815)

Trapped and Inserted Air (809)

Z1 Y1 Y1

Trapped Air (814) Pump

Trang 8

Table 3 shows an average absolute difference of 1.1% between the resonant frequencies of the

measured data and the model with trapped air under the pseudo no-air situation, thereby

verifying the model To realize the air near the pump, another air capacitor equivalent to a 14.2

cm3 air pocket is inserted at location 812 as shown in Fig 25 The simulation results based on the

developed models are presented in Fig 26 Comparing Figs 23 and 26, it can be observed that the

simulation results and the measured data still have good agreement after the air is inserted into

the sensing line

Fig 25 Five-segment equivalent pi circuit model for the Kingston plant raw water pressure

sensing line with an air pocket inserted near the pump (Lin & Holbert, 2010)

-70 -60 -50 -40 -30 -20 -10 0 10 20 30

Fig 26 Transfer functions of the Kingston steam plant raw water pressure sensing system

based on the developed pressure system model

6 Conclusions and Future Work

This chapter has detailed the establishment of online condition monitoring methods for pressure

sensing systems Each anomaly is uniquely represented by electrical equivalents, in particular:

 blockage – modified resistance, inductance, and capacitance,

 voids – additional parallel capacitance, and

 leakage – additional parallel resistance

Models of blockage, voids, and leakage associated with instrument lines based on their

electrical representations in conjunction with analyses of the operational data from a NPP

and field test measurements from an operating fossil power plant are presented The operational data and field test measurement analysis results demonstrate behaviour consistent with the simulation results, and thereby validate the developed models

Future research for extending the work presented in this chapter could include:

 studying the situation when multiple anomaly types occur in the sensing system,

 developing effective diagnostic indicators based on the spectral feature variations due to the presence of sensing line anomalies, and

 investigating the applicability of using the developed anomaly models for fault isolation and location

7 References

American Society of Mechanical Engineers (ASME) (2007) Power piping ASME Standard, ASME

B31.1

Barbero, J.; Blázquez, J & Vela, O (2000) Bubbles in the sensing line of nuclear power plant

pressure transmitters: the shift of spectrum resonances Nuclear Engr and Design, Vol

199, No 3, 327-334

Bergh, H & Tijdeman, H (1965) Theoretical and experimental results for the dynamic response

of pressure measuring systems National Aero and Astronautical Research Institute,

Amsterdam, NLR-TR F.238

Blázquez, J & Ballestrín, J (1995) Pressure transmitter surveillance: The dominant real pole case

Prog in Nucl Energy, Vol 29, No 3/4, 139-145

Clark, C (1985) A differential pressure transducer for the measurement of high-frequency

fluctuations in liquids Journal of Physics: Scientific Instruments, Vol 18, 297-302

Gibson, F W (1970) Measurement of the effect of the air bubbles on the speed of sound in water

Acoustical Society of America, Vol 48, No 5, 1195-1197

Glover, J D & Sarma, M S (2000) Power System Analysis and Design Brooks/Cole, CA USA

Gogolyuk, P.; Lysiak, V & Grinberg, I (2004) Mathematical modeling of a synchronous motor

and centrifugal pump combination in steady state Proc of the IEEE PES Power System

Conference and Exposition, 1444-1448

Grunberg, L & Nissan, A H (1949) Mixture law for viscosity Nature, Vol 164, No 4175,

799-800

Hashemian, H M.; Mitchell, D W.; Fain, R E.& Petersen, K M (1993) Long term performance

and aging characteristics of nuclear plant pressure transmitters Report prepared for the U.S Nuclear Regulatory Commission, NUREG/CR-5851

Hashemian, H M (2006) Maintenance of Process Instrumentation in Nuclear Power Plants Springer,

ISBN 978-3-540-33703-4, Berlin, Germany

Iberall, A S (1950) Attenuation of oscillatory pressures in instrument lines Research of the

