YK 6 On load voltage regulating controller Operation Instruction Guizhou Changzheng Electric Co ,Ltd Welcome to use On Load Tap Changer of Guizhou Changzheng! Please read the operating instructions of[.]

Trang 1

YK-6 On-load voltage regulating

controller

Operation Instruction

Guizhou Changzheng Electric Co.,Ltd

Trang 2

Welcome to use On Load Tap Changer of Guizhou Changzheng!

Please read the operating instructions of this product before you put the on load tap changer into service Please pay special attention to the following items:

1 Check and accept the products according to the packing list when receiving products Keep the evidence if there are any damages during transportation in order to claim compensation from the responsible party and protect your rights

2 The tap changer only can be used with the transformer which specified in the order You need to consult with our company in advance if you want to change the purpose of this product

3 The installation, put into operation, maintenance and repair of the product should

be complied with the operating instructions and relevant provisions of security

All data in this manual may be different in details from the tap-changer that we delivered We reserve the right to change without notice

Trang 3

Content

1 General introduction………1

2 Main technical parameters………1

3 Panel drawings………2

4 Outline and installation method………3

5 Controller wiring………4

6 Controller interface and parameter settings………6

7 Operation and maintenance………15

8 File and spare parts………15

9 Notice to customer………15

10 Appendix: MODBUS communication protocol………15

2019.5.10

Trang 4

1 General introduction

1.1 Safety instructions

Personnel engaged in the installation, commissioning, operation, maintenance and repair of this unit must:

- Qualified professional qualifications

- Strict compliance with the operating instructions of this manual

Illegal operation or misuse may result in:

- serious personal injury

- Damage to the device and the user's equipment

- Reduce the efficiency of this unit

This instruction emphasized some important matters of safety instruction in four ways

Warning

Give the word of “Warning” when ignoring a requirement will cause the life damage

of operator This is a warning of danger to life and health, disregarding this warning can lead to the serious or fatal injury

Careful

Give the word of “Careful” when ignoring a requirement will lead to the damage to the equipments This information indicates particular danger to this device or other equipment of the user, but the serious or fatal injury can’t be excluded

2 Main technical parameter

1 set RS485 communicate port;

1 set optical fiber: multimode ,62.5/125μm,ST Contact, wave length 820nm, maximum transmission distance 1kM。

The above two are used to communicate with the local control module ZDK controller, mutually standby, follow the MODBUS protocol

Trang 5

AC 0-500V

Voltage regulation accuracy

Range: 0.1-9.9%, step 0.1%

Actual voltage Range: 0-500V

1 group BCD code

1 group status signal

1 group alarm signal

Passive normally open contact output (contact load capacity: 1A / 240V AC, 0.5A / 24V

DC, 0.3A / 220V DC)

(Input by external device)

Interface

1 group RS485 (A, B) communication port

1 group TCP / IP 100M network port (RJ45)

9

Display content

1 Tap position, tap position action status

2 various parameter settings

3 Parameter display: various status signals, local body failure, temperature, the number of operations

4 Log records query

3.1 Front panel diagram (Figure 1)

Touch screen Button

Trang 6

3.2 Back panel diagram (Figure 2)

4 Outline and installation

4.1 Outline as show as Figure 3

Trang 7

4.2 Installation method can be used screws to install fixed for the front panel,also can

be used on both sides of the bracket locking installation (Figure 4)

Figure 4 (both sides of the bracket locking installation method diagram)

Trang 8

5.1 Working power connection

Working power AC 85 ~ 265V, 50 / 60Hz

5.2 Controller and motor drive unit connection

The connection between controller and electric mechanism is provided with

RS485 communication port and optical fiber interface These two ports are used for communication with ZDK controller of local ZD motor control unit and are mutually standby Routine recommended RS485 communication port, the use of optical

interface to be special orders

X3 terminal shown in Table 2

Table 2 Terminal

number

Terminal

labeling

Terminal meaning

Signal

X3-1 A

Communication Interface RS485

Follow the MODBUS protocol

G for the shield connection X3-2 B

X3-3 G

5.3 X1 input, output terminals shown in Table 3

Table 3 Terminal

X1-3 D-COM Tap position BCD code COM

BCD code output

Passive normally open contact (Contact load capacity: 1A / 240V AC, 0.5A / 24V DC, 0.3A / 220V DC)

