| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |[.]
Trang 1protect against gases
or gases and particles or
particles only Ð
Requirements, testing,
marking
August 1999
Trang 2National foreword
This British Standard is the UK implementation of
EN 1827:1999+A1:2009 It supersedes BS EN 1827:1999, which is withdrawn
The start and finish of text introduced or altered by amendment is indicated in the text by tags Tags indicating changes to CEN text carry the number of the CEN amendment For example, text altered by CEN amendment A1 is indicated by !"
The UK participation in its preparation was entrusted by Technical Committee PH/4, Respiratory protection, to Subcommittee PH/4/3, Facepieces
A list of organizations represented on this subcommittee can be obtained on request to its secretary
This publication does not purport to include all the necessary provisions of a contract Users are responsible for its correct application
Compliance with a British Standard cannot confer immunity from legal obligations.
This British Standard, having
been prepared under the
direction of the Health and
Environment Sector Committee,
was published under the
authority of the Standards
Committee and comes into effect
on 15 June 1999
© BSI 2009
Amendments/corrigenda issued since publication
Amd No Date Text affected
10669Corrigendum No 1
August 1999 Title corrected on front cover
31 August 2009 Implementation of CEN
amendment A1:2009
Trang 3NORME EUROPÉENNE
English Version
Respiratory protective devices - Half masks without inhalation
valves and with separable filters to protect against gases or
gases and particles or particles only - Requirements, testing,
marking
Appareils de protection respiratoire - Demi-masques sans
soupape inspiratoire et avec filtres démontables, contre les
gaz, contre les gaz et les particules, ou contre les
particules uniquement - Exigences, essais, marquage
Atemschutzgeräte - Halbmasken ohne Einatemventile und mit trennbaren Filtern zum Schutz gegen Gase, Gase und Partikeln oder nur Partikeln - Anforderungen, Prüfung,
Kennzeichnung
This European Standard was approved by CEN on 26 December 1998 and includes Amendment 1 approved by CEN on 1 st May 2009 CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member
This European Standard exists in three official versions (English, French, German) A version in any other language made by translation under the respons bility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom
EUROPEAN COMMITTEE FOR STANDARDIZATION
C O M I T É E U R O P É E N D E N O R M A L I S A T I O N
E U R O P Ä I S C H E S K O M I T E E FÜ R N O R M U N G
Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2009 CEN All rights of exploitation in any form and by any means reserved
worldwide for CEN national Members
Ref No EN 1827:1999+A1:2009: E
Trang 47.15 Gas filter capacity 9
7.16 Particle filter penetration 11
7.17 Clogging (Optional) 11
7.18 Compatibility with skin 12
7.19 Carbon dioxide content of inhalation
7.20 Breathing resistance without clogging
13 7.21 Inward leakage 15
8.5 Cleaning and disinfecting 19
8.6 Exhalation valves (if fitted) 19
8.7 Gas filter capacity 21
8.8 Particle filter penetration 21
Trang 5Foreword
This document (EN 1827:1999+A1:2009) has been prepared by Technical Committee CEN/TC 79
"Respiratory protective devices", the secretariat of which is held by DIN
This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by December 2009, and conflicting national
standards shall be withdrawn at the latest by December 2009
This European Standard supersedes EN 1827:1999
This document includes Amendment 1, approved by CEN on 2009-05-01
The start and finish of text introduced or altered by amendment is indicated in the text by tags
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom
Trang 6Introduction
A given respiratory protective device can only be approved when the individual components satisfy the requirements of the test specification which may be a complete standard or part of a standard, and practical performance tests have been carried out successfully on complete apparatus where specified in the appropriate standard If for any reason a complete apparatus is not tested then simulation of the apparatus is permitted provided the respiratory characteristics and weight distribution are similar to those of the complete apparatus
1 Scope
This European Standard specifies performance requirements, test methods and marking requirements for half masks (re-usable) without inhalation valves and with separable filters (designed for a maximum of single shift use) to protect against gases or gases and particles or particles only It does not cover devices designed for use in circumstances where there is or might
be an oxygen deficiency (oxygen less than 17 % by volume) or for escape purposes
Laboratory and practical performance tests are included for the assessment of compliance with the requirements
2 Normative references
!The following referenced documents are indispensable for the application of this document For dated references, only the edition cited applies For undated references, the latest edition of the referenced document (including any amendments) applies."
