Nahman, Senior Member, IEEE Faculty of Electrical Engineering 11001 Belgrade, Yugoslavia Abstract - The resistance to ground of a wide set of square and rectangular grid electrodes c
Trang 1IEEE Transactions on Power Delivery, Vol 11, No 3, July 1996 1337
RESISTANCE TO GROUND OF COMBINED
J.M Nahman, Senior Member, IEEE
Faculty of Electrical Engineering
11001 Belgrade, Yugoslavia
Abstract - The resistance to ground of a wide set of square
and rectangular grid electrodes combined with multiple rods,
buried in uniform and two-layer soils, has been analyzed
using available exact computer software Based upon the
results of this analysis, analytical expressions and graphs for
electrodes resistance to ground are provided, appropriate for
practical application
I INTRODUCTION The resistance to ground of substations ground
electrodes is one of the most important parameters
determining the potential rise of the grounded equipment
and other metalwork within substation with respect to the
remote earth as well as the potentials which might be
transferred outside the substation Several computer
models have been developed for the analysis of the ground
electrodes performances buried both in uniform and
nonuniform soils [1-4], making possible an exact
calculation of all ground electrodes parameters including
the resistance to ground Some approximate analwcal
expressions for grids [5-91 in uniform soil and in two-layer
soils [7,10-131 have been suggested Expressions for
rodbeds and combined grid-multiple rods electrodes in
uniform soil [5] and two-layer soils have been also
developed Ell-131 The expressions proposed by Schwarz
[ 5 ] , appropriately modified for soil nonuniformity, have
been demonstrated to provide very good estimates of the
resistance to ground of a wide set of electrodes shapes
which, unfortunately, is not the case with some other
available expressions, as discussed in [11,12] However,
the application of the modified Schwarz's approach
96 WM 003-4 PWRD A paper recommended and approved by the IEEE
Substations Committee of the IEEE Power Engineering Society for
presentation at the 1996 IEEEPES Winter Meeting, January.21-25, 1996,
Baltimore, MD Manuscript submitted July 24, 1995; made avaiable for
printing November 13, 1995
V.B Djordjevic Energoprojekt - Hidroinzenjering
1 1070 Belgrade, Yugoslavia implies the utilization of several graphs, including interpolations, which might be cumbersome in some cases Therefore, relatively simple analytical expressions for grids and combined grid-multiple rods electrodes with rods lengths being twice the upper soil depth have been proposed matching well with the exactly calculated data for a very wide set of electrodes and soil parameters [13] This paper studies square and rectangular grids combined with rods distributed along the grid perimeter only and both along the grid perimeter and within the grid A fixed rod length I = 3 m has been presumed A general analytical expression for the resistance to ground
of all electrodes shapes under consideration has been
derived for uniform soil case being in very good agreement with the exactly calculated data Correction factors for
two-layer soils are also provided as graphs and analytical expressions The expressions proposed can be used as a
good estimate of substation ground electrodes resistance to ground in practical design Furthermore, they explicitly indicate the effects of various parameters upon the
electrodes ground resistance which might serve as a good
orientation in the design phase
11 ANALYSIS OF THE RESISTANCE TO GROUND
A Ground electrodes
Square and rectangular grids have been analyzed with
2" , n = 0, 2, 4, 6, 8, meshes combined with vertical rods distributed evenly along the grid perimeter only (figs 1&2) and along the grid perimeter and along the diagonals
of the grid (figs 3624) Areas covered by the electrodes have been varied from 10 x 10 m2 up to 200 x 200 m2 , for square grids, and from 10 x 20 m2 up to 200 x 400 m2, for
rectangular grids
