1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Iec 60034 1 2017

152 1 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Tiêu đề Rotating electrical machines – Part 1: Rating and performance
Chuyên ngành Electrical Engineering
Thể loại International Standard
Năm xuất bản 2017
Thành phố Geneva
Định dạng
Số trang 152
Dung lượng 2,09 MB

Các công cụ chuyển đổi và chỉnh sửa cho tài liệu này

Cấu trúc

  • 4.1 Declaration of duty (17)
  • 4.2 Duty types (18)
    • 4.2.1 Duty type S1 – Continuous running duty (18)
    • 4.2.2 Duty type S2 – Short-time duty (19)
    • 4.2.3 Duty type S3 – Intermittent periodic duty (19)
    • 4.2.4 Duty type S4 – Intermittent periodic duty with starting (20)
    • 4.2.5 Duty type S5 – Intermittent periodic duty with electric braking (22)
    • 4.2.6 Duty type S6 – Continuous operation periodic duty (23)
    • 4.2.7 Duty type S7 – Continuous operation periodic duty with electric braking (24)
    • 4.2.8 Duty type S8 – Continuous operation periodic duty with related load/speed changes (24)
    • 4.2.9 Duty type S9 – Duty with non-periodic load and speed variations (26)
    • 4.2.10 Duty type S10 – Duty with discrete constant loads and speeds (26)
  • 5.1 Assignment of rating (28)
  • 5.2 Classes of rating (28)
    • 5.2.1 Rating for continuous running duty (28)
    • 5.2.2 Rating for short-time duty (28)
    • 5.2.3 Rating for periodic duty (28)
    • 5.2.4 Rating for non-periodic duty (29)
    • 5.2.5 Rating for duty with discrete constant loads and speeds (29)
    • 5.2.6 Rating for equivalent loading (29)
  • 5.3 Selection of a class of rating (29)
  • 5.4 Allocation of outputs to class of rating (30)
  • 5.5 Rated output (30)
    • 5.5.1 DC generators (30)
    • 5.5.2 AC generators (30)
    • 5.5.3 Motors (30)
    • 5.5.4 Synchronous condensers (30)
  • 5.6 Rated voltage (30)
    • 5.6.1 DC generators (30)
    • 5.6.2 AC generators (31)
  • 5.7 Co-ordination of voltages and outputs (31)
  • 5.8 Machines with more than one rating (31)
  • 6.1 General (31)
  • 6.2 Altitude (31)
  • 6.3 Maximum ambient air temperature (31)
  • 6.4 Minimum ambient air temperature (32)
  • 6.5 Water coolant temperature (32)
  • 6.6 Standstill, storage and transport (32)
  • 6.7 Purity of hydrogen coolant (32)
  • 7.1 Electrical supply (32)
  • 7.2 Form and symmetry of voltages and currents (33)
    • 7.2.1 AC motors (33)
    • 7.2.2 AC generators (34)
    • 7.2.3 Synchronous machines (34)
    • 7.2.4 DC motors supplied from static power converters (35)
  • 7.3 Voltage and frequency variations during operation (36)
  • 7.4 Three-phase a.c. machines operating on unearthed systems (38)
  • 7.5 Voltage (peak and gradient) withstand levels (38)
  • 8.1 Thermal class (39)
  • 8.2 Reference coolant (39)
  • 8.3 Conditions for thermal tests (40)
    • 8.3.1 Electrical supply (40)
    • 8.3.2 Temperature of machine before test (40)
    • 8.3.3 Temperature of coolant (40)
    • 8.3.4 Measurement of coolant temperature during test (40)
  • 8.4 Temperature rise of a part of a machine (41)
  • 8.5 Methods of measurement of temperature (41)
    • 8.5.1 General (41)
    • 8.5.2 Resistance method (41)
    • 8.5.3 Embedded temperature detector (ETD) method (41)
    • 8.5.4 Thermometer method (41)
  • 8.6 Determination of winding temperature (41)
    • 8.6.1 Choice of method (41)
    • 8.6.2 Determination by resistance method (42)
    • 8.6.3 Determination by ETD method (44)
    • 8.6.4 Determination by thermometer method (44)
  • 8.7 Duration of thermal tests (45)
    • 8.7.1 Rating for continuous running duty (45)
    • 8.7.2 Rating for short-time duty (45)
    • 8.7.3 Rating for periodic duty (45)
    • 8.7.4 Ratings for non-periodic duty and for duty with discrete constant loads (45)
  • 8.8 Determination of the thermal equivalent time constant for machines of duty (45)
  • 8.9 Measurement of bearing temperature (45)
  • 8.10 Limits of temperature and of temperature rise (46)
    • 8.10.1 General (46)
    • 8.10.2 Indirect cooled windings (46)
    • 8.10.3 Direct cooled windings (51)
    • 8.10.4 Adjustments to take account of hydrogen purity on test (52)
    • 8.10.5 Permanently short-circuited windings, magnetic cores and all structural (52)
    • 8.10.6 Commutators and sliprings, open or enclosed and their brushes and (52)
  • 9.1 Routine tests (54)
  • 9.2 Withstand voltage test (55)
  • 9.3 Occasional excess current (57)
    • 9.3.1 General (57)
    • 9.3.2 Generators (58)
    • 9.3.3 Motors (except commutator motors and permanent magnet motors) (58)
    • 9.3.4 Commutator machines (58)
  • 9.4 Momentary excess torque for motors (58)
    • 9.4.1 Polyphase induction motors and d.c. motors (58)
    • 9.4.2 Polyphase synchronous motors (59)
    • 9.4.3 Other motors (59)
  • 9.5 Pull-up torque (59)
  • 9.6 Safe operating speed of cage induction motors (59)
  • 9.7 Overspeed (60)
  • 9.8 Short-circuit current for synchronous machines (61)
  • 9.9 Short-circuit withstand test for synchronous machines (61)
  • 9.10 Commutation test for commutator machines (62)
  • 9.11 Total harmonic distortion (THD) for synchronous machines (62)
    • 9.11.1 General (62)
    • 9.11.2 Limits (62)
    • 9.11.3 Tests (62)
  • 10.1 General (62)
  • 10.2 Marking (63)
  • 11.1 Protective earthing of machines (64)
  • 11.2 Shaft-end key(s) (66)
  • 12.1 General (66)
  • 12.2 Tolerances on values of quantities (66)
  • 13.1 General (68)
  • 13.2 Immunity (68)
    • 13.2.1 Machines not incorporating electronic circuits (68)
    • 13.2.2 Machines incorporating electronic circuits (69)
  • 13.3 Emission (69)
  • 13.4 Immunity tests (69)
  • 13.5 Emission measurements (69)

Nội dung

4.2 Duty types 4.2.1 Duty type S1 – Continuous running duty Operation at a constant load maintained for sufficient time to allow the machine to reach thermal equilibrium, see Figure 1..

Declaration of duty

The purchaser is responsible for declaring the duty, which can be specified in one of three ways: a) numerically, if the load remains constant or varies predictably; b) as a time sequence graph illustrating the variable quantities; or c) by choosing a duty type from S1 to S10 that is at least as demanding as the anticipated duty.

The duty type shall be designated by the appropriate abbreviation, specified in 4.2, written after the value of the load

An expression for the cyclic duration factor is given in the relevant duty type figure

The purchaser typically cannot supply the moment of inertia of the machine (J M) or the relative thermal life expectancy (TL), as detailed in Annex A; these values are supplied by the manufacturer.

Where the purchaser does not declare a duty, the manufacturer shall assume that duty type S1 (continuous running duty) applies.

Duty types

Duty type S1 – Continuous running duty

Operation at a constant load maintained for sufficient time to allow the machine to reach thermal equilibrium, see Figure 1

The appropriate abbreviation is S1 t t t Θ max

P V electrical losses Θ temperature Θ max maximum temperature attained t time

Figure 1 – Continuous running duty – Duty type S1

Duty type S2 – Short-time duty

Operating a machine at a constant load for a limited time, which is shorter than the duration needed to achieve thermal equilibrium, is followed by a sufficient de-energized rest period This rest allows the machine temperatures to stabilize within 2 K of the coolant temperature, as illustrated in Figure 2.