EN 132 Respiratory protective devices – Definitions of terms and pictograms
EN 134 Respiratory protective devices – Nomenclature of components
!EN 149" Respiratory protective devices – Filtering half masks to protect against
particles – Requirements, testing, marking
!deleted text"
!EN 13274-7:2008, Respiratory protective devices – Methods of test – Part 7: Determination of
particle filter penetration"
!EN 14387:2004, Respiratory protective devices – Gas filter(s) and combined filter(s) -
Requirements, testing, marking"
Trang 7!ISO 6941" Textile fabrics – Burning behaviour – Measurement of flame spread
properties of vertically oriented specimens
3 Terms and definitions
For the purposes of this European Standard the definitions in EN 132 and the nomenclature from
EN 134 apply
Gas filters remove specified gases Combined filters remove dispersed solid and/or liquid particles and specified gases The term "gases" is taken to include vapours
Particle filters remove solid and/or liquid particles
A solid aerosol is defined as a dispersion of solid particles in air A liquid aerosol is defined as a dispersion of liquid particles in air
4 Description
A half mask without inhalation valves covers the nose and mouth and the chin, has no inhalation valves and may or may not have exhalation valves It comprises a facepiece and separable and replaceable filters It provides adequate sealing for the intended use on the face of the wearer against the ambient atmosphere, when the skin is dry or moist and when the head is moved
Inhalation air enters through the filter and passes directly to the nose and mouth area of the device Exhaled air passes through the filter and an exhalation valve (if fitted) to the ambient atmosphere
In addition to providing protection against gases these devices can be designed to protect against both solid and liquid aerosols
5 Classification
5.1 General
Half masks shall be classified according to the types and classes of filters used
5.2 Filter types
Type FM A - for use against certain organic gases and vapours with a boiling point higher than 65
°C as specified by the manufacturer
Type FM B - for use against certain inorganic gases and vapours as specified by the manufacturer (excluding carbon monoxide)
Type FM E - for use against sulfur dioxide and other acid gases and vapours as specified by the manufacturer
Type FM K - for use against ammonia and organic ammonia derivatives as specified by the manufacturer
Trang 8Type FM AX - for use against certain low boiling organic compounds as specified by the manufacturer
Type FM SX - for use against specific named gases and vapours
!Type FM P NR - for single shift use against particles."
Any combination of these types is permitted
5.3 Filter classes
5.3.1 Gas filter classes
Class 1 - low capacity (Gas 1)
Class 2 - medium capacity (Gas 2)
The protection provided by class 2 devices includes that provided by the corresponding class 1 device of the same type
FM AX and FM SX filters are not classified
5.3.2 Particle filter classes
!Class 1 low filtering efficiency (FM P1 NR)
Class 2 medium filtering efficiency (FM P2 NR)
Class 3 high filtering efficiency (FM P3 NR)
The protection provided by a FM P2 NR - or FM P3 NR - filter also includes that provided by the corresponding filter of lower class or classes."
EXAMPLE Half mask without inhalation valve EN 1827:1999 FM E1 P2 NR D."
7 Requirements
7.1 General
In all tests, all test samples shall meet the requirements
Trang 97.2 Nominal values and tolerances
Unless otherwise specified, the values stated in this European Standard are expressed as nominal values Except for temperature limits, values which are not stated as maxima or minima shall be subject to a tolerance of ± 5 % Unless otherwise specified, the ambient temperature for testing shall be (24 ± 8) °C, and the temperature limits shall be subject to an accuracy of ± 1 °C
7.3 Visual inspection
The visual inspection shall include the marking and the information supplied by the manufacturer
Testing shall be done in accordance with 8.3
7.4 Materials
Materials used shall be suitable to withstand handling and wear over the period for which the half mask is designed to be used After testing in accordance with 8.2.4, 8.12 and 8.13 none of the devices shall have suffered mechanical failure of the facepiece body, straps or filter elements
Testing shall be done in accordance with 8.3
7.5 Flammability
Parts of a complete device that might be exposed to a flame during use shall not burn or continue
to burn for more than 5 s after removal from the flame
Testing shall be done in accordance with 8.3 and 8.4