National Bureau of Standards, Vol 45, No 1, 85-108

International Society of Automation (ISA) (1999) Nuclear safety-related instrument-sensing line

piping and tubing standard for use in nuclear power plants ISA Standard, ISA 67.02.01–

1999

International Society of Automation (ISA) (2005) Fossil fuel power plant instrument piping

installation ISA Standard, ISA 77.70-1994 (R2005)

Izquierdo, J.; Pérez, R & Iglesias, P L (2004) Mathematical models and methods in the water

industry Mathematical and Computer Modelling, Vol 39, No 11/12, 1353-1374

Trang 9

Pressure sensing line diagnostics in nuclear power plants 121

Table 3 shows an average absolute difference of 1.1% between the resonant frequencies of the

measured data and the model with trapped air under the pseudo no-air situation, thereby

verifying the model To realize the air near the pump, another air capacitor equivalent to a 14.2

cm3 air pocket is inserted at location 812 as shown in Fig 25 The simulation results based on the

developed models are presented in Fig 26 Comparing Figs 23 and 26, it can be observed that the

simulation results and the measured data still have good agreement after the air is inserted into

the sensing line

Fig 25 Five-segment equivalent pi circuit model for the Kingston plant raw water pressure

sensing line with an air pocket inserted near the pump (Lin & Holbert, 2010)

-70 -60 -50 -40 -30 -20 -10 0 10 20 30

Fig 26 Transfer functions of the Kingston steam plant raw water pressure sensing system

based on the developed pressure system model

6 Conclusions and Future Work

This chapter has detailed the establishment of online condition monitoring methods for pressure

sensing systems Each anomaly is uniquely represented by electrical equivalents, in particular:

 blockage – modified resistance, inductance, and capacitance,

 voids – additional parallel capacitance, and

 leakage – additional parallel resistance

Models of blockage, voids, and leakage associated with instrument lines based on their

electrical representations in conjunction with analyses of the operational data from a NPP

and field test measurements from an operating fossil power plant are presented The operational data and field test measurement analysis results demonstrate behaviour consistent with the simulation results, and thereby validate the developed models

Future research for extending the work presented in this chapter could include:

 studying the situation when multiple anomaly types occur in the sensing system,

 developing effective diagnostic indicators based on the spectral feature variations due to the presence of sensing line anomalies, and

 investigating the applicability of using the developed anomaly models for fault isolation and location

7 References

American Society of Mechanical Engineers (ASME) (2007) Power piping ASME Standard, ASME

B31.1

Barbero, J.; Blázquez, J & Vela, O (2000) Bubbles in the sensing line of nuclear power plant

pressure transmitters: the shift of spectrum resonances Nuclear Engr and Design, Vol

199, No 3, 327-334

Bergh, H & Tijdeman, H (1965) Theoretical and experimental results for the dynamic response

of pressure measuring systems National Aero and Astronautical Research Institute,

Amsterdam, NLR-TR F.238

Blázquez, J & Ballestrín, J (1995) Pressure transmitter surveillance: The dominant real pole case

Prog in Nucl Energy, Vol 29, No 3/4, 139-145

Clark, C (1985) A differential pressure transducer for the measurement of high-frequency

fluctuations in liquids Journal of Physics: Scientific Instruments, Vol 18, 297-302

Gibson, F W (1970) Measurement of the effect of the air bubbles on the speed of sound in water

Acoustical Society of America, Vol 48, No 5, 1195-1197

Glover, J D & Sarma, M S (2000) Power System Analysis and Design Brooks/Cole, CA USA

Gogolyuk, P.; Lysiak, V & Grinberg, I (2004) Mathematical modeling of a synchronous motor

and centrifugal pump combination in steady state Proc of the IEEE PES Power System

Conference and Exposition, 1444-1448

Grunberg, L & Nissan, A H (1949) Mixture law for viscosity Nature, Vol 164, No 4175,

799-800

Hashemian, H M.; Mitchell, D W.; Fain, R E.& Petersen, K M (1993) Long term performance

and aging characteristics of nuclear plant pressure transmitters Report prepared for the U.S Nuclear Regulatory Commission, NUREG/CR-5851