The appropriate abbreviation is S2, followed by an indication of the duration of the duty,

P V electrical losses Θ temperature Θ max maximum temperature attained t time

∆t P operation time at constant load

Duty type S3 – Intermittent periodic duty

NOTE Periodic duty implies that thermal equilibrium is not reached during the time on load

The article discusses a series of identical duty cycles, each comprising a period of operation under constant load followed by a de-energized rest phase, as illustrated in Figure 3 In this duty cycle, the starting current is managed to ensure it does not significantly impact the temperature rise.

The appropriate abbreviation is S3, followed by the cyclic duration factor

P V electrical losses Θ temperature Θ max maximum temperature attained t time

T C time of one load cycle

∆t P operation time at constant load

∆t R time de-energized and at rest Cyclic duration factor = ∆t P /T C

Duty type S4 – Intermittent periodic duty with starting

NOTE Periodic duty implies that thermal equilibrium is not reached during the time on load

A sequence of identical duty cycles, each cycle including a significant starting time, a time of operation at constant load and a time de-energized and at rest, see Figure 4

The correct abbreviation is S4, which is accompanied by the cyclic duration factor, the moment of inertia of the motor (J_M), and the moment of inertia of the load (J_ext), both referenced to the motor shaft.

P V electrical losses T C time of one load cycle Θ temperature ∆t D starting/accelerating time Θ max maximum temperature attained ∆t P operation time at constant load

∆t R time de-energized and at rest Cyclic duration factor = (∆t D + ∆t P )/T C

Figure 4 – Intermittent periodic duty with starting – Duty type S4

Duty type S5 – Intermittent periodic duty with electric braking

NOTE Periodic duty implies that thermal equilibrium is not reached during the time on load

A series of identical duty cycles is defined, with each cycle comprising a starting time, a period of operation under constant load, a duration of electric braking, and a resting phase when de-energized, as illustrated in Figure 5.

The correct abbreviation is S5, which is accompanied by the cyclic duration factor, the moment of inertia of the motor (J_M), and the moment of inertia of the load (J_ext), both referenced to the motor shaft.

P load T C time of one load cycle

P V electrical losses ∆t D starting/accelerating time Θ temperature ∆t P operation time at constant load Θ max maximum temperature attained ∆t F time of electric braking t time ∆t R time de-energized and at rest

Figure 5 – Intermittent periodic duty with electric braking – Duty type S5

Duty type S6 – Continuous operation periodic duty

NOTE Periodic duty implies that thermal equilibrium is not reached during the time on load

A sequence of identical duty cycles includes periods of operation under constant load followed by periods of operation at no load, with no downtime or rest periods.

The appropriate abbreviation is S6, followed by the cyclic duration factor

P V electrical losses T C time of one load cycle Θ temperature ∆t P operation time at constant load Θ max maximum temperature attained ∆t V operation time at no-load

Figure 6 – Continuous operation periodic duty – Duty type S6

Duty type S7 – Continuous operation periodic duty with electric braking

NOTE Periodic duty implies that thermal equilibrium is not reached during the time on load

The article describes a series of identical duty cycles, where each cycle includes a starting phase, a period of operation under constant load, and a phase of electric braking Notably, there is no interval of de-energization or rest during these cycles, as illustrated in Figure 7.

The appropriate abbreviation is S7, followed by the moment of inertia of the motor (J M ) and the moment of inertia of the load (J ext ), both referred to the motor shaft

P V electrical losses T C time of one load cycle Θ temperature ∆t D starting/accelerating time Θ max maximum temperature attained ∆t P operation time at constant load Cyclic duration factor = 1 ∆t F time of electric braking

Figure 7 – Continuous operation periodic duty with electric braking – Duty type S7

Duty type S8 – Continuous operation periodic duty with related load/speed changes

NOTE Periodic duty implies that thermal equilibrium is not reached during the time on load

A series of identical duty cycles is characterized by a constant load operation at a predetermined rotational speed, followed by one or more operations at varying constant loads corresponding to different speeds This variation can be achieved, for instance, by altering the number of poles in induction motors Notably, there is no period of de-energization or rest during these cycles.

The correct abbreviation is S8, which includes the motor's moment of inertia (J M) and the load's moment of inertia (J ext), both referenced to the motor shaft Additionally, it encompasses the load, speed, and cyclic duration factor for each speed condition.

Example: S8 J M = 0,5 kg × m 2 J ext = 6 kg × m 2 16 kW 740 min −1 30 %

P V electrical losses T C time of one load cycle Θ temperature ∆t D starting/accelerating time Θ max maximum temperature attained ∆t P operation time at constant load

(P1, P2, P3) n speed ∆t F time of electric braking (F1, F2)

Figure 8 – Continuous operation periodic duty with related load/speed changes – Duty type S8

Duty type S9 – Duty with non-periodic load and speed variations

The duty involves non-periodic variations in load and speed within the allowable operating range, often featuring frequent overloads that can significantly surpass the reference load.

For this duty type, a constant load appropriately selected and based on duty type S1 is taken as the reference value ("P ref " in Figure 9) for the overload concept t t t t Θ

P ref reference load ∆t D starting/accelerating time

P V electrical losses ∆t P operation time at constant load Θ temperature ∆t F time of electric braking Θ max maximum temperature attained ∆t R time de-energized and at rest n speed ∆t S time under overload

Figure 9 – Duty with non-periodic load and speed variations – Duty type S9

Duty type S10 – Duty with discrete constant loads and speeds

A duty cycle is defined by a set number of discrete load values, or equivalent loading, along with speed, if applicable Each load and speed combination must be sustained long enough for the machine to achieve thermal equilibrium Notably, the minimum load in a duty cycle can be zero, indicating a no-load condition or when the machine is de-energized and at rest.

The abbreviation S10 represents the per unit quantities p/∆t for the specific load and its duration, along with the per unit quantity TL for the relative thermal life expectancy of the insulation system The reference for thermal life expectancy is based on continuous running duty and permissible temperature rise limits for duty type S1 When the system is de-energized and at rest, the load is denoted by the letter r.

The TL value must be rounded to the nearest multiple of 0.05 Guidance on the importance of this parameter and how to derive its value can be found in Annex A.

For this duty type a constant load appropriately selected and based on duty type S1 shall be taken as the reference value (‘P ref ’ in Figure 10) for the discrete loads

The discrete load values typically represent equivalent loading derived from time integration It is not essential for each load cycle to be identical; rather, each load must be sustained long enough to achieve thermal equilibrium Additionally, every load cycle should be integrable to ensure a consistent relative thermal life expectancy.

P i constant load within a load cycle t i time of a constant load within a cycle

P ref reference load based on duty type S1 T C time of one load cycle

P V electrical losses, denoted as ∆Θ, represent the difference in temperature rise of the winding at various loads during a single cycle compared to the temperature rise associated with the reference load Θ at duty cycle S1 This analysis considers the temperature n speed and the reference temperature Θref at the specified duty type S1.

Figure 10 – Duty with discrete constant loads – Duty type S10

Assignment of rating

The manufacturer is responsible for assigning the rating as outlined in section 3.2, choosing from the classes defined in sections 5.2.1 to 5.2.6 The selected class designation must be indicated following the rated output In the absence of a specified designation, the rating defaults to continuous running duty.

When accessory components like reactors and capacitors are integrated by the manufacturer into a machine, the rated values must pertain to the supply terminals of the entire system.

NOTE This does not apply to power transformers connected between the machine and the supply

Special considerations are required when assigning ratings to machines fed from or supplying static converters IEC TS 60034-25 gives guidance on this.

Classes of rating

Rating for continuous running duty

A rating at which the machine may be operated for an unlimited period, while complying with the requirements of this document

This class of rating corresponds to duty type S1 and is designated as for the duty type S1.

Rating for short-time duty

A rating at which the machine may be operated for a limited period, starting at ambient temperature, while complying with the requirements of this document

This class of rating corresponds to duty type S2 and is designated as for the duty type S2.

