Giáo trình điều khiển hệ thống lạnh
Trang 1Solenoid Solenoid Coil
Head Pressure Liquid Line Valve Bl oren
Control Filter-Drier
Moisture Liquid Indicator
Regulator —
Accumulator
£ Filter-Drier
Low Pressure Core Control
Trang 2Air Temp Control And Defrost Control
Trang 11Temperature Sensing Elements
Trang 13
Temperature Sensing Elements
Fig 13-6 Schematic diagram of simplified thermosutic
control.
Trang 14Fig 13-27 Bimetal-wpe temperature sensing cÌemenL.
Trang 15;
_
differenual adjusuments.
Trang 16Range Adjustment
Glass tube
Contacts
713-11 Space Control Versus
Evaporator Control
Trang 17Differential Pressure Control
Trang 18High or Low Pressure Control
Trang 19Dual-Pressure Controls
adjustment (Changes both point only)
cut-out adjustment (Cut-in factory set)
Fig 13-10 Dual-pressure control (Courtesy of Penn Controls, Inc.)
Trang 20Pump-Down Cycle
Trang 21
Evaporator Capatity Control
control Closing the solenoid valve in the liquid line o;
segment A renders this porton of the evaporator inopera
tive The capacity reduction obtained is proportional t, the surface area cycled out
Trang 22Evaporator Capatity Control
Kennard Division, American Air Filter Company, inc.)
Trang 23Evaporator Capatity Control
Rennar
Trang 24Evaporator Capatity Control
wary the quanury of air passing over the evaporator As the
damper moves toward the closed posiuon, the resistance
against which the blower must work is increased so that the total quantity of air circulated decreases
so that the bypass damper opens wider as the face damper
is closed off With this arrangement the quantry of air passing over the evaporator can be regulated by allowing more or less air to bypass the evaporator However, regard- less of the position of the dampers, the total quanury of air circulated remains practically the same.
Trang 25Compressor Capatity Control
Trang 26
Compressor Capatity Control
Typical solenoid vaive (shown energized)
‡ O.D
tubing inlet
—_——- *
Connect to discharge side
of compressor
Wires to electrical
eu ae 2” O.D tubing
Trang 27
Compressor Capatity Control
bypass valve is replaced with a manual or solenoid Stop valve The check valve is required with unloaded starting
to prevent blow-back of the high-pressure gas from the con-
denser.
Trang 28Compressor Capatity Control
ritor mixes with, and is desuperheated by, the refrigeranc
t the evaporator, thereby eliminating the possibilicy of
Overheating the compressor as a result of excessive super-
heating of the suction vapor In addidon, bypassed hoc
keeps refrigerant velociry in the evaporator relatively high
tnd improves oil return during periods of reduced load- inv Where a refrigeranc distributor is used, it is recom- Mencled that the bypass be connected direcdy-
Trang 29Compressor Capatity Control
rator upstream of the expansion valve bulb makes it possi- ble to reduce and control suction superheat by overiceding
the evaporacor The expansion valve bulb should be Io-
cated a minimum of 3 ft downstream of the bypass connec- tion A solenoid stop valve is required in pump-—dowm sys- terms to provide positive shucoff of bvoass line
Trang 30
Compressor Capatity Control
Fig 13-19d Hot gas is desuperheated by direct expansion cooling from separate
thermostatic expansion valve This method is ideal for remote systems where the compressor is located some distance away from the evaporator section Where pressure drops are substantial, externally equalized TEVs should be used.
Trang 31Compressor Capatity Control