The grids are presumed to be buried at depth h = 0.5 m and rods are taken to be 3 m long Grids conductor and rods diameters qual 0.01 m and 0.064 my respectively The upper soil depths H = 1 m , 3 m, 5 m and 10 m have been considered (fig 5) The ratio of upper (PI) and lower
0885-8977/961$05.00 0 1996 IEEE
Trang 21338
(p2) soil layers
range (0.2, 5)
CSOl
resistivities has been varied within the
CS64
C§04
Fig 1, Sample combined square eledrodes
CS16
CS256
Fig 2 Sample combined rectangular electrodes
Fig 3 Sample combined square electrodes
throughout the grid
CRD16
Fig 4 Sample " b i n d rectangular electrodes
with rods spread throughout the grid
0.5 m
P
2
Fig 5 Presumed electrcde and soil stratification
B Resistance to ground for uniform soil The resistances to ground for a set of 140 electrodes samples buried in uniform soil have been calculated by completely modeling The electrodes samples have been generated from the patterns displayed in figs 1 to 4 by varying parameters A and H:
From the results obtained the following general expression for the resistance to ground has been deduced, agreeing well with the calculated data
where A is the area covered by the grid in r d , N i s the total number of the grid meshes and l i s the individual rod length in m This expression has been confirmed to be
valid for all electrodes shapes from figs 1 to 4
Trang 31339
the graphs in figs 6 - 12 plotting C, as a function of pip,
As factor C,values are very slightly affected by the rods distributed within the grid, for these electrodes the graphs for corresponding electrodes having only peripheral rods canbeused
Furthermore, as shown [13], (1) yields very good estimates
for grids alone also, when I= 0 has to be inserted
The calculations performed have shown that the rods
distributed within the electrodes grids very slightly af€ect
the resistance to ground values This is owing to the
screening effect among the grid conductors and rods
located within the grid which reduces the currents
emanating from these rods
Table 1 quotes exact ground resistance values and
corresponding errors of (1) for a representative set of
ground electrodes samples It is observable that (1) has
yielded very good estimates of ground resistances in all
cases
Table 1 Resisten- to ground of electrodes samples
for uniform soil with p = 100Qn
C Nonunifonnity correction factor
To extend the application of the uniform soil resistance
formula to the two soil layer case, a resistance
nonuniformity correction factor C, is introduced
R = c,R;,
In (2) R denotes the resistance to ground of a ground
electrode when buried in the two - layer soil and R, is the
resistance to ground of the same electrode buried in
uniform soil with resistivity being equal to the resistivity
of the upper layer of the two - layer soil
Factor C, has been calculated for 2200 cases generated
for electrodes shapes from figs 1 to 4 by varying
the results of this calculations have been used to construct
Trang 41340
3K
I 1
0,o
P2/P 1 Fig 8 Factor Cr vakm for CS electrodes for upper soil depth H = 1Om
I I I I 1 1 1 1 1
I I I I I I I I I I I I I I l l
P2/Pl
Fs 10 Factor Cr v a k for CR electrodes for upper soil depth H = 5m
7 -
I I I I I I l l I I I 1 1 1 1 1
Fig 9 Factor Cr v a k s for CR electrodes for upper s o l depth H = Im Fig 11 Factor Cr v a h for CR electrodes for upper soil depth H = l h
Trang 51341
statement As observable, factor C, values for CRD for all electrodes shapes in figs 1 to 4 Maximum error of electrodes in fig 12 are practically the same as these for (3) & (4) for the electrodes analyzed has been established
the corresponding CR electrodes, displayed in fig 9 to be 18% In the great majority of the cases being studied
the errors are less than lo%, in absolute terms
435 " ' " [
T
Consider electrode CS 64 covering area A = 100 x 100 m', buried in a two layer soil with resistivities pI = 50 Rm and
pz = 250 Rm Depth of the upper soil layer is H= 10 m
F o r p = p , = 50 a m , A = 100 x 100 m2, N = 64 and k3m, we obtain by applying (1)
R,, = 0.13- 50 ( 1 - lie) log,, ( 24,,00) = 0.228 n
100