Rating for periodic duty

A rating at which the machine may be operated on duty cycles, while complying with the requirements of this document

This class of rating corresponds to one of the periodic duty types S3 to S8 and is designated as for the corresponding duty type

Unless otherwise specified, the duration of a duty cycle shall be 10 min and the cyclic duration factor shall be one of the following values:

Rating for non-periodic duty

A rating at which the machine may be operated non-periodically while complying with the requirements of this document

This class of rating corresponds to the non-periodic duty type S9 and is designated as for the duty type S9.

Rating for duty with discrete constant loads and speeds

The machine can operate continuously under duty type S10, adhering to specified requirements, with a maximum permissible load that considers all components, including insulation systems and bearings, in relation to thermal life expectancy and expansion Unless stated otherwise in relevant IEC standards, this maximum load should not exceed 1.15 times the load value for duty type S1 The minimum load can be zero, allowing for no-load operation or when the machine is de-energized and at rest Additional application considerations for this rating class are detailed in Annex A.

This class of rating corresponds to the duty type S10 and is designated as for the duty type S10

NOTE Other relevant IEC standards may specify the maximum load in terms of limiting winding temperature (or temperature rise) instead of per unit load based on duty type S1.

Rating for equivalent loading

The rating for testing indicates the constant load at which a machine can operate until thermal equilibrium is achieved, leading to a stator winding temperature rise equivalent to the average temperature increase during one complete load cycle of the designated duty type.

The determination of an equivalent rating should take account of the varying load, speed and cooling of the duty cycle

This class of rating, if applied, is designated 'equ'.

Selection of a class of rating

A machine manufactured for general purpose shall have a rating for continuous running duty and be capable of performing duty type S1

If the duty has not been specified by the purchaser, duty type S1 applies and the rating assigned shall be a rating for continuous running duty

When a machine is intended to have a rating for short-time duty, the rating shall be based on duty type S2, see 4.2.2

For machines designed to handle varying loads, including periods of no-load or times when the machine is de-energized and at rest, the appropriate rating should be classified as a periodic duty rating This rating must be based on one of the specified duty types, ranging from S3 to S8, as outlined in sections 4.2.3 to 4.2.8.

When a machine is intended to supply non-periodically variable loads at variable speeds, including overloads, the rating shall be a rating for non-periodic duty based on duty type S9, see 4.2.9

For machines designed to handle discrete constant loads, including periods of overload or no-load conditions, the appropriate rating should be based on duty type S10, as outlined in section 4.2.10.

Allocation of outputs to class of rating

In the determination of the rating:

For duty types S1 to S8, the specified value(s) of the constant load(s) shall be the rated output(s), see 4.2.1 to 4.2.8

For duty types S9 and S10, the reference value of the load based on duty type S1 shall be taken as the rated output, see 4.2.9 and 4.2.10.

Rated output

DC generators

The rated output is the output at the terminals and shall be expressed in watts (W).

AC generators

The rated output is the apparent power at the terminals and shall be expressed in volt- amperes (VA) together with the power factor

The rated power factor for synchronous generators shall be 0,8 lagging (over-excited), unless otherwise specified by the purchaser

NOTE A P-Q capability diagram (power chart) indicating the limits of operation, provides more detailed information on generator’s performance.

Motors

The rated output is the mechanical power available at the shaft and shall be expressed in watts (W)

In certain countries, the mechanical power output of motors is commonly expressed in horsepower, where 1 horsepower (h.p.) is equivalent to 745.7 watts, and 1 metric horsepower (ch or cheval) has a specific conversion as well.

Synchronous condensers

The rated output is the reactive power at the terminals and shall be expressed in volt-amperes reactive (var) in leading (under-excited) and lagging (over-excited) conditions.

Rated voltage

DC generators

For direct current (d.c.) generators designed to function within a limited voltage range, the rated output and current should be applicable at the maximum voltage of that range, unless stated otherwise.

AC generators

A.C generators designed for operation within a limited voltage range must have their rated output and power factor applicable at any voltage within that range, unless specified otherwise.

Co-ordination of voltages and outputs

Building machines for every voltage rating is impractical Typically, for a.c machines, preferred voltage ratings above 1 kV are determined by design and manufacturing factors, as outlined in Table 1.

Rated voltage kV Minimum rated output kW (or kVA)

Machines with more than one rating

For machines with more than one rating, the machine shall comply with this document in all respects at each rating

For multi-speed machines, a rating shall be assigned for each speed

When a rated quantity, such as output, voltage, or speed, can take on multiple values or vary continuously between two limits, it is essential to specify the rating at these values or limits This requirement excludes voltage and frequency variations during operation, as outlined in section 7.3, and does not apply to star-delta connections used for starting.

General

Machines must be appropriate for specified site conditions during operation, standstill, storage, and transportation Table 5 outlines the cold coolant inlet temperatures for various cooling types For any site operating conditions that differ from these values, refer to the corrections provided in Clause 8.

Machines operating outside the range of the standard site conditions shall require special consideration.

Altitude

The altitude shall not exceed 1 000 m above sea-level.

Maximum ambient air temperature

The ambient air temperature shall not exceed 40 °C.

Minimum ambient air temperature

Unless otherwise specified, the ambient air temperature for all machines must not fall below −15 °C However, for machines with a rated output exceeding 3,300 kW (or kVA) per 1,000 min⁻¹, those with a rated output below 600 W (or VA), machines featuring a commutator, sleeve bearings, or using water as a primary or secondary coolant, the minimum ambient temperature requirement is set at 0 °C.

Water coolant temperature

For the reference water coolant temperature see Table 5 For other water coolant temperatures see Table 10 The water coolant temperature shall not be less than +5 °C.

Standstill, storage and transport

When temperatures lower than specified in 6.4 are expected during transportation, storage, or after installation at standstill, the purchaser shall inform the manufacturer and specify the expected minimum temperature

Before energizing the machine after extended periods of inactivity, storage, or transportation, it is essential to implement special measures Additionally, specific precautions may be required during non-operational periods Always refer to the manufacturer's instructions for guidance.

Purity of hydrogen coolant

Hydrogen cooled machines shall be capable of operating at rated output under rated conditions with a coolant containing not less than 95 % hydrogen by volume

NOTE For safety reasons, the hydrogen content should at all times be maintained at 90 % or more, it being assumed that the other gas in the mixture is air

To calculate efficiency per IEC 60034-2 standards, the gaseous mixture must consist of 98% hydrogen and 2% air by volume, adhering to the specified pressure and temperature of the re-cooled gas, unless otherwise agreed Windage losses should be determined based on the corresponding density.

Electrical supply

For three-phase alternating current (a.c.) machines operating at 50 Hz or 60 Hz and designed for direct connection to distribution or utilization systems, the rated voltages must be based on the nominal voltages specified in IEC 60038.

NOTE For large high-voltage a.c machines, the voltages may be selected for optimum performance

For a.c machines connected to static converters these restrictions on voltage, frequency and waveform do not apply In this case, the rated voltages shall be selected by agreement

For electrical machines with Type I insulation systems as per IEC 60034-18-41, designed for voltage source converter supply, manufacturers can assign an impulse voltage insulation class (IVIC) The insulation system should meet IVIC C for phase-to-phase and IVIC B for phase-to-ground, or as mutually agreed upon The IVIC level must be documented and ideally displayed on the nameplate.

NOTE For more information on special considerations for converter fed machines, see IEC TS 60034-25

Bus transfers or fast reclosing of an a.c machine, often necessitated by voltage ride-through requirements of grid codes, can result in extremely high peak currents that jeopardize the stator winding overhang Additionally, these actions can generate peak torque levels reaching up to 20 times the rated torque, posing risks to the mechanical structure, including couplings and both driven and driving equipment Consequently, such operations should only be conducted if explicitly specified and approved by the manufacturers of the electric machines and associated equipment.

For electric machines and driven equipment rated at ≤ 10 MW or MVA, slow reclosing exceeding 1.5 times the open circuit time constant is permissible if approved by the manufacturers In contrast, for ratings greater than 10 MW or MVA, the minimum allowable time for slow reclosing must be established through transient analysis by the system integrator, contingent upon manufacturer acceptance.