Hashemian, H M (2006) Maintenance of Process Instrumentation in Nuclear Power Plants Springer,

ISBN 978-3-540-33703-4, Berlin, Germany

Iberall, A S (1950) Attenuation of oscillatory pressures in instrument lines Research of the

National Bureau of Standards, Vol 45, No 1, 85-108

International Society of Automation (ISA) (1999) Nuclear safety-related instrument-sensing line

piping and tubing standard for use in nuclear power plants ISA Standard, ISA 67.02.01–

1999

International Society of Automation (ISA) (2005) Fossil fuel power plant instrument piping

installation ISA Standard, ISA 77.70-1994 (R2005)

Izquierdo, J.; Pérez, R & Iglesias, P L (2004) Mathematical models and methods in the water

industry Mathematical and Computer Modelling, Vol 39, No 11/12, 1353-1374

Trang 10

Izquierdo, J & Iglesias, P L (2002) Mathematical modeling of hydraulic transients in simple

systems Mathematical and Computer Modelling, Vol 35, No 7/8, 801-812

Kafesaki, M.; Penciu, R S & Economou, E N (2000) Air bubbles in water: A strongly multiple

scattering medium for acoustic wave The American Physical Society, Vol 84, No 26,

6050-6053

Landua, L D & Lifshitz, E M (1959) Fluid Mechanics, Addison-Wesley, London

Lee, P J.; Vítkovský, J P.; Lambert, M F.; Simpson, A R & Liggett, J A (2005) Leak location

using the pattern of the frequency response diagram in pipelines: a numerical study

Journal of Sound and Vibration, Vol 284, No 3-5, 1051-1073

Lee, P.J.; Lambert, M F.; Simpson, A R.; Vítkovský, J P & Liggett, J (2006) Experimental

verification of the frequency response method for pipeline leak detection Journal of

Hydraulic Research, Vol 44, No 5, 693–707

Lin, K & Holbert, K E (2009a) Applying the equivalent pi circuit to the modeling of hydraulic

pressurized lines Mathematics and Computers in Simulation, Vol 79, No 7, 2064-2075

Lin, K & Holbert, K E (2009b) Blockage diagnostics for nuclear power plant pressure

transmitter sensing lines Nuclear Engineering and Design, Vol 239, No 2, 365–372 Lin, K & Holbert, K E (2010) Void diagnostics in liquid-filled pressure sensing lines Progress in

Nuclear Energy, Vol 52, No 5, 503-511

Matko, D.; Geiger, G & Gregoritza, W (2000) Pipeline simulation techniques Mathematics and

Computers in Simulation, Vol 52, No 3, 211-230

Matko, D & Geiger, G (2002) Models of pipelines in transient mode Mathematical and Computer

Modelling of Dynamical Systems, Vol 8, No 1, 117-136

Müllens, J A & Thie, J A (1989) Pressure noise in pressurized water reactors U.S Nuclear

Regulatory Commission, NUREG/CR-5383

Olson, H F (1957) Acoustical Engineering, D Van Nostrand Co., ISBN 0193007045, Princeton

Schohl, G A (1987a) Tests at Kingston Plant of Techniques for Void Detection in Sensing Lines,

Tennessee Valley Authority Report WR28-1-670-100

Schohl, G A (1987b) Additional Test and Analysis of Techniques for Air Detection in Sensing

Lines, Tennessee Valley Authority Report WR28-1-670-102

Schohl, G A.; Vigander, S & Kuzniak, W C (1987) Detection of air in sensing lines from

standing wave frequencies, Transactions of the American Nuclear Society, Vol 55, 720-721

Schohl, G A & Vigander, S (1989) Air detector for liquid-filled sensing lines U.S Patent, no

4,858,460

Schönfeld, J C (1954) Analogy of hydraulic, mechanical, acoustic and electric systems Applied