X1-4 D01 Tap position bit BCD code 20

X1-5 D02 Tap position bit BCD code 21

X1-6 D04 Tap position bit BCD code 22

X1-7 D08 Tap position bit BCD code 23

X1-8 D10 Tap position bit BCD code20

X1-9 D20 Tap position tens BCD code21

X1-10 S-COM Limit output common Status signal

Trang 9

X1-11 LMT1 Min position limit output output

X1-12 LMTN Max position limit output

X1-13 RUN Run signal output

X1-14 I-R Remote command state

X1-15 I-D Motor drive command status

X1-16 I-L Local (controller) instruction status

X1-17 I-A Automatic control instructions state

X1-18 W-COM Alarm signal common

Alarm signal output

X1-19 STEP-OU

X1-20 FAULT Fault alarm

X1-21 1→N Remote command input (1 → N)

Remote input

Passive normally open contact (Input by external device)

X1-22 STOP Remote command input (stop)

X1-23 N→1 Remote command input (N → 1)

X1-24 R-COM Remote command input common

5.4 TCP / IP (RJ45) network port to transmit the tap position, operation command signals, various status signals, alarm signals, etc., for connection with other intelligent devices (LED) The network port can also be used with another YK-6 controller port

to connect to run in parallel functions

5.5 When sampling the voltage input, connect the potential transformer PT, the access range is AC 0-500V

5.6 Ground mark " " must be reliably grounded

6.Controller interface and parameter settings

The controller uses 4.3-inch LCD touch

The maximum number of controllers that can parallel

connection and using network ports is 2

Prompt:

Only the realization of automatic voltage regulator control

access to the sampling voltage

Trang 10

6.1 Turn on the main interface

Power on the controller after the main interface appears

System fault: When controller detects a fault in local electric mechanism,

mark is displayed and flashes, otherwise the mark is not displayed on the interface Communication failure: When controller has a problem with local electric mechanism

communication connection, the mark is displayed and flashes, otherwise the interface does not display this mark

Prompt:

In all the settings and query interface are blocked 1 → N, N → 1, STOP

instruction operation, only in the main interface can be instruction operation

Setting

Alone

Search

Manual

Trang 11

6.2 User interface

Run ID: Displayed while the tap switch is running Displayed when 1→N, displayed when N→1

6.3 Query Interface

After touching the mark on the home screen, the query interface is displayed

6.4 Real-time parameter display interface

When the “Parameter” icon is touched on the query interface, the real-time parameter display interface is displayed

Trang 12

参数 Parameter

Working status: There are three kinds of status: local, stop, and remote

Instruction selection: There are three states: manual, automatic, and remote

Lock state: There are two states, unlock and lock (For external access blocking signal detection)

Running status: There are two kinds of status, they are in place and running

Control status: There are two kinds of status: ready and fault

Fault type: There are three types of status, namely, open/closed, power failure, and self-test failure

Communication address: The communication address between this controller and the local ZDK controller It is set to "1" at the factory

6.5 Log Display Interface

When the "Log" icon is touched on the query interface, the log display interface

Trang 13

6.6 Parameter Setting Interface

After to touching the on the home screen, the parameter setting interface is displayed

Disable operation identification: " " mark appears during all parameter setting, and latch 1 → N, N → 1, STOP instruction operation

6.7 Working Mode Selection Interface

The operating mode selection interface is displayed after touching the "operation mode" mark under the parameter setting interface

In this interface, the "Alone" mode is the default setting of the controller When parallel control is required, "parallel master" or "parallel slave" is selected

6.8 Communication Address Setting Interface

When the “parallel slave” icon is touched under the operation mode selection interface, the communication address setting interface is displayed

Trang 14

In parallel operation, when the controller is set to "parallel master", the controller

communication address defaults to 01; when the controller is set to "parallel slave",

the communication address needs to be reset, and all slave address codes participating

in the parallel connection must not be repeated

6.9 instruction selection interface

When the “Instruction Select” icon is touched under the parameter setting

interface, the command selection interface is displayed

The "Manual" mode under this interface is the controller default setting

6.10 Automatic Mode Parameter Setting Interface

The automatic mode parameter setting interface is displayed after touching the

"automatic" mark on the instruction selection interface

Trang 15

Only the setting value field needs to be set in this interface

Delay time setting: Set according to the required operating frequency of the switch in the range of 5-180S; set the delay time, it must be more than 10 seconds Under the premise of guaranteeing the power supply quality, set the delay time as long

as possible This can avoid frequent tap changer operation and extend the life of the switch