It is not required that the device still has to be useable after the test
7.6 Cleaning and disinfecting
Any part of the device designed to be used for more than a single shift (single-use), shall withstand the cleaning and disinfecting agents and procedures recommended by the manufacturer
Testing shall be done in accordance with 8.5
Parts of the device likely to come into contact with the wearer shall have no sharp edges or burrs
Testing shall be done in accordance with 8.3
7.9 Demountable parts
All parts designed to be demountable shall be readily connected and secured, where possible by hand
Trang 10Testing shall be done in accordance with 8.3 and 8.13
7.10 Head harness
7.10.1 The head harness shall be designed so that the device can be donned and removed easily
Testing shall be done in accordance with 8.12 and 8.13
7.10.2 The head harness shall be adjustable or self-adjusting and shall be sufficiently robust to
hold the device firmly in position and be capable of maintaining inward leakage requirements for the device
Testing shall be done in accordance with 8.12 and 8.13
7.11 Connections
The connection between filter(s) and half mask shall be robust and reliable The connection shall
be achieved by use of a special connection Threads specified in EN 148-1, EN 148-2 or EN 148-3 shall not be used If a thread connection is used, it shall not be possible to connect this to the threads specified in EN 148-1, EN 148-2 or EN 148-3
Testing shall be done in accordance with 8.3, 8.12 and 8.13
7.12 Exhalation valves
7.12.1 Exhalation valve(s) (if fitted) shall function correctly in all orientations
Testing shall be done in accordance with 8.12
7.12.2 Exhalation valves (if fitted) shall be protected against or be resistant to dirt and mechanical
damage They may be shrouded or include any other device that may be necessary to comply with 7.21
Testing shall be done in accordance with 8.3
7.12.3 Exhalation valve(s) (if fitted) shall continue to operate correctly after a continuous flow of
300 l/min over a period of 30 s
Testing shall be done in accordance with 8.6.1
7.12.4 Where the exhalation valve housing is attached to the faceblank, the housing shall
withstand axially a tensile force of 10 N applied for 10 s
Testing shall be done in accordance with 8.6.2
Trang 117.14 Mass
The total weight of filter(s) used in devices meeting the requirements of this European Standard shall not exceed 300 g
Testing shall be done in accordance with 8.3
7.15 Gas filter capacity
NOTE The minimum breakthrough time is intended only for laboratory tests under
standardized conditions It does not give an indication of the possible service time in practical use Possible service times can differ from the breakthrough times determined according to this European Standard in both directions, positive or negative, depending on the conditions of use
7.15.1 The filters shall meet the requirements for minimum breakthrough times given in tables 1, 2
or 3
Testing shall be done in accordance with 8.7
7.15.2 Where the filter is designed for a combination of types of gases, it shall meet the
requirements of each type separately
Testing shall be done in accordance with 8.7
Trang 12Table 1 - Minimum breakthrough times for gas filters of types FM A, FM B, FM E and FM K
Filter Test gas Test gas concentration in
air
Breakthrough concentration
Minimum breakthrough time
Trang 13Table 2 - Minimum breakthrough times for gas filters of type FM AX
Filter Test gas Test gas concentration
in air
Breakthrough concentration
Minimum breakthrough time
Table 3 - Minimum breakthrough times for gas filters of type FM SX
Sorption When tested in accordance with !7.8.5.1 of EN 14387:2004",
FM SX filters shall have a breakthrough time of not less than 20 min
Desorption When tested in accordance with !7.8.5.2 of EN 14387:2004",
the effluent concentration from FM SX filters shall not exceed
5 ml/m³ of test gas
7.16 Particle filter penetration
The requirements for the maximum penetration of the test aerosol as specified in EN 143 for each class of particle filter shall be met
Testing shall be done in accordance with 8.8
7.17 Clogging (Optional)
7.17.1 General
!For single shift use separable particle filtering elements, the clogging test is an optional test." When such devices are claimed to meet clogging performance requirements they shall be subjected to the dolomite dust clogging procedure specified in EN 149
7.17.2 Filter penetration
!After the clogging procedure, the filter penetration shall not exceed the values given in 7.16
Testing shall be done in accordance with 5.2 of EN13274-7:2008."