Form and symmetry of voltages and currents

AC motors

7.2.1.1 AC motors rated for use on a power supply of fixed frequency, supplied from an a.c generator (whether local or via a supply network) shall be suitable for operation on a supply voltage having a harmonic voltage factor (HVF) not exceeding:

– 0,02 for single-phase motors and three-phase motors, including synchronous motors but excluding motors of design N (see IEC 60034-12), unless the manufacturer declares otherwise

The HVF shall be computed by using the following formula:

= n 2 where u n is the ratio of the harmonic voltage U n to the rated voltage U N ; n is the order of harmonic (not divisible by three in the case of three-phase a.c motors); k = 13

Three-phase a.c motors must be designed to operate on a three-phase voltage system where the negative-sequence component does not exceed 1% of the positive-sequence component for extended durations, or 1.5% for short periods lasting a few minutes Additionally, the zero-sequence component should also remain below 1% of the positive-sequence component.

When the limiting values of the high-voltage factor (HVF) and the negative-sequence and zero-sequence components are present simultaneously at rated load, it is crucial that this does not cause harmful temperatures in the motor It is advised that the resulting temperature rise should not exceed approximately 10 K, in accordance with the limits outlined in this document.

In areas with significant single-phase loads, such as induction furnaces, and in rural regions with mixed industrial and domestic systems, power supplies may experience distortion that exceeds acceptable limits Consequently, special arrangements will be required to address these issues.

7.2.1.2 AC motors supplied from static converters have to tolerate higher harmonic contents of the supply voltage; see IEC TS 60034-25

When the supply voltage is highly non-sinusoidal, such as that produced by static converters, both the root mean square (r.m.s.) value of the total waveform and the fundamental component are crucial for assessing the performance of an alternating current (a.c.) machine.

AC generators

Three-phase a.c generators must be capable of powering circuits that, when connected to a system of balanced and sinusoidal voltages, ensure that the harmonic current factor (HCF) does not exceed 0.05 Additionally, the system of currents should maintain that neither the negative-sequence component nor the zero-sequence component surpasses 5% of the positive-sequence component.

The HCF shall be computed by using the following formula:

2 n 2 where i n is the ratio of the harmonic current I n to the rated current I N ; n is the order of harmonic; k = 13

When deformation and imbalance limits are reached simultaneously under rated load, it is crucial that this does not cause harmful temperatures in the generator It is advised that any resulting temperature increase should not exceed approximately 10 K, in accordance with the specified limits in this document.

Synchronous machines

Three-phase synchronous machines must operate continuously on an unbalanced system without exceeding the rated current for any phase The ratio of the negative-sequence current component (I₂) to the rated current (Iₙ) should not surpass the limits specified in Table 2 Additionally, under fault conditions, the product of the squared ratio (I₂/Iₙ)² and time (t) must also remain within the values outlined in Table 2.

Table 2 – Unbalanced operating conditions for synchronous machines

Item Machine type Maximum I 2 / I N value for continuous operation Maximum ( I 2 / I N ) 2 × t in seconds for operation under fault conditions

Salient pole machines and PM excited machines

1 Indirect cooled windings motors 0,1 20 generators 0,08 20 synchronous condensers 0,1 20

2 Direct cooled (inner cooled) stator and/or field windings motors 0,08 15 generators 0,05 15 synchronous condensers 0,08 15

3 Indirect cooled rotor windings air-cooled 0,1 15 hydrogen-cooled 0,1 10

4 Direct cooled (inner cooled) rotor windings

>1 250 ≤1 600 MVA 0,05 5 a For these machines, the value of I 2 /I N is calculated as follows:

I b For these machines, the value of (I 2 /I N ) 2 × t , in seconds, is calculated as follows:

(I 2 / I N ) 2 × t = 8 – 0,005 45 (S N – 350) where in the two footnotes, S N is the rated apparent power in MVA.

DC motors supplied from static power converters

When a d.c motor is powered by a static power converter, the pulsating voltage and current can negatively impact its performance This leads to increased losses and a rise in temperature, making commutation more challenging compared to a d.c motor powered by a pure d.c source.

Motors with a rated output exceeding 5 kW, designed for use with a static power converter, must be specifically engineered for the designated supply Additionally, motor manufacturers may require the inclusion of external inductance to minimize supply undulation.

The static power converter supply shall be characterized by means of an identification code, as follows:

CCC is the identification code from Table 3, which is based on IEC 61148;

U aN is represented by three or four digits that denote the rated alternating voltage at the converter's input terminals, measured in volts (V) The frequency, denoted by f, is indicated by two digits representing the rated input frequency in hertz (Hz).

L consists of one, two or three digits indicating the series inductance to be added externally to the motor armature circuit, in mH If this is zero, it is omitted

(Configuration name) Pair number “m” for arms in IEC 61148

Clause No and title in IEC 61148

(Mixed bridge) m = 3 Same as above

(Full bridge) m = 2 Same as above

(Mixed bridge) m = 2 Same as above

Motors with a rated output of up to 5 kW can be compatible with any static power converter, regardless of whether external inductance is used It is essential that the motor's rated form factor is not exceeded and that the insulation level of the motor armature circuit is suitable for the rated alternating voltage at the static power converter's input terminals.

The output current of the static power converter is assumed to have minimal undulation, ensuring that the current ripple factor remains below 0.1 under rated conditions.

Voltage and frequency variations during operation

A.C machines designed for operation on a fixed frequency power supply from an a.c generator, whether local or from a supply network, experience voltage and frequency variations classified into zone A or zone B, as illustrated in Figure 11 for generators and synchronous condensers, and Figure 12 for motors.

For d.c machines, when directly connected to a normally constant d.c bus, zones A and B apply only to the voltages

A machine must continuously perform its primary function within zone A, as outlined in Table 4, although it is not required to fully meet performance standards at rated voltage and frequency, as indicated by the rating point in Figures 11 and 12 Additionally, temperature increases may exceed those observed at rated voltage and frequency.

A machine must effectively perform its primary function within zone B, although it may show greater performance deviations at rated voltage and frequency compared to zone A Additionally, temperature increases in zone B are likely to exceed those observed at rated conditions and will generally be higher than in zone A It is advisable to avoid prolonged operation at the edge of zone B.

In real-world scenarios, machines may occasionally need to function beyond zone A, but these instances should be minimized in terms of value, duration, and frequency Implementing timely corrective measures, such as reducing output, can help prevent temperature-related damage and extend the machine's lifespan.

The temperature-rise limits outlined in this document are applicable at the rating point, but these limits may be exceeded as the operating point deviates from the rating point In extreme conditions at the boundaries of zone A, temperature rises can exceed the specified limits by approximately 10 K.

An a.c motor can only start at the lower voltage limit if its starting torque is sufficiently aligned with the load's counter-torque, although this is not mandated by the clause For details on the starting performance of design N motors, refer to IEC 60034-12.

NOTE 3 For machines covered by IEC 60034-3, different voltage and frequency limits apply

Table 4 – Primary functions of machines

Item Machine type Primary function

1 AC generator, excluding item 5 Rated apparent power (kVA), at rated power factor where this is separately controllable

2 AC motor, excluding items 3 Rated torque (Nm)

3 Synchronous motor Rated torque (Nm), the excitation maintaining either rated field current or rated power factor, where this is separately controllable

4 Synchronous condenser Rated reactive power (kVAr) within the zone applicable to a generator, see Figure 11, unless otherwise agreed

5 Synchronous generator driven by steam turbines or combustion gas turbines with rated output ≥10 MVA

6 DC generator Rated output (kW)

7 DC motor Rated torque (Nm), the excitation of a shunt motor maintaining rated speed, where this is separately controllable

Y axis voltage p.u 2 zone B (outside zone A)

Figure 11 – Voltage and frequency limits for generators Figure 12 – Voltage and frequency limits for motors

Three-phase a.c machines operating on unearthed systems

Three-phase a.c machines must be designed for continuous operation with the neutral grounded or close to earth potential They should also function on unearthed systems with one line at earth potential for brief periods, such as during normal fault clearance For continuous or extended operation under these conditions, a machine with appropriate insulation levels is necessary.

If the winding does not have the same insulation at the line and neutral ends, this shall be stated by the manufacturer

Consulting the machine manufacturer is essential before earthing or interconnecting the machine's neutral points, as it poses risks related to zero-sequence current components across various frequencies and potential mechanical damage to the windings during line-to-neutral fault conditions.