Scientific Research B, Vol 3, No 1, 417-450

Sherstyuk, A N (2000) Speed of sound in a homogeneous liquid-air mixture Chemical and

Petroleum Engineering, Vol 36, Nos 5-6, 363-366

Sullivan, G P.; Pugh, R.; Melendez, A P & Hunt, W D (2004) Operations & Maintenance Best

Practices, A guide to achieving operational efficiency, Release 2.0, U.S Department of Energy, Federal Energy Management Program

Thie, J.A (1981) Power Reactor Noise American Nuclear Society, ISBN 0-89448-025-1, La Grange

Park, Illinois

Tyree, M T & Ewers, F W (1991) The hydraulic architecture of trees and other woody plants

New Phytologist, Vol 119, No 3, 345-360

Westerhof, N et al (1969) Analog studies of the human systemic arterial tree Journal of

Biomechanics, Vol 2, No 2, 121-143

Trang 11

Probabilistic Safety Assessment and Risk-Informed Decision-Making 123

Probabilistic Safety Assessment and Risk-Informed Decision-Making

Probabilistic Safety Assessment is a standardized tool for assessing and improving nuclear

power plant safety (ASME RA-S-2002, 2002; S-294, 2005; RA-S-2008, 2008) It is also used for

assessment and improvement of the reliability of various systems in other industries, e.g air

and space industry and chemical industry For the case of new nuclear power plants it may

be required as a part of the safety analysis report, which is the main document needed for

licensing of the plant operation

2 History and State of the Art

Probabilistic risk analysis or probabilistic safety assessment has developed significantly in

the last five decades from its first steps (Keller & Modarres, 2005), when the report known as

WASH-740 was written in the year 1957 (WASH-740, 1957)

The term probabilistic risk analysis was more used in United States of America, while term

probabilistic safety assessment was more used in Europe Sometimes, the term probabilistic

safety assessment was even used to specify only the systems reliability and accident

sequences up to the core damage frequency, which may only refer to level 1, while the term

probabilistic risk analysis was used to specify also the containment systems, which may

refer to level 2, and consequence analysis, which may refer to level 3, in addition

(NUREG/CR-2300, NUREG/CR-2815, 1985)

The WASH-740 study focused on the undesired consequences of large loss of coolant

accident as the leading source of the worst radiation release into the environment

A decade later, the risk curves were developed, which showed the small risk of nuclear

power plants compared to other risks including risk caused by human activities and risk

caused by nature itself (Farmer, 1967)

A report WASH-1400 was written in the year 1975 and a large debate followed about the

applicability of the methods and results (WASH-1400, 1975) When the accident at Three

Mile Island happened, it was soon concluded, that suggestions of WASH-1400 were very

useful and wider applicability of the methods and results followed in the United States of

America in order to prevent similar and other accidents (NUREG/CR-2300, 1982;

NUREG/CR-2728, 1983; NUREG/CR-2815, 1985) Similarly, more efforts were put to

8

Trang 12

probabilistic safety assessment in other countries such as Germany (GRS, 1980) and France

(Brisbois et al., 1990)

After the Chernobyl accident in Ukraine, the probabilistic safety assessment has become an

obligation for all plants worldwide e.g the Generic Letter 88-20 in United States of America

(GL 88-20, 1988), e.g the decree for probabilistic safety assessment in Slovenia

A number of documents were prepared nationally (1150, 1989;

NUREG/CR-4550, 1990; HSE, 1992) and internationally (50-P-4, 1992; 50-P-8, 1995; 50-P-12, 1996)

including guidelines and examples of applications (NUREG/CR-6141, 1995) Wider

performance of probabilistic safety assessment followed in the industry and in the

regulatory bodies (YVL-2.8, 2003; S-294, 2005) The activities include the developed

standards for probabilistic safety assessment (ASME RA-S-2002, 2002; S-294, 2005; IEC

61025, 2006; RA-S-2008, 2008) Standard ASME RA-S-2002 evolved from year 2002 to 2005

and 2008

The further step of assessing risks was achieved by development of risk-informed

decision-making, which has brought forward the risk analyses into the acceptance of decisions

considering the risk analyses results The background for risk-informed decision-making in

