Power triangle for the load: = Real power loss in the line is zero... The equivalent circuit referred to the low-voltage side is shown below: 3.17 a Neglecting the exciting current of th
Trang 1
TO ACCOMPANY
Trang 2
Contents
Trang 42.1 (a) A1= ∠ ° =5 30 5 cos30[ ° + jsin 30° =] 4.33+ j 2.5
Trang 5(b) Z = +3 j8− j4= +3 j4= ∠5 53.1° Ω
(c) I =(100 0∠ °) (5 53.1∠ ° = ∠ −) 20 53.1 A°
6 3
Trang 6The circuit transformed to phasor domain is shown below:
ωω
terminal of the generator
P VI
Q VI
ωω
P VI
Trang 8(b) υ(t), i(t), and p(t) are plotted below: (See next page)
(c) The instantaneous power has an average value of 3.46 W, and the frequency is twice that
of the voltage or current
Trang 9sin 2sin 2
Instantaneous power supplied (to sustain the changing energy in the magnetic field) has a
Trang 10(c) Z R j L 1
j C
ωω
which are the reactive powers into L and C, respectively
Thus p t( )=P(1 cos 2+ ωt)−Q Lsin 2ωt−Q Csin 2ωt ←
2
2 2
2 2
2 2
2 2
Trang 112 2
2 2
0.1S10
Trang 12L L L
P pf
=
=
Trang 13Power triangle for the load:
=
Real power loss in the line is zero
Trang 141.867730.84 10
240
10.38385.547 10
V
∠ °
Trang 15At the new pf of 0.8 lagging, P TOTAL of 60kW results in the new reactive power Q′ , such
∴The required capacitor’s kVAR is Q C =80−45=35 kVAR ←
C C
1 2 MAX
V V P
X
2.32 4 Mvar minimizes the real power line losses, while 4.5 Mvar minimizes the MVA power flow
into the feeder
Trang 172.36 Note that there are two buses plus the reference bus and one line for this problem After
converting the voltage sources in Fig 2.23 to current sources, the equivalent source
The rest is left as an exercise to the student
2.37 After converting impedance values in Figure 2.29 to admittance values, the bus admittance
Trang 182.38 The admittance diagram for the system is shown below:
V V
Trang 19V V V V V
1 3
Trang 20( / 3) 120.15 36.8730 24.02 66.87 A
an a
V I
circuit is shown below:
Total impedance viewed from the input terminals is
V I Z
Trang 21(b) Phase voltage at load terminals V2 =120 0∠ ° − +(2 j4 5 0)( ∠ ° )
2.44 (a) The per-phase equivalent circuit for the problem is shown below:
Trang 22With phase voltage V2 as reference,
( )
* 3
* 2
R S I V
LL
S I V
Trang 23Using voltage division: / 3
Trang 24S I
2 3
LL
P I
Trang 252.49 (a) Let Z Y = Z A= Z B= Z C for a balanced Y-load
Trang 27Total apparent power dissipated in all three phases in the load
Trang 312 2
Trang 32t V
Trang 331.5sin10 V2
out
t t
5.5 10
24.2227.3
Trang 343.11 Turns Ratio= =a N N1 2=66 /11.5=5.74
With high-voltage side designated as 1, and L-V side as 2,
1
Trang 35(b)
2 2
j N
Trang 37Note: Real and reactive losses, 0.87 kW and 1.95 kVARS, absorbed by the feeder and
transformer, are the same in all cases Highest efficiency occurs for unity P.F
(EFF=Pout Ps/ × 100=(50 / 50.87 ×100) =98.29%)
( )
2 2
2 2
Trang 38The equivalent circuit referred to the low-voltage side is shown below:
3.17 (a) Neglecting the exciting current of the transformer, the equivalent circuit of the
transformer, referred to the high-voltage (primary) side is shown below:
The rated (full) load current, Ref to HV-side, is given by
Trang 393.18
2 1
V Z
Trang 40(c) P spu + jQ spu =V spu I spu* =(1.0375 1.1505∠ °)(1.0 36.87∠ ° )
460
115460
10.5820,000
3
115V115
0.661320,000
20,000
173.9 A115
base
base
base
V Z I
T pu T pu Line Load pu
V I
Trang 41L pu
10 40
2.778 70 pu3.6
Trang 42( )( )
1 1
Y pu pu
V I
3.23 Select a common base of 100MVA and 22kV (not 33kV printed wrongly in the text) on the
generator side; Base voltage at bus 1 is 22kV; this fixes the voltage bases for the remaining buses in accordance with the transformer turns ratios Using Eq 3.3.11, per-unit reactances
on the selected base are given by
10.45The load impedance in OHMS is
LL L
L
V Z
Trang 43The per-unit equivalent circuit is shown below:
3.24 (a) The per-unit voltage at bus 4, taken as reference, is
0.665 36.87Current drawn by the motor is
0.95 0
m m
S I V j
Trang 44The impedance diagram in PU is shown below:
3.26 Base impedance on the low-voltage, 3.81kV-side is