Voltage (peak and gradient) withstand levels

For a.c machines, the manufacturer shall declare a limiting value for the peak voltage and for the voltage gradient in continuous operation, if required by the customer

For machines used in power drive systems (PDS), see also IEC TS 60034-25

For machines with a specified Impulse Voltage Insulation Class IVIC, see IEC 60034-18-41 in the case of machines designed to operate without partial discharges

For high-voltage a.c machines, see also IEC 60034-15

For creepage and clearance distances of bare live copper, see IEC 60664-1

Thermal class

A thermal class in accordance with IEC 60085 shall be assigned to the insulation systems used in machines

It is the responsibility of the manufacturer of the machine to interpret the results obtained by thermal endurance testing according to the appropriate part of IEC 60034-18

NOTE 1 The thermal class of a new insulation system should not be assumed to be directly related to the thermal capability of the individual materials used in it

NOTE 2 The continued use of an existing insulation system is acceptable where it has been proved by satisfactory service experience.

Conditions for thermal tests

Electrical supply

During the thermal testing of an AC machine, it is crucial that the high voltage factor (HVF) of the supply does not exceed 0.015 Additionally, the negative-sequence voltage component must remain below 0.5% of the positive-sequence component, with the zero-sequence component's influence being disregarded.

According to the agreement, the negative-sequence component of the current system can be measured in place of the negative-sequence component of the voltage system It is stipulated that the negative-sequence component of the current system must not exceed 2.5% of the positive-sequence component.

Temperature of machine before test

If the temperature of a winding is to be determined from the increase of resistance, the initial winding temperature shall not differ from the coolant by more than 2 K

For short-time rating tests (duty type S2), it is essential that the machine's initial temperature during the thermal test is maintained within 5 K of the coolant temperature.

Temperature of coolant

A machine may be tested at any convenient value of coolant temperature See Table 12 (for indirect cooled windings) or Table 15 (for direct cooled windings).

Measurement of coolant temperature during test

The coolant temperature during testing should be determined by averaging the readings from temperature detectors taken at equal intervals during the last quarter of the test duration To minimize errors caused by the time lag in temperature changes of large machines in response to coolant temperature variations, it is essential to implement all reasonable precautions to reduce these fluctuations.

8.3.4.2 Closed machines without heat exchangers (cooled by surrounding ambient air or gas)

Ambient air or gas temperature must be measured using multiple detectors strategically positioned at various points around the machine, including halfway up and at distances of 1 to 2 meters It is essential that each detector is shielded from radiant heat and drafts to ensure accurate readings.

8.3.4.3 Open machines and machines cooled by air or gas from a remote source through ventilation ducts and machines with separately mounted heat exchangers

The temperature of the primary coolant shall be measured where it enters the machine

8.3.4.4 Closed machines with machine-mounted or internal heat exchangers

The temperature of the primary coolant shall be measured where it enters the machine The temperature of the secondary coolant shall be measured where it enters the heat exchanger.

Temperature rise of a part of a machine

The temperature rise, denoted as ∆θ, refers to the difference between the temperature of a specific machine component, measured using the method outlined in section 8.5, and the coolant temperature, which is measured according to section 8.3.4.

To ensure accurate comparison with temperature rise limits (refer to Table 8 or Table 9) or temperature limits (see Table 13), it is essential to measure the temperature right before shutting down the machine at the conclusion of the thermal test, as outlined in section 8.7.

When this is not possible, for example, when using the direct measurement of resistance method, see 8.6.2.3

For machines evaluated under actual periodic duty (duty types S3 to S8), the temperature recorded at the conclusion of the test should be noted as the temperature at the midpoint of the rise period that results in the highest heating during the final operational cycle.

Methods of measurement of temperature

General

Three methods of measuring the temperature of windings and other parts are recognized:

– embedded temperature detector (ETD) method;

Different methods shall not be used as a check upon one another

For indirect testing see IEC 60034-29.

Resistance method

The temperature of the windings is determined from the increase of the resistance of the windings.

Embedded temperature detector (ETD) method

Temperature is measured using built-in detectors such as resistance thermometers, thermocouples, or semiconductor negative coefficient detectors, strategically placed in areas that become inaccessible once the machine is fully assembled.

Thermometer method

Temperature measurement in completed machines is conducted using thermometers on accessible surfaces This includes various types of thermometers such as bulb-thermometers, non-embedded thermocouples, and resistance thermometers In environments with strong or fluctuating magnetic fields, alcohol thermometers are preferred over mercury thermometers for accurate readings.

Determination of winding temperature

Choice of method

In general, for measuring the temperature of the windings of a machine, the resistance method in accordance with 8.5.2 shall be applied (but see also 8.6.2.3.3)

For a.c stator windings of machines having a rated output of 5 000 kW (or kVA) or more the ETD method shall be used

For alternating current (a.c.) stator windings in machines with a rated output between 200 kW and 5,000 kW, manufacturers must select either the resistance method or the ETD method, unless an alternative agreement is made.

For alternating current (a.c.) stator windings in machines with a rated output of 200 kW (or kVA) or less, manufacturers are required to select either the direct measurement method or the superposition method for resistance measurement, unless an alternative agreement is made.

For machines with a rated output of 600 W (or VA) or less, temperature measurement can be conducted using thermometers when the windings are non-uniform or when complex connections are present The temperature rise limits specified in Table 8, item 1d) for the resistance method must be adhered to.

The thermometer method is essential in situations where the resistance method is impractical for measuring temperature rise, particularly with low-resistance commutating coils and compensating windings It is also applicable to single layer windings, whether rotating or stationary, and is commonly used during routine tests on mass-produced machines.

For a.c stator windings having only one coil-side per slot, the ETD method shall not be used for verifying compliance with this document: the resistance method shall be used

For accurate temperature monitoring of windings in service, an embedded detector at the bottom of the slot is ineffective as it primarily measures the iron core temperature A detector positioned between the coil and the wedge provides a closer approximation of the winding temperature, making it more suitable for service checks Since this temperature may be relatively low, establishing the relationship between it and the temperature measured by the resistance method requires a thermal test.

For other windings having one coil-side per slot and for end windings, the ETD method shall not be used for verifying compliance with this document

The resistance method is commonly used for armature windings with commutators and field windings in d.c machines Additionally, for stationary field windings with multiple layers, the ETD method is applicable.

Determination by resistance method

One of the following methods shall be used:

– direct measurement at the beginning and the end of the test, using an instrument having a suitable range;

– measurement by d.c current/voltage in d.c windings, by measuring the current in and the voltage across the winding, using instruments having suitable ranges;

– measurement by d.c current/voltage in a.c windings, by injecting direct current into the winding when de-energized;

– Measurement by d.c current/voltage in a.c windings, by superposing small amount of d.c current into the winding, when energized

The temperature rise, θ 2 – θ a , may be obtained from the formula:

The initial resistance measurement occurs at a winding temperature of θ₁ (°C), while the winding temperature at the conclusion of the thermal test is θ₂ (°C) Additionally, the coolant temperature at the end of the thermal test is denoted as θₐ (°C).

R 1 is the resistance of the winding at temperature θ 1 (cold);

R 2 is the resistance of the winding at the end of the thermal test; k is the reciprocal of the temperature coefficient of resistance at 0 °C of the conductor material

For aluminium k = 225 unless specified otherwise

For practical purposes, the following alternative formula may be found convenient:

To accurately measure temperatures at the conclusion of a thermal test using the direct measurement resistance method, a swift shutdown is essential This process necessitates a well-organized procedure and a sufficient number of personnel.

If the initial resistance reading is obtained within the time interval specified in Table 6, that reading shall be accepted for the temperature measurement

Rated output ( P N ) kW or kVA Time interval after switching off power s

If resistance readings cannot be obtained within the time frame specified in Table 6, they should be taken as soon as possible, but no later than twice the specified interval Additional readings must be recorded approximately every minute until a clear decline from the maximum value is observed These readings should be plotted against time, ideally using a semi-logarithmic scale for temperature or resistance The temperature value derived from this plot will be regarded as the shutdown temperature In cases where successive measurements indicate rising temperatures post-shutdown, the highest recorded value should be used.