United States of America is policy document from 1995 (60 FR 42622, 1995) The application

procedures are described in regulatory guides, which evolved in years of their use (RG

1.174, 2002; RG 1.177, 1998; RG 1.200, 2007; RG 1.201, 2006) The practical applications are

conducted (Vaurio, 1995; Harunuzzaman & Aldemir, 1996; Čepin & Mavko, 1997; Martorell

et al., 2006)

National Aeronautics and Space Administration began to use probabilistic risk assessment

methods in 1967, following the disastrous fire on Apollo 1 (PRA NASA Guide, 2002)

Engineers completed a fault tree analysis for the entire Apollo system They relied on highly

conservative measures and data They estimated so high failure probabilities for Apollo

missions that the results led to a distrust of probabilistic risk assessment results However,

following the Challenger explosion in 1986, probabilistic risk assessment at national

aeronautics and space administration was revived, and the Columbia break-up in 2003

reiterated the need for risk analyses

National aeronautics and space administration used risk assessment and a combination of

fault and event trees methods to model possible accident scenarios for the shuttle and

International Space Station (ISS) programs (Maggio, 1996)

2.1 Lessons from the past

Unfortunately, the probabilistic safety assessment has always achieved more attention after

some major accident That was the case with Three Mile Island and Chernobyl in the nuclear

industry and in the case of Apollo and Challenger in the case of space industry

Nowadays, the probabilistic safety assessment is performed and it is used for

decision-making in the most of the nuclear power plants and in the space programs (Apostolakis,

2004) The emphasis of probabilistic safety assessment to nuclear power plants as a

standardised way to assess and improve safety is placed forward in this book

3 Methods of Probabilistic Safety Assessment

The primary methods, which are integrated into probabilistic safety assessment, include

fault tree analysis and event tree analysis (Kumamoto & Henley, 1996; NUREG/CR-2300,

1982; NUREG/CR-2815, 1985) The fault tree analysis is oriented to analyses of systems (NUREG-0492, 1981; Vesely et al., 2002; IEC 61025, 2006) The event tree analysis is oriented

to connections between the systems (Papazoglou, 1998; Swaminathan & Smidts, 1999)

3.1 Fault Tree Analysis

The fault tree is a tool to identify and assess all combinations of undesired events in the context of system operation and its environment that can lead to the undesired state of a system (NUREG-0492, 1981; Vesely et al., 2002; Čepin & Mavko, 2002) It is not a process to identify all undesired events, but it is oriented only to those which can lead to the undesired state of the system

Undesired state of the system is represented by a top event The top event is an undesired event, which represents undesired state of the system of interest The top event of the fault tree example on Fig 1 is defined as “SS1 fails to deliver water from point A to point B” and

it means that the safety system 1 fails to accomplish its mission

The bottom part of Fig 1 represents the example system, for which the fault tree is developed SS1 system has to deliver specified amount of water from point A to B Example system includes two redundant lines of the system One line of the system is of enough capacity to accomplish success criteria of the system: line 1 or line 2 can realise the system mission

Box B3 represents the pump B3, which has to run and box B4 represents the valve B4, which has to be open in order that the water is delivered to point B Box B1 represents operator action, which insures water, if automatic pump operation and valve opening on line 1 are not successful Box B5 represents the pump B5, which has to run and box B6 represents the valve B6, which has to be open in order that the water is delivered to point B Box B2 represents operator action, which insures water, if automatic pump operation and valve opening on line 2 are not successful The initial states of components include stopped pumps and closed valves