Per-unit value should be the same as 6.2 pu
6648.4
Trang 453.27 Transformer reactance on its own base is
Trang 473.32 (a)
For positive sequence, V H1 leads V M1 by 90°, and V H1 lags V X1 by 90°
For negative sequence, V H2 lags V M2 by 90°, and V H2 leads V X2 by 90°
(b)
For positive sequence V H1 leads V X1 by 90° and V X1 is in phase with V M1 For
Δ – zig/zag transformer can be used to obtain the advantages of a Δ − transformer Y
without phase shift
Trang 48(c)
For positive sequence, V H1 lags V X1 by 23.4°
For negative sequence, V H2 leads V X2 by 23.4°
3.33
3.34 (a)
Trang 49(b)
Trang 50(b)
6 3
and transformer ac absorbs 12.5 Mvars The total reactive power delivered by the
open-Δ transformer to the resistive load is therefore zero
Trang 513.38 (a) The single-line diagram and the per-phase equivalent circuit, with all parameters in per
unit, are given below:
Current supplied to the load is
= ∠ − ° +
Trang 52Terminal voltage of the generator is 23 1.0374× =23.86 kV
The real power supplied by the generator is
*
ReV I t a = 1.0374 2.4 cos× −26.02° +55.84° =2.16 pu
Trang 53Per-unit positive-sequence reactance diagram
Trang 54S base = 100 MVA
V base H= 500 kV in transmission-line Zones
V base X= 20 kV in motor/generator Zones
1500
0.1pu1000
3
18
201500
3 18 0.81000
28.87 kA
20 360.14
0.1 0.1
20.7454 21.88 pu
Trang 55base X
H X
I
I I
1.506 kA;
base X
H X
I
I I
Trang 56and selecting a base of 20 kV in the generator circuit,
The voltage base in the transmission line is 230 kV and the voltage base in the motor circuit
176.3
2 1
Trang 573.46 The motors together draw 180 MW, or 180 0.6 pu
With phase-a voltage at the motor terminals as reference,
13.20.9565 0 pu13.8
The magnitude of the voltage at the generator terminals is
Note that the transformer phase shifts have been neglected here
shown below:
230
0 kV,3
a n
Trang 58a n a j
S
S I
V I
Three-phase complex power supplied by the generator is
diagram is drawn below:
Trang 59Generator current magnitude = I1 = 1659.1 A ←
Three-phase complex power delivered to the load is
Trang 60On the common base of 100 MVA for the entire system,
2 1
2 2
2 1
2 2
Trang 610.05 per unit
=
Trang 62(b)
Per unit positive sequence
(c)
Per unit positive sequence
3.53 With a base of 15 MVA and 66 kV in the primary circuit, the base for secondary circuit is
15 MVA and 13.2 kV, and the base for tertiary circuit is 15 MVA and 2.3 kV,
21
3.54 The constant voltage source is represented by a generator having no internal impedance On
a base of 5 MVA, 2.3 kV in the tertiary, the resistance of the load is 1.0 pu Expressed on a
5
Trang 63On a base of 15 MVA, 13.2 kV, the reactance of the motor is
15
7.5
X′′ = × =
The impedance diagram is given below:
Note that the phase shift that occurs
between the Y-connected primary and
the Δ-connected tertiary has been
10 kVA is transformed by magnetic induction
100 kVA is transformed electrically
At full-load current, winding losses
Trang 64479.5 316.256 A
Trang 65H H
V V
The autotransformer connection is shown below:
With windings carrying rated currents, the autotransformer rating is
LOSS
Trang 66The total autotransformer loss is same as the two-winding transformer, since the windings are subjected to the same rated voltages and currents as the two-winding transformer
3.59
Load Load Load
Trang 67(a) No regulating transformer, C=1.0
Using current division:
2 1
Using the admittance parameters from Example 4.14(a)
The voltage magnitude regulating transformer increases the reactive power delivered by
line L-2 43.970 (from 0.2222 to 0.3198) with a relatively small change in the real power delivered by line L2
22 21
Trang 68The phase-angle regulating transformer increases the real power delivered by line L2
31.8% (from 0.3849 to 0.5074) with a relatively small change in the reactive power
delivered by line L2
3.60 Losses are minimum at 0 degrees = 16.606 MW (there can be a +/- 0.1 variation in this
value values of the power flow solution tolerance)
3.61 Minimum occurs at a tap of 1.0 = 16.604 (there can be a +/- 0.1 variation in this value