If a resistance reading cannot be made until after twice the time interval specified in Table 6, this method of correction shall only be used by agreement

8.6.2.3.4 Windings with one coil-side per slot

For machines with a single coil-side per slot, the resistance method can be applied through direct measurement, provided the machine stops within the time frame outlined in Table 6 If the machine requires more than 90 seconds to come to a complete stop after power is turned off, the superposition method may be utilized, subject to prior agreement.

Determination by ETD method

The detectors shall be suitably distributed throughout the winding and the number of detectors installed shall be not less than six

Efforts will be made to position detectors at locations where the highest temperatures are expected, ensuring they are adequately protected from contact with the primary coolant while maintaining safety standards.

The highest reading from the ETD elements shall be used to determine the temperature of the winding

ETD elements or their connections may fail and give incorrect readings Therefore, if one or more readings are shown to be erratic, after investigation they should be eliminated

8.6.3.2 Two or more coil-sides per slot

The detectors shall be located between the insulated coil-sides within the slot in positions at which the highest temperatures are likely to occur

8.6.3.3 One coil-side per slot

The detectors shall be located between the wedge and the outside of the winding insulation in positions at which the highest temperatures are likely to occur, but see also 8.6.1

Temperature detectors must be positioned between two adjacent coil-sides within the end windings, specifically in areas where the highest temperatures are expected Each detector's sensing point should maintain close contact with the coil-side surface and be sufficiently protected from coolant effects, as referenced in section 8.6.1.

When installing a temperature detector in the end windings of high voltage machines, it is crucial to ensure that the insulation's stress grading remains intact and that potential differences along the winding overhang do not create issues Additionally, the measuring system's ground is capacitively coupled to the high voltage system, meaning that disconnecting the measurement ground can result in immediate overvoltages Therefore, it is essential to implement safety measures to prevent potential damage and avoid serious injuries.

If the stator winding is a direct liquid-cooled bar type, installing a temperature detector in the nozzle area of each bar can indicate potential blockages in the conductor strand cooling passage by monitoring the water outlet temperature.

Determination by thermometer method

To ensure accurate temperature monitoring, thermometers should be strategically positioned at locations where the highest temperatures are expected, such as near the core iron in the end windings These thermometers must be adequately shielded from direct contact with the primary coolant while maintaining effective thermal contact with the winding or other machine components.

The highest reading from any thermometer shall be taken to be the temperature of the winding or other part of the machine.

Duration of thermal tests

Rating for continuous running duty

The test shall be continued until thermal equilibrium has been reached.

Rating for short-time duty

The duration of the test shall be the time given in the rating.

Rating for periodic duty

The manufacturer's assigned rating for equivalent loading should be applied until thermal equilibrium is achieved If an actual duty test is conducted, the specified load cycle must be maintained until nearly identical temperature cycles are observed The criterion for this is that the temperature plot's corresponding points of successive duty cycles must have a gradient of less than 1 K per half hour Measurements should be taken at reasonable intervals over time as needed.

Ratings for non-periodic duty and for duty with discrete constant loads

The rating for equivalent loading assigned by the manufacturer (see 5.2.6) shall be applied until thermal equilibrium has been reached.

Determination of the thermal equivalent time constant for machines of duty

The thermal equivalent time constant under normal ventilation conditions can be approximated from the cooling curve, similar to the method described in section 8.6.2.3 This time constant is calculated to be 1.44 times the duration required for the machine to cool to half of its full load temperature rise after being disconnected from the power supply.

Measurement of bearing temperature

Either the thermometer method or the ETD method may be used

The measuring point shall be as near as possible to one of the two locations specified in Table 7

Type of bearing Measuring point Location of measuring point

Ball or roller A In the bearing housing preferably in contact with the outer ring of the bearing, but not more than 10 mm a from it b

B Outer surface of the bearing housing as close as possible to the outer ring of the bearing

Sleeve or tilting pad A In the pressure zone of the bearing shell c and not more than

10 mm a from the oil-film gap b

In the bearing shell, the distance is measured to the nearest point of the ETD or thermometer bulb For an 'inside out' machine, point A is located within 10 mm of the inner ring on the stationary part, while point B is positioned on the outer surface of the stationary part, as close as possible to the inner ring The bearing shell supports the bearing material and is secured in the housing, with the pressure zone being the section of the circumference that bears the rotor weight and radial loads.

To ensure accurate temperature measurements, it is essential to minimize the thermal resistance between the temperature detector and the object being measured This can be achieved by filling air gaps with thermally conductive paste.

Temperature differences exist between measuring points A and B, as well as between these points and the hottest part of the bearing, influenced by factors such as bearing size For sleeve bearings with pressed-in bushings and ball or roller bearings with an inside diameter of up to 150 mm, the temperature difference between points A and B is generally negligible However, for larger bearings, this temperature difference can reach approximately 15 K.

Limits of temperature and of temperature rise

General

Limits for operation are defined based on the site conditions outlined in Clause 6 and the continuous running duty rating The article also details how to adjust these limits when operating under different conditions or ratings Additionally, it provides guidelines for modifying the limits during thermal testing when the test site conditions vary from the operating site.

Under rated conditions, the temperature at the hottest point of each winding typically remains below the specified thermal class temperature of the insulation system.

The limits are stated relative to the reference coolant specified in Table 5

A rule is given to allow for the purity of hydrogen coolant.

Indirect cooled windings

Temperature rises under reference conditions shall not exceed the limits given in Table 8 (air coolant) or Table 9 (hydrogen coolant) as appropriate for both, ETD and R method if applicable

The temperature differences observed between the ETD and R methods can vary significantly from the limits outlined in Table 8 and Table 9, influenced by the specific machine design and cooling system This analysis does not aim to directly compare the ETD and R methods.

For operating conditions beyond continuous running duty and for rated voltages exceeding 12,000 V, adjustments to the limits must be made as specified in Table 10 Additionally, refer to Table 11 for the coolant temperature limits assumed in Table 10.

In the case of thermometer readings made in accordance with 8.6.1, the limit of temperature rise shall be according to Table 8

For windings that are indirectly cooled by air, if the conditions at the testing location differ from those at the operating site, the adjusted limits specified in Table 12 must be applied at the testing site.

If the adjusted limits in Table 12 result in temperatures at the test site deemed excessive by the manufacturer, an agreement must be reached on the testing procedure and limits.

Adjustments for windings indirectly cooled by hydrogen are not provided at the test site, as it is highly improbable that they will undergo testing at rated load outside of the operating site.

Table 8 outlines the permissible temperature rise limits for windings indirectly cooled by air across various thermal classes, including 130 (B), 155 (F), 180 (H), and 200 (N) The measurement methods utilized are thermometer (Th), resistance (R), and embedded temperature detector (ETD) For AC windings in machines with outputs of 5000 kW or more, the temperature rise limits range from 80-85°C to 145-150°C In machines with outputs between 200 kW and 5000 kW, the limits are set from 80-90°C to 145-160°C For AC windings with outputs of 200 kW or less, the limits are 80°C to 145°C, while those with rated outputs below 600 W have limits from 85°C to 150°C Additionally, self-cooled AC windings without a fan and/or with encapsulated windings also follow similar temperature rise limits The table further details temperature limits for windings of armatures with commutators and field windings of AC and DC machines, with specific notes for synchronous machines with cylindrical rotors.

Insulated stationary field windings of DC machines with multiple layers exhibit varying resistance values, ranging from 70 to 160 ohms Low-resistance field windings of DC machines, also with multiple layers, show compensation windings with resistance values between 80 and 145 ohms Single-layer windings of AC and DC machines, whether exposed or varnished, have resistance values from 90 to 155 ohms For high-voltage AC windings, refer to item 4 of Table 10 for adjustments The superposition test method applied to windings rated at 200 kW or less, with thermal classes 130 (B) and 155 (F), may allow temperature rise limits to exceed by 5 K This also applies to multiple layer windings, provided that the under layers are in contact with the circulating primary coolant.