The fault tree is developed in sense of faults So, the top event usually means that the system under investigation fails or at least one of its functions fails If the system success criteria require at least one out of two system portions to operate, the failure to meet this success criteria is represented in the top event as a failure of two out of two system portions The duality between success criteria and failure occurrences has to be considered properly Logical gates connect the basic events to the top event Logical gates on Fig 1 are represented with abbreviations Gi (e.g G1, G2, G3 and G4) They represent the logic connections between the components of the system They include the logic connection between operation of the system and operator actions They are identified by the name code and they include description They are defined from point of view of possible faults, which can cause the top event Each logical gate can be either the AND gate, where both input event occurrences are required for the output event, or the OR gate, where at least one of input event occurrences is required for the output event , or the K/N gate, where at least K input event occurrences are required for the output event In theory, other logical gates can

be used, such as NOR or NAND, but they are usually excluded from practical use Negated gates are not desired because of assumptions used at evaluation of the fault trees

Gate G1 represents the failure of line 1 to deliver water to point B

Gate G2 represents the failure of line 2 to deliver water to point B

Trang 13

Probabilistic Safety Assessment and Risk-Informed Decision-Making 125

probabilistic safety assessment in other countries such as Germany (GRS, 1980) and France

(Brisbois et al., 1990)

After the Chernobyl accident in Ukraine, the probabilistic safety assessment has become an

obligation for all plants worldwide e.g the Generic Letter 88-20 in United States of America

(GL 88-20, 1988), e.g the decree for probabilistic safety assessment in Slovenia

A number of documents were prepared nationally (1150, 1989;

NUREG/CR-4550, 1990; HSE, 1992) and internationally (50-P-4, 1992; 50-P-8, 1995; 50-P-12, 1996)

including guidelines and examples of applications (NUREG/CR-6141, 1995) Wider

performance of probabilistic safety assessment followed in the industry and in the

regulatory bodies (YVL-2.8, 2003; S-294, 2005) The activities include the developed

standards for probabilistic safety assessment (ASME RA-S-2002, 2002; S-294, 2005; IEC

61025, 2006; RA-S-2008, 2008) Standard ASME RA-S-2002 evolved from year 2002 to 2005

and 2008

The further step of assessing risks was achieved by development of risk-informed

decision-making, which has brought forward the risk analyses into the acceptance of decisions

considering the risk analyses results The background for risk-informed decision-making in

United States of America is policy document from 1995 (60 FR 42622, 1995) The application

procedures are described in regulatory guides, which evolved in years of their use (RG

1.174, 2002; RG 1.177, 1998; RG 1.200, 2007; RG 1.201, 2006) The practical applications are

conducted (Vaurio, 1995; Harunuzzaman & Aldemir, 1996; Čepin & Mavko, 1997; Martorell

et al., 2006)

National Aeronautics and Space Administration began to use probabilistic risk assessment

methods in 1967, following the disastrous fire on Apollo 1 (PRA NASA Guide, 2002)

Engineers completed a fault tree analysis for the entire Apollo system They relied on highly

conservative measures and data They estimated so high failure probabilities for Apollo

missions that the results led to a distrust of probabilistic risk assessment results However,

following the Challenger explosion in 1986, probabilistic risk assessment at national

aeronautics and space administration was revived, and the Columbia break-up in 2003

reiterated the need for risk analyses

National aeronautics and space administration used risk assessment and a combination of

fault and event trees methods to model possible accident scenarios for the shuttle and

International Space Station (ISS) programs (Maggio, 1996)

2.1 Lessons from the past

Unfortunately, the probabilistic safety assessment has always achieved more attention after

some major accident That was the case with Three Mile Island and Chernobyl in the nuclear

industry and in the case of Apollo and Challenger in the case of space industry

Nowadays, the probabilistic safety assessment is performed and it is used for

decision-making in the most of the nuclear power plants and in the space programs (Apostolakis,

2004) The emphasis of probabilistic safety assessment to nuclear power plants as a

standardised way to assess and improve safety is placed forward in this book

3 Methods of Probabilistic Safety Assessment

The primary methods, which are integrated into probabilistic safety assessment, include

fault tree analysis and event tree analysis (Kumamoto & Henley, 1996; NUREG/CR-2300,

