EN 15316-2-1, Heating systems in buildings — Method for calculation of system energy requirements and system efficiencies — Part 2-1: Space heating emission systems
EN 15316-2-3, Heating systems in buildings — Method for calculation of system energy requirements and system efficiencies — Part 2-3: Space heating distribution systems
Table A.4 — User and heating system, identification information (for use in 6.3)
Heated surface All
Type of building Residential Non residential
Nominal heat generation power < 100 kW > 100 kW < 100 kW > 100 kW Owner / administrator name Required Required Required Required
Address Required Required Required Required
Total floor area or volume Required Required Required Required Heated floor area or volume Required Required Required Required
Age of the building a Required Required Required Required
Height above sea level Required Required Required Required Design outside temperature Required Required Required Required
Building category and use b Required Required Required Required
Building height Required Required Required Required
Type of building thermal insulation c Required Required Required Required Conservation of building insulation d Required Required Required Required Building plans / sketch Optional Required Optional Required
List of heated zones Required Required Required Required Occupancy patterns and timing Required Required Required Required Date of installation of the heating system Required Required Required Required Heating system design Required Required Required Required Commissioning reports Optional Required Optional Required
Energy declaration e Required Required Required Required
Functional diagram Required Required Required Required
Control system identification Required Required Required Required Location of main components Required Required Required Required Attached systems data Required Required Required Required Heating medium quality reports Optional Required Optional Required
a 0 to 20 Years / 20 to 50 Years / more than 50 years.
b House / apartment / office/ etc. as defined in EPBD annex.
c Non insulated / external insulation / internal insulation.
d Original / improved / damaged.
e Depending on installation date.
Table A.5 — Space heating emission sub-system, identification information (for use in 6.8)
Heated surface All
Type of building Residential Non residential
Nominal heat generation power < 100 kW > 100 kW < 100 kW > 100 kW
Type of heat emitters a Required Required Required Required
Heat emitter hydraulic connection type b Required Required Required Required Number of heat emitters Optional Required Optional Required
a For each zone.
b Direct / by-pass or two pipes / single pipe.
Table A.6 — Space heating emission control sub-system, identification information (for use in 6.9)
Heated surface All
Type of building Residential Non residential
Nominal heat generation power < 100 kW > 100 kW < 100 kW > 100 kW
Type of local control a Required Required Required Required
Type of central control b Required Required Required Required
Setting of outdoor reset function for flow temperature
Required Required Required Required
Time control type c Required Required Required Required
List of controls available to users Required Required Required Required User instruction available Required Required Required Required
a Manual / zone / room.
b None / external temperature compensation.
c None / fixed time schedule / occupancy based.
Table A.7 — Space heating distribution sub-system, identification information (for use in 6.10)
Heated surface All
Type of building Residential Non residential
Nominal heat generation power < 100 kW > 100 kW < 100 kW > 100 kW
Network typology a Required Required Required Required
Expansion system type b Required Required Required Required
List of zones Required Required Required Required
Circulation type c Required Required Required Required
Status of piping insulation of space heating
distribution system Required Required Required Required
Circulation pump(s) maximum rated power Required Required Required Required Circulation pump(s) set power Required Required Required Required Circulation pump(s) type d Required Required Required Required Circulation pump(s) working point e Optional Required Optional Required
Unbalancing symptoms f Required Required Required Required
a Zones / vertical columns.
b Open vented / closed.
c Gravity / forced.
d Fixed speed / adjustable speed / constant differential pressure / variable/proportional differential pressure.
e Head and flow rate.
f Example: unequal room temperatures, time delay, different ∆θs on heat emitters.
Table A.8 — Generation sub-system, identification information (for use in 6.11.1)
Heated surface All
Type of building Residential Non residential
Nominal heat generation power < 100 kW > 100 kW < 100 kW > 100 kW Number of boilers installed Required Required Required Required Total installed nominal power Required Required Required Required
Fuel(s) Required Required Required Required
Type of generation control Required Required Required Required Hydraulic circuit functional diagram Required Required Required Required
Spare units Required Required Required Required
Other generation sub-systems, type Required Required Required Required
Table A.9 — Heating system boiler, identification information (for use in 6.11.2)
Fuel type Gaseous and liquid Solid
Nominal heat generation power < 100 kW > 100 kW < 100 kW > 100 kW
Boiler duty (heat/dhw) Required Required Required Required
Fuel(s) Required Required Required Required
Fuel feed typology a Optional Optional Required Required
Boiler manufacturer Required Required Required Required
Boiler model Required Required Required Required
Boiler serial number Optional Optional Optional Optional
Maximum power rated input b Required Required Required Required Maximum power rated output c Optional Optional Optional Optional Minimum power rated input b Required Required Required Required Minimum power rated output c Optional Optional Optional Optional Boiler manufacture date or year Required Required Required Required
Boiler classification d Optional Optional Optional Optional
Condensing/non condensing Required Required Required Required CE labelling efficiency stars (if available) Required Required Required Required Burner manufacturer and model e Required Required Required Required
Burner power range e Required Required Required Required
Power modulation type f Required Required Required Required
a Automatic or manual.