Setting voltage and voltage regulation accuracy settings:

Connect a sampling voltage of 100V; adjust the output voltage of the regulator so that the output voltage deviates from the ±2.5% voltage value of the 100V sampling voltage, that is:

Lower limit voltage = setting voltage - setting voltage × pressure regulation accuracy;

The upper limit voltage = setting voltage + setting voltage × precision of voltage regulation;

Example: setting voltage is 100V, voltage regulation accuracy is set to 2.5%; Then: the lower limit voltage = 100V-100V × 2.5% = 97.5V;

The upper limit voltage = 100V + 100V × 2.5% = 102.5V;

When the sampling voltage is lower than the set lower limit voltage, the controller itself issues a "1→N" command;

When the sampling voltage is higher than the set upper limit voltage, the controller itself issues an "N→1" command;

After the delay time set by the controller is delayed (for example, 10 seconds delay), the switch shall switch to the corresponding 1→N or N→1 direction synchronously, and adjust the voltage to “set voltage”=“actual” The output voltage" realizes the automatic control of the output voltage of the transformer system

Precision of voltage

regulation

Setting voltage

Step size Range

Unit Setting parameter

Content

Setting value

Delay

Prohibit operation

Trang 16

6.11 Auto-adjusting the main interface

When the YK-6 controller operates in the auto-regulation mode, a real-time

histogram will appear below the number of tap positions Both sides of the histogram

display the real-time values of the setting voltage and the actual voltage when the

sampling voltage is within the setting range The bar graph is green when there is no

need to regulate the voltage, and it is red when it is out of the setting range When the

sampling voltage exceeds the setting range and the corresponding delay time is

performed, the pressure adjustment command is automatically issued

6.12 Parallel Voltage Regulator Main Interface

When the YK-6 controller is operating in the shunt regulator mode, the

mark is displayed on the left side of the screen

When the controller participating in the parallel connection loses

Trang 17

synchronization, the mark is displayed at the bottom right of the interface

6.13 Participate in parallel interface

After touching the mark on the main interface of the parallel voltage regulator, the participating parallel interface is displayed

参与并联控制器 Participating in parallel control

从机 1 Slave 1

分接位置 Tap position 00

This screen shows all slaves participating in parallel control

Prompt:

After the mark is displayed, all 1 → N, N → 1, and STOP

instructions are operated, and the controller sends an out-of-step alarm signal Synchronization corrections need to be set up to be manually corrected

individually

Trang 18

6.14 Time setting interface

6.15 Network Parameters Interface

In the TCP / IP settings, the IP address is the IP address of the controller If you need

to access the unit by IP address, set the corresponding address

Prohibit

operation

Prompt:

Working mode selection "parallel main" also need to participate in the parallel

number of slaves to choose from

Trang 19

7 Operating and maintenance

7.1 The user to install the correct wiring and the corresponding parameter settings can

be put into use after the controller

7.2 controller in use, should always be kept clean, there should be no conductive dust covering the body and the terminal

8 Documents and spare parts

 Product Certificate: One

 Manual: One

 1-24 plug: a group (factory installed in the X1 socket)

 1-5 Plug: a group (factory installed in the X2 socket)

 1-3 Plug: a group (factory installed in the X3 socket)

 Mounting bracket: two

10 Appendix: MODBUS protocol

YK-6 controller using MODBUS RTU protocol

YK-6 controller communication physical layer using optical or RS485, baud rate

4800, the data format for the 1 start bit, 8 data bits, no parity, a stop bit

The YK-6 controller opens 03, 05, and 06 function codes to make it easier for the user to read information about the controller, and to perform operations of raising, lowering, and stopping the controller, and modifying the communication address of the machine

Read data (function code 03H)

An example of the following table is an example of reading the current tap position (register 03) from the No 01 slave

The data frame received by the slave (YK-6 controller)

Start address Low

Read data number high

Read data number low

CRC16 low

CRC16 high

Data length Data segment

(2 bytes)

CRC16 low CRC16

high