1982; NUREG/CR-2815, 1985) The fault tree analysis is oriented to analyses of systems (NUREG-0492, 1981; Vesely et al., 2002; IEC 61025, 2006) The event tree analysis is oriented

to connections between the systems (Papazoglou, 1998; Swaminathan & Smidts, 1999)

3.1 Fault Tree Analysis

The fault tree is a tool to identify and assess all combinations of undesired events in the context of system operation and its environment that can lead to the undesired state of a system (NUREG-0492, 1981; Vesely et al., 2002; Čepin & Mavko, 2002) It is not a process to identify all undesired events, but it is oriented only to those which can lead to the undesired state of the system

Undesired state of the system is represented by a top event The top event is an undesired event, which represents undesired state of the system of interest The top event of the fault tree example on Fig 1 is defined as “SS1 fails to deliver water from point A to point B” and

it means that the safety system 1 fails to accomplish its mission

The bottom part of Fig 1 represents the example system, for which the fault tree is developed SS1 system has to deliver specified amount of water from point A to B Example system includes two redundant lines of the system One line of the system is of enough capacity to accomplish success criteria of the system: line 1 or line 2 can realise the system mission

Box B3 represents the pump B3, which has to run and box B4 represents the valve B4, which has to be open in order that the water is delivered to point B Box B1 represents operator action, which insures water, if automatic pump operation and valve opening on line 1 are not successful Box B5 represents the pump B5, which has to run and box B6 represents the valve B6, which has to be open in order that the water is delivered to point B Box B2 represents operator action, which insures water, if automatic pump operation and valve opening on line 2 are not successful The initial states of components include stopped pumps and closed valves

The fault tree is developed in sense of faults So, the top event usually means that the system under investigation fails or at least one of its functions fails If the system success criteria require at least one out of two system portions to operate, the failure to meet this success criteria is represented in the top event as a failure of two out of two system portions The duality between success criteria and failure occurrences has to be considered properly Logical gates connect the basic events to the top event Logical gates on Fig 1 are represented with abbreviations Gi (e.g G1, G2, G3 and G4) They represent the logic connections between the components of the system They include the logic connection between operation of the system and operator actions They are identified by the name code and they include description They are defined from point of view of possible faults, which can cause the top event Each logical gate can be either the AND gate, where both input event occurrences are required for the output event, or the OR gate, where at least one of input event occurrences is required for the output event , or the K/N gate, where at least K input event occurrences are required for the output event In theory, other logical gates can

be used, such as NOR or NAND, but they are usually excluded from practical use Negated gates are not desired because of assumptions used at evaluation of the fault trees

Gate G1 represents the failure of line 1 to deliver water to point B

Gate G2 represents the failure of line 2 to deliver water to point B

Trang 14

The AND gate of the top event shows that both lines has to fail (line 1 has to fail and line 2

has to fail) in order that the system fails

Gate G3 represents failures of automatic actions of pump B3 and valve B4 in order to

provide water to point B

Gate G4 represents failures of automatic actions of pump B5 and valve B6 in order to

provide water to point B

Logical equations suit their graphical representation:

SS1=G1 * G2 G1=G3 * B1 G3=B3 + B4 G2=G4 * B2 G4=B5 + B6

* represents logical AND + represents logical OR

Top event describes

Line 2 of the system

Fig 1 Fault tree example

Basic events are the ultimate parts of the fault tree, which represent undesired events, such

as component failure modes, missed actuation signals, human errors (NUREG/CR-1278,

1983), contributions of testing and maintenance activities and common cause contributions

Basic events on Fig 1 are represented with abbreviations Bi (e.g B1, B2, B3, B4, B5 and B6)