b Combustion power.
c Net power to heating system.
d Bxx or Cyyy : typology of air flue gas circuit, fan position etc.
e If a separate burner is fit to the boiler.
f Fixed, stepped (multistage), continuous modulation.
Table A.10 — Procedures and methodologies required for heating system boiler inspection (for use in 6.11.2)
Fuel type Gaseous and liquid Solid fuel
Nominal heat generation power
(ref. annex) < 100 kW > 100 kW < 100 kW > 100 kW Measurement M.1 Suitable Suitable Suitable Suitable Combustion
power
Maintenance
data M.2 Suitable NO Suitable NO
Measurement C.1 Suitable Suitable Suitable Suitable Boiler basic
settings and combustion efficiency
Maintenance
data C.2 NO NO NO NO
Surface
temperature N.5.1.1 Suitable Suitable Suitable Suitable Losses
through the envelope (radiation losses) a
Tabulated
values N.5.1.2 Suitable Suitable Suitable Suitable
Losses through the chimney with burner off a
Tabulated values
N.5.2 Suitable Suitable Suitable Suitable
Tabulated values
N.5.3.1 Suitable Suitable Suitable Suitable Stand-by
operation N.5.3.2 Suitable Suitable Suitable Suitable Total stand-
by losses test a
Auxiliary heater N.5.3.3 Suitable Suitable Suitable Suitable Database
reference N.1.1 Suitable Suitable Suitable Suitable Default tables N.1.2 Suitable Suitable Suitable Suitable Boiler directive
data N.1.3 Suitable Suitable Suitable Suitable
Boiler cycling method
N.1.4 Suitable Suitable Suitable Suitable Boiler
annual efficiency
Total stand-by
losses N.1.5 Suitable Suitable Suitable Suitable
Settings verification L suitable Suitable Suitable Suitable
a As required by the selected methodology for boiler annual efficiency.
Table A.11 — Procedures and methodologies required for generation sub-system sizing (for use in 6.12.1)
Fuel type Gaseous and liquid Solid
Nominal heat generation power
(ref. annex)
< 100 kW > 100 kW < 100 kW > 100 kW Heat load calculation O.1.1 Suitable Suitable Suitable Suitable Existing heat load calculation O.1.2 Suitable Suitable Suitable Suitable
Energy signature O.1.3 Suitable Suitable Suitable Suitable
Fuel consumption O.1.4 Suitable Suitable Suitable Suitable
Heat emitters installed O.1.5 Suitable Suitable Suitable Suitable NOTE Preferred methodology: energy signature.
Table A.12 — Procedures and methodologies required for determination of performance of space heating sub-systems (for use in 6.13)
Building type Residential Non residential
Nominal heat generation power
(reference)
< 100 kW > 100 kW < 100 kW > 100 kW Emission Tabulated
calculation method
EN 15316-2-1 Suitable Suitable Suitable Suitable
Emission
control Tabulated calculation method
EN 15316-2-1 Suitable Suitable Suitable Suitable
Distribution Tabulated calculation method
EN 15316-2-3 Suitable Suitable Suitable Suitable
Table A.13 — Domestic hot water sub-system, identification information (for use in 6.14)
Type of building Residential Non residential
Nominal heat generation power < 100 kW > 100 kW < 100 kW > 100 kW Type of domestic hot water production a Required Required Required Required Heat source type and duty b Required Required Required Required
Boiler nominal power Required Required Required Required
Heat exchanger capacity Required Required Required Required
Storage volume Required Required Required Required
Type of domestic hot water production control
Required Required Required Required
Type of recirculation c Required Required Required Required
Circulation pump(s) maximum rated power Required Required Required Required Circulation pump(s) set power Required Required Required Required Circulation pump(s) type d Required Required Required Required
Recirculation timing Required Required Required Required
Status of domestic hot water piping
insulation Required Required Required Required
a Instantaneous / storage.
b Specific generator / heating system generator.
c Gravity / forced.
d Fixed speed / adjustable speed / constant differential pressure / variable/proportional differential pressure.
Annex B (informative)
Examples of national inspection class tables