values of the power flow solution tolerance)
Trang 69The per-unit positive-sequence network is:
3.63 A radial line with tap-changing transformers at both ends is shown below:
1
V′ and V2′ are the supply phase voltage and the load phase voltage, respectively, referred to
are the tap settings in per unit The impedance Z includes the line impedance plus the
referred impedances of the sending end and the receiving end transformers to the
neglecting the phase shift between V S and V R as an approximation, and noting that V S=t V S 1′
and V R =t V R 2′, it can be shown that
Trang 70where Pφ and Qφ are the load real and reactive powers per phase and it is assumed that t t S R = 1
closed, only a very small fraction of that current goes through the load impedance, because
it is much larger than the transformer impedance; so the superposition principle can be
3.65 Same procedure as in PR 3.49 is followed
Trang 73eq
eq a
S
D L
D
4.24 Reduces the electric field strength at the
conductor surfaces and hence reduces corona, power loss, communication
interference, and audible noise
Trang 741.61433.576 10
Pl R A
75+228.10.0807 /km
per conductor (at 75% current capacity)
For 4 conductors per phase:
Trang 754.6 Total transmission line loss 2.5( )
Pl A R
Trang 764.9 (a) Lint =0.05mH/ km Per Conductor
The total inductance decreases 4.1% (increases 5%) at the conductor diameter increases
Trang 774.13 (a) The total line inductance is given by
r D r
Doubling the separation between the conductors causes only about a 13% rise in inductance
7 3
Trang 784.15 For each of six outer conductors:
Trang 794
Trang 80(decrease 1.6%) as the phase spacing increases 10% (decreases 10%)
Trang 814.21 (a) From Table A.4:
2 3
7 1
Trang 824.23 (a) The geometric mean radius of each phase is calculated as
Trang 84( )( ) ( )
AB
BC
AC
D D D
Trang 86with I a as reference, instantaneous flux linkage is
4.8ln0.25 /12
Trang 87(b) ( 12)
11 1
3.2ln0.25 /12
Trang 884.37 (a) Eq (4.9.15): capacitance to neutral 2 F/m
ππε
Trang 894.40 (a) D eq =38.8 8.8 17.6× × =11.084 m
12 1
11.084ln
9.069ln
C1, Y1, and I chg decrease 1.5% (increase 1.7%)
As the phase spacing increases 10% (decreases 10%)
LL
C
D D
ππε
12
11 1
Sc D C
Q
ππ
Trang 90For the larger, 1351 kcmil conductors (smallel, 700 kcmil conductors)
4.43 (a) For drake, Table A.4 lists the outside diameter as 1.108 in
Total three-phase reactive power supplied by the capacitance is given by
Trang 9215.12 m and 0.0164 m
eq
12 23 31 9
C
H D
Trang 93Neglecting Earth effect, (8.854 10 12)
20ln0.06677
H H
Trang 94( ) 1 ( )3
0.693ft
N GMR=rN A − = × ×
T E
Trang 954.51 (a) From Problem 4.30,
the conductor diameter increases 25 % (decreases 25%) The ground level electric field
Trang 97Chapter 5
Transmission-Lines: Steady-State Operation
ANSWERS TO MULTIPLE-CHOICE TYPE QUESTIONS
Trang 99base L L
S I
Trang 101(ii) For nominal T-circuit
A0.8
3126 V3.126 kV
Trang 102(b) Sending-End 3-Phase Power = P S=3 1905.3 207.76 0.79( )( )
Trang 1045.11 (a) The series impedance per phase Z = +(r j L lω )
P P
φη
φ
R S
P P
φ φ
Trang 1055.12 (a) The nominal π circuit is shown below:
The line admittance for 100 mi is
3 3
185.5 10100
C
Y X
Trang 106sinh 0.034862 sin 0.39848 radians
Trang 109φ φ
Trang 110At the sending end
Line to line voltage magnitude 1.1102 215
16
(b) Refer to Table 5.1 of the text
Trang 111X X A
Trang 1120.4973 87.55134.8 85.3
l
l
γγ
Trang 1135.24 Z′ = =B 98.25 86.69∠ °Ω =5.673+j98.09Ω
6 2
F
l l
Trang 114( )
6 3
99.68
274.91.319 10 S
Trang 115S R
V V P
Trang 1175.30 0 ( )
1 1
0
/2
eq SL C
eq SC
L z
Z
D
Ln D
μππε
9 0
3771
1036
velocity of
propagation
/1
3 4
πω
×
Trang 1185.31 (a) For a lossless line, β ω= LC =2π( )60 0.97 0.0115 10× × −9
0.001259 rad/km
=
30.97 10
60.0115 10
Z j
Trang 119From the practical line loadability,
For a lossless line, the maximum power that can be transmitted under steady-state
Then V1=V2(coshγl+sinhγl)=V e2 γl =V e e2 αl j lβ (1)
e I
e S
e P
α
Trang 1205.34 For a lossless line, Z C L
2
2 2
12
l ZY
l V
γπ