They are identified by name code and they include description of the failure mode and

identification of the component under investigation

Basic event B3 represents failure of pump B3 to start and run for specified period of time at

specified capacity Basic event B4 represents failure of valve B4 to open and stay open for

the specified period of time Basic event B1 represents failure of operator to establish water

flow if automatic action was not successful Similarly is with basic events B2, B5 and B6 on

the other line

The fault tree is mathematically represented by a set of Boolean equations or by the fault

tree figure itself The Boolean equations and the fault tree for the example system are

presented on Fig 1

Numbers below the basic events represent their failure probabilities, which are either obtained from data bases or they are calculated with the probabilistic models based on data about the previous experience with those or similar components and their failure modes that are defined in the respective basic events

The qualitative fault tree analysis is the process of Boolean reduction of a set of Boolean equations The rules of Boolean algebra are presented on Table 1 The sign for product suits the AND logic and the sign for sum suits the OR logic

Associate Law (X+Y)+Z=X+(Y+Z) (XY)Z=X(YZ) Distributive Law X(Y+Z)=XY+XZ (X+Y)Z=XZ+YZ

The logical equation representing the fault tree has to be written as the sum of products The rules of the Boolean algebra are used for rewriting of the equation For example fault tree from Fig 1 , eq 2 represents such required reformulation of eq 1

SS1 = B3*B1* B5*B2+B4*B1*B5*B2+ B3*B1*B6*B2+ B4*B1* B6*B2 (2) The general expression for the minimal cut sets is the following

n

i i

MCS SS

SS - top event, MCSi - minimal cut set i,

n - number of minimal cut sets

Trang 15

Probabilistic Safety Assessment and Risk-Informed Decision-Making 127

The AND gate of the top event shows that both lines has to fail (line 1 has to fail and line 2

has to fail) in order that the system fails

Gate G3 represents failures of automatic actions of pump B3 and valve B4 in order to

provide water to point B

Gate G4 represents failures of automatic actions of pump B5 and valve B6 in order to

provide water to point B

Logical equations suit their graphical representation:

SS1=G1 * G2 G1=G3 * B1

G3=B3 + B4 G2=G4 * B2 G4=B5 + B6

* represents logical AND + represents logical OR

Top event describes

Line 2 of the system

Fig 1 Fault tree example

Basic events are the ultimate parts of the fault tree, which represent undesired events, such

as component failure modes, missed actuation signals, human errors (NUREG/CR-1278,

1983), contributions of testing and maintenance activities and common cause contributions

Basic events on Fig 1 are represented with abbreviations Bi (e.g B1, B2, B3, B4, B5 and B6)

They are identified by name code and they include description of the failure mode and

identification of the component under investigation

Basic event B3 represents failure of pump B3 to start and run for specified period of time at

specified capacity Basic event B4 represents failure of valve B4 to open and stay open for

the specified period of time Basic event B1 represents failure of operator to establish water

flow if automatic action was not successful Similarly is with basic events B2, B5 and B6 on

the other line

The fault tree is mathematically represented by a set of Boolean equations or by the fault

tree figure itself The Boolean equations and the fault tree for the example system are

presented on Fig 1

Numbers below the basic events represent their failure probabilities, which are either obtained from data bases or they are calculated with the probabilistic models based on data about the previous experience with those or similar components and their failure modes that are defined in the respective basic events

The qualitative fault tree analysis is the process of Boolean reduction of a set of Boolean equations The rules of Boolean algebra are presented on Table 1 The sign for product suits the AND logic and the sign for sum suits the OR logic

Associate Law (X+Y)+Z=X+(Y+Z) (XY)Z=X(YZ) Distributive Law X(Y+Z)=XY+XZ (X+Y)Z=XZ+YZ

The logical equation representing the fault tree has to be written as the sum of products The rules of the Boolean algebra are used for rewriting of the equation For example fault tree from Fig 1 , eq 2 represents such required reformulation of eq 1

SS1 = B3*B1* B5*B2+B4*B1*B5*B2+ B3*B1*B6*B2+ B4*B1* B6*B2 (2) The general expression for the minimal cut sets is the following

n

i i

MCS SS

SS - top event, MCSi - minimal cut set i,

n - number of minimal cut sets

Ngày đăng: 20/06/2014, 11:20

TỪ KHÓA LIÊN QUAN