Trang 147.17.3 Breathing resistance
7.17.3.1 Devices with exhalation valves
a) the inhalation resistance shall not exceed the values given in table 4;
b) the exhalation resistance shall not exceed 3 mbar at 160 l/min continuous flow (table 4)
Testing shall be done in accordance with 8.11
7.17.3.2 Devices without exhalation valves
The inhalation and exhalation resistance shall not exceed the values given in table 4
Testing shall be done in accordance with 8.11
Table 4 - Maximum breathing resistance after clogging
Devices with exhalation valves
Devices without exhalation valves
Type
Class
Maximum inhalation resistance at
95 l/min
mbar
Maximum exhalation resistance at
3,0 3,0
4,0 5,0
FM Gas1 P2
FM Gas1 P3
9,0 11,0
3,0 3,0
4,0 5,0
FM Gas2 P2
FM Gas2 P3
10,6 12,6
3,0 3,0
4,0 5,0
FM AX P2
FM AX P3
10,6 12,6
3,0 3,0
4,0 5,0
FM SX P2
FM SX P3
10,6 12,6
3,0 3,0
4,0 5,0
7.18 Compatibility with skin
Materials that can come into contact with the wearer's skin shall not be known to be likely to cause irritation or any other adverse effect to health
Testing shall be done in accordance with 8.3
7.19 Carbon dioxide content of inhalation air
The carbon dioxide content of the inhalation air (dead space) shall not exceed an average of 1,0 %
by volume
Testing shall be done in accordance with 8.10
Trang 157.20 Breathing resistance without clogging
7.20.1 General
The breathing resistances of complete devices with the various combinations of filters shall meet the requirements of tables 5, 6 and 7 as appropriate
7.20.2 Inhalation resistance
7.20.2.1 Half masks with gas filters
The inhalation resistance shall meet the requirements specified in table 5
Testing shall be done in accordance with 8.11
Table 5 - Inhalation resistance
7.20.2.2 Half masks with combined filters
The inhalation resistance shall meet the requirements specified in table 6
Testing shall be done in accordance with 8.11
Trang 16Table 6 - Inhalation resistance
7.20.2.3 Half masks with particle filters
The inhalation resistance shall meet the requirements given in table 7
Testing shall be done in accordance with 8.11
Table 7 - Inhalation resistance
The exhalation resistance of the complete device shall not exceed 3 mbar
Testing shall be done in accordance with 8.11
Trang 17Testing shall be done in accordance with 8.12
7.22 Field of vision
The field of vision is acceptable if determined so in practical performance tests
Testing shall be done in accordance with 8.13
7.23 Practical performance
The device shall undergo practical performance tests under realistic conditions These general tests serve the purpose of checking the equipment for imperfections that cannot be determined by the tests described elsewhere in this European Standard
Where practical performance tests show the apparatus has imperfections related to wearer's acceptance, the test house shall provide full details of those parts of the practical performance tests which revealed these imperfections This will enable other test houses to duplicate the tests and assess the results thereof
Testing shall be done in accordance with 8.13
The complete device in the state as received shall be subjected to the following thermal cycle:
a) for 24 h to a dry atmosphere at (70 ± 3) °C;
Trang 18be at least 10times the mass of the steel case This may be achieved by bolting the steel plate to a hard floor without dampening elements
8.2.3.2 Procedure
The devices or filters shall be tested as received, removed from their packaging but still sealed The devices shall be placed vertically in the case (K) so that the sealed packages do not touch each other during the test, allowing 6 mm horizontal movement and free vertical movement The test apparatus shall be operated at the rate of approximately 100 rotations/min for approximately
20 min and a total of 2000 rotations After the test, any loose material that may have been released from the device shall be removed prior to the performance testing
Trang 208.2.4 Simulated wearing (S.W.)