Table 9 – Limits of temperature rise of windings indirectly cooled by hydrogen

1 AC windings of machines having outputs of 5 000 kW (or kVA) or more or having a core length of 1 m or more

Absolute hydrogen pressure b ≤ 150 kPa (1,5 bar) – 85 a – 105 a

2a AC windings of machines having outputs of less than

5 000 kW (or kVA), or having a core length of less than 1 m 80 85 a 100 110 a

2b DC field windings of a.c and d.c machines other than those in items 3 and 4 80 – 105 –

3 DC field windings of machines having cylindrical rotors 85 – 105 – 4a Low-resistance field windings of more than one layer and compensating windings 80 – 100 –

Single-layer windings with exposed bare or varnished metal surfaces are rated for temperatures between 90°C and 110°C For adjustments related to high-voltage alternating current (a.c.) windings, refer to item 4 in Table 10 Notably, the temperature rise limit is influenced by hydrogen pressure in this case Additionally, this category encompasses multi-layer field windings, provided that each under layer is in contact with the circulating primary coolant.

Table 10 – Adjustments to limits of temperature rise at the operating site of indirect cooled windings to take account of non-reference operating conditions and ratings

Item Operation conditions or rating Adjustment to limit of temperature rise (∆ θ ) in

1a Maximum temperature of ambient air or of the cooling gas at inlet to the machine ( θ c ) and for altitudes of up to

If the difference between the thermal class and the observable limit of temperature, consisting of the sum of the reference cold coolant inlet temperature of

40 °C and the limit of temperature rise according to Table 8 and

Table 9 is less or equal to 5 K:

For a higher altitude replace 40 °C with the value given in Table 11

0 °C ≤ θ c ≤ 40 °C Increased by the amount by which the coolant temperature is less than 40 °C

1b Maximum temperature of ambient air or of the cooling gas at the inlet to the machine ( θ c ) and for altitudes of up to 1 000 m

If the difference between the thermal class and the observable limit of the temperature, consisting of the sum of the reference cold coolant inlet temperature of

40 °C and the limit of temperature rise according to Table 8 and

For a higher altitude replace 40 °C with the value given in Table 11

0 °C ≤ θ c ≤ 40 °C The limit of temperature rise ∆ θ for cold gas temperature θ c shall be ref C ThCl

∆ θ ref limit of temperature rise according to Table 8 or Table 9 at 40 °C θ ThCl temperature of the thermal class (for example 130 °C or 155 °C) θ Cref reference cold coolant temperature

1c 40 °C < θ c ≤ 60 °C Reduced by the amount by which the coolant temperature exceeds 40 °C 1d θ c < 0 °C or θ c > 60 °C By agreement

The maximum temperature of the water at the inlet to water-cooled heat exchangers, as well as the maximum temperature of the ambient water for submersible machines with surface cooling or machines utilizing water jacket cooling, is denoted as \( \theta_w \).

5 °C ≤ θ w ≤ 25 °C Increased by 15 K and by the difference between 25 °C and θ w θ w > 25 °C Increased by 15 K and reduced by the difference between θ w and 25 °C

Item Operation conditions or rating Adjustment to limit of temperature rise ( ∆ θ ) in

3a Altitude (H) – general rule 1 000 m < H ≤ 4 000 m and maximum ambient air temperature not specified

It is assumed that the decreased cooling effect due to altitude is balanced by a reduction in maximum ambient temperature, which remains below 40 °C, ensuring that the total temperature does not exceed this limit.

40 °C plus the Table 8 and Table 9 temperature rises a

The capability of power plant generators is influenced by altitude, as it affects air pressure However, if the absolute coolant pressure remains constant, no adjustments to the generator's capability are necessary, regardless of the altitude.

4 Rated stator winding voltage (U N ) 12 kV < U N ≤ 24 kV ∆θ for embedded temperature detectors (ETD) shall be reduced by 1 K for each 1 kV (or part thereof) from 12 kV up to and including 24 kV

5 b Rating for short-time duty (S2), with rated output less than 5 000 kW (kVA) Increased by 10 K

6 b Rating for non-periodic duty (S9) ∆ θ may be exceeded for short periods during the operation of the machine

The machine's duty rating of 7b for discrete loads (S10) allows for temporary exceedance of the temperature rise (∆θ) during operation It is important to note that for every 100 meters of altitude increase, the ambient temperature decrease is estimated at 1% of the maximum allowable temperature rise.

1 000 m, the maximum ambient air temperature at the operating site can be as shown in Table 11 b For air-cooled windings only

Table 11 – Assumed maximum ambient temperature

Direct cooled windings

Temperatures under reference conditions shall not exceed the limits given in Table 13

For other operating site conditions the limits shall be adjusted according to Table 14

If conditions at the test site differ from those at the operating site, the adjusted limits given in Table 15 shall apply at the test site

If the adjusted limits in Table 15 result in temperatures at the test site deemed excessive by the manufacturer, an agreement must be reached regarding the testing procedure and limits.

Adjustments to take account of hydrogen purity on test

For windings cooled by hydrogen, whether directly or indirectly, temperature rise limits and total temperature limits remain unchanged when the hydrogen concentration in the coolant is between 95% and 100%.

Permanently short-circuited windings, magnetic cores and all structural

components (other than bearings) whether or not in contact with insulation

The temperature rise or the temperature shall not be detrimental to the insulation of that part or to any other part adjacent to it.

Commutators and sliprings, open or enclosed and their brushes and

The temperature rise or temperature of any commutator, slipring, brush or brushgear shall not be detrimental to the insulation of that part or any adjacent part

The temperature of a commutator or slipring must not exceed the limits that the selected brush grade and material can withstand while handling current throughout the entire operating range.

Table 12 – Adjusted limits of temperature rise at the test site (∆θ T ) for windings indirectly cooled by air to take account of test site operating conditions

Item Test condition Adjusted limit at test site ∆ θ T

1 Temperature difference of reference coolant at test site

2 Difference of altitudes of test site (H T ) and operating site (H) 1 000 m < H ≤ 4 000 m

H > 4 000 m or H T > 4 000 m By agreement NOTE 1 ∆ θ is given in Table 8 and adjusted if necessary in accordance with Table 10

NOTE 2 If temperature rise is to be measured above the temperature of the water where it enters the cooler, the effect of altitude on the temperature difference between air and water should strictly be allowed for However, for most cooler designs, the effect will be small, the difference increasing with increasing altitude at the rate of roughly 2 K per 1 000 m If an adjustment is necessary, it should be by agreement

Table 13 – Limits of temperature of directly cooled windings and their coolants

Method of measurement Thermo- meter °C

Item Part of the machine

1 Coolant at the outlet of direct-cooled a.c windings These temperatures are preferred to the values given in item 2 as the basis of rating

1a) Gas (air, hydrogen, helium, etc.) 110 – – 130 – –

3 Field windings of turbine type machines

3a) Cooled by gas leaving the rotor through the following number of outlet regions b

3b) Liquid cooled Observance of the maximum coolant temperature given in item 1b) will ensure that the hotspot temperature of the winding is not excessive

4 Field windings of a.c and d.c machines having d.c excitation other than in item 3

To maintain optimal performance, it is crucial to observe the maximum coolant temperature specified in item 1b), ensuring that the winding's hotspot temperature remains within safe limits No adjustments are applicable for high-voltage a.c windings, as detailed in Table 14, item 2 Additionally, rotor ventilation is categorized based on the number of radial outlet regions along the rotor's length, with special outlet regions for the coolant of the end windings counted as one outlet each Furthermore, a common outlet region for two axially opposed flows is considered as two distinct regions.

Table 14 – Adjustments to limits of temperature at the operating site for windings directly cooled by air or hydrogen to take account of non-reference operating conditions and ratings

Item Operating condition or rating Adjustment to limit of temperature in Table 13

1 Temperature θ c of reference coolant 0 °C ≤ θ c ≤ 40 °C Reduction by the amount of the difference between

40 °C and θ c However, by agreement, a smaller reduction may be applied, provided that for θ c < 10 °C the reduction is made at least equal to the difference between 10 °C and θ c

40 °C < θ c ≤ 60 °C No adjustment θ c < 0 °C or θ c > 60 °C By agreement

2 Rated stator winding voltage (U N ) U N > 11 kV No adjustment

The heat flow is mainly towards the coolant inside the conductors and not through the main insulation of the winding

Table 15 – Adjusted limits of temperature at the test site θ T for windings directly cooled by air to take account of test site operating conditions

Item Test condition Adjusted limit of temperature at test site θ T

1 Difference of reference coolant temperatures of test site ( θ cT ) and

Absolute value of ( θ c – θ cT ) ≤ 30 K θ T = θ operating site ( θ c ) Absolute value of

2 Difference of altitudes of test site (H T ) and operating site (H)

H > 4 000 m or H T > 4 000 m By agreement NOTE θ is given in Table 13 and adjusted if necessary in accordance with Table 14

Routine tests

Routine tests are essential factory tests conducted on all machines assembled at the manufacturer's facility These tests can be performed even if the machine is not fully assembled, as long as it is missing non-essential components Additionally, routine tests do not require the machine to be coupled, with the exception of the open-circuit test for synchronous machines.