the voltage at the open receiving end is higher
than that at the sending end,for small ,for
the medium and long-line models
Trang 121For maximum power, dP dQ/ = 0 :
S R MAX
R
ZV V
Trang 122( )( ) ( )
( )
2 max
R LL
P I
From Table A.4, the thermal limit for 3 ACSR 1113 kcmil conductors is
3 1.11 3.33 kA/ p hase.× = The current 1.966 kA corresponding to the theoretical steady-state stability limit is well below the thermal limit of 3.33 kA
and unity power factor
Q pf
Trang 123230
529100
base L base base
SIL SIL
From Eq (5.4.21) of the text,
Trang 124Nominal voltage level for the transmission line is
5.43 The maximum amount of real power that can be transferred to the load at unity pf with a bus
voltage greater than 0.9 pu (688.5 kV) is 2950 MW
5.44 The maximum about of reactive power transfer that can be transferred to the load with a bus
voltage greater than 0.9 pu is 650 Mvar
Trang 125988 MW
R
thermal limits are not exceeded
δδδ
×
Trang 126exceeded Therefore the voltage drop limit determines loadability for this line Based on 95 per unit
δδ
Trang 1275.47 (a) l=200 kM; The steady-state limit is:
At the voltage drop limit:
Trang 130(b) By shifting the origin from 0′ to 0, the power diagram is shown in Fig (b) above
For a given load and a given value of |V R|, 0′ =A |V R| |V S| |B| the loci of point A will
two such circles (known as receiving-end circles) are shown below:
(c) Line 0A in the figure above is the load line whose intersection with the power circle
2
received for the two sending-end voltages
The reactive power that must be supplied at the receiving end in order to maintain constant |V R| when the sending-end voltage decreases from |V S1| to |V S2| is given by
AB, which is parallel to the reactive-power axis
Problem 5.37(a) solution, one gets
Trang 131(b) For a lossless line, Z C = L C/ is purely real and γ = jβ is purely imaginary Also
Z′ is now the impedance of a pure inductance
C
V P
θβ
SIL
l
θβ
(c) For βl=0.002 radiansl =(0.1146 )l °, and θ12 = ° , 45
Applying the result of part (b), one gets
0.707sin 0.1146
SIL
P
°
(d) Thermal limit governs the short lines;
Stability limit prevails for long lines
←
5.53 The maximum power that can be delivered to the load is 10,250 MW
5.54 For 8800 MW at the load the load bus voltage is maintained above 720 kV even if 2 lines
are taken out of service (8850 MW may be OK since the voltage is 719.9 kV)
Trang 1325.55 From Problem 5.23, the shunt admittance of the equivalent π circuit without compensation is
at full load Therefore
Y Z
Trang 133compensated line are
3
compensated line series capacitors
receiving-end series capacito
Trang 134Equivalent ABCD parameters of the compensated line are
3
Receiving end Sending end Uncompansated line from Pr 5.13
The equivalent series reactance of four lines with two intermediate substations and one line section out-of-service is then:
Trang 135From Eq (5.4.26) with δ = °35 , V R=0.95per unit, and P=9000 MW;
L REAC
N X
N B
3 Line
Trang 1365.62 See solution of Pr 5.18 for γl Z, C,coshγl, and sinh lγ
For the uncompensated line:
γγγ
the new series arm impedance is
γγ
Thus, the maximum power that can be transmitted is increased by about 300%
5.63 The shunt admittance of the entire line is
6
From Fig 5.4 of the text, for the case of ‘shunt admittance’,
Trang 137The voltage regulation with the shunt reactor connected at no load is given by
0.0667124.13
−
=
which is a considerable reduction compared to 0.247 for the regulation of the
uncompensated line (see solution of Pr 5.18)
5.64 (a) From the solution of Pr 5.31,
The capacitive reactance is given by (see Eq 2.3.5 in text)
433.38567.85
L C
C
X
j S
Trang 138The receiving end voltage per phase 500 0 kV 288.675 0 kV
5.65 The maximum amount of real power which can be transferred to the load at unity pf with a
bus voltage greater than 0.9 pu is 3900 MW
5.66 The maximum amount of real power which can be transferred to the load at unity pf with a
bus voltage greater than 0.9 pu is 3400 MW (3450 MW may be OK since pu voltage is 0.8985)