Conditioning by simulated wearing shall be carried out by the following process
A breathing machine is adjusted to 25 cycles/min and 2,0 l/stroke The half mask is mounted on a Sheffield dummy head For testing, a saturator is incorporated in the exhalation branch between the breathing machine and the dummy head, the saturator being set at a temperature in excess of
37 °C to allow for the cooling of the air before it reaches the mouth of the dummy head The air shall be saturated at (37 ± 2) °C at the mouth of the dummy head In order to prevent excess water spilling out of the dummy's mouth and contaminating the half mask the head shall be inclined so that the water runs away from the mouth and is collected in a trap
The breathing machine is brought into operation, the saturator switched on and the test equipment allowed to stabilize The half mask under test shall then be mounted on the dummy head During the test time of 3 h in total at approximately 20 min intervals the half mask shall be completely removed from the dummy head and refitted such that during the test period it is fitted ten times to the dummy head
8.3 Visual inspection
All samples are subject to visual inspection as specified elsewhere in this European Standard
The visual inspection shall be carried out where appropriate by the test house prior to laboratory or practical performance tests
8.4 Flammability
A total of four devices shall be tested: two in the state as received and two after temperature conditioning in accordance with 8.2.2
The single burner test is carried out according to the following procedure
The facepiece is put on a metallic dummy head which is motorized such that it describes a horizontal circle with a linear speed, measured at the tip of the nose, of (60 ± 5) mm/s
The head is arranged to pass over a propane burner the position of which can be adjusted By means of a suitable gauge, the distance between the top of the burner and the lowest part of the facepiece (when positioned directly over the burner) shall be set to (20 ± 2) mm
A burner described in !ISO 6941" has been found suitable
With the head turned away from the area adjacent to the burner, the propane gas is turned on, the pressure adjusted to between 0,2 bar and 0,3 bar and the gas ignited By means of a needle valve and fine adjustments to the supply pressure, the flame height shall be set to (40 ± 4) mm This is measured with a suitable gauge The temperature of the flame measured at a height of (20 ± 2)
mm above the burner tip by means of a 1,5 mm diameter mineral insulated thermocouple probe, shall be (800 ± 50) °C
Failure to meet the temperature requirement indicates that a fault such as a partially blocked burner exists This shall need to be rectified
The head is set in motion and the effect of passing the facepiece once through the flame shall be noted
Trang 21The test shall be repeated to enable an assessment to be made of all materials on the exterior of the device Any one component shall be passed through the flame once only
8.5 Cleaning and disinfecting
As many samples shall be cleaned and disinfected following the description in the information supplied by the manufacturer as are used for the inward leakage tests
Compliance shall be assessed during the tests described in 8.12
8.6 Exhalation valves (if fitted)
8.6.1 Exhalation valve (flow test)
A total of three samples shall be tested: one in the state as received and two temperature conditioned in accordance with 8.2.2
8.6.2 Exhalation valve (pull test)
A total of three samples shall be tested: one in the state as received, one temperature conditioned
in accordance with 8.2.2 and one conditioned by simulated wearing in accordance with 8.2.4
Clamp the device as shown in figure 2 and apply a load of 10 N for 10 s Examine the housing for signs of damage or loosening in the faceblank
Trang 22Figure 2 - Fixture for faceblank
Trang 238.7 Gas filter capacity
A total of six devices or filters shall be tested for each test gas: three conditioned by the test for mechanical strength in accordance with 8.2.3, and three conditioned by the test for mechanical strength in accordance with 8.2.3 followed by conditioning by simulated wearing in accordance with 8.2.4
For those samples conditioned with mechanical strength and simulated wearing, testing shall be started within 15 min after completion of the simulated wearing procedure Care shall be taken to store these test samples in an air tight container between conditioning and testing
All performance tests shall be conducted so that the test gas or air will pass through the filter horizontally
The complete device shall be clamped and sealed to a suitable adapter without influencing the effective filter surface The exhalation valve (if fitted) shall be sealed
!Testing shall be done in accordance with EN 14387."
8.8 Particle filter penetration
!A total of 9 samples shall be tested for each aerosol:
3 in the state as received,
3 conditioned by simulated wearing in accordance with 8.2.4
3 conditioned by the test for mechanical strength in accordance with 8.2.3 followed by temperature conditioning in accordance with 8.2.2
Samples which are tested by mechanical strength followed by temperature conditioning shall be tested for exposure with a specified mass of test aerosol of 120 mg according to 5.3 of
EN 13274-7:2008
The other samples shall be tested for penetration according to 5.2 of EN 13274-7:2008
Testing shall be done in accordance with EN 13274-7:2008."
8.9 Clogging
A total of three devices or filters shall be tested: one in the state as received, and two after temperature conditioning in accordance with 8.2.2
Testing shall be done in accordance with EN 149
8.10 Carbon dioxide content of inhalation air
A total of three devices shall be tested: all in the state as received
The equipment consists essentially of a breathing machine with solenoid valves controlled by the breathing machine, a connector, a CO2 flowmeter and a CO2 analyser
The equipment shall subject the device to a respiration cycle by the breathing machine
Typical test arrangements are shown in figures 3 and 4
Trang 24Key
1 Breathing machine 6 Carbon dioxide analyser
2 Auxiliary lung 7 Solenoid valve
3 Non-return valve 8 Dummy head
4 Flowmeter 9 Sampling tube for inhalation air
5 Compensator 10 Carbon dioxide absorber
a Carbon dioxide
Figure 3 - Scheme of typical test rig for carbon dioxide content of inhalation air