The minimum test schedule for machines with a rated output of 20 MW (MVA) or less, as detailed in Table 16, applies to those assembled and tested in the factory For machines rated above 200 kW (kVA), additional routine tests may be conducted This category of synchronous machines encompasses brushless permanent magnet machines.

For d.c machines, depending on size and design, a commutation test under load may be performed as a routine test

Table 16 – Minimum routine tests for machines assembled and tested in the factory of the manufacturer

Synchronous machines DC machines with separate or shunt excitation Motors Generators

1 Resistance of windings (cold) Yes Yes Yes

2 No-load losses and current e Yes – –

3a No-load losses at unity power factor b – Yes d –

3b No-load excitation current at rated voltage by open-circuit test b

4 Excitation current at rated speed and rated armature voltage

5 Open circuit secondary induced voltage at standstill (wound rotor) c

6a Direction of rotation Yes Yes – Yes

The withstand voltage test, as outlined in IEC 60050-411:1996, section 9.2, is applicable with certain exceptions Permanent magnet machines are excluded from this requirement For safety reasons, the test may be conducted at a reduced voltage It is important to note that only one of the tests, either 3a or 3b, is necessary Additionally, there is no need for temperature stabilization when measuring no-load losses.

Withstand voltage test

A test voltage must be applied between the windings under examination and the machine's frame, ensuring that the core and non-tested windings are connected to the frame This test is to be conducted only on a new, fully assembled machine under conditions that mimic normal operation, either at the manufacturer's facility or after installation on-site Additionally, a withstand voltage test should be performed following the completion of the entire testing sequence.

NOTE 1 For high voltage machines, additional methods as described in the parts of IEC 60034-27 can be used to proof the suitability of the machine winding insulation system

The test voltage frequency should match the manufacturer's factory power frequency, with the voltage waveform closely resembling a sine wave The final voltage value must align with Table 17 For machines rated at 6 kV or higher, if power frequency equipment is unavailable, a d.c test may be conducted at a voltage 1.7 times the r.m.s value specified in Table 17, subject to agreement.

NOTE 2 It is recognized that, during a d.c test, the surface potential distribution along the end winding insulation and the ageing mechanisms are different from those occurring during an a.c test

For polyphase machines with a rated voltage exceeding 1 kV, the test voltage must be applied between each phase and the frame, ensuring that the core and other phases are connected to the frame The testing begins at a voltage not exceeding half of the full test voltage, which should then be increased steadily or in increments of no more than 5% of the full value, with a minimum duration of 10 seconds for this increase The full test voltage must be maintained for 1 minute, as specified in Table 17, without any failures occurring during this period, in accordance with IEC 60060-1.

During the routine testing of quantity produced machines up to 200 kW (or kVA) and rated for

U N ≤ 1 kV, the 1 min test may be replaced by a test of 1 s at 120 % of the test voltage specified in Table 17

The acceptance withstand voltage test conducted on the windings at full voltage should not be repeated However, if the purchaser requests a second test after additional drying, the test voltage must be set at 80% of the voltage indicated in Table 17.

To establish the test voltage for d.c motors powered by static power converters, use the greater value between the motor's direct voltage and the r.m.s phase-to-phase rating of the alternating voltage at the static power converter's input terminals, as outlined in Table 17.

Voltage variation according to 7.3 should not be considered when determining the test voltage

Completely rewound windings shall be tested at the full test voltage for new machines

When conducting withstand voltage tests for partially rewound windings or overhauled machines, it is essential to follow a specific procedure For partially rewound windings, testing should occur at 75% of the test voltage designated for new machines, ensuring that the old winding parts are thoroughly cleaned and dried beforehand In the case of overhauled machines, after proper cleaning and drying, the test voltage should be set to 1.5 times the rated voltage, with a minimum of 1,000 V for rated voltages of 100 V or higher, and a minimum of 500 V for rated voltages below 100 V.

Item Machine or part Test voltage (r.m.s.)

1 Insulated windings of rotating machines of rated output less than 1 kW (or kVA) and of rated voltage less than 100 V with the exception of those in items 4 to 8

2 Insulated windings of rotating machines of rated output less than 10 000 kW (or kVA) with the exception of those in item 1 and items 4 to 8 b

1 000 V + twice the rated voltage with a minimum of

3 Insulated windings of rotating machines of rated output 10 000 kW (or kVA) or more with the exception of those in items 4 to 8 b

- up to and including 24 000 V 1 000 V + twice the rated voltage

4 Separately excited field windings of d.c machines 1 000 V + twice the maximum rated circuit voltage with a minimum of 1 500 V

5 Field windings of synchronous generators, synchronous motors and synchronous condensers

- up to, and including 500 V, Ten times the rated field voltage with a minimum of

- above 500 V 4 000 V + twice the rated field voltage

Item Machine or part Test voltage (r.m.s.)

5b) When a machine is intended to be started with the field winding short-circuited or connected across a resistance of value less than ten times the resistance of the winding

Ten times the rated field voltage with a minimum of

When starting the machine, it is essential to connect the field winding across a resistance that is at least ten times greater than the winding's resistance, or to initiate the process with the field windings in an open circuit, regardless of whether a field-dividing switch is used.

The voltage across the terminals of the field winding can reach up to 1,000 V, in addition to twice the maximum value of the root mean square (r.m.s.) voltage that may occur under specified starting conditions This applies to both the entire field winding and any individual section in the case of a sectionalized field winding.

6 Secondary (usually rotor) windings of induction machines or synchronous induction motors if not permanently short-circuited (e.g if intended for rheostatic starting)

For non-reversing motors or those that can only reverse from a standstill, the voltage should be 1,000 V plus twice the open-circuit standstill voltage measured between the slip rings or secondary terminals with the rated voltage applied to the primary windings In contrast, for motors that are reversed or braked by changing the primary supply while in operation, specific voltage considerations must be taken into account.

1 000 V + four times the open-circuit standstill secondary voltage as defined in item 6a)

7 Exciters (except as below) As for the windings to which they are connected

Exception 1: exciters of synchronous motors

(including synchronous induction motors) if connected to earth or disconnected from the field windings during starting

1 000 V + twice the rated exciter voltage, with a minimum of 1 500 V

Exception 2: separately excited field windings of exciters (see item 4)

To avoid redundancy, it is preferable not to repeat the tests outlined in items 1 to 7 However, if testing is necessary for a group of electrically interconnected machines and apparatus, each of which has already successfully passed its withstand voltage test, the applied test voltage should be set at 80% of the lowest test voltage required for any individual component within the arrangement.

9 Devices that are in physical contact with windings, for example, temperature detectors, shall be tested to the machine frame

During the withstand test on the machine, all devices in physical contact with the winding shall be connected to the machine frame

For two-phase windings with a common terminal, the highest r.m.s voltage between any two terminals during operation must be used in calculations Withstand tests for machines with graded insulation require mutual agreement The voltage between field winding terminals under specified starting conditions can be measured at a reduced supply voltage, with adjustments made based on the ratio of the specified starting voltage to the test voltage When multiple machines are electrically connected, the maximum voltage relative to earth should be considered Additionally, the leakage current during the withstand voltage test will vary depending on the machine's size.

Occasional excess current

Momentary excess torque for motors

Total harmonic distortion (THD) for synchronous machines

Immunity

Ngày đăng: 17/04/2023, 10:26

TÀI LIỆU CÙNG NGƯỜI DÙNG

TÀI LIỆU LIÊN QUAN