By inserting X = 10 m and A = 100 x 100 m' in
expression (4) for pipI >1, we calculate
x =0.5710g10(~)+0.0610g1~(10~10)log,,(64~1~)
x = 0.657
P2/Pl and, then, according to (3) and (2)
Fig 12 Factor Cr values for CRD electrodes for upper soa depul H = hn
The factor C, values can be fairly well assessed using
the empirical expression
with
X =
0.657
C = [ z) = 2.879
R = 2.879 * 0.228 = 0.656
Exact value of R for the case under consideration is R =
0.628 R which means that the relative error of the
approximate approach equals 4,6%
P
for -2 < 1
05910g1, (I;)+ -
0 5 7 1 0 g l o ( ~ ) +
IV CONCLUSIONS +0.01610g,, (4.2H)Oog,,( N f i ) ) * PI
(4) Graphs and approximate analpcal expressions are suggested for the calculation of the resistance to ground of square and rectangular grid electrodes combined with multiple rods, buried in uniform and two-layer soils The
expressions derived and the graphs provided can be used
in practical substations ground electrodes design
for -> P2 1
PI
+o.o6log,,(1oH)~og,,(~
Trang 61342
[l] F.Dawalibi, D.Mudhedkar, "Multi step analysis of
interconnected grounding electrodes", IEEE Trans., PAS 95,
N0.1, Jan 1976, pp.113-119
[2] J.Nahman, "Digital calculation of earthing systems in
nonuniform soil", Archiv f Elektrotehn., Bd 62, No.1, 1980,
pp 19-24
[3] J.Nahman, D.Salamon, "Earthing system modelling by
element aggregation", Proc IEE, Pt C, Vol 133, No.1,
Jan~ary 1986, pp.54-58
[4] E.B.Joy, N.Paik, T.E.Brewer, R.E.Wilson, R.P.Webb,
A.Meliopoulos, "Graphical data for ground grid "lysis",
IEEE Trans., PAS-102, No.9, Sept 1983, pp.3038-3048
[5] S.J.Schwan, " Resistance of grounding systems", Trans
Amer Inst Elec Engrs., Vo1.73,1954, pp.1010 1016
[6] P.G.Laurent, "Les bases generales de la technique des mises
la terre dans les installations electriques", Bull Soc Fr
Electr., Vol 1, 1951, pp.368402
[7] P.G.Laurent, "Guide sur la calcul, Fexecution et la mesure
des prises de terre", Rev Gen Electr., Vol 81, 1972,
pp.455467
[SI J.Nahman, S.Skuletic, "Resistances to ground and mesh
voltages of ground grids" Proc.IEE, Pt C, Vo1.126, No.1,
1979, pp.57-61
[9] Y.L.Chow, M.M.A.Salama,"A simplified method for
the substation grid resistance", IEEE Trans.,
calculating
PWRD-9, N0.2, April 1994, pp.736-742
[lo] M.M.A.Salama, M.M.EI Sherbiny, Y.L.Chow, "A formula
for resistance of substation grounding grid in two layer soil",
IEEE PES 1995 Winter M paper 95 WM 001 8 PWRD
[I I] J.Nahman, D.Salamon," Analytical expressions for the
resistance of grounding grids in nonuniform soil", IEEE
Trans PAS-103, No.4, April 1984 pp.880-885
[ 121 J.Nahman, D.Salamon, "Analytical expressions for the
resistance of rodbeds and of combined grounding systems in
nonuniform soil", IEEE Trans PWRD-1, No.3, July 1986
pp 90-96
[13] J.Nahman, VDjordjevic, "Resistance to earth of grid and
combined earth electrodes in uniform and two-layer soils"
submitted for publication to IEE Proc Part C., Dec 1994
Jovan M Nahrnen was born in Belgrade, Yugoslavia He received his Dipl Eng grade in Electric Power Engineering from the Electrical Engineering Faculty, University of Belgrade, in
1960, and TechD from the same University in 1969 In 1960 he joined the Faculty of Electrical Engineering, Belgrade, where he
is employed as a Professor at the Power System w e n t
Dunng the past several years Dr Nahman was active as a
consultant to the industry where he led some research in
pundug systems and neutral grounding and power system planning and reliability
Vladimir B Djordjevic was born in Belgrade, Yugoslavia
He received his Dipl Eng grade in Electric Power Engineering
from the Electrical Enginaxing Faculty, University of Belgrade,
in 1989, and M.Sc from the same University in 1992 In 1989 he
joined the Energoprojekt - Hidroinzenjering Co Ltd., Belgrade, where he is employed as design engineer for hydro power plants, irrigation systems and water treatment plants During the past
few years he was active as an associate to the Faculty of
Electrical Engineering, Belgrade, where he participated in some research in grounding systems